This document is a Technical Specifications section (Section 260544) for sleeves and sleeve seals for electrical raceways and cabling as part of an Electrical Service Upgrades project at a Federal Bureau of Prisons facility in Baton Rouge, Louisiana. The specification, issued March 20, 2026, covers required products including round sleeves (steel wall sleeves per ASTM A53/A53M Type E Grade B Schedule 40 with zinc coating, cast iron wall sleeves, PVC pipe sleeves per ASTM D1785 Schedule 40, molded PVC sleeves, and removable molded PE or PP sleeves), galvanized steel sheet metal sleeves both round and rectangular, modular sleeve seal systems with EPDM rubber interlocking links and carbon steel pressure plates, nonshrink grout per ASTM C1107/C1107M Grade B with 5000 psi 28-day compressive strength, single-component neutral-curing pourable sealants for horizontal surfaces, and multicomponent foam sealants that expand and cure in place without damaging cables.
Installation requirements specify that pipe sleeves should be used unless penetration arrangement requires rectangular sleeves, with a 1/4-inch annular clear space between sleeve and raceway or cable for interior non-fire-rated penetrations, extending 2 inches above finished floor level. For exterior wall penetrations, steel pipe sleeves with mechanical sleeve seal systems should be sized for a 1-inch annular clear space. Rectangular sleeves must be installed without compromising structural wall integrity, with metal sheet covering provided at both surfaces matching surrounding finishes. Sleeve seal systems must be installed in exterior concrete walls and slabs-on-grade at raceway entries, with sealing elements positioned per manufacturer recommendations and bolts tightened to create a watertight seal. All contractors must submit product data for each product type as action submittals.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Federal Bureau of Prisons MCA, LLC
ELECTRICAL SERVICE UPGRADES BATON ROUGE, LOUISIANA
UNICOR, FPI March 20, 2026
SECTION 260544 – SLEEVES AND SLEEVE SEALS FOR ELECTRICAL SYSTEMS, PAGE 1 OF 4
TECHNICAL SPECIFICATIONS
SECTION 260544
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Round sleeves.
2. Rectangular sleeves.
3. Sleeve seal systems.
4. Grout.
5. Pourable sealants.
6. Foam sealants.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
PART 2 - PRODUCTS
2.1 ROUND SLEEVES
A. Wall Sleeves, Steel:
1. Description: ASTM A53/A53M, Type E, Grade B, Schedule 40, zinc coated, plain ends and integral waterstop.
B. Wall Sleeves, Cast Iron:
1. Description: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop.
C. Pipe Sleeves, PVC:
1. Description: ASTM D1785, Schedule 40.
D. Molded Sleeves, PVC:
1. Description: With nailing flange for attaching to wooden forms.
E. Molded Sleeves, PE or PP:
1. Description: Removable, tapered-cup shaped, and smooth outer surface with nailing flange for attaching to wooden forms.
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260544 – SLEEVES AND SLEEVE SEALS FOR ELECTRICAL SYSTEMS, PAGE 2 OF 4
F. Sheet Metal Sleeves, Galvanized Steel, Round:
1. Description: Galvanized-steel sheet; thickness not less than 0.0239 inch; round tube closed with welded longitudinal joint, with tabs for screw-fastening the sleeve to the board.
2.2 RECTANGULAR SLEEVES
A. Sheet Metal Sleeves, Galvanized Steel, Rectangular:
1. Description:
a. Material: Galvanized sheet steel.
b. Minimum Metal Thickness:
1) For sleeve cross-section rectangle perimeter less than 50 inch and with no side larger than 16 inch, thickness must be 0.052 inch.
2) For sleeve cross-section rectangle perimeter not less than 50 inch or with one or more sides larger than 16 inch, thickness must be 0.138 inch.
2.3 SLEEVE SEAL SYSTEMS
A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable or between raceway and cable.
1. Sealing Elements: EPDM rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.
2. Pressure Plates: Carbon steel.
3. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, of length required to secure pressure plates to sealing elements.
2.4 GROUT
A. Description: Nonshrink; recommended for interior and exterior sealing openings in non-fire-rated walls or floors.
1. Standard: ASTM C1107/C1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.
2. Design Mix: 5000 psi, 28-day compressive strength.
3. Packaging: Premixed and factory packaged.
2.5 POURABLE SEALANTS
A. Description: Single-component, neutral-curing elastomeric sealants of grade indicated below.
1. Grade: Pourable (self-leveling) formulation for openings in floors and other horizontal surfaces that are not fire rated.
B. Sustainability Criteria:
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260544 – SLEEVES AND SLEEVE SEALS FOR ELECTRICAL SYSTEMS, PAGE 3 OF 4
2.6 FOAM SEALANTS
A. Description: Multicomponent, liquid elastomers that, when mixed, expand and cure in place to produce a flexible, nonshrinking foam. Foam expansion must not damage cables or crack penetrated structure.
B. Sustainability Criteria:
PART 3 - EXECUTION
3.1 INSTALLATION OF SLEEVES FOR NON-FIRE-RATED ELECTRICAL PENETRATIONS
A. Sleeves for Conduits Penetrating Above-Grade, Non-Fire-Rated, Concrete and Masonry-Unit
Floors and Walls:
1. Interior Penetrations of Non-Fire-Rated Walls and Floors:
a. Seal space outside of sleeves with mortar or grout. Pack sealing material solidly between sleeve and wall or floor so no voids remain. Tool exposed surfaces smooth; protect material while curing.
b. Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in
Section 079200 "Joint Sealants."
2. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
3. Size pipe sleeves to provide 1/4 inch annular clear space between sleeve and raceway or cable, unless sleeve seal system is to be installed.
4. Install sleeves for wall penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of walls. Cut sleeves to length for mounting flush with both surfaces of walls. Deburr after cutting.
5. Install sleeves for floor penetrations. Extend sleeves installed in floors 2 inch above finished floor level. Install sleeves during erection of floors.
B. Sleeves for Conduits Penetrating Non-Fire-Rated Wall Assemblies:
1. Use circular metal sleeves unless penetration arrangement requires rectangular sleeved opening.
2. Seal space outside of sleeves with approved joint compound for wall assemblies.
C. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible boot-type flashing units applied in coordination with roofing work.
D. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve seal systems. Size sleeves to allow for 1 inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.
E. Underground, Exterior-Wall and Floor Penetrations:
Federal Bureau of Prisons MCA, LLC
UNICOR, FPI March 20, 2026
SECTION 260544 – SLEEVES AND SLEEVE SEALS FOR ELECTRICAL SYSTEMS, PAGE 4 OF 4
1. Install steel pipe sleeves with integral waterstops. Size sleeves to allow for 1 inch annular clear space between raceway or cable and sleeve for installing sleeve seal system. Install sleeve during construction of floor or wall.
2. Install steel pipe sleeves. Size sleeves to allow for 1 inch annular clear space between raceway or cable and sleeve for installing sleeve seal system. Grout sleeve into wall or floor opening.
3.2 INSTALLATION OF RECTANGULAR SLEEVES AND SLEEVE SEALS
A. Install sleeves in existing walls without compromising structural integrity of walls. Do not cut structural elements without reinforcing the wall to maintain the designed weight bearing and wall stiffness.
B. Install conduits and cable with no crossings within the sleeve.
C. Fill opening around conduits and cables with expanding foam without leaving voids.
D. Provide metal sheet covering at both wall surfaces and finish to match surrounding surfaces.
Metal sheet must be same material as sleeve.
3.3 INSTALLATION OF SLEEVE SEAL SYSTEMS
A. Install sleeve seal systems in sleeves in exterior concrete walls and slabs-on-grade at raceway entries into building.
B. Install type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.