25-0009 ACM Report.pdf
PDF 64 KB Posted
- Attached to
- Repair BEQ FC555
- Solicitation number
- N4008526R9043
About this file
This is an Asbestos Inspection Report for Building FC555 (Forward Maint Alpha Company BEQ) at MCB Camp Lejeune, dated September 2, 2025. The building was constructed in 1978 and currently holds a Hazard Rank 3/Green designation as of March 2023. The report documents a comprehensive asbestos survey history spanning from 2002 through March 2023, tracking the identification, testing, and condition of asbestos-containing materials (ACM) within the structure.
The inspection identified non-friable ACM present in the building, including tar paper and roofing sealants in the attic/old roof perimeter and parapet wall flashings (2,880 square feet), and residual mastic patches at mechanical rooms and under existing flooring in dormitory rooms (ranging from 2-5 square feet as of the most recent 2023 inspection). The report notes that no friable ACM has been identified. Testing results from multiple sampling dates confirm the presence of chrysotile asbestos (denoted as "9" in the testing columns) in tar paper, roofing sealants, and residual mastic. The Camp Lejeune Asbestos Program Manager maintains oversight of the building and can be contacted at 910-451-5837. The report emphasizes that intact and undisturbed ACM does not constitute a significant health hazard, and recommends avoiding disturbance, preventing damage to materials, and reporting any changes in condition to the Program Manager. Periodic inspections of the ACM will continue to evaluate condition changes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| N4008525B0009 Specs.pdf | ||
| 25-0009 SID.pdf | ||
| 25-0009 BOD.pdf | ||
| 25-0009 Asbestos and Lead Survey.pdf | ||
| 25-0009 APPD.pdf | ||
| RFP 250009.pdf | ||
| N4008525B0009 DWGs.pdf | ||
| 25-0009 DM.pdf | ||
| 25-0009 GEO.pdf | ||
| 25-0009 FPDA.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS INSPECTION REPORT of:
Building # FC555
MCB CAMP LEJEUNE
Tuesday, September 2, 2025
Print Date
Tuesday, September 2, 2025 Page 1 of 9Print Date:
INSPECTION SUMMARY
BLDG #:
OCCUPANT:
YEAR BUILT:
BUILDING COMMENTS:
FC555
FORWARD MAINT ALPHA
COMPANY BEQ
HAZ RANK 3/GREEN [MAR2023]
ROOFING MATERIALS
MAR2023
ACM REMAINS
SEPT2019
NO CHANGES
JUN2016
ACM REMAINS
NOV2013
LIMITED RESIDUAL MASTIC AND ROOFING MATERIALS REMAIN
AUG2011
BUILDING HAS BEEN RENOVATED, OLD FLOORING REMOVED/ REPLACED, OLD ROOFING AND RESIDUAL MASTIC REMAINS ADDL
SAMPLING, ACM CONFIRMED, NO ADDL ACM ID'D
NOV08
PVS. ACM REMAINS, ADDL SAMPLING, ACM INCLUDES:
RESIDUAL TILE MASTIC
ROOFING TAR PAPER
ROOFING SEALANTS
SEP05
PVS. ACM TILE AND MASTIC REMAINS; ADDL SAMPLING, NO ADDL ACM ID'D
JUL02 AES
ACM INCLUDES:
12" BEIGE TILE AND ADHESIVE
ASBESTOS MANAGER: 910-451-5837
Friable ACM(s) identified
Non-friable ACM(s) identified
NOTICE: The following asbestos-containing materials have been identified in this structure. Refer to survey findings for additional information or contact the Asbestos Program Manager. Please note ACM that is intact and undisturbed is not considered a significant health hazard to building occupants.
DESCRIPTION LOCATION Date Quantity
DESCRIPTION LOCATION Date Quantity
No friable ACM records found in database
NOTIFICATION OF ACM IN BUILDING
TAR PAPER, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
11/17/2008
Tuesday, September 2, 2025 Page 2 of 9Print Date:
ROOFING SEALANT, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
(INCORPORATES HMs 30, 32, 34)
11/17/2008
RESIDUAL MASTIC 2 SFPATCHES AT MECHANICAL ROOMS
(PREVIOUS HM01 FLOORING);
POTENTIAL PATCHES UNDER NEW/
EXISTING FLOORING [HM40] IN DORM
ROOMS
11/17/2008
ROOFING SEALANT, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
(INCORPORATES HMs 30, 32, 34)
9/18/2019
TAR PAPER, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
9/18/2019
RESIDUAL MASTIC 5 SFPATCHES AT MECHANICAL ROOMS
(PREVIOUS HM01 FLOORING);
POTENTIAL PATCHES UNDER NEW/
EXISTING FLOORING [HM40] IN DORM
ROOMS
9/18/2019
RESIDUAL MASTIC 4 SFPATCHES AT MECHANICAL ROOMS
(PREVIOUS HM01 FLOORING);
POTENTIAL PATCHES UNDER NEW/
EXISTING FLOORING [HM40] IN DORM
ROOMS
8/24/2011
TAR PAPER, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS (w/HM31)
8/24/2011
ROOFING SEALANT, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
(INCORPORATES HMs 30, 32, 34)
8/24/2011
ROOFING SEALANT, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
(INCORPORATES HMs 30, 32, 34)
11/12/2013
TAR PAPER, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
6/9/2016
ROOFING SEALANT, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
(INCORPORATES HMs 30, 32, 34)
6/9/2016
RESIDUAL MASTIC 4 SFPATCHES AT MECHANICAL ROOMS
(PREVIOUS HM01 FLOORING);
POTENTIAL PATCHES UNDER NEW/
EXISTING FLOORING [HM40] IN DORM
ROOMS
6/9/2016
RESIDUAL MASTIC 4 SFPATCHES AT MECHANICAL ROOMS
(PREVIOUS HM01 FLOORING);
POTENTIAL PATCHES UNDER NEW/
EXISTING FLOORING [HM40] IN DORM
ROOMS
11/12/2013
TAR PAPER, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS (w/HM31)
11/12/2013
Tuesday, September 2, 2025 Page 3 of 9Print Date:
Tested Non ACM or REMOVED Materials
DESCRIPTION LOCATION Date
RESIDUAL MASTIC 2 SFPATCHES AT MECHANICAL ROOMS
(PREVIOUS HM01 FLOORING);
POTENTIAL PATCHES UNDER NEW/
EXISTING FLOORING [HM40] IN DORM
ROOMS
3/28/2023
TAR PAPER, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
3/28/2023
ROOFING SEALANT, BLACK 2,880 SFATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS
(INCORPORATES HMs 30, 32, 34)
3/28/2023
ROOFING SEALANT, SILVER ATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS (OVER HM
30, 31)
11/17/2008
MISCELLANEOUS SEALANT MECHANICAL ROOMS AT DUCT TO
CHASE PLATES
11/17/2008
DUCT SEALANT, GRAY DORM ROOM OVHD DUCTS AND
DEBRIS/ DRIPPAGE IN MECHANICAL
ROOMS
11/17/2008
MISCELLANEOUS SEALANT CONDUIT PACKING/ FIRESTOP IN
CENTRAL PIPE CHASES
11/17/2008
INTERIOR CAULKING, METAL PIPE CHASE DOORS 11/17/2008
CAULKING MATERIAL DEBRIS IN MECHANICAL ROOMS (SEE
ALSO HM23)
11/17/2008
INTERIOR CAULKING, DORM ROOMS (AND CONVERTED
MECHANICAL ROOMS) AT HEAD
AREAS, SHOWER TILE WALLS (SEE
ALSO HM29)
11/17/2008
INTERIOR CAULKING, PIPE CHASES AT CABLE/ CONDUIT
PENETRATIONS
11/17/2008
ROOFING MATERIAL, ROOFING SYSTEM UNDERLAYMENT
BOARD DEBRIS
11/17/2008
ROOFING MATERIAL, ROOF/ ATTIC; MAIN ROOF MEMBRANE
UNDERLAYMENT (SEE ALSO HM30, 31,
32)
11/17/2008
TEXTURED CEILING MATERIAL THROUGHOUT HOMOGENOUS
BUILDINGS
9/20/2005
TAR PAPER, BLACK NEW ROOF, UNDER ASPHALT SHINGLES 8/24/2011
12" BEIGE FLOOR TILE AND ADHESIVE OFFICES AND LIVING QUARTERS 7/18/2002
EXTERIOR CAULKING, METAL DOORS TO PIPE CHASES
THROUGHOUT
9/20/2005
DUCT SEALANT, GRAY CHASES AND ATTIC/ OLD ROOF DUCTS
THROUGHOUT
9/20/2005
EXTERIOR CAULKING, BRICK EXPANSION JOINTS, EAST AND
WEST CENTER
9/20/2005
Tuesday, September 2, 2025 Page 4 of 9Print Date:
ACM only presents a health hazard when asbestos fibers are airborne and inhaled.
Avoid disturbance which will release fibers. The presence of asbestos does not constitute a health hazard.
HEALTH ASPECTS:
Do not disturb or cause damage to ACM. Do not sand, grind or abrade materials or cause damage with any type of equipment.
CONDITIONS TO AVOID:
Report any damage, dust or debris that may come from ACM or suspect ACM, or any change in the condition of materials, or accidental disturbance to the Asbestos
Program Manager.
REPORTS OF DAMAGE:
Corrective action initiated to minimize fiber release and protect personnel. RESPONSE ACTION:
ACM will be inspected periodically to evaluate any changes in condition.INSPECTION:
The Camp Lejeune Asbestos Program Manager maintains a copy of the survey for the building.
RECORDKEEPING:
CAMP LEJEUNE Asbestos Program Manager: Phone: (910) 451-5837
EXTERIOR CAULKING, CONCRETE DECK JOINTS AT WALLS 11/17/2008
JOINT MATERIAL DORM ROOM HEAD AREA CEILINGS
(SKIM COAT)
11/17/2008
FELT PAPER DORM ROOM SHOWER PAN LINER
MATERIAL (UNDER TILE AND
CONCRETE)
8/24/2011
BUILT-UP ROOFING ATTIC/ ROOF; TOP LAYER MAIN
MEMBRANE
8/24/2011
ROOFING SEALANT, BLACK NEW ROOF; ACCESS HATCH FLASHINGS 8/24/2011
ROOFING SEALANT, GRAY NEW ROOF; ACCESS HATCH FLASHINGS 8/24/2011
12" TAN FLOOR TILE AND ADHESIVE [NEW] FLOORING THROUGHOUT 8/24/2011
12" BEIGE FLOOR TILE AND ADHESIVE OFFICES AND LIVING QUARTERS 11/17/2008
TEXTURED CEILING MATERIAL MECH ROOM 11/17/2008
ROOFING MATERIAL, ROOF/ ATTIC, MAIN ROOF MEMBRANE
(SEE ALSO HM30, 31, 32)
8/24/2011
12" BEIGE FLOOR TILE AND ADHESIVE OFFICES AND LIVING QUARTERS 9/20/2005
INTERIOR CAULKING, DORM ROOMS (AND CONVERTED
MECHANICAL ROOMS) AT HEAD
AREAS, SHOWER TILE WALLS (SEE
ALSO HM29); DOORS INTERIOR AND
EXTERIOR
8/24/2011
ROOFING SEALANT, SILVER ATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS (OVER HM
30, 31)
8/24/2011
ROOFING SEALANT, SILVER ATTIC/ OLD ROOF; PERIMETER
PARAPET WALL FLASHINGS (OVER HM
30, 31)
11/12/2013
Tuesday, September 2, 2025 Page 5 of 9Print Date:
SAMPLES COLLECTED
Sample Sample
Date
HA Sample Location Chr
Amo
Oth
Description
FC555-01-00 7/18/200201 FC550 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
FC555-01-00ri05 9/20/200501 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
FC555-01-00ri07 11/17/200801 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
FC555-11-10 9/20/200511 1ST FL NORTH CNTR CHASE 0 0 0EXTERIOR CAULKING, GRAY
FC555-12-10 9/20/200512 CHASE 0 0 0DUCT SEALANT, GRAY
FC555-13-10 9/20/200513 NORTH WING, SE OFFICE 0 0 0TEXTURED CEILING
MATERIAL
FC555-14-10 9/20/200514 1ST FL EAST CNTR 0 0 0EXTERIOR CAULKING, GRAY
FC555-20-20 11/17/200820 1ST FL NORTH CNTR CHASE 0 0 0EXTERIOR CAULKING, WHITE
FC555-21-20 11/17/200821 1ST FL NORTH, NE RM 0 0 0JOINT MATERIAL
FC555-21-21 11/17/200821 1ST FL SOUTH, NW RM 0 0 0JOINT MATERIAL
FC555-21-22 11/17/200821 1ST FL SOUTH, SE RM 0 0 0JOINT MATERIAL
FC555-21-23 11/17/200821 2ND FL NORTH, EAST CNTR
RM
0 0 0JOINT MATERIAL
FC555-21-24 11/17/200821 2ND FL NORTH, NW RM 0 0 0JOINT MATERIAL
FC555-21-25 11/17/200821 2ND FL SOUTH, SW RM 0 0 0JOINT MATERIAL
FC555-21-26 11/17/200821 3RD FL SOUTH, SE RM 0 0 0JOINT MATERIAL
FC555-21-27 11/17/200821 3RD FL NORTH, NE RM 0 0 0JOINT MATERIAL
FC555-21-28 11/17/200821 3RD FL NORTH, EAST CNTR
RM
0 0 0JOINT MATERIAL
FC555-22-20 11/17/200822 1ST FL SOUTH CHASE, SOUTH 0 0 0INTERIOR CAULKING, YELLOW
FC555-23-20 11/17/200823 1ST FL NORTH, WEST CNTR
MR
0 0 0INTERIOR CAULKING, WHITE
FC555-23-21 11/17/200823 2ND FL NORTH, WEST CNTR
MR
0 0 0INTERIOR CAULKING, WHITE
FC555-23-22 11/17/200823 2ND FL SOUTH, WEST CNTR
MR
0 0 0INTERIOR CAULKING, WHITE
Tuesday, September 2, 2025 Page 6 of 9Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC555-23-23 11/17/200823 2ND FL SOUTH, WEST CNTR
MR
0 0 0INTERIOR CAULKING, WHITE
FC555-23-24 11/17/200823 3RD FL NORTH, WEST CNTR
MR
0 0 0INTERIOR CAULKING, WHITE
FC555-23-30 8/24/201123 1ST FL CNTR LOUNGE 0 0 0INTERIOR CAULKING, WHITE
FC555-23-31 8/24/201123 1ST FL NORTH, WEST CNTR
MECH RM
0 0 0INTERIOR CAULKING, WHITE
FC555-23-32 8/24/201123 1ST FL NORTH, WEST CNTR
MECH RM DOOR
0 0 0INTERIOR CAULKING, WHITE
FC555-24-20 11/17/200824 1ST FL NORTH, WEST CNTR
MR
0 0 0MISCELLANEOUS
SEALANT
RED
FC555-24-21 11/17/200824 3RD FL NORTH, WEST CNTR
MR
0 0 0MISCELLANEOUS
SEALANT
RED
FC555-25-20 11/17/200825 1ST FL NORTH, WEST CNTR
MR
0 0 0DUCT SEALANT, GRAY
FC555-25-21 11/17/200825 3RD FL NORTH, WEST CNTR
MR
0 0 0DUCT SEALANT, GRAY
FC555-26-00ri13 11/12/201326 N/A 9 9 9RESIDUAL MASTIC BLACK
FC555-26-00ri16 6/9/201626 N/A 9 9 9RESIDUAL MASTIC BLACK
FC555-26-00ri19 9/18/201926 N/A 9 9 9RESIDUAL MASTIC BLACK
FC555-26-00ri23 3/28/202326 N/A 9 9 9RESIDUAL MASTIC BLACK
FC555-26-20 11/17/200826 1ST FL SOUTH, WEST CNTR
MECH RM
3 0 0RESIDUAL MASTIC BLACK
FC555-26-30 8/24/201126 2ND FL SOUTH, WEST CNTR
MECH RM
3 0 0RESIDUAL MASTIC BLACK
FC555-27-20 11/17/200827 2ND FL NORTH CHASE,
SOUTH CNTR
0 0 0MISCELLANEOUS
SEALANT
GRAY
FC555-28-20 11/17/200828 3RD FL SOUTH, SOUTH 0 0 0INTERIOR CAULKING, GRAY
FC555-29-20 11/17/200829 3RD FL NORTH, WEST CNTR
MR
0 0 0CAULKING MATERIAL WHITE
FC555-30-00ri13 11/12/201330 N/A 9 9 9TAR PAPER, BLACK
FC555-30-00ri16 6/9/201630 N/A 9 9 9TAR PAPER, BLACK
FC555-30-00ri19 9/18/201930 N/A 9 9 9TAR PAPER, BLACK
Tuesday, September 2, 2025 Page 7 of 9Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC555-30-00ri23 3/28/202330 N/A 9 9 9TAR PAPER, BLACK
FC555-30-20 11/17/200830 ATTIC/ ROOF; SOUTH CNTR 45 0 0TAR PAPER, BLACK
FC555-30-21 11/17/200830 ATTIC/ ROOF; NORTH CNTR 35 0 0TAR PAPER, BLACK
FC555-30-30 8/24/201130 ATTIC/ ROOF; SOUTH CNTR 4 0 0TAR PAPER, BLACK
FC555-31-00ri11 8/24/201131 N/A 9 9 9ROOFING SEALANT, BLACK
GRAY, SILVER
FC555-31-00ri13 11/12/201331 N/A 9 9 9ROOFING SEALANT, BLACK
GRAY, SILVER
FC555-31-00ri16 6/9/201631 N/A 9 9 9ROOFING SEALANT, BLACK
GRAY, SILVER
FC555-31-00ri19 9/18/201931 N/A 9 9 9ROOFING SEALANT, BLACK
GRAY, SILVER
FC555-31-00ri23 3/28/202331 N/A 9 9 9ROOFING SEALANT, BLACK
GRAY, SILVER
FC555-31-20 11/17/200831 ROOF/ ATTIC; SOUTH CNTR 8 0 0ROOFING SEALANT,
BLACK
GRAY, SILVER
FC555-31-21 11/17/200831 ROOF/ ATTIC; NORTH CNTR 0 0 0ROOFING SEALANT,
BLACK
GRAY, SILVER
FC555-32-00ri13 11/12/201332 N/A 9 9 9ROOFING SEALANT, SILVER
FC555-32-20 11/17/200832 ATTIC/ ROOF; SOUTH CNTR 3 0 0ROOFING SEALANT,
SILVER
FC555-32-21 11/17/200832 ATTIC/ ROOF, NORTH CNTR 3 0 0ROOFING SEALANT,
SILVER
FC555-32-30 8/24/201132 ATTIC/ ROOF; SOUTH CNTR 5 0 0ROOFING SEALANT,
SILVER
FC555-33-20 11/17/200833 ATTIC/ ROOF; SOUTH CNTR 0 0 0ROOFING MATERIAL, BROWN
FC555-34-20 11/17/200834 ATTIC/ ROOF, SOUTH CNTR 0 0 0ROOFING MATERIAL, BLACK
FC555-34-21 11/17/200834 ATTIC/ ROOF, NORTH CNTR 2 0 0ROOFING MATERIAL, BLACK
FC555-34-30 8/24/201134 ATTIC/ ROOF; SOUTH CNTR
ON CONCRETE
0 0 0ROOFING MATERIAL, BLACK
FC555-34-31 8/24/201134 ATTIC/ ROOF; CNTR ON
CONCRETE
0 0 0ROOFING MATERIAL, BLACK
FC555-34-32 8/24/201134 ATTIC/ ROOF; NORTH CNTR
ON CONCRETE
0 0 0ROOFING MATERIAL, BLACK
Tuesday, September 2, 2025 Page 8 of 9Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC555-40-30 8/24/201140 1ST FL SOUTH, NE RM117
CLOSET
0 0 012" TAN FLOOR TILE
AND ADHESIVE
FC555-40-30tem 8/24/201140 1ST FL SOUTH, NE RM117
CLOSET
0 0 012" TAN FLOOR TILE
AND ADHESIVE
FC555-40-31 8/24/201140 1ST FL SOUTH, SW RM128 0 0 012" TAN FLOOR TILE
AND ADHESIVE
FC555-40-32 8/24/201140 2ND FL SOUTH, SW RM226 0 0 012" TAN FLOOR TILE
AND ADHESIVE
FC555-40-33 8/24/201140 3RD FL NORTH, EAST CNTR
RM311
0 0 012" TAN FLOOR TILE
AND ADHESIVE
FC55-41-31 8/24/201141 3RD FL NORTH, WEST MECH
RM
0 0 0FELT PAPER BLACK
FC555-41-30 8/24/201141 2ND FL SOUTH, WEST MECH
RM
0 0 0FELT PAPER BLACK
FC555-42-30 8/24/201142 ATTIC/ ROOF; SOUTH CNTR 0 0 0BUILT-UP ROOFING BLACK
FC555-42-31 8/24/201142 ATTIC/ ROOF; CNTR 0 0 0BUILT-UP ROOFING BLACK
FC555-42-32 8/24/201142 ATTIC/ ROOF; NORTH CNTR 0 0 0BUILT-UP ROOFING BLACK
FC555-43-30 8/24/201143 ROOF; SOUTH ACCESS
HATCH
0 0 0ROOFING SEALANT,
BLACK
FC555-44-30 8/24/201144 ROOF; SOUTH ACCESS
HATCH
0 0 0ROOFING SEALANT,
GRAY
FC555-45-30 8/24/201145 ROOF; SOUTH ACCESS
HATCH
0 0 0TAR PAPER, BLACK
Tuesday, September 2, 2025 Page 9 of 9Print Date: