About this file

Mechanical System Renovation Specifications for Florida National Guard Palmetto Readiness Center

This is a mechanical engineering construction document prepared by BAL Engineering, Inc. for the Florida Department of Military Affairs regarding HVAC system upgrades at the Palmetto Readiness Center located at 1107 14th Avenue West, Palmetto, Florida 34221. The project scope includes removal of existing DX split system air handlers (AHU-3 and AHU-4) and associated condensing units, installation of new air handlers with hot gas reheat for humidity control, installation of new condensing units (CU-3 and CU-4) secured to concrete housekeeping pads, installation of stand-alone and ducted dehumidifiers to serve multiple zones, and removal of existing exhaust fans with new fan installation. The document provides detailed mechanical load summaries based on Florida Building Code 8th Edition (2023) design conditions (outdoor 94°F dry bulb/77°F wet bulb, indoor 75°F dry bulb/50% RH), with AHU-3 requiring 66,500 BTU total cooling and AHU-4 requiring 43,400 BTU total cooling. Equipment schedules identify specific manufacturers including Trane air handlers, Mitsubishi mini-split units, and Greenheck exhaust fans with corresponding capacities and electrical specifications. The mechanical plans indicate seven existing air handling units to remain (AHU-1, AHU-2, AHU-5, AHU-6, AHU-7), three new units to be installed (AHU-3N, AHU-4N, MAC-1N), and seven condensing units with varying capacities from 1 to 18.1 tons. Construction documents are dated March 30, 2026, with Addendum 02 issued June 17, 2026.

The specifications require strict compliance with Florida Building Code 8th Edition (2023), NFPA standards (90A, 101), ASHRAE standards (62.1-2019, 126-2016, 180-2018), and SMACNA duct construction standards. All ductwork must be internally insulated with minimum 1.5-inch R-6 duct liner, with supply ducts rated for 3-inch pressure class upstream of VAV boxes and 1-inch downstream, and return ducts at minimum -3-inch pressure class. Duct leakage is limited to 2 percent for ducts rated ≤2 inches WG and 1 percent for higher ratings, verified through independent NEBB or AABC certified test and balance agencies. Condensate drain lines must be copper, sized one diameter larger than unit connections (minimum 3/4 inch), with all lines sloped at minimum 1/8 inch per foot and insulated with 3/4-inch seamless closed-cell rubber insulation. Refrigerant piping requires sizing per manufacturer recommendations with suction lines insulated in 3/4-inch closed-cell rubber with UV-resistant coating for exterior exposure. The document includes eight alternate bid items addressing parking stormwater mitigation, LED lighting upgrades, exterior facade refinishing, impact glazing replacement, fence systems, pavement overlays, and vault dehumidification systems. All equipment must be labeled with laminated plastic signs, and roof-mounted equipment must be secured per Florida Product Approval listings or third-party structural engineer certification. An independent commissioning authority must be retained to perform HVAC system commissioning per Florida Energy Conservation Code, with as-built drawings, O&M manuals, and commissioning reports due within 90 days of certificate of occupancy.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FBC FLORIDA BUILDING CODE 8TH EDITION (2023) ENERGY CONSERVATION

PROJECT LOAD SUMMARYC403.2.1

PROJECT: FLORIDA NATIONAL GUARD

PALMETTO READINESS

CENTER

1107 14TH AVE WEST

PALMETTO, FLORIDA 34221

OWNER: DEPARTMENT OF MILITARY

AFFAIRS

P.O. BOX 1008

ST. AUGUSTINE, FLORIDA,

32085-1008

AHU-3[N]/CU-3[N] AHU-4[N]/CU-4[N]

ZONE AREA: 1700 ZONE AREA: 1923

CONDITIONED AREA: 1700 CONDITIONED AREA: 1923

SIZING METHOD: HEAT BALANCE METHOD SIZING METHOD: HEAT BALANCE METHOD

OUTDOOR DRY BULB: 94.0 OUTDOOR DRY BULB: 94.0

OUTDOOR WET BULB: 77.0 OUTDOOR WET BULB: 77.0

INDOOR DRY BULB: 75 INDOOR DRY BULB: 75

INDOOR RH: 50% INDOOR RH: 50%

TOTAL COOLING REQUIRED: 66,500 TOTAL COOLING REQUIRED: 43,400

TOTAL HEATING REQUIRED: 25,000 TOTAL HEATING REQUIRED: 23,000

TOTAL SENSIBLE GAIN: 54,400 TOTAL SENSIBLE GAIN: 38,600

TOTAL LATENT GAIN: 12,100 TOTAL LATENT GAIN: 4,800

GRAINS WATER (DIFFERENCE): 114.7 - 64 = 50.7 GRAINS WATER (DIFFERENCE): 114.7 - 64 = 50.7

MAC-1[N]/MCU-1[N]

ZONE AREA: 210

CONDITIONED AREA: 210

SIZING METHOD: HEAT BALANCE METHOD

OUTDOOR DRY BULB: 94.0

OUTDOOR WET BULB: 77.0

INDOOR DRY BULB: 75

INDOOR RH: 50%

TOTAL COOLING REQUIRED: 12,000

TOTAL HEATING REQUIRED: 0

TOTAL SENSIBLE GAIN: 9,240

TOTAL LATENT GAIN: 2,760

GRAINS WATER (DIFFERENCE): 78.6-64.6 = 14.0

GENERAL MECHANICAL NOTES

M

230000

1. THE INTENT OF THESE NOTES AND MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE SCOPE OF WORK AND ALERT THE CONTRACTOR OF FIELD CONDITIONS. CONTRACTOR TO VISIT SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK AND PROVIDE ADDITIONAL OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS AND COORDINATE WITH ELECTRICAL, PLUMBING AND FIRE PROTECTION SUBCONTRACTOR BEFORE ANY CONSTRUCTION WORK. NO ALLOWANCES WILL BE MADE FOR THE CONTRACTOR'S UNFAMILIARITY WITH THE JOB SITE AND CONDITIONS.

2. PLANS SHALL NOT BE SCALED. PLANS INDICATE THE SCHEMATIC LAYOUT AND LOCATION OF THE MECHANICAL SYSTEM COMPONENTS. UNLESS SPECIFIC DIMENSIONS ARE NOTED, THE ACTUAL LOCATION OF THESE COMPONENTS SHALL BE DETERMINED IN THE FIELD IN COORDINATION WITH THE WORK OF OTHER TRADES, THE USE OF MANUFACTURER’S SHOP DRAWINGS AND SIMILAR CERTIFIED DATA. THE ELEVATION OF EXPOSED DUCTWORK SHALL BE COORDINATED

WITH THE ARCHITECT PRIOR TO ORDERING ANY DUCTWORK.

3. NO EXCLUSIONS FROM OR LIMITATIONS IN THE LANGUAGE USED IN THE CONTRACT DOCUMENTS SHALL BE INTERPRETED AS MEANING THAT THE EQUIPMENT, APPURTENANCES, AND/OR ACCESSORIES NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM ARE NOT TO BE PROVIDED AS REQUIRED.

a. THE CONTRACTOR SHALL HAVE A COMPLETE SET OF THE CONTRACT DOCUMENTS. THE SEPARATE DIVISIONAL DRAWINGS AND SPECIFICATIONS DO

NOT RELIEVE THE CONTRACTOR FROM THE RESPONSIBILITY TO PROVIDE THE WORK WHICH IS INDICATED ON ANY OF THE DRAWINGS OR DIVISION OF THE SPECIFICATIONS. REVIEW AND COORDINATE THE SCOPE OF WORK TO ASSURE A COMPLETE FUNCTIONAL SYSTEM IS INSTALLED. SHOP

DRAWINGS OF ALL EQUIPMENT AND MATERIALS FOR REVIEW.

4. SUBMIT SHOP DRAWINGS OF ALL EQUIPMENT AND MATERIALS FOR REVIEW. WHERE MANUFACTURERS ARE LISTED IN THE PROJECT MANUAL, ONE OF THOSE MANUFACTURERS SHALL BE PROVIDED UNLESS A REQUEST FOR SUBSTITUTION HAS BEEN SUBMITTED PRIOR TO BID AND THE MANUFACTURER SUBSEQUENTLY IS LISTED AS AN ACCEPTABLE MANUFACTURER IN AN ADDENDUM. PARTIAL SUBMITTALS WILL NOT BE ACCEPTED FOR REVIEW AND APPROVAL.

INSTALL AND TEST ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS AND RECOMMENDATIONS. FOR ALL EQUIPMENT, WHICH HAS BEEN SCHEDULED DIRECTLY ON THE DRAWINGS, PROVIDE WITHIN THE SUBMITTAL, A PERFORMANCE SCHEDULE FOR THE PROPOSED EQUIPMENT IN THE EXACT SAME FORMAT AS INCLUDED ON THE CONTRACT DOCUMENTS. FAILURE TO PROVIDE THE REQUIRED PERFORMANCE SCHEDULE WILL RESULT IN REJECTION OF THE ENTIRE SUBMITTAL. SUBMIT DRAWINGS AND CUT SHEETS FOR ALL PRODUCTS ALL AT ONE TIME. INDEX ALL ITEMS TO THE PROJECT MANUAL OR DRAWINGS AS APPLICABLE. SHOP DRAWINGS THAT DEVIATE FROM THE REQUIREMENTS OF THE CONTRACT DOCUMENTS SHALL LIST ALL DIFFERENCES IN A COVER LETTER ATTACHED TO THE FRONT OF THE SUBMITTAL. ANY UNLISTED DEVIATIONS FOUND DURING THE REVIEW WILL RESULT IN THE REJECTION OF THE ENTIRE SUBMITTAL. FOR ITEMS REVIEWED AND MARKED "REJECTED" OR "REVISE AND RESUBMIT”, ONLY ONE ADDITIONAL SUBMITTAL WILL BE REVIEWED TO VERIFY PRODUCT COMPLIANCE WITH THE CONTRACT DOCUMENTS. SHOULD FURTHER SUBMITTALS BE REQUIRED FOR THE DESIGN PROFESSIONAL TO VERIFY THE SUBMITTAL WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS, THE HOURLY RATE OF $150.00 PLUS EXPENSES WILL BE

BILLED TO THE CONTRACTOR FOR THE PROFESSIONAL(S) TIME IS SPENT ON THE REVIEW.

5. DUCTWORK, AIR DEVICES AND OTHER ITEMS OF THE AIR DISTRIBUTION SYSTEM SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING STRUCTURE AND NOT FROM THE CEILING OR CEILING SUSPENSION SYSTEM. COORDINATE LOCATION OF AIR DEVICES AND LOUVERS WITH ELECTRICAL, ARCHITECTURAL, AND PLUMBING WORK. AIR DEVICES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE FROM AT LEAST TWO POINTS.

6. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF "SMACNA" DUCT CONSTRUCTION STANDARDS AND COMPLY WITH THE LATEST "NFPA" 90A REQUIREMENTS. ALL DUCT\'WORK SHALL BE LEAK TESTED IN ACCORDANCE WITH SMACNA AND ASHRAE STANDARDS, AND BE COMPLETED BY THE TEST AND BALANCE COMPANY AND WITNESSED BY THE OWNER. DUCT LEAKAGE RATE SHALL NOT EXCEED 2% FOR DUCTS RATED

LESS THAN OR EQUAL TO 2" W.G., AND 1% FOR DUCTS RATED GREATER THAN 2” W.G.

a. ALL MAIN SUPPLY AND RETURN AIR DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED G90 SHEET METAL INTERNALLY INSULATED WITH MINIMUM

1-1/2” THICKNESS R-6 DUCT LINER INSULATION PER INTERNALLY LINED DUCT DETAIL, SEAL ALL DUCT JOINTS WITH HARDCAST, UNLESS OTHERWISE

NOTED.

1. DUCT LINER EQUAL TO JOHNS MANVILLE LINACOUSTIC R-300 OR EQUAL OR ARMACELL AP ARMAFLEX.

b. ALL BRANCH SUPPLY, RETURN, EXHAUST, AND OUTSIDE AIR DUCTWORK SHALL BE GALVANIZED G90 SHEET METAL. SEAL ALL DUCT JOINTS WITH

HARDCAST. ALL SUPPLY. RETURN AND OUTSIDE AIR DUCTS SHALL BE INSULATED WITH BLANKET TYPE INSULATION WITH VAPOR BARRIER (MINIMUM INSTALLED R 6.0). DUCT INSULATION SHALL BE LABELED AND MARKED AT THE REQUIRED INTERVALS AS REQUIRED BY THE FLORIDA BUILDING CODE.

EXHAUST AIR DUCTS SERVING ENERGY RECOVERY UNIT SHALL BE INSULATED.

c. DUCT PRESSURE CLASSES SHALL BE AS FOLLOWS:

1. SUPPLY UPSTREAM OF VAV BOXES 3" PRESSURE CLASS.

2. SUPPLY DOWNSTREAM OF VAV BOXES 1" PRESSURE CLASS.

3. RETURN MIN. -3" PRESSURE CLASS.

4. EXHAUST -2" PRESSURE CLASS

d. PROVIDE TURNING VANES IN ALL RECTANGULAR AND SQUARE DUCT ELBOWS GREATER THAN 8" IN WIDTH.

e. CONSTRUCT AND INSTALL DUCTWORK IN ACCORDANCE WITH THE LATEST SMACNA GUIDELINES.

f. PROVIDE HANGER AND DUCT WORK ACCESSORIES AS PER SMACNA RECOMMENDATIONS.

g. FLEXIBLE CONNECTION SHALL BE PROVIDED BETWEEN ALL AIR MOVING APPARATUS AND DUCTWORK WIDTH SHALL NOT BE LESS THAN 4" AND EQUAL

TO DURO-DYNE FLEXIBLE DUCT CONNECTOR.

h. DUCTWORK SHALL BE SEALED IN ACCORDANCE WITH THE LATEST EDITION OF SMACNA DUCT CONSTRUCTION STANDARDS.

7. ALL DUCT DIMENSIONS SHOWN\IN ON DRAWINGS ARE CLEAR INSIDE

8. ALL VOLUME DAMPERS SHALL BE OPPOSED BLADE TYPE. PROVIDE A ONE-FOOT-LONG PLASTIC STRIP OF MATERIAL FROM ALL DAMPER HANDLES TO ASSIST

TEST AND BALANCE AGENCY IN IDENTIFYING ALL DAMPERS. IN AREAS WHERE THE FINAL DAMPER INSTALLATION PROHIBITS ACCESS FOR TEST AND BALANCE, PROVIDE MANUAL REMOTE CABLE CONTROLS EQUAL TO YOUNG REGULATOR MODEL 830ACC/270—896. ACCESS TO END OF CABLE TO BE FLUSH IN CEILING NEATLY CONCEALED WITH THREADED CAP. PAINT CAP TO MATCH CEILING COLOR. INDICATE LOCATIONS OF ALL CAPS ON DUCTWORK COORDINATION DRAWINGS AND OBTAIN WRITTEN APPROVAL FROM ARCHITECT/ENGINEER PRIOR TO INSTALLATION. REMOVE MATERIAL FROM EXPOSED DUCT DAMPERS

AFTER SUBSTANTIAL COMPLETION.

9. ALL DUCT ELBOWS SHALL INCLUDE AIR FLOW DIRECTIONAL VANES AS PER ”SMACNA” DUCT CONSTRUCTION STANDARDS. SPLITTER VANES SHALL BE PROVIDED IN ALL ELBOWS AND DUCT OFFSETS WITH ANGLES BETWEEN 15 DEGREE AND 90 DEGREES AS PER FIG. 2—5 OF THE SMACNA MANUAL. 90 DEGREE

ELBOWS SHALL HAVE TURNING VANES.

10. PROVIDE CONICAL SPIN—IN FITTINGS AT ALL CONNECTIONS OF ROUND SHEET METAL OR FLEXIBLE SUPPLY AIR DUCTS TO RIGID RECTANGULAR DUCT.

11. ALL PIPING AND/OR DUCTWORK MUST BE INSTALLED 6” AWAY FROM ANY FIRE RATED WALL.

12. FOR SEALING OF FIRE DAMPER AND PIPE OR DUCT PENETRATION THROUGH FIRE-RATED WALLS, REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.

ALL PIPE PENETRATIONS SHALL BE SEALED USING APPROVED UL DETAILS. ALL FIRE DAMPERS SHALL BE DYNAMIC TYPE.

13. PROVIDE ADDITIONAL DUCTWORK AND PIPING SUPPORTS ON BOTH SIDES AND WITHIN 18" OF FIRE RATED WALLS. DUCTWORK OR PIPING SHALL NOT BE

SUPPORTED FROM ANY FIRE-RATED WALL.

14. FLEXIBLE DUCTS SHALL BE FACTORY INSULATED (MINIMUM R—6) AND INCLUDE A VINYL VAPOR JACKET AND HELIX STEEL WIRE. ”FLEXMASTER” TYPE

5M OR APPROVED EQUAL. FLEXIBLE DUCT SHALL BE ATTACHED WITH THERMAFLEX STAINLESS STEEL SNAP LOCK CLAMPS. THE MAXIMUM LENGTH OF

FLEXIBLE DUCT SHALL BE 6’—0". SUPPORT ELBOWS USING THERMAFLEX FLEXFLOW ELBOW.

15. SMOKE AND HIGH TEMPERATURE PROTECTION OF MECHANICAL AIR DISTRIBUTION SYSTEMS.

a. DUCT MOUNTED SMOKE DETECTORS SHALL BE FURNISHED AND WIRED UNDER DIVISION 26 (ELECTRICAL) AT LOCATIONS INDICATED ON THE PLANS

AND AS HEREIN SPECIFIED. DUCT DETECTORS SHALL COMPLY WITH UL 268A.

b. MECHANICAL PLANS INDICATE THE APPROXIMATE LOCATION OF DUCT DETECTORS. ASSIST THE SMOKE DETECTOR INSTALLER IN LOCATING AND

INSTALLING THE DETECTORS IN ACCORDANCE WITH MANUFACTURER’S INSTALLATION INSTRUCTIONS. WHEN RECOMMENDED CLEARANCES CAN NOT BE MAINTAINED, SIMULATE A SMOKE AIR FLOW TEST OF EACH DEVICE AND PROVIDE A COPY OF THE FIELD TEST TO THE OWNER’S REPRESENTATIVE.

16. PROVIDE A MINIMUM 12“ X 12” INSULATED AND DOUBLE GASKETED DUCT ACCESS DOOR ADJACENT TO EACH DUCT MOUNTED SMOKE DETECTOR TO FACILITATE INSPECTION OF DUCT DETECTOR TUBES. ACCESS DOOR SHALL NOT REQUIRE TOOLS TO BE OPENED.

17. PROVIDE P—TRAPS AS PER DETAIL AT ALL CONDENSATE DRAIN LINE CONNECTIONS. SLOPE DRAIN LINES TOWARD THE POINT OF DISCHARGE (MIN 1/8"/FOOT).

INSULATE CONDENSATE DRAIN LINES WITH 3/4" THICK SEAMLESS CLOSED CELL RUBBER PIPE INSULATION. CONDENSATE DRAIN LINES TO BE COPPER. LINES SHALL BE ONE DIAMETER LARGER THAN THE UNIT DRAIN CONNECTION, BUT NOT LESS THAN 3/4 INCH. PROVIDE CLEANOUTS AT ALL CHANGES OF DIRECTION.

THE FOLLOWING MINIMUM PIPE SIZES SHALL BE USED:

EQUIPMENT CAPACITY MINIMUM PIPE DIAMETER

a. UP TO 20 TONS 3/4”

b. OVER 20 TONS UP TO 40 TONS 1“

18. PROVIDE FLEXIBLE CONNECTIONS BETWEEN ALL AIR MOVING APPARATUS AND DUCTWORK. RECOMMENDED WIDTH IS 4".

19. WHERE INDICATED ON DRAWINGS AND/OR EQUIPMENT SCHEDULES EXTERNAL STATIC PRESSURE IS DEFINED AS NOT INCLUDING LOSSES DUE TO UNIT

MOUNTED FILTER(S), RETURN AIR PLENUM OR MIXING BOXES. THOSE LOSSES SHALL BE PART OF THE EQUIPMENT INTERNAL LOSSES SAME AS THOSE CAUSED

BY COILS, CABINET, ETC.

20. ROOF MOUNTED EQUIPMENT SHALL BE SECURED TO THE CURB AND THE CURBS SHALL BE SECURED TO THE STRUCTURE IN ACCORDANCE WITH THE EQUIPMENT’S FLORIDA PRODUCT APPROVAL LISTING OR PROVIDED WITH A THIRD PARTY STRUCTURAL ENGINEERS SIGNED AND SEALED INSTALLATION

DETAILS.

21. PROVIDE PAINTED GALVANIZED EXPANDED METAL GRILLE OVER ALL CONDENSER COILS.

22. ALL EQUIPMENT (AIR HANDLERS, CONDENSING UNITS, ROOFTOP UNITS, ETC.) SHALL BE LABELED WITH PLASTIC SIGNS, LAMINATED. ENGRAVED: 1/8" THICK

BLANKS FOR SIGNS SHALL BE A MINIMUM OF 1 1/4" HIGH, WITH 3/4" HIGH LETTERS. LENGTH OF THE SIGN SHALL BE THE SUM OF THE LETTERS/NUMBERS PLUS 3/4” EACH END. SIGNS DESIGNATED FOR INSTALLATION ON THE OUTSIDE, IN OPEN AREAS, OR LOCATED IN A PROTECTED AREA THAT IS SUBJECT TO DIRECT SUNLIGHT, SHALL BE UV RATED, DESIGNATED AND MANUFACTURED TO BE EXPOSED TO THE ELEMENTS. SUBMITTAL DATA INDICATING THE ABOVE WILL BE REQUIRED. LABELS SHALL ALSO INCLUDE THE ROOM NUMBER, CORRESPONDING AIR HANDLER LOCATION OR AREA SERVED TO ASSIST IN THE DETERMINATION OF THE SERVICE LOCATION OF SAID EQUIPMENT. PROVIDE ADDITIONAL NAMEPLATE ON CEILING GRID DIRECTLY BELOW EQUIPMENT CONCEALED ABOVE CEILINGS TO AID IN LOCATING THE UNIT. NAMEPLATE DESIGNATION SHALL CONSIST OF UNIT NUMBER. LABELS SHALL BE PERMANENTLY AFFIXED TO

EQUIPMENT BY USE OF RIVET OR SCREW TYPE FASTENERS.

23. EQUIPMENT SHALL BE MANUFACTURED AND/OR COATED AS REQUIRED FOR INSTALLATION IN A SEA COAST ENVIRONMENT.

24. ALL WALL MOUNTED TEMPERATURE AND HUMIDITY SENSORS SHALL BE INSTALLED AT A CENTER LINE ELEVATION OF 4’ 0” ABOVE FINISHED FLOOR UNLESS

OTHERWISE NOTED ON DRAWINGS. LOCATION OF THE WALL MOUNTED THERMOSTAT SHALL BE COORDINATED WITH OTHER TRADES FOR A NEAT APPEARANCE. THE FINAL LOCATION OF THERMOSTAT SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT OR HIS REPRESENTATIVE IN THE FIELD. WHEN

THE SENSOR IS INSTALLED ON EXTERIOR WALLS, PROVIDE AN INSULATED SUB—BASE.

25. RETAIN THE SERVICES OF A NEBB AND/OR AABC CERTIFIED TEST AND BALANCE AGENCY TO PERFORM FINAL TESTING AND BALANCING OF ALL HVAC SYSTEMS.

THE TEST AND BALANCE AGENCY SHALL BE HIRED INDEPENDENTLY FROM THE MECHANICAL CONTRACTOR THROUGH THE GENERAL CONTRACTOR. RECORD ALL DATA ON STANDARD ’AABC’ OR OTHER APPROVED FORMS AND SUBMIT TO THE ARCHITECT FOR REVIEW.

26. PROVIDE SCHEDULE 40 STEEL PIPE SLEEVES FOR CONDENSATE DRAIN LINES PENETRATING EXTERIOR WALLS. NEATLY SEAL VOIDS AROUND PIPING WITH A

WEATHER TIGHT PERMANENT NON-SHRINKING SEALANT.

27. REFRIGERANT LINES SHALL BE SIZED AS PER THE AIR CONDITIONING EQUIPMENT MANUFACTURER’S RECOMMENDATIONS. PROVIDE SIZING AND ACCESSORY DATA WITH THE EQUIPMENT PACKAGE SUBMITTAL. PIPING IS TO BE FILLED WITH DRY NITROGEN WHILE SOLDERING. TEST, CLEAN, AND DEHYDRATE PIPES AND PROVIDE CRITICAL CHARGE OF REFRIGERANT AS PER EQUIPMENT MANUFACTURER’S RECOMMENDATION. PROVIDE ALL NECESSARY VALVES. TRAPS, FILTER/DRYERS. SIGHT GLASS, ETC. AS REQUIRED FOR A COMPLETE AND READY TO OPERATE INSTALLATION. INCLUDE ACCESSIBLE SERVICE FITTINGS. BI—

FLOW LIQUID LINE FILTER DRYER SHALL BE PROVIDED IN HEAT PUMP UNITS.

28. ALL SUCTION LINE REFRIGERANT PIPING SHALL BE INSULATED WITH 3/4" THICK SEAMLESS CLOSED CELL RUBBER PIPE INSULATION. INSULATION EXPOSED TO THE OUTSIDE ENVIRONMENT SHALL BE PAINTED WITH TWO COATS OF UV RESISTANT WHITE ARMAFLEX PAINT OR PROVIDED WITH A FACTORY UV RESISTANT

OUTER LAYER.

29. EQUIPMENT SERVICE ACCESS: PROVIDE ADEQUATE SERVICE SPACE AROUND AIR HANDLING UNITS, VARIABLE VOLUME BOXES, ELECTRIC DUCT HEATERS AND THE PULL SIDE OF FILTERS, OR AS REQUIRED BY THE MANUFACTURER’S INSTALLATION INSTRUCTIONS. THE SERVICE AREA SHALL BE CLEAR OF DUCTS, PIPES, CONDUITS, WALL STUDS, CEILING HANGERS. AND ANY OTHER CONSTRUCTION APPURTENANCE.

30. ALL AIR HANDLING UNITS SHALL BE PROVIDED WITH A FLOAT SWITCH IN THE PRIMARY DRAIN LINE OR IN THE EQUIPMENT SUPPLIED DRAIN PAN, LOCATED AT A POINT HIGHER THAN THE PRIMARY DRAIN LINE CONNECTION AND BELOW THE OVERFLOW RIM OF SUCH PAN, WIRED TO SHUT DOWN THE ENTIRE SYSTEM

WHEN THE PRIMARY DRAIN BECOMES OBSTRUCTED.

31. ADEQUATE MEANS OF PROTECTION FOR ALL UTILITIES SHALL BE PROVIDED AND IF UTILITIES ARE DAMAGED DURING WORKING OPERATIONS, SUCH SHALL BE

REPAIRED TO THE SATISFACTION OF THE OWNER, AT NO COST TO THE CONTRACT.

32. ACCESS PANELS THAT MAY BE REQUIRED FOR INSPECTION OF DUCTWORK, PIPING. DUCT MOUNTED DEVICES OR PIPE MOUNTED DEVICES SHALL BE PROVIDED AND ADEQUATELY SIZED. REFER TO THE ARCHITECTURAL CONTRACT DOCUMENTS FOR DOOR SPECIFICATIONS.

33. ALL DUCTWORK SHALL BE STORED IN CLEAN AREAS. PROTECT ALL DUCTWORK FROM DUST AND DEBRIS WHILE IT IS STORED ON SITE. WHILE UNDER CONSTRUCTION, ALL INSTALLED DUCTWORK SHALL BE TEMPORARILY SEALED WITH DUCT PROTECTION FILM PRIOR TO TEST AND BALANCE IN ORDER TO LIMIT ACCUMULATION OF CONSTRUCTION DUST INSIDE THE DUCTWORK SYSTEM. IF EITHER OF THESE PROCEDURES IS NOT CONDUCTED, THE ENTIRE ASSOCIATED DUCTWORK SYSTEM AND MECHANICAL EQUIPMENT SHALL BE CLEANED TO THE OWNER'S SATISFACTION.

34. RETAIN THE SERVICES OF AN INDEPENDENT COMMISSIONING AUTHORITY TO PERFORM COMMISSIONING SERVICES OF ALL NEW HVAC SYSTEMS AND CONTROL SYSTEMS IN ACCORDANCE WITH THE FLORIDA ENERGY CONSERVATION CODE. THE COMMISSIONING AUTHORITY SHALL BE HIRED INDEPENDENTLY FROM THE MECHANICAL CONTRACTOR THROUGH THE GENERAL CONTRACTOR. THE COMMISSIONING AUTHORITY CANNOT BE THE SAME AS THE TEST AND BALANCE CONTRACTOR. THE COMMISSIONING AUTHORITY SHALL DEVELOP A COMMISSIONING PLAN, PERFORM FUNCTIONAL TESTING WITH THE ASSISTANCE OF THE ASSOCIATED CONTRACTOR(S), AND PROVIDE A PRELIMINARY AND FINAL COMMISSIONING REPORT.

35. AS-BUILT DRAWINGS, O&M MANUALS, CERTIFIED TEST AND BALANCE REPORT, AND THE FINAL COMMISSIONING REPORT ARE TO BE PROVIDED TO THE OWNER WITHIN 90 DAYS OF THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY AND SHALL BE SUBMITTED TO THE ARCHITECT FOR REVIEW.

36. SYSTEMS SHALL BE MAINTAINED IN ACCORDANCE WITH ASHRAE STANDARD 180—2018— STANDARD PRACTICE FOR INSPECTION AND MAINTENANCE OF

COMMERCIAL BUILDING HVAC SYSTEMS.

CODE COMPLIANCE

M

220000

1. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE 8TH EDITION (2023) FLORIDA BUILDING CODE

A. BUILDING EDITION

B. EXISTING BUILDING EDITION

C. MECHANICAL EDITION

D. PLUMBING EDITION

E. FUEL GAS EDITION

F. ENERGY EFFICIENCY EDITION

G. 8TH EDITION (2023) FLORIDA FIRE PREVENTION CODE.

2. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

A. NFPA-1 NATIONAL FIRE CODE WITH FLORIDA MODIFICATIONS

B. NFPA-70 NATIONAL ELECTRIC CODE

C. NFPA-72 NATIONAL FIRE ALARM CODE

D. NFPA-90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS E. NFPA-90B STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR CONDITION SYSTEMS

F. NFPA-101 NATIONAL LIFE SAFETY CODE

3. AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING ENGINEERS, INC. (ASHRAE) A. ASHRAE GUIDELINE 4-2008 - PREPARATION OF OPERATING AND MAINTENANCE DOCUMENTATION FOR BUILDING SYSTEMS B. ASHRAE STANDARD 62.1-2019 AND APPROVED ADDENDA - VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

C. ASHRAE STANDARD 126-2016 - METHOD OF TESTING HVAC AIR DUCTS

D. ASHRAE STANDARD 180-2016 - STANDARD PRACTICE FOR INSPECTION AND MAINTENANCE OF COMMERCIAL BUILDING

HVAC SYSTEMS.

4. SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION (SMACNA)

OUTDOOR

INDOOR

CONDITION

42.0°F

69.0°F

WINTER

DRY BULB

94.0°F

74.0°F

SUMMER

DRY BULB

61.8°F

WET BULB

77.0°F

DESIGN CONDITIONS

M

230000

NOTE:

ALL SYMBOLS OR ABBREVIATIONS MAY NOT APPEAR ON PLANS. CONTRACTOR

IS ONLY RESPONSIBLE FOR EQUIPMENT INDICATED ON CONSTRUCTION PLANS

OR BY SPECIFICATION.

BD

AD

NEW DUCTWORK OR

EQUIPMENT

NEW COMBINATION

FIRE/SMOKE DAMPER

NEW AUTOMATIC

SMOKE

DAMPER

NEW AUTOMATIC FIRE

DAMPER

COUNTER BALANCED

BACKDRAFT DAMPER

MANUAL VOLUME DAMPER

WITH 2" INSULATION

STAND-OFF

DRAWING SYMBOL DESCRIPTION DRAWING SYMBOL DESCRIPTION

EXISTING DUCTWORK OR

EQUIPMENT

DUCTWORK OR EQUIPMENT

TO BE REMOVED

NEW SMOKE

WALL

PENETRATION

NEW INTERNALLY LINED

DUCTWORK

ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION

INSULATED FLEXIBLE

DUCTWORK

DUCT ACCESS DOOR

ROUND DUCT TURNING

DOWN

ROUND DUCT TURNING UP

SUPPLY OR OA DUCT

TURNING DOWN

SUPPLY OR OA DUCT

TURNING UP

RETURN DUCT TURNING

DOWN

RETURN DUCT TURNING UP

EXHAUST DUCT TURNING

DOWN

EXHAUST DUCT TURNING UP

MITERED ELBOW WITH

TURNING VANESMITERED ELBOW

NEW / EXISTING

THERMOSTAT

NEW / EXISTING HUMIDISTAT

NEW / EXISTING

COMBINATION THERMOSTAT

/ HUMIDISTAT

NEW / EXISTING CO2 SENSOR

NEW / EXISTING FIRESTAT

NEW / EXISTING MOTOR

ACTUATOR

NEW / EXISTING SMOKE

DETECTOR (PROVIDED BY

DIV. 26)

PLAN NOTE

REVISION MARK

DEMOLITION NOTE

POINT OF DISCONNECT OR

CONNECTION

SUPPLY AIR DEVICE

EXHAUST AIR DEVICE

ROUND SUPPLY AIR DEVICE

RETURN AIR DEVICE

SIDEWALL SUPPLY

AIR

DEVICE

SIDEWALL EXHAUST

OR

RETURN AIR DEVICE

1" UNDERCUT FLOW ARROW

LEGEND

M

230000

ABBREVIATIONS

H

T

T/H

CO2

H

T

T/H

CO2

F

SD

M

F

SD

M

NEW / EXISTING SMOKE

DETECTOR (PROVIDED BY

DIV. 26)

TS TS

KEF

SA

MUA

EF

KH

SF

CT

CH

FP

MB

VV

RTU

CU

AH

AC

RA

OA

EA

[E]

[D]

TYP

CHW

CW

HW

CF

(0)

TF

CONDENSING UNIT

AIR HANDLING UNIT

AIR CONDITIONING UNIT

ROOF TOP UNIT

FAN POWERED VAV BOX

VAV BOX

MIXING BOX

CHILLER

COOLING TOWER

EXHAUST FAN SUPPLY FAN

KITCHEN HOOD

MAKE-UP AIR UNIT

KITCHEN EXHAUST FAN

SUPPLY AIR

RETURN AIR

OUTSIDE AIR

EXHAUST AIR

EXISTING TO REMAIN

TO BE DEMOLISHED

TYPICAL

CHILLED WATER

CONDENSER WATER

HEATING HOT WATER

CIRCULATING FAN

POSITIVE PRESSURE

NEGATIVE PRESSURE

NEUTRAL PRESSURE

TRANSFER FAN

[R] TO BE RELOCATED

MS

HP

MINI SPLIT

HEAT PUMP

L LOUVER

RD

NIC

RETURN AIR DEVICE

NOT IN CONTRACT

ED

UNO

EXHAUST AIR DEVICE

UNLESS NOTES OTHERWISE

CD CONDENSATE DRAIN

F FAN

P PUMP

PCHWP

PRIMARY CHILLED WATER

PUMP

SCHWP

SECONDARY CHILLED

WATER PUMP

CWP CONDENSER WATER PUMP

SD SUPPLY AIR DEVICE

SCOPE OF WORK

M

230000

1. REMOVE EXISTING DX SPLIT SYSTEM AHU-3, AHU-4, AND ASSOCIATED CONDENSING UNITS.

2. REMOVE EXISTING EXHAUST FANS.

3. CLEAN SUPPLY RETURN AND OUTSIDE AIR DUCTWORK TO REMAIN.

4. INSTALL NEW AHU-3, AHU-4, AIR HANDLERS WITH HOT GAS REHEAT FOR HUMIDITY CONTROL.

5. INSTALL NEW CONDENSING UNITS CU-3, CU-4, PROPERLY SECURED TO CONCRETE HOUSEKEEPING PADS.

6. INSTALL NEW STAND-ALONE DEHUMIDIFIERS IN VAULT, SUPPLY AREA AND EQUIPMENT AREA.

7. INSTALL NEW DUCTED DEHUMIDIFIERS TO SERVE AHU-1 AND AHU-2.

ALTERNATE BID ITEMS

A. ALTERNATE BID ITEM NO. 1: PARKING AREA - STORMWATER MITIGATION, ASPHALT MILLING, AND RESURFACE. CONNECT MAIN ARMORY ROOF DRAINS TO

UNDERGROUND STORM DRAIN SYSTEM.

B. ALTERNATE BID ITEM NO. 2: UPGRADE MAIN ARMORY BUILDING INTERIOR AND EXTERIOR LIGHTING TO LED TO INCLUDE UNIT SIGN AND FLAGPOLE.

C. ALTERNATE BID ITEM NO. 3: REFINISH AND REPAINT COMPLETE EXTERIOR STUCCO / BRICK FACADE WITH UP TO 4 COLOR SCHEME. INCLUDE THE PAINTING OF ALL

EXTERIOR HM DOORS AND FRAMES INCLUDING ALL INSIDE AND OUTSIDE FACES.

D. ALTERNATE BID ITEM NO. 4: COMPLETE GLAZING REPLACEMENT OF ALL EXISTING LAMINATED IMPACT GLAZING IN EXISTING ALUMINUM WINDOW FRAME SYSTEMS AT

THE EXTERIOR CLERESTORY LEVEL.

E. ALTERNATE BID ITEM NO. 5: COMPLETE GLAZING REPLACEMENT OF ALL EXISTING LAMINATED IMPACT GLAZING IN ALL EXISTING ALUMINUM WINDOW FRAME SYSTEMS AT ALL THE EXTERIOR 1ST FLOOR LEVEL GLAZED OPENINGS EXCEPT NEW EXTERIOR FIXED WINDOWS & IMPACT GLAZING

FOR KITCHEN ONLY.

F. ALTERNATE BID ITEM NO. 6: PROVIDE NEW 20'-0" WIDE (K-8 FORCE PROTECTION) FENCE SYSTEM) DOUBLE SWING GATE WITH MANUAL FUNCTION TO SOUTH SIDE OF POV PARKING. EXISTING DEAD MAN ANCHOR LAYOUT TO BE RE-CONFIGURED FOR NEW GATE. COMPLETE FUNCTIONAL INSTALLATION

REQUIRED.

G. ALTERNATE BID ITEM NO. 7: PROVIDE MILL AND OVERLAY OF THE NORTH & EAST POV PARKING LOT AS INDICATED IN THE ATTACHED CIVIL DRAWINGS.

H. ALTERNATE BID ITEM NO. 8: PROVIDE NEW DEHUMIDIFIER AND MECHANICAL AIR INSTALLED INTO THE TO THE EXISTING VAULT ROOM # 110 & #111.

SHEET NO.:

PROJECT NO.:

DATE:

SHEET TITLE:

DRAWN BY:

REVISIONS:

CONSULTING ENGINEERS

154A Whitaker Rd.

Lutz, Florida 33549

813.333.2103 www.balengineering.com

Registry No. 31211

TO THE BEST OF THE KNOWLEDGE OF

THE ENGINEERS AND ARCHITECTS,

SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE

MINIMUM BUILDING CODES AND THE

APPLICABLE MINIMUM FIRE SAFETY

STANDARDS

/1

/2

:0 :3

P

M

C U se rs

\A d a m

G o re ck i\ B

A L E n g in e e ri n g In c\ B

A L E n g in e e ri n g In c.

I n te rn a l -

D o cu m e n ts

P ro je ct s\

\2

D M

A C

F M

O P a lm e tt o \W o rk in g

D ra w in g s\

M

P

R

.r vt

AG

M0.1

NOTES, LEGENDS,

AND SCHEDULES

T

H A

V E

W E

S T

P

A L M

E T

T O

F

L

1910.08

MARCH 30, 2026

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

N A

T

IO

N A

L G

U A

R D

A R

M O

R Y

D M

A C

F M

O

P A

L M

E T

T O

E S

P R

E N

O V

A T

IO

N

1 06-17-26 ADDENDUM 02

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY BRYANT A. LYLE ON

JUNE 16, 2026 USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

SHEET NO.:

PROJECT NO.:

DATE:

SHEET TITLE:

DRAWN BY:

REVISIONS:

CONSULTING ENGINEERS

154A Whitaker Rd.

Lutz, Florida 33549

813.333.2103 www.balengineering.com

Registry No. 31211

TO THE BEST OF THE KNOWLEDGE OF

THE ENGINEERS AND ARCHITECTS,

SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE

MINIMUM BUILDING CODES AND THE

APPLICABLE MINIMUM FIRE SAFETY

STANDARDS

/1

/2

:0 :4

P

M

C U se rs

\A d a m

G o re ck i\ B

A L E n g in e e ri n g In c\ B

A L E n g in e e ri n g In c.

I n te rn a l -

D o cu m e n ts

P ro je ct s\

\2

D M

A C

F M

O P a lm e tt o \W o rk in g

D ra w in g s\

M

P

R

.r vt

AG

M0.2

SCHEDULES

T

H A

V E

W E

S T

P

A L M

E T

T O

F

L

1910.08

MARCH 30, 2026

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

N A

T

IO

N A

L G

U A

R D

A R

M O

R Y

D M

A C

F M

O

P A

L M

E T

T O

E S

P R

E N

O V

A T

IO

N

10. PROVIDE 18 INCH TALL INSULATED ROOF CURB.

9. PROVIDE WITH GREASE CUP.

8. PROVIDE WITH EXTENDED WEATHER HOOD INTAKE TO PROVIDE MIN. 10'-0" SEPARATION FROM EXHAUST FAN. INLET SHALL BE PROVIDED WITH ALUMINUM FILTER SCREEN.

7. PROVIDE COMBINATION SUPPLY AND EXHAUST FAN CURB CAP ADAPTOR TO EXISTING CURB. CONTRACTOR SHALL FIELD MEASURE PRIOR TO SUBMITTING FOR APPROVAL.

6. PROVIDE RETROFIT KITCHEN HOOD CONTROL WITH EXHAUST AIR STREAM TEMPERATURE AND SPACE TEMPERATURE FOR AUTOMATIC CONTROL OF THE KITCHEN HOOD SUPPLY AND EXHAUST FAN.

5. UL-762, RESTAURANT EXHAUST.

4. EXHAUST FAN SHALL BE INTERLOCKED WITH AHU-1 AND AHU-2 TO RUN SIMULTANEOUSLY.

3. PROVIDE WITH BIRDSCREEN.

2. PROVIDE WITH FACTORY MOUNTED AND WIRED DISCONNECT SWITCH AND FSC SPEED CONTROLLER COMPATIBLE WITH SUPPLIED MOTOR.

1. AS MANUFACTURED BY GREENHECK OR EQUAL.

NOTES

KSF-1 KITCHEN HOOD KSQ-12-M2 Direct 1,164 1.000 1,750 0.45 1/2 115/60/1 9.8 12.2 20 1,2,7,8,10

KEF-1 KITCHEN HOOD CUE-130-A Direct 1,596 1.000 1,725 0.59 3/4 15.0 115/60/1 13.8 17.2 30 1,2,5,6,7,9,10

EF-2 WOMEN'S LOCKER G-100-VG Direct 700 0.250 1,041 0.06 1/4 4.9 115/60/1 3.8 4.8 15 1,2,3,4,10

EF-1 MEN'S LOCKER G-120-VG Direct 800 0.250 863 0.06 1/4 5.3 115/60/1 3.8 4.8 15 1,2,3,4,10

TAG AREA SERVED MODEL DRIVE TYPE VOLUME (CFM)

EXTERNAL SP

(IN WG)

FAN SPEED

(RPM)

OPERATING

POWER

(HP)

MOTOR SIZE

(HP)

SONES

(INLET)

ELECTICAL

V/C/P

NEC FLA

(AMPS)

MIN CIRCUIT

AMPACITY

(MCA)

MAX

OVERCURRENT

PROTECTION

(MOP)

NOTES

230000

M FAN SCHEDULE

6. RECTANGULAR SURFACE MOUNT HEAVY DUTY GYMNASIUM RETURN GRILLE. REFER TO PLANS FOR DETAILS AND

QUANTITIES.

5. RECTANGULAR MIAMI-DADE QUALIFIED AND FLORIDA PRODUCT APPROVED STATIONARY VERTICAL BLADE WIND DRIVEN

RAIN EXTRUDED ALUMINUM LOUVER

4. RECTANGULAR LOUVERED SURFACE MOUNT RETURN GRILLE. REFER TO PLANS FOR DETAILS AND QUANTITIES

3. SQUARE LOUVERED FACE LAY-IN CEILING RETURN GRILLE. REFER TO PLANS FOR DETAILS AND QUANTITIES

2. RECTANGULAR SURFACE MOUNT SUPPLY AIR GRILLE. REFER TO PLANS FOR DETAILS AND QUANTITIES.

1. SQUARE CONE LAY-IN CEILING SUPPLY AIR DIFFUSER. REFER TO PLANS FOR DETAILS AND QUANTITIES.

NOTES 6 5 4 ---

MODEL 98LA EVH-501D 635 ---

MANUFACTURER PRICE GREENHECK PRICE ---

ACCESSORIES --- BIRD SCREEN --- ---

FINISH BY ARCH. BY ARCH. --- ---

MATERIAL ALUMINUM ALUMINUM ALUMINUM ---

TYPE RETURN INTAKE LOUVER TRANSFER GRILLE ---

ITEM NO. RG-3 L-1 TG-1 ---

NOTES 1 2 3 4

MODEL ASCD 620 635 635

MANUFACTURER PRICE PRICE PRICE PRICE

FRAME LAY-IN 1" FLAT W/ SCREWS LAY-IN 1" FLAT W/ SCREWS

ACCESSORIES --- --- --- ---

FINISH WHITE WHITE WHITE WHITE

MATERIAL ALUMINUM ALUMINUM ALUMINUM ALUMINUM

TYPE SUPPLY SUPPLY RETURN/EXHAUST RETURN/EXHAUST

ITEM NO. SG-1 SG-2 RG-1/EG-1 RG-2/EG-2

233400

M AIR DEVICE SCHEDULE

1 06-17-26 ADDENDUM 02

1,238 9 1,450 Zone Totals: 119 0 120 0 120

130 CORRIDOR 166 0 125 0 0.06 10.0 0 10 0 10

129 OFFICE 6 199 2 240 5 0.06 21.9 0 20 0 20

128 OFFICE 5 201 2 280 5 0.06 22.1 0 23 0 23

127 OFFICE 4 200 2 275 5 0.06 22.0 0 23 0 23

126 OFFICE 3 196 2 180 5 0.06 21.8 0 15 0 15

123 COMMANDER'S... 276 1 350 5 0.06 21.6 0 29 0 29

AHU-3[N]

(ft²) (CFM) (CFM/Person) (CFM/ft²) (CFM) (CFM) (CFM) (CFM) (CFM)

Zone Name / Space Name Floor Area

Maximum Occupants

Maximum Supply Air

Required Outdoor Air

Required Outdoor Air

Required Outdoor Air Total

Required Exhaust Air Total

Provided Outdoor Air Total

Provided Exhaust Air Total

Space Pressure

VENTILATION SCHEDULE

891 21 1,400 Zone Totals: 158 0 195 0 195

122 1ST SGT OFFICE 265 1 300 5 0.06 20.9 0 42 0 42

120 TRAINING RM 1 626 20 1,100 5 0.06 137.6 0 153 0 153

AHU-4[N]

(ft²) (CFM) (CFM/Person) (CFM/ft²) (CFM) (CFM) (CFM) (CFM) (CFM)

Zone Name / Space Name Floor Area

Maximum Occupants

Maximum Supply Air

Required Outdoor Air

Required Outdoor Air

Required Outdoor Air Total

Required Exhaust Air Total

Provided Outdoor Air Total

Provided Exhaust Air Total

Space Pressure

VENTILATION SCHEDULE

BUILDING TOTAL 315 13,841 3,753 TOTAL BUILDING PRESSURE 2,253

AHU-7[E] 3 1,293 140 0.06 0.00 46.6 0 140

AHU-6[N] 4 1,889 165 0.05 0.00 41.2 1,500 -1,335

AHU-5[E] 28 1,114 134 0.06 5.00 4.8 0 134

AHU-4[N] 21 891 195 0.06 5.00 9.3 0 195

AHU-3[N] 9 1,238 120 0.06 4.17 13.3 0 120

AHU-1[E]&AHU-2[E] 250 7,416 3000 0.06 6.67 12.0 0 3,000

SYSTEM

SYSTEM POP.

(PEOPLE)

SYSTEM AREA

(SF)

PROVIDED OA

(CFM)

AVERAGE

(CFM/SF)

AVERAGE

(CFM/PERSON)

EFFECTIVE OA

(CFM/PERSON)

PROVIDED

EXHAUST AIR

ZONE PRESSURE

230000

M BUILDING PRESSURE SUMMARY

7. PROVIDE CONCRETE HOUSEKEEPING PAD AND ANCHOR CONDENSING UNIT TO PAD PER DETAILS.

6. COOLING ONLY MODEL. PROVIDED FOR PROCESS COOLING, NO HEAT.

5. PROVIDE REFRIGERANT PIPING PENETRATION SYSTEME EQUAL TO AIREX TITAN OUTLET WITH

E-FLEX GUARD. COORDINATE EXACT MODEL WITH MANUFACTURER'S RECCOMENDED...

4. PROVIDE MANUFACTURER'S INTEGRAL CONDENSATE PUMP.

3. CONTROLS & POWER TO INDOOR UNIT IS WIRED FROM OUTDOOR CONDENSING UNIT.

2. PROVIDE MANUFACTURER'S WIRED PROGRAMMABLE THERMOSTAT.

1. NEW EVAPORATOR TO BE INSTALLED ON MANUFACTURER'S WALL BRACKET. REFER TO DETAILS.

NOTES:

NOTES --- 1-7

MODEL --- PUY-AK12NL

MANUFACTURER --- MITSUBISHI

WEIGHT LBS. 99

COMPRESSOR POWER MCA/MOCP 16/27

MINIMUM UNIT HSPF2 WATT/HR --

MINIMUM UNIT SEER2/EER2 BTUH/WATT 21.1 / 14.8

ELECTRICAL V/PH./HZ. 208-230/1/60

LOCATION --- EXTERIOR PAD

REFRIGERANT --- R454B

CIRCUITS NO. 1

QUANITY OF COMPRESSORS --- 1

AMBIENT TEMPERATURE °F 95

NOMINAL CAPACITY TONS 1

ITEM NO. --- MSCU-1

MODEL --- MSY-GS12NA

MANUFACTURER --- MITSUBISHI

LOCATION --- 109-MECH/ELECT COMM.

UNIT POWER MCA SEE MCU-2

WEIGHT LBS. 28

CONTROLS --- SEE NOTES 2 & 3

ELECTRICAL V/PH./HZ. 208-230/1/60

HEATING CAPACITY BTUH NONE

OUTSIDE AIR CFM 0

SUPPLY AIR (HIGH/MED/LOW) CFM 265/310/385

TOTAL COOLING CAPACITY BTUH 12,200

ITEM NO. --- MAC-1

233700

M DUCTLESS SPLIT SYSTEM SCHEDULE

8 PROVIDE A PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING TO BOTH SPACE TEMPERATURE AND HUMIDITY.

7 PROVIDE UNIT WITH A REFRIGERANT REHEAT SYSTEM CAPABLE OF INCREASING THE TEMPERATURE OF THE SUPPLY AIR BY TEN DEGREES FOR HUMIDITY CONTROL.

6. PROVIDE A DOUBLE WALL FOAM INJECTED UNIT WITH MODULATING HOT GAS REHEAT COIL IN THE REHEAT POSITION.

5.

PROVIDE A CONDENSER COIL COATING WITH A MINIMUM OF 10,000 HOURS IN THE ASTM B-117 SALT SPRAY TEST. COATING MAY NOT DECREASE HEAT TRANSFER BY MORE THAN 1%.

ADSIL MICROGUARD AND LUVATA INSITU ARE APPROVED. BAKE PHENOLIC COATINGS ARE NOT ACCEPTABLE.

4. PROVIDE CONDENSING UNIT WITH A LOW AMBIENT HEAD PRESSURE CONTROLLER.

3. PROVIDE START UP PERFORMED BY A FACTORY AUTHORIZED TECHNICIAN.

2. PROVIDE DIRECT DRIVE SUPPLY FAN.

1. CONTRACTOR SHALL VERIFY EXISTING UNIT INFORMATION AND PROVIDE IN SCHEDULE FOR AS-BUILT.

NOTES --- 1 1 2 THRU 8 2 THRU 8 1 1 1

CU MODEL --- 5TTA4042A3 5TTA4048A3

AHU MODEL --- 5TEM6D05AV41 5TEM6D05AV41

MANUFACTURER --- TRANE TRANE

LOCATION --- OUTDOOR PAD OUTDOOR PAD OUTDOOR PAD OUTDOOR PAD OUTDOOR PAD OUTDOOR PAD OUTDOOR PAD

OPERATING WEIGHT LBS 246 246

MCA/MOCP @ 208V AMPS/AMPS 16.3 / 25 16.3 / 25

ELECTRICAL V/PH/HZ 208/3/60 208/3/60

CIRCUITS NO. 1 1

QUANTITY OF COMPRESSORS NO. 1 1

COMPRESSOR (EACH) RLA / LRA 12.2 / 120.4 12.2 / 120.4

AMBIENT TEMPERATURE °F 95 95 95 95 95 95 95

CAPACITY TONS 18.1 (2)10.8 3.5 4.0 5.0 4.0 2.5

ITEM NO. --- CU-1[E] CU-2A[E], CU-2B[E] CU-3[N] CU-4[N] CU-5[E] CU-6[E] CU-7[E]

LOCATION --- 116 MECHANICAL 116 MECHANICAL 121 MECHANICAL 2 121 MECHANICAL 2 116 MECHANICAL 109 MECH./ELECT. 132 MECH RM

OPERATING WEIGHT LBS 155 155

EFFICIENCY EER2/SEER2 12.0 / 15.2 12.0 / 15.2

EFFICIENCY EER/IEER --- ---

MCA/MOCP @ 208V AMPS/AMPS 45.0 / 45 32.0 / 45

ELECTRICAL V/PH/HZ 208/1/60 208/1/60

MERV RATING --- 13 13

PRESSURE DROP CLEAN/FINAL IN. WTR./IN. WTR. 0.05/0.60 0.05/0.60

THICKNES INCHES 2" 2"

FILTER TYPE --- PLEATED PLEATED

STEPS --- 1 1

ELECTRIC HEATER KW @ 208V 5.77 5.77

LVG. AIR TEMP. DB/WB °F / °F 57.3 / 55.2 56.7 / 54.4

ENT. AIR TEMP. DB/WB °F / °F 77.5 / 64.8 77.8 / 65.3

REFRIGERANT TYPE --- R-454B R-454B

COOLING COIL ROWS/FINS 4 / 14 3 / 16

FAN WHEEL TYPE --- VARIABLE FC VARIABLE FC

DRIVE TYPE --- DIRECT DIRECT

MOTOR SIZE BHP/HP ---/0.50 ---/0.50

AIR PRESSURE LOSS EXT./TOT. IN. WTR./IN. WTR. 0.5/--- 0.5/---

OUTSIDE AIR CFM 1,500 1,500 120 195 240 165 140

SUPPLY AIR CFM 5,500 7,000 1,450 1,400 1,200 1,625 950

NET SENSIBLE COOLING... BTUH 173,760 204,768 31,245 31,552 28,440 36,613 21,546

NET TOTAL COOLING CAPACITY BTUH 217,200 259,200 40,815 44,767 36,000 47,401 29,893

ITEM NO. --- AHU-1[E] AHU-2[E] AHU-3[N] AHU-4[N] AHU-5[E] AHU-6[E] AHU-7[E]

237313

M CENTRAL STATION DX AIR HANDLING UNITS 1

F E

F E

F E

F E

REF

F E

FE

T

T T

T

T

T

T

X X X

22"x12"[E]

"x

E

"x

E

16"x10"[E] 10"x8"[E]

20"x12"[E]

"x

E

"x

E

"x

E

"x

E

"x

E

"x

E

12"ø[E]

10"ø[E]

10"ø[E]

44"x6"[E]

18"x6"[E]3

"x

E

28"x12"[E]

8"x8"[E]

8"ø[E]

8"ø[E]

8"ø[E]

18"x10"[E]

"x

E

30"x6"[E]

"x

E

10"x8"[E]

24"x20"[E]

8"ø[E]

8"ø[E]

8"ø[E]

8"ø[E]

8"ø[E]

"ø

[E

"ø

[E

"ø

[E

10"x10"[E]

"x

E

"x

E

14"x6"[E]

"x

E

"x

E

20"x6"[E]

"x

E

"x

E

"x

E

"x

E

10"ø[E]

"x

E

"x

E

10"ø[E]

10"ø[E]

10"ø[E]

10"ø[E]

12"ø[E]

"ø [E

"ø [E

"x

E

8"ø[E]

8"ø[E]

"ø

[E

"ø

[E

"x

E

20"x6"[E]

20"x6"[E]

"x

E

CU-2[E] CU-2B[E]

CU-5[E]

1 2 3 4 5 6 7

A

B

C

D

E

F

G

H

I

CU-7[E]

CU-6[D]

CU-3[D]

CU-4[D]

"x

E

CU-1[E]

"x

E

AHU-6[E]

AHU-7[E]

AHU-3[D]

AHU-4[D]

AHU-5[E]

AHU-1[E]

AHU-2[E]

4 4

ENTRY

VESTIBULE

RECRUITER

OFFICE

RECRUITER

CLST.

103WOMENS

VEST

WOMENS

LATRINE

WOMENS

CHANGING

105A

WOMENS

SHOWER

105B

MENS

VEST

MENS LATRINE

MENS

CHANGING

107AMENS SHOWER

107B

MAIL / COPY

ROOM

MECH/ ELECT.

COMMUNICATIONS

VAULT

VAULT

SUPPLY AREA

MECH RM

EQUIPMENT

AREA

TABLES/

CHAIRS

VESTIBULE

VENDING

MECHANICAL

EXECUTIVE

OFFICER

MAIL ROOM

TRAINING

ROOM 1

GYM

MECHANICAL 1

PLT LDR'S

OFFICE

PLT SGT.

OFFICE

KITCHEN MESS

PORCH

OFFICE 3

COMMANDER

READINESS

NCO

TRAINING NCO

BTRY STAFF

DRILL HALL

VESTIBULE

118A

EDH-1[E]

EDH-2[E]

(2) SG-3[E]

8"x8"NK

150 CFM

SG-1[E]

8"øNK

200 CFM

SG-1[E]

8"øNK

200 CFM

SG-1[E]

8"øNK

200 CFM

R-1[E] 24"x20"NK

810 CFM

RG-2[E]

36"x10"NK

665 CFM

RG-1[E]

22"x22"NK

425 CFM

EG-1[E]

16"x10"NK

300 CFM

EG-1[E]

18"x12"NK

500 CFM

SG-2[E]

10"øNK

370 CFM

SG-2[E]

6"øNK

100 CFM

EG-1[E]

18"x12"NK

500 CFM

TG-1[E]

18"x10"NK

330 CFM

TG-1[E]

18"x10"NK

330 CFM

EG-1[E]

16"x10"NK

200 CFM

SG-2[E]

10"øNK

260 CFM

SG-2[E]

6"øNK

100 CFM

TG-1[E]

18"x10"NK

340 CFM

TG-1[E]

18"x10"NK

340 CFM

SG-2[E]

8"øNK

180 CFM

RG-1[E]

10"x10"NK

335 CFM

SG-2[E]

8"øNK

155 CFM

SG-2[E]

8"øNK

140 CFM

RG-1[E]

12"x12"NK

215 CFM

SG-2[E]

8"øNK

120 CFM

SG-2[E]

8"øNK

120 CFM

SG-2[E]

8"øNK

140 CFM

SG-2[E]

8"øNK

125 CFM

RG-1[E]

12"x12"NK

255 CFM

RG-1[E]

8"x8"NK

100 CFM

SG-2[E]

8"øNK

125 CFM

SG-2[E]

8"øNK

150 CFM

RG-1[E]

10"x10"NK

170 CFM

SG-2[E]

8"øNK

180 CFM

SG-2[E]

10"øNK

350 CFM

RG-1[E]

10"x10"NK

325 CFM

RG-1[E]

10"x10"NK

325 CFM

RG-1[E]

22"x22"NK

880 CFM

SG-2[E]

10"øNK

250 CFM

ø10"

SG-2[E]

10"øNK

275 CFM

SG-2[E]

10"øNK

250 CFM

SG-2[E]

10"øNK

275 CFM

RG-2[E]

10"x10"NK

170 CFM

TG-2

12"x8"NK

170 CFM

RG-2[E]

10"x10"NK

170 CFM

TG-2

12"x8"NK

170 CFM

SG-2[E]

12"øNK

250 CFM

SG-2[E]

10"øNK

175 CFM

SG-2[E]

10"øNK

175 CFM

SG-2[E]

12"øNK

250 CFM

SG-2[E]

10"øNK

150 CFM

SG-2[E]

12"øNK

250 CFM

RG-1[E]

6"x6"NK

350 CFM

RG-1[E]

22"x22"NK

725 CFM

RG[D]

48"x42"NK

5500 CFM

RG[D]

48"x42"NK

4000 CFM

SG-1[E]

10"øNK

320 CFM

AHU-5[D]

RG-1[E]

10"x10"NK

250 CFM

SG-2[E]

8"øNK

225 CFM

SG-2[E]

8"øNK

200 CFM

SG-3[E]

8"x4"NK

50 CFM

TG-2[E]

24"x6"NK

0 CFM

TG-2[E]

24"x6"NK

0 CFM

SHEET NO.:

PROJECT NO.:

DATE:

SHEET TITLE:

DRAWN BY:

REVISIONS:

CONSULTING ENGINEERS

154A Whitaker Rd.

Lutz, Florida 33549

813.333.2103 www.balengineering.com

Registry No. 31211

TO THE BEST OF THE KNOWLEDGE OF

THE ENGINEERS AND ARCHITECTS,

SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE

MINIMUM BUILDING CODES AND THE

APPLICABLE MINIMUM FIRE SAFETY

STANDARDS

/1

/2

:0 :4

P

M

C U se rs

\A d a m

G o re ck i\ B

A L E n g in e e ri n g In c\ B

A L E n g in e e ri n g In c.

I n te rn a l -

D o cu m e n ts

P ro je ct s\

\2

D M

A C

F M

O P a lm e tt o \W o rk in g

D ra w in g s\

M

P

R

.r vt

AG

M1.1

GROUND FLOOR

MECHANICAL

DEMOLITION PLAN

T

H A

V E

W E

S T

P

A L M

E T

T O

F

L

1910.08

MARCH 30, 2026

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

N A

T

IO

N A

L G

U A

R D

A R

M O

R Y

D M

A C

F M

O

P A

L M

E T

T O

E S

P R

E N

O V

A T

IO

N

1/8" = 1'-0"M1.1

1 Ground Level Mechanical Demolition Plan

DEMOLITION NOTES

GENERAL PLAN NOTES

1. REFERENCE DRAWING M0.1 FOR ABI LIST, REVIEW REQUIREMENTS OF THE ABI'S TO BE FAMILIAR WITH

HOW A DECLINE OR ACCEPTANCE OF EACH ABI AFFECTS THE SCOPE OF WORK OUTLINED ON THESE

DRAWINGS.

1. EXISTING AIR HANDLER, CONDENSATE PIPING, AND DRAIN PAN TO BE REMOVED.

2. EXISTING CONDENSING UNIT AND REFRIGERANT PIPING TO BE REMOVED.

3. EXISTING THERMOSTAT TO BE REMOVED.

4. EXISTING DUCTWORK TO BE CLEANED.

5. EXISTING DRYWELL, ROCK/GRAVEL AND PIPING TO BE REMOVED.

6. EXISTING MOTORIZED CONTROL DAMPER TO REMAIN.

7. EXISTING MOTORIZED CONTROL DAMPER TO BE REMOVED.

8. EXISTING RETURN GRILLE TO BE REMOVED.

9. EXISTING AIR HANDLER, CONDENSATE PIPING AND DRAIN PAN TO REMAIN.

10. EXISTING CONDENSING UNIT TO REMAIN.

11. EXISTING CONDENSATE PIPING TO BE CUT AT 6” ABOVE GRADE. REMOVE UNDERGROUND PIPING TO

DRYWELL.

12. EXISTING DUCT HEATER TO REMAIN. CONTRACTOR TO CONFIRM OPERATION AND REPORT TO GENERAL

CONTRACTOR.

13. REMOVE EXISTING CONDENSATE PIPING BACK TO AIR HANDLER.

N

1 06-17-26 ADDENDUM 02

/4

1/4" / 1'-0"

1/4" / 1'-0"

/4

1/4" / 1'-0"

/4

1 2 3 4 5 6 7

A

B

C

D

E

F

G

H

I

EF-1[D]

EF-2[D]

KEF-1

KSF-1

OAI-1[E]

"x

E

12"ø[E]

12"ø[E]

12"ø[E]

12"ø[E]

12"ø[E]

12"ø[E]

12"ø[E]

"x

E

56"x14"[E]

"x

E

12"ø[E]

"x

E

"x

E

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

490 CFM

SG-[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

510 CFM

SG-1[E]

12"øNK

490 CFM

SG-1[E]

12"øNK

490 CFM

42"x14"[E]24"x14"[E]

"x

E

12"ø[E]

12"ø[E]

"x

E

12"ø[E]

"x

E

24"x14"[E]

"x

E

24"x14"[E]

SHEET NO.:

PROJECT NO.:

DATE:

SHEET TITLE:

DRAWN BY:

REVISIONS:

CONSULTING ENGINEERS

154A Whitaker Rd.

Lutz, Florida 33549

813.333.2103 www.balengineering.com

Registry No. 31211

TO THE BEST OF THE KNOWLEDGE OF

THE ENGINEERS AND ARCHITECTS,

SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE

MINIMUM BUILDING CODES AND THE

APPLICABLE MINIMUM FIRE SAFETY

STANDARDS

/1

/2

:0 :4

P

M

C U se rs

\A d a m

G o re ck i\ B

A L E n g in e e ri n g In c\ B

A L E n g in e e ri n g In c.

I n te rn a l -

D o cu m e n ts

P ro je ct s\

\2

D M

A C

F M

O P a lm e tt o \W o rk in g

D ra w in g s\

M

P

R

.r vt

AG

M1.2

ROOF AND HIGH

CEILING

MECHANICAL

DEMOLITION PLAN

T

H A

V E

W E

S T

P

A L M

E T

T O

F

L

1910.08

MARCH 30, 2026

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

N A

T

IO

N A

L G

U A

R D

A R

M O

R Y

D M

A C

F M

O

P A

L M

E T

T O

E S

P R

E N

O V

A T

IO

N

1/8" = 1'-0"M1.2

1 Mezzanine Level Mechanical Demolition Plan

DEMOLITION NOTES

1. EXISTING DUCTWORK TO BE CLEANED.

2. EXISTING OA INTAKE TO REMAIN

3. EXISTING EXHAUST FAN TO BE REMOVED.

4. EXISTING KITCHEN EXHAUST AND MAKE-UP FANS TO BE REMOVED. EXISTING COMBINATION CURB TO BE REMOVED.

5. EXISTING ROOF JACK TO REMAIN.

GENERAL PLAN NOTES

1. REFERENCE DRAWING M0.1 FOR ABI LIST, REVIEW REQUIREMENTS OF THE ABI'S TO BE FAMILIAR WITH

HOW A DECLINE OR ACCEPTANCE OF EACH ABI AFFECTS THE SCOPE OF WORK OUTLINED ON THESE

DRAWINGS.

N

1 06-17-26 ADDENDUM 02

F E

F E

F E

F E

REF

F E

F E

F E

F E

F E

F E

FEFE

FD

FD

FD

FD

FP

S S

WAP

S

FP

S S

S

FP

FP

FPFP

T

T

T/H

T

T T H

T

T/H

1 2 3 4 5 6 7

A

B

C

D

E

F

G

H

I

AHU-5[E]

AHU-1[E]

CU-5[E]

CU-2B[E]CU-2[E]

CU-1[E]

AHU-6[E]

CU-6[D]

AHU-2[E]

CU-3[N]

CU-4[N]

AHU-4[N]

AHU-3[N]

AHU-7[E]

10 1

ENTRY

VESTIBULE

RECRUITER

OFFICE

RECRUITER

CLST.

WOMENS

VEST

WOMENS

LATRINE

WOMENS

CHANGING

105A

WOMENS

SHOWER

105B

MENS

VEST

MENS LATRINE

MENS

CHANGING

107A

MENS SHOWER

107B

MAIL / COPY

ROOM

MECH/ ELECT.

COMMUNICATIONS

VAULT

VAULT

SUPPLY AREA

MECH RM

EQUIPMENT

AREA

TABLES/

CHAIRS

VESTIBULE

VENDING

MECHANICAL

EXECUTIVE

OFFICER

MAIL ROOM

TRAINING

ROOM 1

GYM

MECHANICAL 1

PLT LDR'S

OFFICE

PLT SGT.

OFFICE

KITCHEN MESS

PORCH

OFFICE 3

COMMANDER

READINESS

NCO

TRAINING NCO

BTRY STAFF

DRILL HALL

7MAC-1[N]

MCU-1[N]2

SG-2[E]

10"øNK

275 CFM

SG-2[E]

10"øNK

250 CFM

SG-2[E]

10"øNK

250 CFM

SG-2[E]

10"øNK

275 CFM

SG-2[E]

12"øNK

250 CFM

SG-2[E]

10"øNK

175 CFM

SG-2[E]

10"øNK

175 CFM

SG-2[E]

12"øNK

250 CFM

SG-2[E]

10"øNK

150 CFM

SG-2[E]

12"øNK

250 CFM

SG-1[E]

10"øNK

320 CFM

(2) SG-3[E]

8"x8"NK

150 CFM

(2) TG-2[E]

24"x6"NK

0 CFM

R-1[E] 24"x20"NK

810 CFM

SG-1[E]

8"øNK

200 CFM

SG-1[E]

8"øNK

200 CFM

SG-1[E]

8"øNK

200 CFM

SG-2[E]

8"øNK

200 CFM

SG-2[E]

8"øNK

225 CFM

SG-2[E]

10"øNK

370 CFM

SG-2[E]

10"øNK

260 CFM

SG-2[E]

8"øNK

180 CFM

SG-2[E]

8"øNK

155 CFM

SG-2[E]

6"øNK

100 CFM

SG-2[E]

8"øNK

140 CFM

SG-2[E]

8"øNK

140 CFM

SG-2[E]

8"øNK

125 CFM

SG-2[E]

8"øNK

120 CFMSG-2[E]

8"øNK

120 CFM

SG-2[E]

8"øNK

125 CFM

SG-2[E]

8"øNK

150 CFM

SG-2[E]

8"øNK

180 CFM

SG-2[E]

10"øNK

350 CFM

"x

E

"x

E

"x

E

"x

E

20"x12"[E]

"x

E

14"x8"[E] 10"ø[E]

12"x8"[E]

12"x8"[E]

14"x12"[E]

12"ø[E]

28"x12"[E]28"x12"[E]

"x

E

44"x6"[E]

"x

E

10"ø[E]

8"x8"[E]

"x

E

"x

E

"x

E

18"x10"[E]

22"x12"[E]

"x

E

"x

E

24"x12"[E]

20"x6"[E]

20"x6"[E]

16"x10"[E]

"x

E

10"x8"[E]

14"x6"[E]

"x

E

30"x6"[E]

"x

E

"x

E

"x

E

"x

E

SG-2

8"x6"NK

175 CFM

RG-1[E]

10"x10"NK

325 CFM

TG-2

12"x8"NK

170 CFM

TG-2

12"x8"NK

170 CFM

RG-2[E]

10"x10"NK

170 CFM

RG-2[E]

10"x10"NK

170 CFM

RG-2[E]

36"x10"NK

665 CFM

SG-3[E]

8"x4"NK

50 CFM

RG-1[E]

6"x6"NK

350 CFM

8"ø[E]

8"ø[E]

8"ø[E]

"ø [E

] 1

"ø [E

"ø

[E

"ø

[E

"x

E

8"ø[E]

10"x10"[E]

"x

E

20"x12"[E]

SG2[E]

8"x6"NK

175 CFM

RG-1[E]

10"x10"NK

325 CFM

RG-1[E]

12"x12"NK

255 CFM

RG-1[E]

8"x8"NK

100 CFM

RG-1[E]

10"x10"NK

250 CFM

RG-1[E]

12"x12"NK

215 CFM

RG-1[E]

10"x10"NK

170 CFM

RG-1[E]

10"x10"NK

335 CFM

EG-1[E]

18"x12"NK

500 CFM

EG-1[E]

16"x10"NK

200 CFM

TG-1[E]

18"x10"NK

330 CFM

TG-1[E]

18"x10"NK

330 CFM

EG-1[E]

18"x12"NK

500 CFM

EG-1[E]

16"x10"NK

300 CFM

TG-1[E]

18"x10"NK

340 CFM

TG-1[E]

18"x10"NK

340 CFMSG-2[E]

6"øNK

100 CFM

RG-1[E]

22"x22"NK

425 CFM

MAC-1[N]

RG-1[E]

22"x22"NK

880 CFM

AHU-3[N]

OAI-1[E]

RG-1[E]

22"x22"NK

725 CFM

18"x6"[E]

RG-2

8"x4"NK

160 CFM

SG-2

8"x4"NK

160 CFM

AHU-4[N]3

6"ø[N]8"ø[N]

8"ø[N]

CU-7[E]

6"ø[N]

8"ø[N]

RG-3[N]

48"x42"

5000 CFM

RG-3[N]

48"x42"

5000 CFM

SHEET NO.:

PROJECT NO.:

DATE:

SHEET TITLE:

DRAWN BY:

REVISIONS:

CONSULTING ENGINEERS

154A Whitaker Rd.

Lutz, Florida 33549

813.333.2103 www.balengineering.com

Registry No. 31211

TO THE BEST OF THE KNOWLEDGE OF

THE ENGINEERS AND ARCHITECTS,

SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE

MINIMUM BUILDING CODES AND THE

APPLICABLE MINIMUM FIRE SAFETY

STANDARDS

/1

/2

:0 :4

P

M

C U se rs

\A d a m

G o re ck i\ B

A L E n g in e e ri n g In c\ B

A L E n g in e e ri n g In c.

I n te rn a l -

D o cu m e n ts

P ro je ct s\

\2

D M

A C

F M

O P a lm e tt o \W o rk in g

D ra w in g s\

M

P

R

.r vt

AG

M2.1

GROUND FLOOR

MECHANICAL

RENOVATION PLAN

T

H A

V E

W E

S T

P

A L M

E T

T O

F

L

1910.08

MARCH 30, 2026

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

N A

T

IO

N A

L G

U A

R D

A R

M O

R Y

D M

A C

F M

O

P A

L M

E T

T O

E S

P R

E N

O V

A T

IO

N

1/8" = 1'-0"M2.1

1 Ground Level Mechanical Renovation Plan

RENOVATION NOTES

GENERAL PLAN NOTES

1. REFERENCE DRAWING M0.1 FOR ABI LIST, REVIEW REQUIREMENTS OF THE ABI'S TO BE FAMILIAR WITH

HOW A DECLINE OR ACCEPTANCE OF EACH ABI AFFECTS THE SCOPE OF WORK OUTLINED ON THESE

DRAWINGS.

1. INSTALL NEW AIR HANDLER IN NEW DRAIN PAN ON NEW 6" CONCRETE PADS, MODIFY DUCTWORK AS NEEDED TO

ACCOMMODATE NEW UNIT.

2. INSTALL A NEW CONDENSING UNIT ON NEW 6" HIGH CONCRETE PAD. REFER TO DETAIL FOR CONDENSING UNIT TIE

DOWN.

3. INSTALL NEW THERMOSTAT WITH HUMIDITY CONTROL IN NEW LOCATION.

4. INSTALL NEW HUMIDITY SENSORS FOR DEHUMIDIFIERS ASSOCIATED WITH AHU-1 & 2.

5. ROUTE NEW INSULATED REFRIGERANT AND CONDENSATE PIPING THROUGH EXISTING SLEEVED PENETRATION IN

EXTERIOR WALL.

6. BASE BID: CONTRACTOR SHALL PROVIDE AND INSTALL NEW DRYWELL MIN. 10' FROM BUILDING STRUCTURE. REFER

TO DETAIL FOR ADDITIONAL INFORMATION.

ABI NO. 1: NEW 4” DRAIN TO NEW STORM WATER COLLECTION SYSTEM. COORDINATE CONNECTION AND TIE-IN WITH

CIVIL CONTRACTOR IN ACCORDANCE WITH ABI NO.1.

7. EXISTING GREASE HOOD TO REMAIN. RECERTIFY EXISTING ANSUL SYSTEM. PROVIDE NEW CAPTIVE AIR FAN CONTROLLER AND SENSORS FOR CONTROL OF NEW EXHAUST AND SUPPLY FAN ON ROOF. EXISTING KITCHEN

EQUIPMENT TO REMAIN AS-IS.

8. BASE BID: NO SCOPE

ABI NO.8: INSTALL NEW MUNTERS MODEL DEW-50 TURNKEY CONFIGURATION DEHUMIDIFIER. REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS FOR INSTALLATION REQUIREMENTS. REFER TO VAULT WALL

PENETRATION DETAIL.

9. INSTALL NEW WALL MOUNTED MINI-SPLIT, EXTEND CONDENSATE PIPING TO CONNECT TO AHU-6 CONDENSATE DRAIN

THROUGH WALL.

10. EXISTING CONDENSING UNIT TO REMAIN.

11. BASE BID: NO SCOPE

ABI NO. 8: Z-DUCT THROUGH VAULT WALL. MIN. 18” LEGS. ALL CONSTRUCTION SHALL BE WELDED ¼” STEEL PLATE

WITH 1/2” REBAR 3” O.C. EACH DIRECTION AND INSET ON EACH END BY 2”

12. BASE BID: NO SCOPE

ABI NO. 8: EXTEND 8X4 RELIEF DUCT UP THROUGH ROOF.

13. INSTALL NEW DEHUMIDIFIER EQUAL TO MUNTERS HC-300 TIED INTO THE RETURN DUCT OF THE AIR HANDLER IN ACCORDANCE WITH MANUFACTURE RECOMMENDATIONS. REACTIVATION AIR SHALL BE DUCTED TO EXTERIOR WALL AND TERMINATED WITH A WALL VENT INLET / OUTLET UNIT FEATURES A 6KW HEATER AT 240V/1 AND A FLA OF 31A.

14. INSTALL NEW WALL VENT EQUAL TO CANARM WHA SERIES WITH BIRD SCREEN.

15. INSTALL NEW MUNTERS MODEL DEW-50 TURNKEY CONFIGURATION DEHUMIDIFIER. REFER TO MANUFACTURERS

INSTALLATION INSTRUCTIONS FOR INSTALLATION REQUIREMENTS.

N

1 06-17-26 ADDENDUM 02

A

B

D

E

F

G

H

I

1 2 3 4 5 6

C

KEF-1[N]

KSF-1[N]

EF-1[N]

EF-2[N]

OAI-1[E]

"x

E

"x

E

"x

E

"x

E

"x

E

"x

E

12"ø[E]

"x

E

12"ø[E]

"x

E

24"x14"[E]

"x

E

56"x14"[E] 42"x14"[E]

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

510 CFM

SG-[E]

12"ø NK

490 CFM

SG-[E]

12"øNK

490 CFM

BASE BID: NO SCOPE

ABI NO. 8: NEW RELIEF

VENT ON ROOF EQUAL

TO GREENHECK MODEL

FGR. INSTALLED IN

ACCORDANCE WITH

NOA LISTING.

SHEET NO.:

PROJECT NO.:

DATE:

SHEET TITLE:

DRAWN BY:

REVISIONS:

CONSULTING ENGINEERS

154A Whitaker Rd.

Lutz, Florida 33549

813.333.2103 www.balengineering.com

Registry No. 31211

TO THE BEST OF THE KNOWLEDGE OF

THE ENGINEERS AND ARCHITECTS,

SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE

MINIMUM BUILDING CODES AND THE

APPLICABLE MINIMUM FIRE SAFETY

STANDARDS

/1

/2

:0 :4

P

M

C U se rs

\A d a m

G o re ck i\ B

A L E n g in e e ri n g In c\ B

A L E n g in e e ri n g In c.

I n te rn a l -

D o cu m e n ts

P ro je ct s\

\2

D M

A C

F M

O P a lm e tt o \W o rk in g

D ra w in g s\

M

P

R

.r vt

AG

M2.2

ROOF AND HIGH

CEILING

MECHANICAL

RENOVATION PLAN

T

H A

V E

W E

S T

P

A L M

E T

T O

F

L

1910.08

MARCH 30, 2026

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

N A

T

IO

N A

L G

U A

R D

A R

M O

R Y

D M

A C

F M

O

P A

L M

E T

T O

E S

P R

E N

O V

A T

IO

N

1/8" = 1'-0"M2.2

1 Upper Ceiling and Partial Roof Plan

RENOVATION NOTES

GENERAL PLAN NOTES

1. REFERENCE DRAWING M0.1 FOR ABI LIST, REVIEW REQUIREMENTS OF THE ABI'S TO BE FAMILIAR WITH

HOW A DECLINE OR ACCEPTANCE OF EACH ABI AFFECTS THE SCOPE OF WORK OUTLINED ON THESE

DRAWINGS.

1. INSTALL NEW EXHAUST FANS ON EXISTING CURBS. PROVIDE CURB ADAPTERS AS NEEDED.

2. INSTALL NEW KITCHEN EXHAUST AND MAKE-UP AIR FAN ON NEW CURBS, COORDINATE ROOF WORK WITH

GENERAL CONTRACTOR.

3. EXISTING ROOF JACK TO REMAIN.

4. EXISTING OUTSIDE AIR INTAKE TO REMAIN.

5. CONNECT NEW SUPPLY DUCTWORK TO EXISTING HIGH IN CHASE.

6. INSTALL NEW MANUAL VOLUME DAMPER AT EACH SUPPLY MAIN.

N

1 06-17-26 ADDENDUM 02

Sheets
M0.1 - NOTES, LEGENDS, AND SCHEDULES
M0.2 - SCHEDULES
M1.1 - GROUND FLOOR MECHANICAL DEMOLITION PLAN
M1.2 - ROOF AND HIGH CEILING MECHANICAL DEMOLITION PLAN
M2.1 - GROUND FLOOR MECHANICAL RENOVATION PLAN
M2.2 - ROOF AND HIGH CEILING MECHANICAL RENOVATION PLAN