260050 FL - Basic Materials and Methods.pdf

PDF 97 KB Posted

Attached to
Electrical Infrastructure Upgrade (Optics)
Solicitation number
SV0218-26
Issued by

About this file

This document is a Technical Specifications section for electrical service upgrades at the Federal Bureau of Prisons facility in Baton Rouge, Louisiana, issued by UNICOR, FPI on March 20, 2026.

Section 260050 establishes basic electrical materials and methods requirements for the project. Key product specifications include steel pipe sleeves meeting ASTM A 53/A 53M, Type E, Grade B, Schedule 40 standards with galvanized finish, and rectangular sleeves made from galvanized sheet steel with minimum thickness of 0.052 or 0.138 inches depending on size. Sleeve seals must be modular sealing devices with EPDM interlocking links, plastic pressure plates, and carbon steel connecting bolts with corrosion-resistant coating; approved manufacturers include Advance Products & Systems, Inc., Calpico, Inc., Metraflex Co., and Pipeline Seal and Insulator, Inc. Installation requirements mandate compliance with NECA 1 standards, SCH-80 PVC for all underground raceways and turnups, and GRS-wrapped PVC corrosion-protection pipe-wrap tape extending 12 inches on either side of all transitions from underground to above-ground raceways. Penetrations through concrete slabs, masonry walls, and fire-rated assemblies require coordinated sleeve installation with firestopping per Division 7 specifications, 1/4-inch annular clear space between sleeves and raceways unless seals are installed, and extension of floor sleeves 2 inches above finished floor level. Field quality control includes inspection of all sleeve, seal, and firestopping installations for damage and defects.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Federal Bureau of Prisons MCA, LLC

ELECTRICAL SERVICE UPGRADES BATON ROUGE, LOUISIANA

UNICOR, FPI March 20, 2026

SECTION 260050 – BASIC MATERIALS AND METHODS, PAGE 1 OF 5

TECHNICAL SPECIFICATIONS

SECTION 260050

BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Electrical equipment coordination and installation.

2. Sleeves for raceways and cables.

3. Sleeve seals.

4. Common electrical installation requirements.

1.3 DEFINITIONS

A. ATS: Acceptance Testing Specifications.

B. EPDM: Ethylene-propylene-diene terpolymer rubber.

C. NBR: Acrylonitrile-butadiene rubber.

1.4 SUBMITTALS

A. Product Data: For each type of product indicated.

1.5 QUALITY ASSURANCE

A. Test Equipment Suitability and Calibration: Comply with NETA ATS, "Suitability of Test

Equipment" and "Test Instrument Calibration."

1.6 COORDINATION

A. Coordinate arrangement, mounting, and support of electrical equipment:

Federal Bureau of Prisons MCA, LLC

UNICOR, FPI March 20, 2026

SECTION 260050 – BASIC MATERIALS AND METHODS, PAGE 2 OF 5

1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.

2. To provide for ease of disconnecting the equipment with minimum interference to other installations.

3. To allow right of way for piping and conduit installed at required slope.

4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.

B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

C. Coordinate location of access panels and doors for electrical items that are behind finished surfaces or otherwise concealed. Access doors and panels are specified in Division 8 Section

"Access Doors and Frames."

D. Coordinate electrical testing of electrical, mechanical, and architectural items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.

2. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified.

2.2 SLEEVES FOR RACEWAYS AND CABLES

A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.

B. Sleeves for Rectangular Openings: Galvanized sheet steel with minimum 0.052- or 0.138-inch thickness as indicated and of length to suit application.

C. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section "Through-Penetration Firestop Systems."

2.3 SLEEVE SEALS

A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.

Federal Bureau of Prisons MCA, LLC

UNICOR, FPI March 20, 2026

SECTION 260050 – BASIC MATERIALS AND METHODS, PAGE 3 OF 5

1. Manufacturers:

a. Advance Products & Systems, Inc.

b. Calpico, Inc.

c. Metraflex Co.

d. Pipeline Seal and Insulator, Inc.

e.

2. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit.

Include type and number required for material and size of raceway or cable.

3. Pressure Plates: Plastic. Include two for each sealing element.

4. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length required to secure pressure plates to sealing elements. Include one for each sealing element.

PART 3 - EXECUTION

3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E. Right of Way: Give to raceways and piping systems installed at a required slope.

F. All underground raceways and turnups shall be SCH-80 PVC.

G. All transitions from underground raceway to above ground raceway shall be GRS wrapped with

PVC, corrosion-protection, pipe-wrap tape up to 12” on either side of each raceway material type.

3.2 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS

A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.

B. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section "Through-Penetration Firestop Systems."

Federal Bureau of Prisons MCA, LLC

UNICOR, FPI March 20, 2026

SECTION 260050 – BASIC MATERIALS AND METHODS, PAGE 4 OF 5

C. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.

D. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

E. Rectangular Sleeve Minimum Metal Thickness:

1. For sleeve cross-section rectangle perimeter less than 50 inches and no side greater than

16 inches, thickness shall be 0.052 inch.

2. For sleeve cross-section rectangle perimeter equal to, or greater than, 50 inches and 1 or more sides equal to, or greater than, 16 inches, thickness shall be 0.138 inch.

F. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.

G. Cut sleeves to length for mounting flush with both surfaces of walls.

H. Extend sleeves installed in floors 2 inches above finished floor level.

I. Size pipe sleeves to provide 1/4-inch annular clear space between sleeve and raceway or cable unless sleeve seal is to be installed.

J. Seal space outside of sleeves with grout for penetrations of concrete and masonry.

K. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Refer to Division 7 Section "Joint Sealants" for materials and installation.

L. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable penetration sleeves with firestop materials. Comply with Division 7 Section "Through-

Penetration Firestop Systems."

M. Aboveground, Exterior-Wall Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.

3.3 SLEEVE-SEAL INSTALLATION

A. Install to seal underground, exterior wall penetrations.

B. Use type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

Federal Bureau of Prisons MCA, LLC

UNICOR, FPI March 20, 2026

SECTION 260050 – BASIC MATERIALS AND METHODS, PAGE 5 OF 5

3.4 FIRESTOPPING

A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly. Firestopping materials and installation requirements are specified in Division 7 Section "Through-Penetration Firestop Systems."

3.5 FIELD QUALITY CONTROL

A. Inspect installed sleeve and sleeve-seal installations and associated firestopping for damage and faulty work.

END OF SECTION 16050