2202C Alarm panels inc elevator shafts.pdf

PDF 152 KB Posted

Attached to
KENOSHA COUNTY RFB #2202 COUNTYWIDE FIRE INSPECTION
Solicitation number
2202
Issued by
Kenosha County, Kellnersville Village, Wisconsin

About this file

This is a Request for Bid (RFB) issued by Kenosha County, Wisconsin for countywide fire alarm system inspection and maintenance services under Bid #2202C, specifically for alarm panels including elevator shafts. The scope of work requires vendors to inspect, test, and maintain fire alarm systems and their components in accordance with NFPA 72 standards and manufacturer recommendations. Services include annual functional inspections of control equipment, batteries, initiating devices, notification appliances, remote annunciators, transient suppressors, and interface equipment. Specific requirements include physical removal and cleaning of smoke detectors, cleaning of duct detectors with actual manometer readings provided, annual testing of elevator shaft detectors, testing and cleaning of all pull stations, and inspection of battery booster stations where installed. Vendors must be trained and capable of working on existing fire panels and are responsible for returning panels to original working condition if damage or data loss occurs during testing. Inspections must be completed on or before dates specified by the Building Chief, with failure to meet deadlines resulting in liquidated damages.

The file does not specify pricing terms, labor rates, parts catalog pricing, or contract term and renewal options, though vendors are required to provide catalog pricing and labor rates with their bid or within 48 hours of request. Vendor personnel must maintain compliance with all notification requirements, including notifying facility occupants and alarm recipients before and after testing to prevent unnecessary emergency responses. Vendors are required to promptly notify the County's designee of any system impairments, defects, or malfunctions and obtain written authorization and quotation acceptance before performing corrective work that would result in additional costs. All defects or malfunctions not corrected during inspection must be reported in writing to the County's designee within 24 hours.

View the file

Other files

File Type Posted
2202D Kitchen hoods.pdf PDF
2202 PSB suppression.pdf PDF
2202 Brookside suppression 2.pdf PDF
2202 Alarm Inspection Brighton Dale Links.pdf PDF
2202 Alarm Inspection Courthouse.pdf PDF
2202 Alarm Inspection Parking Ramp.pdf PDF
2202 KCDC suppression.pdf PDF
2202 Pets suppression.pdf PDF
2202 Alarm Inspection Admin Bldg.pdf PDF
2202 KCJC ext.pdf PDF
2202 Alarm Inspection Public Safety Bldg.pdf PDF
2202 KCAB ext.pdf PDF
2202 PSB suppression 2.pdf PDF
2202 Alarm Inspection KCDC.pdf PDF
2202 Alarm Inspection Kemper.pdf PDF
2202 Addendum 3.pdf PDF
2202 Addendum 1.pdf PDF
2202 Alarm Inspection Pre-Trail Bldg.pdf PDF
2202D Offer Form.xlsx XLSX spreadsheet
2202B Sprinklers, Hydrants, Backflow preventers.pdf PDF
2202A2 Offer Form.xlsx XLSX spreadsheet
2202 Pets ext 2.pdf PDF
2202 KCDC ext.pdf PDF
2202 Courthouse ext.pdf PDF
Vendor Responsibility Form.pdf PDF
2202A Fire extinguishers hoses.pdf PDF
2202 Fire Inspection Bid.pdf PDF
2202 KCC ext.pdf PDF
2202C Offer Form.xlsx XLSX spreadsheet
2202 Brookside suppression.pdf PDF
2202 Pets ext.pdf PDF
2202 Alarm Inspection Fleet Maintenance.pdf PDF
2202B Offer Form.xlsx XLSX spreadsheet
2202 Alarm Inspection Brookside.pdf PDF
2202 PT ext.pdf PDF
2202 Alarm Inpection Job Center.pdf PDF
2202 PSB ext.pdf PDF
2202 Alarm Inspection KCDC E Storage Bldg.pdf PDF
2202 Alarm Inspection Kenosha County Center.pdf PDF
2202A Offer Form.xlsx XLSX spreadsheet
2202 Addendum 2.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KENOSHA COUNTY BID 2202C

WISCONSIN PAGE 1 OF 3

COUNTY OF KENOSHA

REQUEST FOR BID (RFB) #2202

COUNTYWIDE FIRE INSPECTION –

2202C – ALARM PANELS including ELEVATOR SHAFTS

FIRE ALARM SYSTEM INSPECTION REQUIREMENTS

Vendor shall inspect, test, and maintain fire alarm systems, their initiating devices, and notification appliances in accordance with the requirements of the all the latest NFPA requirements and NFPA 72 and the manufacturers recommendations, even if the manufacturer’s requirements are more stringent.

• Vendor personnel must be trained, capable, and able to work on the existing fire panels, as stated in the Bidders Qualifications, section 12.

• The successful bidder is responsible for returning the panel(s) back to the original work condition if the programming is lost or damage during testing.

• The vendor shall be liable for all damages to the alarm system during system testing or working on the unit, unless determined by an independent contractor that the testing did not cause the damage. Charges occurred from the independent contractor shall be paid by the party responsible for the damaged product or system.

• Vendor is responsible for data lost during test due to unexpected data loss due to the vendor’s technician’s negligence during the test and to bring the system back to its original condition.

• Vendor must be able to test, certify, install devices and update the fire panel.

• Vendor must physically remove and takedown the unit to clean the smoke detectors.

• Vendor must physically clean all duct detectors according to manufacturer’s specifications.

• Vendor must be within 18 inches of the smoke head to trip head.

o Reason for requirement is because some vendors tried to use a spray can to smoke the device at a distance of more than 15 feet which proved unsatisfactory. Kenosha County wants to assure that the devices are tested and that the testing device reaches the detectors. A SOLO KIT may be used only if the extension tool is long enough to reach the detector to satisfy NFPA and the manufacture’s requirement.

• Provide the actual manometer readings for all duct detectors.

• Manometer: The NOTIFIER (Installation and Maintenance Instructions for Model DHX-502

Intelligent Air Duct Smoke Detector Housing) addresses the manometer on page 7, section 7.1.

o See attached for the NOTIFIER (Installation and Maintenance Instructions).

• Test all elevator shaft detectors annually. Smoke detectors in elevator shafts are required for annual inspections and must be reported.

• Check battery booster stations where installed.

WISCONSIN PAGE 2 OF 3

• Record and provide a report of the actual sensitivity readings - not the panel readings, include information of how each device was tested. Heat, smoke and duct detectors are to be inspected annually. The codes require two-year inspection intervals, but Kenosha County requirements are for annual inspections of all devices.

• Vendor must test, open and clean all pull stations.

• The vendor's inspection, testing, and maintenance programs shall satisfy the requirements of the

NFPA code and shall conform to the equipment manufacturer’s recommendations and shall verify correct operation of the fire alarm system.

Inspection Schedule

• Fire panel and alarm system inspections shall take place on or before the dates listed specified by the Building Chief. Failure to perform the inspection and complete any repairs by the listed dates, the bidder will be responsible for liquidated damages, section 33 of the bid.

Notification

• Before proceeding with any testing, the vendor, through the County’s designee for each facility, shall notify all persons and facilities receiving alarm, supervisory, or trouble signals and all building occupants of the testing to prevent unnecessary response.

• At the conclusion of testing, those previously notified, shall be notified that testing has been concluded.

• The vendor shall coordinate system testing with The County’s designee for each facility at each location to prevent interruption of critical building systems or equipment.

Inspection and Testing

• The vendor shall perform functional inspections and testing annually or in accordance with the schedules in NFPA or more often if required by the authority having jurisdiction. Tests shall be conducted using appropriate methods listed in NFPA and as prescribed by the manufacturer. The following items, at a minimum, shall be included:

o Control Equipment o Batteries o Transient Suppressors o Remote Annunciators o Initiating Devices o Interface Equipment o Alarm Notification Appliances

System Impairments

• The vendor shall notify The County’s designee for each facility when a fire alarm system or part thereof is impaired. Impairments to systems shall include out-of-service events.

• The vendor shall promptly notify the County’s designee to receive authorization to make corrections that would result in additional cost, before correcting the system defects and malfunctions. A written quotation and County’s acceptance is required before beginning any work.

• The vendor shall notify the County’s designee for each facility when an impairment period is completed or discontinued.

WISCONSIN PAGE 3 OF 3

• If a defect or malfunction is not corrected at the conclusion of system inspection, testing, or maintenance, the vendor shall inform the County’s designee for each facility of the impairment before leaving the facility and provide a written report of the impairment within 24 hours.

Maintenance, Parts and Labor

• The vendor shall promptly correct system defects and malfunctions. Fire alarm system equipment shall be maintained in accordance with the manufacturer’s instructions. The bidder should provide catalog pricing and labor rate with bid or within 48 hours upon request.