260526 FL - Grounding and Bonding for Electrical Systems.pdf
PDF 111 KB Posted
- Attached to
- Electrical Infrastructure Upgrade (Optics)
- Solicitation number
- SV0218-26
About this file
This is a technical specification section for grounding and bonding systems for electrical service upgrades at the Federal Bureau of Prisons facility in Baton Rouge, Louisiana, prepared by MCA, LLC for UNICOR/FPI, effective March 20, 2026.
The specification establishes requirements for installation of grounding and bonding systems including distribution grounding, ground bonding, and foundation steel electrodes. Products required include bare copper conductors (solid, stranded, and tinned per ASTM standards), grounding buses made of predrilled annealed copper bars, and various connector types (welded exothermic-welding kits, mechanical bus-bar connectors, beam clamps, cable-to-cable connectors, ground rod clamps, and service post connectors). Grounding electrodes specified include copper-clad steel ground rods (3/4 inch by 10 feet), chemical-enhanced grounding electrodes with factory-attached No. 4/0 AWG bare conductors, and hot-dip galvanized ground plates. All electrical components must be listed and labeled per NFPA 70 and comply with UL 467 standards. Installation requirements mandate solid conductors for No. 8 AWG and smaller, stranded conductors for No. 6 AWG and larger, green-colored insulation with yellow striping for grounding conductors, horizontal grounding bus installation 6 inches above finished floor on insulated spacers, and exothermic welding for below-grade connections. Field quality control includes physical and mechanical inspections, ground resistance testing by fall-of-potential method per IEEE 81 conducted at least two days after precipitation, with maximum acceptable ground resistance values ranging from 1 ohm for electronic equipment to 10 ohms for systems under 500 kVA capacity. Testing must be performed at ground rods before any conductors are connected, with detailed dimensioned drawings and test reports required documenting rod locations, depths, and environmental conditions.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Federal Bureau of Prisons MCA, LLC
ELECTRICAL SERVICE UPGRADES BATON ROUGE, LOUISIANA
UNICOR, FPI March 20, 2026
SECTION 260526 – GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS, PAGE 1 OF 7
TECHNICAL SPECIFICATIONS
SECTION 260526
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes grounding and bonding systems and equipment.
B. Section includes grounding and bonding systems and equipment, plus the following special applications:
1. Distribution grounding.
2. Ground bonding
3. Foundation steel electrodes.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
1.3 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Plans showing dimensioned locations of grounding features specified in "Field Quality Control" Article, including the following:
1. Ground rods.
2. Grounding arrangements and connections for separately derived systems.
B. Field quality-control reports.
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For grounding to include in emergency, operation, and maintenance manuals.
1. Include the following:
a. Plans showing as-built, dimensioned locations of system described in "Field
Quality Control" Article, including the following:
1) Ground rods.
2) Grounding arrangements and connections for separately derived systems.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260526 – GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS, PAGE 2 OF 7
b. Instructions for periodic testing based on NETA MTS.
1) Tests must determine if ground-resistance or impedance values remain within specified maximums, and instructions must recommend corrective action if values do not.
2) Include recommended testing intervals.
PART 2 - PRODUCTS
2.1 SYSTEM DESCRIPTION
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Comply with UL 467 for grounding and bonding materials and equipment.
2.2 CONDUCTORS
A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.
B. Bare Copper Conductors:
1. Solid Conductors: ASTM B3.
2. Stranded Conductors: ASTM B8.
3. Tinned Conductors: ASTM B33.
4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch in diameter.
5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.
6. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-
5/8 inch wide and 1/16 inch thick.
7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors terminated with copper ferrules; 1-5/8 inch wide and 1/16 inch thick.
C. Grounding Bus: Predrilled rectangular bars of annealed copper, 1/4 by 4 inch in cross section, with 9/32 inch holes spaced 1-1/8 inch apart. Stand-off insulators for mounting must comply with UL 891 for use in switchboards, 600 V and must be Lexan or PVC, impulse tested at
5000 V.
2.3 CONNECTORS
A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260526 – GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS, PAGE 3 OF 7
B. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.
C. Mechanical-Type Bus-Bar Connectors: Cast silicon bronze, solderless compression-type wire terminals, and long-barrel, two-bolt connection to ground bus bar.
D. Compression-Type Bus-Bar Connectors: Copper or copper alloy, with two wire terminals.
E. Beam Clamps: Mechanical type, terminal, ground wire access from four directions, with dual, tin-plated or silicon bronze bolts.
F. Cable-to-Cable Connectors: Compression type, copper or copper alloy.
G. Conduit Hubs: Mechanical type, terminal with threaded hub.
H. Ground Rod Clamps: Mechanical type, copper or copper alloy, terminal with hex head bolt.
I. Ground Rod Clamps: Mechanical type, copper or copper alloy, terminal with hex head bolt.
J. Lay-in Lug Connector: Mechanical type, copper with set screw.
K. Service Post Connectors: Mechanical type, bronze alloy terminal, in short- and long-stud lengths, capable of single and double conductor connections.
L. Signal Reference Grid Clamp: Mechanical type, stamped-steel terminal with hex head screw.
M. Straps: Solid copper, cast-bronze clamp. Rated for 600 A.
N. Tower Ground Clamps: Mechanical type, copper or copper alloy, terminal one-piece clamp.
O. U-Bolt Clamps: Mechanical type, copper or copper alloy, terminal listed for direct burial.
P. Water Pipe Clamps:
1. Mechanical type, two pieces with zinc-plated bolts.
a. Material: Steel.
b. Listed for direct burial.
2. U-bolt type with malleable-iron clamp and copper ground connector.
2.4 GROUNDING ELECTRODES
A. Ground Rods: Copper-clad steel, 3/4 inch by 10 ft.
B. Chemical-Enhanced Grounding Electrodes: Copper tube, straight or L-shaped, charged with nonhazardous electrolytic chemical salts.
1. Termination: Factory-attached No. 4/0 AWG bare conductor at least 48 inch long.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260526 – GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS, PAGE 4 OF 7
2. Backfill Material: Electrode manufacturer's recommended material.
C. Ground Plates: 1/4 inch thick, hot-dip galvanized.
PART 3 - EXECUTION
3.1 APPLICATIONS
A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for
No. 6 AWG and larger unless otherwise indicated.
B. Grounding Conductors: Green-colored insulation with continuous yellow stripe.
C. Isolated Grounding Conductors: Green-colored insulation with more than one continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal inspection, with alternating bands of green and yellow tape, with at least three bands of green and two bands of yellow.
D. Grounding Bus: Install in electrical equipment rooms, in rooms housing service equipment, and elsewhere as indicated.
1. Install bus horizontally, on insulated spacers 2 inch minimum from wall, 6 inch above finished floor unless otherwise indicated.
2. Where indicated on both sides of doorways, route bus up to top of door frame, across top of doorway, and down; connect to horizontal bus.
E. Conductor Terminations and Connections:
1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.
2. Underground Connections: Welded connectors except at test wells and as otherwise indicated.
3. Connections to Ground Rods at Test Wells: Bolted connectors.
4. Connections to Structural Steel: Welded connectors.
3.2 GROUNDING AT THE SERVICE
A. Equipment grounding conductors and grounding electrode conductors must be connected to the ground bus. Install a main bonding jumper between the neutral and ground buses.
3.3 GROUNDING SEPARATELY DERIVED SYSTEMS
A. Generator: Install grounding electrode(s) at the generator location. The electrode must be connected to the equipment grounding conductor and to the frame of the generator.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260526 – GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS, PAGE 5 OF 7
3.4 EQUIPMENT GROUNDING
A. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:
1. Feeders and branch circuits.
2. Lighting circuits.
3. Receptacle circuits.
4. Single-phase motor and appliance branch circuits.
5. Three-phase motor and appliance branch circuits.
6. Flexible raceway runs.
7. Armored and metal-clad cable runs.
8. Busway Supply Circuits: Install insulated equipment grounding conductor from grounding bus in the switchgear, switchboard, or distribution panel to equipment grounding bar terminal on busway.
B. electrode and a separate insulated equipment grounding conductor in addition to grounding conductor installed with branch-circuit conductors.
3.5 INSTALLATION
A. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.
B. Ground Rods: Drive rods until tops are 2 inch below finished floor or final grade unless otherwise indicated.
1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating if any.
2. Use exothermic welds for all below-grade connections.
3. For grounding electrode system, install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes, and connect to the service grounding electrode conductor.
C. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit.
1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.
2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install bonding so vibration is not transmitted to rigidly mounted equipment.
3. Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection is required, use a bolted clamp.
D. Grounding and Bonding for Piping:
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260526 – GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS, PAGE 6 OF 7
1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes;
use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.
2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.
3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.
E. Grounding for Steel Building Structure: Install a driven ground rod at base of each corner column and at intermediate exterior columns at distances not more than 60 ft. apart.
F. Concrete-Encased Grounding Electrode (Ufer Ground): Fabricate according to NFPA 70; use a minimum of 20 ft. of bare copper conductor not smaller than No. 4 AWG.
1. If concrete foundation is less than 20 ft. long, coil excess conductor within base of foundation.
2. Bond grounding conductor to reinforcing steel in at least four locations and to anchor bolts. Extend grounding conductor below grade and connect to building's grounding grid or to grounding electrode external to concrete.
G. Concrete-Encased Grounding Electrode (Ufer Ground): Fabricate according to NFPA 70; using electrically conductive coated steel reinforcing bars or rods, at least 20 ft. long. If reinforcing is in multiple pieces, connect together by the usual steel tie wires or exothermic welding to create the required length.
H. Connections: Make connections so possibility of galvanic action or electrolysis is minimized.
Select connectors, connection hardware, conductors, and connection methods so metals in direct contact are galvanically compatible.
1. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer in order of galvanic series.
2. Make connections with clean, bare metal at points of contact.
3. Coat and seal connections having dissimilar metals with inert material to prevent future penetration of moisture to contact surfaces.
3.6 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.
2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with a calibrated torque wrench according to manufacturer's written instructions.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260526 – GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS, PAGE 7 OF 7
3. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal. Make tests at ground rods before any conductors are connected.
a. Measure ground resistance no fewer than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance.
b. Perform tests by fall-of-potential method according to IEEE 81.
4. Prepare dimensioned Drawings locating each test well, ground rod and ground-rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.
B. Grounding system will be considered defective if it does not pass tests and inspections.
C. Prepare test and inspection reports.
D. Report measured ground resistances that exceed the following values:
1. Power and Lighting Equipment or System with Capacity of 500 kVA and Less: 10 ohms.
2. Power and Lighting Equipment or System with Capacity of 500 to 1000 kVA: 5 ohms.
3. Power and Lighting Equipment or System with Capacity More Than 1000 kVA: 3 ohms.
4. Power Distribution Units or Panelboards Serving Electronic Equipment: 1 ohm.
5. Substations and Pad-Mounted Equipment: 5 ohms.
6. Manhole Grounds: 10 ohms.
E. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect promptly and include recommendations to reduce ground resistance.