2202 Alarm Inspection Brookside.pdf
PDF 1 MB Posted
- Solicitation number
- 2202
- Issued by
- Kenosha County, Kellnersville Village, Wisconsin
About this file
This is an NFPA 72 System Record of Inspection and Testing report for Brookside Care Center, a senior care center and Community-Based Residential Facility (CBRF) located at 3508 Washington Road, Kenosha, Wisconsin, operated by Kenosha County. The inspection and testing were conducted by Siemens Industry, Inc. and covered a comprehensive fire alarm and detection system serving approximately 36 pages of detailed testing documentation. The inspection period spanned from May 23, 2022 through May 27, 2022, with system restoration to normal operation completed on May 27, 2022 at 1500 hours. The facility's fire alarm system utilizes a Notifier NFS2-3030D control panel located at the Willowbrook Entrance, with primary power of 120 volts, 20 amps, and secondary backup power provided by sealed lead-acid batteries rated at 24 hours standby and 15 minutes alarm mode capacity. The system incorporates 295 notification appliances including alarm speakers and visual strobes, 61 duct smoke detectors, 18 heat detectors, 43 manual pull stations, and 309 system smoke detectors distributed across multiple floors and zones.
Testing results revealed overall system functionality with one critical failure: a Notification Appliance Power Extender Panel (FCPS 8, device 01:01-01:NP-008) located in the Willowbrook IT Room exhibited battery failure at 10% capacity and requires replacement. Additionally, five duct smoke detectors associated with RTU 3 failed to shut down the connected HVAC units during activation, specifically devices D055, D056, D057, D060, and D062, all Notifier INNOVAIR/FSD-75IPL models. All other initiating devices, including 309 system smoke detectors and 18 heat detectors, passed functional testing with appropriate sensitivity readings. Notification appliances achieved 100% pass rate across all 295 devices tested. The monitoring organization is Alarm Detection Systems, Inc. (Account #183109), with digital transmission means and local documentation retained by facility management. Testing was performed in accordance with NFPA 72 standards by Siemens technicians Stanley Laitinen and Alexander Hanus, with acceptance by Scott McClain, Kenosha County representative.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFPA 72 REPORT
© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 36
SYSTEM RECORD OF INSPECTION AND TESTING
System Name: BROOKSIDE Panel Name: 01 - BROOKSIDE
Inspection/Test Start Date/Time: 23 May 2022 0600 Inspection/Test Completion Date/Time: 27 May 2022 1500
Contract Info: Kenosha County 2022 (2600149454) Notification Number: 5102244789
Supplemental Form(s) Attached: Yes
1. PROPERTY INFORMATION
Name of property: BROOKSIDE CARE CENTER (4433-53144-00024)
Address: 3508 WASHINGTON RD. KENOSHA, WI. 53144
Description of property: SENIOR CARE CENTER/CBRF
Name of property representative: KENOSHA COUNTY (30078447), Scott McClain
Address: 1010 56TH ST, KENOSHA, WI 53140-3738
Phone: None Fax: None E-mail: scott.mcclain@kenoshacounty.org
2. TESTING AND MONITORING INFORMATION
Testing organization: SIEMENS
Address: 6737 West Washington Street, Suite 2110, Milwaukee, WI 53215
Phone: 414-475-3700 Fax: NA E-mail: NA
Monitoring organization: ALARM DETECTION SYSTEMS, INC.
Address: WILLOWBROOK ENTRANCE ABOVE CEILING
Phone: 1-630-844-6302 Fax: NA E-mail: NA
Account number: ACCT.# 183109 P.C. 1001 Phone line 1: NA Phone line 2: NA
Means of transmission: Digital
Entity to which alarms are retransmitted: NA Phone: NA
3. DOCUMENTATION
On-site location of the required record documents and site-specific software: DOCUMENTS RETAINED BY FACILITIES
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
System Name: BROOKSIDE Panel Name: 01 - BROOKSIDE
Panel Location and Address: WILLOW BROOK ENTRANCE, 3508 WASHINGTON RD., KENOSHA, WI, 53144
Manufacturer: NOTIFIER Model number: NFS2-3030D
4.2 Software and Firmware
Firmware revision number:
4.3 System Power
4.3.1 Primary (Main) Power
Nominal voltage: 120 Amps: 20 Location: WILLOW BROOK ENTRANCE
Overcurrent protection type: Breaker Amps: 20
Disconnecting means location: Panel LS-1 Breaker 17
4.3.2 Secondary Power
Type: Storage Battery Location: WILLOW BROOK ENTRANCE
Battery type (if applicable): Sealed Lead Acid Manufactured Date: 18 Sep 2021
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24 In alarm mode (minutes): 15
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 36
4.4 Notification Appliance Power Extender Panels
4.4.1 Primary Power
ID Location Input Volts
Panel Amps
Over-current Type
Over-current Amps
Primary Supply Location
Disconnect Location
01:01-01:DP-001 1st Fl Willowbrook Entrance Above Ceiling
BREAKER
01:01-01:NP-001 1st Fl 200 Hall - Room 868 NAC
BREAKER EC/A 4 #4
01:01-01:NP-002 1st Fl 200 Hall - Room 868 NAC
BREAKER EC/A 4 #4
01:01-01:NP-003 1st Fl 400 Hall - Room 811 NAC
BREAKER EL/B #8
01:01-01:NP-004 1st Fl 400 Hall - Room 811 NAC
BREAKER EL/B #8
01:01-01:NP-005 1st Fl R1 - IT Room R146 NAC 5 BREAKER OS/1B #33
01:01-01:NP-006 1st Fl R1 - IT Room R146 NAC 6 BREAKER OS/1B 33
01:01-01:NP-007 1st Fl R1 - IT Room C246 NAC 7 BREAKER OS/2B 35
01:01-01:NP-008 1st Fl Willowbrook - IT Room
C157 FCPS 8
BREAKER OS/1C #67
01:01-01:NP-009 1st Fl Willowbrook - IT Room
C157 FCPS 9
BREAKER OS/1C #67
01:01-01:NP-010 1st Fl 400 Hall - Room 811 NAC
BREAKER EL/B #8
01:01-01:NP-011 1st Fl Willowbrook - IT Room C157 Master Sync
BREAKER OS/1C #67
01:01-01:RP-001 1st Fl 200 Hall - Room 868 AMP
BREAKER EC/A # 2
01:01-01:RP-002 1st Fl R1 - IT Room R146 AMP 2 BREAKER OS/1B #35
4.4.2 Secondary Power
ID Location Battery Type
Manufactured Date
Voltage Rating
Amp Rating
Standby Hours
Alarm Minutes
01:01-01:DP-001 1st Fl Willowbrook Entrance Above Ceiling SLA 2021-10-07 12/12 7 AH 24 15
01:01-01:NP-001 1st Fl 200 Hall - Room 868 NAC 1 SLA 2021-10-28 12/12 7AH 24 15
01:01-01:NP-002 1st Fl 200 Hall - Room 868 NAC 2 SLA 2020-10-15 12/12 7AH 24 15
01:01-01:NP-003 1st Fl 400 Hall - Room 811 NAC 3 SLA 2020-09-15 12/12 7AH 24 15
01:01-01:NP-004 1st Fl 400 Hall - Room 811 NAC 4 SLA 2020-09-15 12/12 7AH 24 15
01:01-01:NP-005 1st Fl R1 - IT Room R146 NAC 5 SLA 2019-04-01 12/12 7AH 24 15
01:01-01:NP-006 1st Fl R1 - IT Room R146 NAC 6 SLA 2019-04-01 12/12 7AH 24 15
01:01-01:NP-007 1st Fl R1 - IT Room C246 NAC 7 SLA 2020-09-15 12/12 7AH 24 15
01:01-01:NP-008 1st Fl Willowbrook - IT Room C157 FCPS 8 SLA 2019-04-26 12/12 7AH 24 15
01:01-01:NP-009 1st Fl Willowbrook - IT Room C157 FCPS 9 SLA 2019-04-01 12/12 7AH 24 15
01:01-01:NP-010 1st Fl 400 Hall - Room 811 NAC 10 SLA 2020-09-15 12/12 7AH 24 15
01:01-01:NP-011 1st Fl Willowbrook - IT Room C157 Master Sync
SLA 2020-09-15 12/12 7AH 24 15
01:01-01:RP-001 1st Fl 200 Hall - Room 868 AMP 1 SLA 2020-05-29 12/12 55 AH 24 15
01:01-01:RP-002 1st Fl R1 - IT Room R146 AMP 2 SLA 2020-08-14 12/12 55 AH 24 15
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: BRIANNA Time: 0600
Building management Contact: SCOTT MCCLAIN Time: 0600
Building occupants Contact: BY SCOTT MCCLAIN Time: 0600
Authority having jurisdiction (AHJ) Contact: NA Time: NA
Other, if required Contact: NA Time: NA
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 36
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection or Functional Test Comments
Control unit Functional None
Disconnect switches Functional None
Fuses Functional None
Ground-fault monitoring Functional None
Interface Equipment Functional None
Lamps/LEDs/LCDs Functional None
Local annunciator Functional None
Primary Power Functional None
Remote annunciators Functional None
Remote power panels Functional None
Supervision Functional None
Trouble signals Functional None
6.2 Secondary Power
Description Visual Inspection or Functional Test Comments
Battery condition Functional MAN. DATE 9-18- 2021 (2) 55 AH BATTERIES
Charger test Functional 27.88
Discharge test Functional 100%/100%
Load voltage Functional 13.85/13.77
Remote panel batteries Functional None
6.3 Notification Appliance Power Extender Panels Secondary Power
ID Location Battery Voltage
Battery Amps
Test Method
Pass/ Fail
01:01-01:DP-001 1st Fl Willowbrook Entrance Above Ceiling 13.79 100% Functional Pass
01:01-01:NP-001 1st Fl 200 Hall - Room 868 NAC 1 13.73/13.78 100%/100% Functional Pass
01:01-01:NP-002 1st Fl 200 Hall - Room 868 NAC 2 13.77/13.77 100%/100% Functional Pass
01:01-01:NP-003 1st Fl 400 Hall - Room 811 NAC 3 13.68/13.65 100%/100% Functional Pass
01:01-01:NP-004 1st Fl 400 Hall - Room 811 NAC 4 13.68/13.86 100%/100% Functional Pass
01:01-01:NP-005 1st Fl R1 - IT Room R146 NAC 5 13.81/1376. 100%/100% Functional Pass
01:01-01:NP-006 1st Fl R1 - IT Room R146 NAC 6 13.75/13.76 100%/100% Functional Pass
01:01-01:NP-007 1st Fl R1 - IT Room C246 NAC 7 13.77/13.76 100%/100% Functional Pass
01:01-01:NP-008 1st Fl Willowbrook - IT Room C157 FCPS 8 13.65/12.56 100%/10% Functional Fail
01:01-01:NP-009 1st Fl Willowbrook - IT Room C157 FCPS 9 13.72/13.78 100%/100% Functional Pass
01:01-01:NP-010 1st Fl 400 Hall - Room 811 NAC 10 13.67/13.73 100%/100% Functional Pass
01:01-01:NP-011 1st Fl Willowbrook - IT Room C157 Master Sync 13.67/13.74 100%/100% Functional Pass
01:01-01:RP-001 1st Fl 200 Hall - Room 868 AMP 1 13.78/13.80 100%/100% Functional Pass
01:01-01:RP-002 1st Fl R1 - IT Room R146 AMP 2 13.80/13.76 100%/100% Functional Pass
6.4 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
6.5 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.6 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 36
6.7 Supervising Station Monitoring
Description Received Time / Elapsed
Time Pass/Fail Comments
Alarm signal Yes NA / NA Pass None
Alarm restoration Yes NA / NA Pass None
Trouble signal Yes NA / NA Pass None
Trouble restoration Yes NA / NA Pass None
Supervisory signal No NA / NA Na None
Supervisory restoration No NA / NA Na None
6.8 Public Emergency Alarm Reporting System
Description Yes No Time Comments
Alarm signal NA NA
Alarm restoration NA NA
Trouble signal NA NA
Trouble restoration NA NA
Supervisory signal NA NA
Supervisory restoration NA NA
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: CINDY Time: 1500
Building management Contact: SCOTT MCCLAIN Time: 1500
Building occupants Contact: BY SCOTT MCCLAIN Time: 1500
Authority having jurisdiction (AHJ) Contact: Time:
Other, if required Contact: NA Time: NA
8. SYSTEM RESTORED TO NORMAL OPERATION
Date: 27 May 2022 Time: 1500
9. CERTIFICATION
This Testing Was Performed in Accordance with Applicable NFPA Standards.
Signed:
Stanley Laitinen, Alexander Hanus Date: 5-27-2022
Printed name: STANLEY LAITINEN,ALEXANDER HANUS Title: Technician License No.: SL#150654,AH#148912
Organization: SIEMENS Phone: 414-475-3700
Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service, Programming
10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED
NAC Panels
Address Location Model Comment:
01:01-01:NP-
1st Fl Willowbrook - IT Room
C157 FCPS 8
NOTIFIER FCPS6 (2) 7 AH BATTERIES REQUIRE REPLACEMENT
Duct Smoke Detectors (P)
Address Location Model Comment:
01:L1-L1-D055 1st Fl C-Attic Area:
Administration - RTU3:
Return
NOTIFIER
INNOVAIR/FSD-
75IPL
DP-0.10- DID NOT SHUT DOWN UNIT.
01:L1-L1-D056 1st Fl C-Attic Area:
Administration - RTU3:
Supply
NOTIFIER
INNOVAIR/FSD-
75IPL
DP-0.10- DID NOT SHUT DOWN UNIT.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 36
Duct Smoke Detectors (P)
Address Location Model Comment:
01:L1-L1-D057 1st Fl C-Attic Area: Memory Care - Center Area: Supply
NOTIFIER
INNOVAIR/FSD-
75IPL
DP-0.05-DID NOT SHUT DOWN UNIT.
01:L2-L2-D060 1st Fl C-Attic Area: Center Area -RTU 3 Supply
NOTIFIER
INNOVAIR/FSD-
75IPL
DP-0.10 DID NOT SHUT DOWN UNIT
01:L2-L2-D062 1st Fl C-Attic Area: Center Area - RTU 3-Return
NOTIFIER
INNOVAIR/FSD-
DP-0.05-DID NOT SHUT DOWN UNIT.
11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE
The undersigned accepted the test report for the system as specified herein:
Signed:
Printed name: Scott McClain Date:
Organization: KENOSHA COUNTY (30078447) Phone: None
Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements.
Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.
12. OTHER
12.1 Special Procedures
ELEVATOR RECALL KEY-FEOK-1
12.2 Comments
ALL SMOKE DETECTORS PASSED SENSITIVITY READINGS AND DIFFERENTIAL TESTING.
DIFFERENTIAL PRESSURE RANGES: MODEL DNR 0.01-1.11 IN. OF WATER. MODEL: INNOVAIR/FSP751PL 0.0015 - 1.2 IN.
OF WATER
ALL AHU SHUTDOWNS FUNCTIONED PROPERLY WITH THE EXCEPTION OF THOSE RELATED TO RTU 3.
ALL DOORS RELEASED PROPERLY UNDER ALARM CONDITIONS.
NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: BROOKSIDE CARE CENTER (4433-53144-00024)
Address: 3508 WASHINGTON RD. KENOSHA, WI. 53144
2. NOTIFICATION APPLIANCE TEST RESULTS
2.1 Notification Appliances Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
295 295 100% 0 0% 0 0% Alarm Speakers
187 187 100% 0 0% 0 0% Alarm Speakers w/Strobe
124 124 100% 0 0% 0 0% Visual Alarms
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 36
2.2 Notification Appliances Testing Results by Type
Alarm Speakers
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
1 05/25/22 01-01:AN-001 1st Fl 100's Country Kitchen Functional Pass
2 05/25/22 01-01:AN-002 1st Fl 100's Dining Room Functional Pass
3 05/25/22 01-01:AN-003 1st Fl 200's Country Kitchen Functional Pass
4 05/25/22 01-01:AN-004 1st Fl 200's Dining Room Functional Pass
5 05/25/22 01-01:AN-005 1st Fl 400/500 Activity Room: North Functional Pass
6 05/25/22 01-01:AN-006 1st Fl 400/500 Activity Room: South Functional Pass
7 05/25/22 01-01:AN-007 1st Fl 400 TV Room Functional Pass
8 05/25/22 01-01:AN-008 1st Fl 500 Dining Room: Center Functional Pass
9 05/25/22 01-01:AN-009 1st Fl 500 Dining Room: East Functional Pass
10 05/25/22 01-01:AN-010 1st Fl 500 Dining Room: West Functional Pass
11 05/25/22 01-01:AN-011 1st Fl 600/700 Activity Room: East Functional Pass
12 05/25/22 01-01:AN-012 1st Fl 600/700 Activity Room: West Functional Pass
13 05/25/22 01-01:AN-013 1st Fl 600/700 Hall by Activities Room Functional Pass
14 05/25/22 01-01:AN-014 1st Fl 600 Dining: Center Functional Pass
15 05/25/22 01-01:AN-015 1st Fl 600 Dining: East Functional Pass
16 05/25/22 01-01:AN-016 1st Fl 600 Dining: West Functional Pass
17 05/25/22 01-01:AN-017 1st Fl 700 TV Room Functional Pass
18 05/25/22 01-01:AN-018 Bsmnt Break Room Functional Pass
19 05/25/22 01-01:AN-019 1st Fl Business Office Conf Room Functional Pass
20 05/25/22 01-01:AN-020 1st Fl Business Office Cubicles: North Functional Pass
21 05/25/22 01-01:AN-021 1st Fl Business Office Cubicles: South Functional Pass
22 05/25/22 01-01:AN-022 1st Fl Corr by Room 501 Functional Pass
23 05/25/22 01-01:AN-023 1st Fl East Activity Room Functional Pass
24 05/25/22 01-01:AN-024 1st Fl East Country Kitchen Functional Pass
25 05/25/22 01-01:AN-025 1st Fl East Dining Room by Door Functional Pass
26 05/25/22 01-01:AN-026 1st Fl East Entrance Vestibule Functional Pass
27 05/25/22 01-01:AN-027 1st Fl East Entrance Vestibule Functional Pass
28 05/25/22 01-01:AN-028 Bsmnt East Hall: Center Functional Pass
29 05/25/22 01-01:AN-029 Bsmnt East Hall: North Functional Pass
30 05/25/22 01-01:AN-030 Bsmnt East Hall: South Functional Pass
31 05/25/22 01-01:AN-031 1st Fl East Living Room Functional Pass
32 05/25/22 01-01:AN-032 1st Fl Hall by 100's Restroom Functional Pass
33 05/25/22 01-01:AN-033 1st Fl Hall by 600 Kitchen Functional Pass
34 05/25/22 01-01:AN-034 1st Fl Hall by 100's Restroom Functional Pass
35 05/25/22 01-01:AN-035 1st Fl Hall by Business Office Conference Room Functional Pass
36 05/25/22 01-01:AN-036 1st Fl Hall by Business Office: North Functional Pass
37 05/25/22 01-01:AN-037 1st Fl Hall by Business Office: South Functional Pass
38 05/25/22 01-01:AN-038 1st Fl Hall by East Activity Room Functional Pass
39 05/25/22 01-01:AN-039 1st Fl Hall by Elevator Car 1 Functional Pass
40 05/25/22 01-01:AN-040 1st Fl Hall by Elevator Seating Area Functional Pass
41 05/25/22 01-01:AN-041 1st Fl Hall by Exam Room Functional Pass
42 05/25/22 01-01:AN-042 1st Fl Hall by FACP Functional Pass
43 05/25/22 01-01:AN-043 1st Fl Hall by Kitchen Functional Pass
44 05/25/22 01-01:AN-044 1st Fl Hall by Massage Room: East Functional Pass
45 05/25/22 01-01:AN-045 1st Fl Hall by Massage Room: West Functional Pass
46 05/25/22 01-01:AN-046 Bsmnt Hall by Mechanical Room Functional Pass
47 05/25/22 01-01:AN-047 Bsmnt Hall by North Exit Functional Pass
48 05/25/22 01-01:AN-048 1st Fl Hall by North Office Functional Pass
49 05/25/22 01-01:AN-049 1st Fl Hall by Patio Door Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 36
Alarm Speakers
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
50 05/25/22 01-01:AN-050 1st Fl Hall by Room 103 Functional Pass
51 05/25/22 01-01:AN-051 1st Fl Hall by Room 107 Functional Pass
52 05/25/22 01-01:AN-052 1st Fl Hall by Room 108 Functional Pass
53 05/25/22 01-01:AN-053 1st Fl Hall by Room 110 Functional Pass
54 05/25/22 01-01:AN-054 1st Fl Hall by Room 111 Functional Pass
55 05/25/22 01-01:AN-055 1st Fl Hall by Room 111 Functional Pass
56 05/25/22 01-01:AN-056 1st Fl Hall by Room 112 Functional Pass
57 05/25/22 01-01:AN-057 1st Fl Hall by Room 114 Functional Pass
58 05/25/22 01-01:AN-058 1st Fl Hall by Room 122 Functional Pass
59 05/25/22 01-01:AN-059 1st Fl Hall by Room 124 Functional Pass
60 05/25/22 01-01:AN-060 1st Fl Hall by Room 201 Functional Pass
61 05/25/22 01-01:AN-061 1st Fl Hall by Room 205 Functional Pass
62 05/25/22 01-01:AN-062 1st Fl Hall by Room 207 Functional Pass
63 05/25/22 01-01:AN-063 1st Fl Hall by Room 209 Functional Pass
64 05/25/22 01-01:AN-064 1st Fl Hall by Room 210 Functional Pass
65 05/25/22 01-01:AN-065 1st Fl Hall by Room 213 Functional Pass
66 05/25/22 01-01:AN-066 1st Fl Hall by Room 214 Functional Pass
67 05/25/22 01-01:AN-067 1st Fl Hall by Room 217 Functional Pass
68 05/25/22 01-01:AN-068 1st Fl Hall by Room 218 Functional Pass
69 05/25/22 01-01:AN-069 1st Fl Hall by Room 219 Functional Pass
70 05/25/22 01-01:AN-070 1st Fl Hall by Room 223 Functional Pass
71 05/25/22 01-01:AN-071 1st Fl Hall by Room 503 Functional Pass
72 05/25/22 01-01:AN-072 1st Fl Hall by Room 507 Functional Pass
73 05/25/22 01-01:AN-073 1st Fl Hall by Room 509 Functional Pass
74 05/25/22 01-01:AN-074 1st Fl Hall by Room 513 Functional Pass
75 05/25/22 01-01:AN-075 1st Fl Hall by Room 514 Functional Pass
76 05/25/22 01-01:AN-076 1st Fl Hall by Room 517 Functional Pass
77 05/25/22 01-01:AN-077 1st Fl Hall by Room 526 Functional Pass
78 05/25/22 01-01:AN-078 1st Fl Hall by Room 604 Functional Pass
79 05/25/22 01-01:AN-079 1st Fl Hall by Room 608 Functional Pass
80 05/25/22 01-01:AN-080 1st Fl Hall by Room 612 Functional Pass
81 05/25/22 01-01:AN-081 1st Fl Hall by Room 614 Functional Pass
82 05/25/22 01-01:AN-082 1st Fl Hall by Room 615 Functional Pass
83 05/25/22 01-01:AN-083 1st Fl Hall by Room 618 Functional Pass
84 05/25/22 01-01:AN-084 1st Fl Hall by Room 619 Functional Pass
85 05/25/22 01-01:AN-085 1st Fl Hall by Room 622 Functional Pass
86 05/25/22 01-01:AN-086 1st Fl Hall by Room 703 Functional Pass
87 05/25/22 01-01:AN-087 1st Fl Hall by Room 707 Functional Pass
88 05/25/22 01-01:AN-088 1st Fl Hall by Room 709 Functional Pass
89 05/25/22 01-01:AN-089 1st Fl Hall by Room 712 Functional Pass
90 05/25/22 01-01:AN-090 1st Fl Hall by Room 714 Functional Pass
91 05/25/22 01-01:AN-091 1st Fl Hall by Room 718 Functional Pass
92 05/25/22 01-01:AN-092 1st Fl Hall by Room 719 Functional Pass
93 05/25/22 01-01:AN-093 1st Fl Hall by Room 723 Functional Pass
94 05/25/22 01-01:AN-094 1st Fl Hall by Room C102 Functional Pass
95 05/25/22 01-01:AN-095 1st Fl Hall by Room C104 Functional Pass
96 05/25/22 01-01:AN-096 1st Fl Hall by Room C111 Functional Pass
97 05/25/22 01-01:AN-097 1st Fl Hall by Room C112 Functional Pass
98 05/25/22 01-01:AN-098 1st Fl Hall by Room C137 Functional Pass
99 05/25/22 01-01:AN-099 1st Fl Hall by Room C140 Functional Pass
100 05/25/22 01-01:AN-100 1st Fl Hall by Room R115 Functional Pass
101 05/25/22 01-01:AN-101 1st Fl Hall by Room R119 Functional Pass
102 05/25/22 01-01:AN-102 1st Fl Hall by Room R120 Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 8 of 36
Alarm Speakers
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
103 05/25/22 01-01:AN-103 1st Fl Hall by Room R122 Functional Pass
104 05/25/22 01-01:AN-104 1st Fl Hall by Room R202 Functional Pass
105 05/25/22 01-01:AN-105 1st Fl Hall by Room R207 Functional Pass
106 05/25/22 01-01:AN-106 1st Fl Hall by Room R208 Functional Pass
107 05/25/22 01-01:AN-107 1st Fl Hall by Room R211 Functional Pass
108 05/25/22 01-01:AN-108 1st Fl Hall by Salon: Center Functional Pass
109 05/25/22 01-01:AN-109 1st Fl Hall by South Office Functional Pass
110 05/25/22 01-01:AN-110 1st Fl Hall by Wheelchair Storage Functional Pass
111 05/25/22 01-01:AN-111 1st Fl Kitchen Functional Pass
112 05/25/22 01-01:AN-112 1st Fl Kitchen Functional Pass
113 05/25/22 01-01:AN-113 1st Fl Kitchen Functional Pass
114 05/25/22 01-01:AN-114 1st Fl Kitchen Functional Pass
115 05/25/22 01-01:AN-115 1st Fl Living Room Functional Pass
116 05/25/22 01-01:AN-116 1st Fl Middle: Nurses Area Functional Pass
117 05/25/22 01-01:AN-117 1st Fl Namaste Room Functional Pass
118 05/25/22 01-01:AN-118 1st Fl North Country Kitchen Functional Pass
119 05/25/22 01-01:AN-119 1st Fl North Dining Room Functional Pass
120 05/25/22 01-01:AN-120 1st Fl North Dining Room Functional Pass
121 05/25/22 01-01:AN-121 1st Fl North Dining Room: East Functional Pass
122 05/25/22 01-01:AN-122 1st Fl North Dining Room: West Functional Pass
123 05/25/22 01-01:AN-123 1st Fl North Living Room Functional Pass
124 05/25/22 01-01:AN-124 1st Fl North Living Room Functional Pass
125 05/25/22 01-01:AN-125 1st Fl North Seating Area Functional Pass
126 05/25/22 01-01:AN-126 1st Fl Nurses Station Functional Pass
127 05/25/22 01-01:AN-127 1st Fl Private Dining Functional Pass
128 05/25/22 01-01:AN-128 1st Fl Room 401 Functional Pass
129 05/25/22 01-01:AN-129 1st Fl Room 409 Functional Pass
130 05/25/22 01-01:AN-130 1st Fl Room 410 Functional Pass
131 05/25/22 01-01:AN-131 1st Fl Room 414 Functional Pass
132 05/25/22 01-01:AN-132 1st Fl Room 415 Functional Pass
133 05/25/22 01-01:AN-133 1st Fl Room 418 Functional Pass
134 05/25/22 01-01:AN-134 1st Fl Room 426 Functional Pass
135 05/25/22 01-01:AN-135 1st Fl Room C101 Functional Pass
136 05/25/22 01-01:AN-136 1st Fl Room C102 Functional Pass
137 05/25/22 01-01:AN-137 1st Fl Room C103 Functional Pass
138 05/25/22 01-01:AN-138 1st Fl Room C104 Functional Pass
139 05/25/22 01-01:AN-139 1st Fl Room C105 Functional Pass
140 05/25/22 01-01:AN-140 1st Fl Room C106 Functional Pass
141 05/25/22 01-01:AN-141 1st Fl Room C107 Functional Pass
142 05/25/22 01-01:AN-142 1st Fl Room C108 Functional Pass
143 05/25/22 01-01:AN-143 1st Fl Room C109 Functional Pass
144 05/25/22 01-01:AN-144 1st Fl Room C110 Functional Pass
145 05/25/22 01-01:AN-145 1st Fl Room C111 Functional Pass
146 05/25/22 01-01:AN-146 1st Fl Room C112 Functional Pass
147 05/25/22 01-01:AN-147 1st Fl Room C113 Functional Pass
148 05/25/22 01-01:AN-148 1st Fl Room C114 Functional Pass
149 05/25/22 01-01:AN-149 1st Fl Room C115 Functional Pass
150 05/25/22 01-01:AN-150 1st Fl Room C116 Functional Pass
151 05/25/22 01-01:AN-151 1st Fl Room C117 Functional Pass
152 05/25/22 01-01:AN-152 1st Fl Room C118 Functional Pass
153 05/25/22 01-01:AN-153 1st Fl Room C119 Functional Pass
154 05/25/22 01-01:AN-154 1st Fl Room C120 Functional Pass
155 05/25/22 01-01:AN-155 1st Fl Room C121 Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 9 of 36
Alarm Speakers
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
156 05/25/22 01-01:AN-156 1st Fl Room C122 Functional Pass
157 05/25/22 01-01:AN-157 1st Fl Room C122 Functional Pass
158 05/25/22 01-01:AN-158 1st Fl Room C124 Functional Pass
159 05/25/22 01-01:AN-159 1st Fl Room R101 Functional Pass
160 05/25/22 01-01:AN-160 1st Fl Room R102 Functional Pass
161 05/25/22 01-01:AN-161 1st Fl Room R103 Functional Pass
162 05/25/22 01-01:AN-162 1st Fl Room R104 Functional Pass
163 05/25/22 01-01:AN-163 1st Fl Room R105 Functional Pass
164 05/25/22 01-01:AN-164 1st Fl Room R106 Functional Pass
165 05/25/22 01-01:AN-165 1st Fl Room R107 Functional Pass
166 05/25/22 01-01:AN-166 1st Fl Room R108 Functional Pass
167 05/25/22 01-01:AN-167 1st Fl Room R109 Functional Pass
168 05/25/22 01-01:AN-168 1st Fl Room R110 Functional Pass
169 05/25/22 01-01:AN-169 1st Fl Room R111 Functional Pass
170 05/25/22 01-01:AN-170 1st Fl Room R112 Functional Pass
171 05/25/22 01-01:AN-171 1st Fl Room R113 Functional Pass
172 05/25/22 01-01:AN-172 1st Fl Room R114 Functional Pass
173 05/25/22 01-01:AN-173 1st Fl Room R115 Functional Pass
174 05/25/22 01-01:AN-174 1st Fl Room R116 Functional Pass
175 05/25/22 01-01:AN-175 1st Fl Room R117 Functional Pass
176 05/25/22 01-01:AN-176 1st Fl Room R118 Functional Pass
177 05/25/22 01-01:AN-177 1st Fl Room R119 Functional Pass
178 05/25/22 01-01:AN-178 1st Fl Room R120 Functional Pass
179 05/25/22 01-01:AN-179 1st Fl Room R121 Functional Pass
180 05/25/22 01-01:AN-180 1st Fl Room R122 Functional Pass
181 05/25/22 01-01:AN-181 1st Fl Room R123 Functional Pass
182 05/25/22 01-01:AN-182 1st Fl Room R124 Functional Pass
183 05/25/22 01-01:AN-183 1st Fl Room R201 Functional Pass
184 05/25/22 01-01:AN-184 1st Fl Room R202 Functional Pass
185 05/25/22 01-01:AN-185 1st Fl Room R203 Functional Pass
186 05/25/22 01-01:AN-186 1st Fl Room R204 Functional Pass
187 05/25/22 01-01:AN-187 1st Fl Room R205 Functional Pass
188 05/25/22 01-01:AN-188 1st Fl Room R206 Functional Pass
189 05/25/22 01-01:AN-189 1st Fl Room R207 Functional Pass
190 05/25/22 01-01:AN-190 1st Fl Room R208 Functional Pass
191 05/25/22 01-01:AN-191 1st Fl Room R209 Functional Pass
192 05/25/22 01-01:AN-192 1st Fl Room R210 Functional Pass
193 05/25/22 01-01:AN-193 1st Fl Room R211 Functional Pass
194 05/25/22 01-01:AN-194 1st Fl Room R212 Functional Pass
195 05/25/22 01-01:AN-195 1st Fl Room R213 Functional Pass
196 05/25/22 01-01:AN-196 1st Fl Room R214 Functional Pass
197 05/25/22 01-01:AN-197 1st Fl Room R215 Functional Pass
198 05/25/22 01-01:AN-198 1st Fl Room R216 Functional Pass
199 05/25/22 01-01:AN-199 1st Fl Room R217 Functional Pass
200 05/25/22 01-01:AN-200 1st Fl Room R218 Functional Pass
201 05/25/22 01-01:AN-201 1st Fl Room R219 Functional Pass
202 05/25/22 01-01:AN-202 1st Fl Room R220 Functional Pass
203 05/25/22 01-01:AN-203 1st Fl Room R221 Functional Pass
204 05/25/22 01-01:AN-204 1st Fl Room R222 Functional Pass
205 05/25/22 01-01:AN-205 1st Fl Room R223 Functional Pass
206 05/25/22 01-01:AN-206 1st Fl Room R224 Functional Pass
207 05/25/22 01-01:AN-207 1st Fl South Country Kitchen Functional Pass
208 05/25/22 01-01:AN-208 1st Fl South Dining Room Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 10 of 36
Alarm Speakers
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
209 05/25/22 01-01:AN-209 1st Fl South Dining Room Functional Pass
210 05/25/22 01-01:AN-210 1st Fl South Dining Room: East Functional Pass
211 05/25/22 01-01:AN-211 1st Fl South Dining Room: West Functional Pass
212 05/25/22 01-01:AN-212 1st Fl South Hall: North Functional Pass
213 05/25/22 01-01:AN-213 1st Fl South Hall: South Functional Pass
214 05/25/22 01-01:AN-214 1st Fl South Living Room Functional Pass
215 05/25/22 01-01:AN-215 1st Fl South Living Room Functional Pass
216 05/25/22 01-01:AN-216 1st Fl South Living Room: East Functional Pass
217 05/25/22 01-01:AN-217 1st Fl South Living Room: West Functional Pass
218 05/25/22 01-01:AN-218 1st Fl Southport room: East - Center Functional Pass
219 05/25/22 01-01:AN-219 1st Fl Southport room: East - North Functional Pass
220 05/25/22 01-01:AN-220 1st Fl Southport room: East - South Functional Pass
221 05/25/22 01-01:AN-221 1st Fl Southport room: West - Center Functional Pass
222 05/25/22 01-01:AN-222 1st Fl Southport room: West - North Functional Pass
223 05/25/22 01-01:AN-223 1st Fl Southport room: West - South Functional Pass
224 05/25/22 01-01:AN-224 1st Fl South Seating Area Functional Pass
225 05/25/22 01-01:AN-225 1st Fl The Bistro: Center Functional Pass
226 05/25/22 01-01:AN-226 1st Fl The Bistro: North Functional Pass
227 05/25/22 01-01:AN-227 1st Fl The Bistro: South Functional Pass
228 05/25/22 01-01:AN-228 1st Fl Therapy Conference Room Functional Pass
229 05/25/22 01-01:AN-229 1st Fl Therapy Connector Hall: South Functional Pass
230 05/25/22 01-01:AN-230 1st Fl Therapy Gym: East Functional Pass
231 05/25/22 01-01:AN-231 1st Fl Therapy Gym: East Center Functional Pass
232 05/25/22 01-01:AN-232 1st Fl Therapy Gym: West Functional Pass
233 05/25/22 01-01:AN-233 1st Fl Therapy Gym: West Center Functional Pass
234 05/25/22 01-01:AN-234 1st Fl Therapy Hall: East Functional Pass
235 05/25/22 01-01:AN-235 1st Fl Therapy Hall: East Center Functional Pass
236 05/25/22 01-01:AN-236 1st Fl Therapy Hall: West Functional Pass
237 05/25/22 01-01:AN-237 1st Fl Therapy Hall: West Center Functional Pass
238 05/25/22 01-01:AN-238 1st Fl Therapy Office Functional Pass
239 05/25/22 01-01:AN-239 1st Fl Training Room: Entrance Functional Pass
240 05/25/22 01-01:AN-240 1st Fl Training Room: North Functional Pass
241 05/25/22 01-01:AN-241 1st Fl Training Room: South Functional Pass
242 05/25/22 01-01:AN-242 1st Fl TV Room Functional Pass
243 05/25/22 01-01:AN-243 1st Fl Wander Path Hall East: North Functional Pass
244 05/25/22 01-01:AN-244 1st Fl Wander Path Hall East: South Functional Pass
245 05/25/22 01-01:AN-245 1st Fl Wander Path Hall: Seating Area Functional Pass
246 05/25/22 01-01:AN-246 1st Fl Wander Path Hall West: Center Functional Pass
247 05/25/22 01-01:AN-247 1st Fl Wander Path Hall West: East Functional Pass
248 05/25/22 01-01:AN-248 1st Fl Wander Path Hall West: West Functional Pass
249 05/25/22 01-01:AN-249 1st Fl West Country Kitchen Functional Pass
250 05/25/22 01-01:AN-250 1st Fl West Cubicles Functional Pass
251 05/25/22 01-01:AN-251 1st Fl West Dining Room Functional Pass
252 05/25/22 01-01:AN-252 1st Fl West Dining Room by Door Functional Pass
253 05/25/22 01-01:AN-253 1st Fl West Living Room Functional Pass
254 05/25/22 01-01:AN-254 1st Fl West Restroom by 02 Storage Functional Pass
255 05/25/22 01-01:SP-001 2nd Fl Activity Room Functional Pass
256 05/25/22 01-01:SP-002 2nd Fl Country Kitchen Functional Pass
257 05/25/22 01-01:SP-003 2nd Fl Country Kitchen Functional Pass
258 05/25/22 01-01:SP-004 2nd Fl Dining Room Functional Pass
259 05/25/22 01-01:SP-005 2nd Fl Dining Room Functional Pass
260 05/25/22 01-01:SP-006 2nd Fl Dining Room Functional Pass
261 05/25/22 01-01:SP-007 2nd Fl Hall by Room R202 Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 11 of 36
Alarm Speakers
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
262 05/25/22 01-01:SP-008 2nd Fl Hall by Room R207 Functional Pass
263 05/25/22 01-01:SP-009 2nd Fl Hall by Room R208 Functional Pass
264 05/25/22 01-01:SP-010 2nd Fl Hall by Room R211 Functional Pass
265 05/25/22 01-01:SP-011 2nd Fl Hall by Room R216 Functional Pass
266 05/25/22 01-01:SP-012 2nd Fl Hall by Room R217 Functional Pass
267 05/25/22 01-01:SP-013 2nd Fl Hall by Room R219 Functional Pass
268 05/25/22 01-01:SP-014 2nd Fl Hall by Room R222 Functional Pass
269 05/25/22 01-01:SP-015 2nd Fl Nurses Room Functional Pass
270 05/25/22 01-01:SP-016 2nd Fl Room R201 Functional Pass
271 05/25/22 01-01:SP-017 2nd Fl Room R202 Functional Pass
272 05/25/22 01-01:SP-018 2nd Fl Room R203 Functional Pass
273 05/25/22 01-01:SP-019 2nd Fl Room R204 Functional Pass
274 05/25/22 01-01:SP-020 2nd Fl Room R205 Functional Pass
275 05/25/22 01-01:SP-021 2nd Fl Room R206 Functional Pass
276 05/25/22 01-01:SP-022 2nd Fl Room R207 Functional Pass
277 05/25/22 01-01:SP-023 2nd Fl Room R208 Functional Pass
278 05/25/22 01-01:SP-024 2nd Fl Room R209 Functional Pass
279 05/25/22 01-01:SP-025 2nd Fl Room R210 Functional Pass
280 05/25/22 01-01:SP-026 2nd Fl Room R211 Functional Pass
281 05/25/22 01-01:SP-027 2nd Fl Room R212 Functional Pass
282 05/25/22 01-01:SP-028 2nd Fl Room R214 Functional Pass
283 05/25/22 01-01:SP-029 2nd Fl Room R215 Functional Pass
284 05/25/22 01-01:SP-030 2nd Fl Room R216 Functional Pass
285 05/25/22 01-01:SP-031 2nd Fl Room R217 Functional Pass
286 05/25/22 01-01:SP-032 2nd Fl Room R218 Functional Pass
287 05/25/22 01-01:SP-033 2nd Fl Room R219 Functional Pass
288 05/25/22 01-01:SP-034 2nd Fl Room R220 Functional Pass
289 05/25/22 01-01:SP-035 2nd Fl Room R221 Functional Pass
290 05/25/22 01-01:SP-036 2nd Fl Room R222 Functional Pass
291 05/25/22 01-01:SP-037 2nd Fl Room R223 Functional Pass
292 05/25/22 01-01:SP-038 2nd Fl Room R224 Functional Pass
293 05/25/22 01-01:SP-039 2nd Fl Room R221 Functional Pass
294 05/25/22 01-01:SP-040 2nd Fl TV Room Functional Pass
295 05/25/22 01-01:SP-041 2nd Fl TV Room Functional Pass
Alarm Speakers w/Strobe
Functional
Pass/ Fail
1 05/25/22 01-01:AV-001 1st Fl 100/200 Courtyard (Outside) Functional Pass
2 05/25/22 01-01:AV-002 1st Fl 100/200 Courtyard (Outside) Functional Pass
3 05/25/22 01-01:AV-003 1st Fl 100's Dining Room Functional Pass
4 05/25/22 01-01:AV-004 1st Fl 100's Nurses Office Functional Pass
5 05/25/22 01-01:AV-005 1st Fl 100's Nurses Office Medication Room Functional Pass
6 05/25/22 01-01:AV-006 1st Fl 200's Dining Room Functional Pass
7 05/25/22 01-01:AV-007 1st Fl 200's Nurses Office Functional Pass
8 05/25/22 01-01:AV-008 1st Fl 200's Nurses Office Medication Room Functional Pass
9 05/25/22 01-01:AV-009 1st Fl 400 02 Storage Functional Pass
10 05/25/22 01-01:AV-010 1st Fl 400/500 Entry Functional Pass
11 05/25/22 01-01:AV-011 1st Fl 400's Nurses Station Functional Pass
12 05/25/22 01-01:AV-012 1st Fl 400's Nurses Station: Med Room Functional Pass
13 05/25/22 01-01:AV-013 1st Fl 400 TV Room Functional Pass
14 05/25/22 01-01:AV-014 1st Fl 500 Conference Room Functional Pass
15 05/25/22 01-01:AV-015 1st Fl 500 Kitchen Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 12 of 36
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
16 05/25/22 01-01:AV-016 1st Fl 500 Nurse's Station Functional Pass
17 05/25/22 01-01:AV-017 1st Fl 500 Nurse's Station: Med Room Functional Pass
18 05/25/22 01-01:AV-018 1st Fl 500 Staff Office Functional Pass
19 05/25/22 01-01:AV-019 1st Fl 600/700 Entry Functional Pass
20 05/25/22 01-01:AV-020 1st Fl 600 Kitchen Functional Pass
21 05/25/22 01-01:AV-021 1st Fl 600 Nurse's Station Functional Pass
22 05/25/22 01-01:AV-022 1st Fl 600 Nurse's Station: Med Room Functional Pass
23 05/25/22 01-01:AV-023 1st Fl 600 Staff Office Functional Pass
24 05/25/22 01-01:AV-024 1st Fl 700 Conference Room Functional Pass
25 05/25/22 01-01:AV-025 1st Fl 700 Nurse's Station Functional Pass
26 05/25/22 01-01:AV-026 1st Fl 700 Nurse's Station: Med Room Functional Pass
27 05/25/22 01-01:AV-027 1st Fl 700 TV Room Functional Pass
28 05/25/22 01-01:AV-028 1st Fl Administrator's Office Functional Pass
29 05/25/22 01-01:AV-029 1st Fl AV Device 1 East Admissions Office Functional Pass
30 05/25/22 01-01:AV-030 1st Fl AV Device 1 South Seating Area Storage Functional Pass
31 05/25/22 01-01:AV-031 Bsmnt Break Room: East Functional Pass
32 05/25/22 01-01:AV-032 Bsmnt Break Room: West Functional Pass
33 05/25/22 01-01:AV-033 1st Fl Business Office Functional Pass
34 05/25/22 01-01:AV-034 1st Fl Business Office: Conference Room Functional Pass
35 05/25/22 01-01:AV-035 1st Fl Business Office Copy Room Functional Pass
36 05/25/22 01-01:AV-036 1st Fl Center Office Functional Pass
37 05/25/22 01-01:AV-037 1st Fl East Activity Room Functional Pass
38 05/25/22 01-01:AV-038 1st Fl East Dining Room Functional Pass
39 05/25/22 01-01:AV-039 1st Fl East Dining Room Functional Pass
40 05/25/22 01-01:AV-040 1st Fl East Entrance Vestibule Functional Pass
41 05/25/22 01-01:AV-041 Bsmnt East Hall: South Functional Pass
42 05/25/22 01-01:AV-042 1st Fl East Laundry Room C146 Functional Pass
43 05/25/22 01-01:AV-043 1st Fl East Living Room Functional Pass
44 05/25/22 01-01:AV-044 1st Fl East Soiled Linen Functional Pass
45 05/25/22 01-01:AV-045 Bsmnt Elevator Equipment Room Functional Pass
46 05/25/22 01-01:AV-046 1st Fl Elevator Lobby Functional Pass
47 05/25/22 01-01:AV-047 Bsmnt Elevator Lobby Functional Pass
48 05/25/22 01-01:AV-048 Bsmnt Elevator Lobby by Stairs Functional Pass
49 05/25/22 01-01:AV-049 1st Fl Elevator Seating Area Functional Pass
50 05/25/22 01-01:AV-050 1st Fl Enclosed Activity Room Functional Pass
51 05/25/22 01-01:AV-051 1st Fl Entry to Memory Care Functional Pass
52 05/25/22 01-01:AV-052 Bsmnt Exercise Room Functional Pass
53 05/25/22 01-01:AV-053 1st Fl Family Room Functional Pass
54 05/25/22 01-01:AV-054 1st Fl Hall by 02 Room Functional Pass
55 05/25/22 01-01:AV-055 Bsmnt Hall by 3W Stairs Functional Pass
56 05/25/22 01-01:AV-056 Bsmnt Hall by 4W Stairs Functional Pass
57 05/25/22 01-01:AV-057 1st Fl Hall by 100's Middle Storage Functional Pass
58 05/25/22 01-01:AV-058 1st Fl Hall by 200's Restroom Functional Pass
59 05/25/22 01-01:AV-059 1st Fl Hall by 400/500 Activity Room Functional Pass
60 05/25/22 01-01:AV-060 1st Fl Hall by 400 Smoke Door Functional Pass
61 05/25/22 01-01:AV-061 1st Fl Hall by 400 TV Rm Functional Pass
62 05/25/22 01-01:AV-062 1st Fl Hall by 500 Restroom Functional Pass
63 05/25/22 01-01:AV-063 1st Fl Hall by 700 Conference Room Functional Pass
64 05/25/22 01-01:AV-064 Bsmnt Hall by Boiler Room Functional Pass
65 05/25/22 01-01:AV-065 1st Fl Hall by Business Office Functional Pass
66 05/25/22 01-01:AV-066 1st Fl Hall by Business Office Restroom Functional Pass
67 05/25/22 01-01:AV-067 Bsmnt Hall by Coolers Functional Pass
68 05/25/22 01-01:AV-068 1st Fl Hall by East Activity Room Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 13 of 36
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
69 05/25/22 01-01:AV-069 1st Fl Hall by FACP Functional Pass
70 05/25/22 01-01:AV-070 1st Fl Hall by FACP Functional Pass
71 05/25/22 01-01:AV-071 Bsmnt Hall by Maintenance Exit Functional Pass
72 05/25/22 01-01:AV-072 1st Fl Hall by North Restroom Functional Pass
73 05/25/22 01-01:AV-073 1st Fl Hall by North Smoke Door Functional Pass
74 05/25/22 01-01:AV-074 1st Fl Hall by Patio Door Functional Pass
75 05/25/22 01-01:AV-075 1st Fl Hall by R-2 Seating Area Functional Pass
76 05/25/22 01-01:AV-076 1st Fl Hall by Rehab Directors Office Functional Pass
77 05/25/22 01-01:AV-077 Bsmnt Hall by Restrooms Functional Pass
78 05/25/22 01-01:AV-078 1st Fl Hall by Room 101 Functional Pass
79 05/25/22 01-01:AV-079 1st Fl Hall by Room 102 Functional Pass
80 05/25/22 01-01:AV-080 1st Fl Hall by Room 112 Functional Pass
81 05/25/22 01-01:AV-081 1st Fl Hall by Room 213 Functional Pass
82 05/25/22 01-01:AV-082 1st Fl Hall by Room 215 Functional Pass
83 05/25/22 01-01:AV-083 1st Fl Hall by Room 224 Functional Pass
84 05/25/22 01-01:AV-084 1st Fl Hall by Room 505 Functional Pass
85 05/25/22 01-01:AV-085 1st Fl Hall by Room 606 Functional Pass
86 05/25/22 01-01:AV-086 1st Fl Hall by Room C103 Functional Pass
87 05/25/22 01-01:AV-087 1st Fl Hall by Room C106 Functional Pass
88 05/25/22 01-01:AV-088 1st Fl Hall by Room C108 Functional Pass
89 05/25/22 01-01:AV-089 1st Fl Hall by Room C109 Functional Pass
90 05/25/22 01-01:AV-090 1st Fl Hall by Room C113 Functional Pass
91 05/25/22 01-01:AV-091 1st Fl Hall by Room C115 Functional Pass
92 05/25/22 01-01:AV-092 1st Fl Hall by Room C116 Functional Pass
93 05/25/22 01-01:AV-093 1st Fl Hall by Room C119 Functional Pass
94 05/25/22 01-01:AV-094 1st Fl Hall by Room C120 Functional Pass
95 05/25/22 01-01:AV-095 1st Fl Hall by Room C122 Functional Pass
96 05/25/22 01-01:AV-096 1st Fl Hall by Room C123 Functional Pass
97 05/25/22 01-01:AV-097 1st Fl Hall by Room C124 Functional Pass
98 05/25/22 01-01:AV-098 1st Fl Hall by Room C141 Functional Pass
99 05/25/22 01-01:AV-099 1st Fl Hall by Room R113 Functional Pass
100 05/25/22 01-01:AV-100 1st Fl Hall by Room R114 Functional Pass
101 05/25/22 01-01:AV-101 1st Fl Hall by Salon: North Functional Pass
102 05/25/22 01-01:AV-102 1st Fl Hall by Salon: South Functional Pass
103 05/25/22 01-01:AV-103 Bsmnt Hall by South Exit Functional Pass
104 05/25/22 01-01:AV-104 1st Fl Hall by South Office Functional Pass
105 05/25/22 01-01:AV-105 1st Fl Hall by South Restroom Functional Pass
106 05/25/22 01-01:AV-106 1st Fl Hall by South Restroom Functional Pass
107 05/25/22 01-01:AV-107 1st Fl Hall by Stair 9 Functional Pass
108 05/25/22 01-01:AV-108 1st Fl Hall by Therapy Conference Room Functional Pass
109 05/25/22 01-01:AV-109 1st Fl Hall by Therapy Office Functional Pass
110 05/25/22 01-01:AV-110 1st Fl IT Room Functional Pass
111 05/25/22 01-01:AV-111 1st Fl Kitchen Functional Pass
112 05/25/22 01-01:AV-112 Bsmnt Kitchen Functional Pass
113 05/25/22 01-01:AV-113 1st Fl Kitchen Functional Pass
114 05/25/22 01-01:AV-114 1st Fl Kitchen Functional Pass
115 05/25/22 01-01:AV-115 1st Fl Kitchen Functional Pass
116 05/25/22 01-01:AV-116 Bsmnt Laundry Functional Pass
117 05/25/22 01-01:AV-117 1st Fl Laundry Room C148 Functional Pass
118 05/25/22 01-01:AV-118 1st Fl Living Room Functional Pass
119 05/25/22 01-01:AV-119 1st Fl Living Room Functional Pass
120 05/25/22 01-01:AV-120 Bsmnt Locker Room: North Functional Pass
121 05/25/22 01-01:AV-121 Bsmnt Locker Room: South Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 14 of 36
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
122 05/25/22 01-01:AV-122 1st Fl Medical Records Functional Pass
123 05/25/22 01-01:AV-123 1st Fl Medical Records File Room Functional Pass
124 05/25/22 01-01:AV-124 1st Fl Middle IT Room Functional Pass
125 05/25/22 01-01:AV-125 1st Fl Middle: Med Room Functional Pass
126 05/25/22 01-01:AV-126 1st Fl Middle Nurse's Area Functional Pass
127 05/25/22 01-01:AV-127 1st Fl Middle Nurse's Area Functional Pass
128 05/25/22 01-01:AV-128 1st Fl Namaste Room Functional Pass
129 05/25/22 01-01:AV-129 1st Fl North Activity Storage Functional Pass
130 05/25/22 01-01:AV-130 1st Fl North Dining Room Functional Pass
131 05/25/22 01-01:AV-131 1st Fl North Dining Room Functional Pass
132 05/25/22 01-01:AV-132 1st Fl North Exam Room Functional Pass
133 05/25/22 01-01:AV-133 1st Fl North Hall by Tub Room Functional Pass
134 05/25/22 01-01:AV-134 1st Fl North Hall by Tub Room Functional Pass
135 05/25/22 01-01:AV-135 1st Fl North Living Room Functional Pass
136 05/25/22 01-01:AV-136 1st Fl North Living Room Functional Pass
137 05/25/22 01-01:AV-137 1st Fl North Office Functional Pass
138 05/25/22 01-01:AV-138 1st Fl North Seating Area Functional Pass
139 05/25/22 01-01:AV-139 1st Fl North Seating Area Storage Functional Pass
140 05/25/22 01-01:AV-140 1st Fl Nurse's Station Functional Pass
141 05/25/22 01-01:AV-141 1st Fl Nurse's Station: Med Room Functional Pass
142 05/25/22 01-01:AV-142 Bsmnt Nursinig Central Supply: East Functional Pass
143 05/25/22 01-01:AV-143 Bsmnt Nursinig Central Supply: West Functional Pass
144 05/25/22 01-01:AV-144 1st Fl Office by Reception Functional Pass
145 05/25/22 01-01:AV-145 1st Fl Private Dining Functional Pass
146 05/25/22 01-01:AV-146 1st Fl Receptionist Office Functional Pass
147 05/25/22 01-01:AV-147 1st Fl Room C139 Functional Pass
148 05/25/22 01-01:AV-148 1st Fl Room C140 Functional Pass
149 05/25/22 01-01:AV-149 1st Fl Room C141: Conference Room Functional Pass
150 05/25/22 01-01:AV-150 1st Fl Shared Office Functional Pass
151 05/25/22 01-01:AV-151 1st Fl South Dining Room Functional Pass
152 05/25/22 01-01:AV-152 1st Fl South Dining Room Functional Pass
153 05/25/22 01-01:AV-153 1st Fl South Hall: North Functional Pass
154 05/25/22 01-01:AV-154 1st Fl South Hall: South Functional Pass
155 05/25/22 01-01:AV-155 1st Fl Staff Office Functional Pass
156 05/25/22 01-01:AV-156 1st Fl The Bistro: East Functional Pass
157 05/25/22 01-01:AV-157 1st Fl The Bistro: West Functional Pass
158 05/25/22 01-01:AV-158 1st Fl Therapy Connector Hall: North Functional Pass
159 05/25/22 01-01:AV-159 1st Fl Therapy Gym: East Functional Pass
160 05/25/22 01-01:AV-160 1st Fl Therapy Gym: Entrance Functional Pass
161 05/25/22 01-01:AV-161 1st Fl Therapy Gym: West Functional Pass
162 05/25/22 01-01:AV-162 1st Fl Therapy Hall by Emergency Exit Functional Pass
163 05/25/22 01-01:AV-163 1st Fl Therapy Hall: East Functional Pass
164 05/25/22 01-01:AV-164 1st Fl Therapy Office Functional Pass
165 05/25/22 01-01:AV-165 1st Fl Training Room Functional Pass
166 05/25/22 01-01:AV-166 1st Fl Tub Room Functional Pass
167 05/25/22 01-01:AV-167 1st Fl TV Room Functional Pass
168 05/25/22 01-01:AV-168 1st Fl West Cubicles Functional Pass
169 05/25/22 01-01:AV-169 1st Fl West Dining Room Functional Pass
170 05/25/22 01-01:AV-170 1st Fl West Living Room Functional Pass
171 05/25/22 01-01:SV-001 2nd Fl Activities Room Functional Pass
172 05/25/22 01-01:SV-002 2nd Fl Activity Room Functional Pass
173 05/25/22 01-01:SV-003 2nd Fl Activity Storage Room Functional Pass
174 05/25/22 01-01:SV-004 2nd Fl Dining Room Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 15 of 36
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
175 05/25/22 01-01:SV-005 2nd Fl Dining Room Functional Pass
176 05/25/22 01-01:SV-006 2nd Fl Elevator Lobby Functional Pass
177 05/25/22 01-01:SV-007 2nd Fl Hall by Restroom Functional Pass
178 05/25/22 01-01:SV-008 2nd Fl Hall by Room 201 Functional Pass
179 05/25/22 01-01:SV-009 2nd Fl Hall by Room R203 Functional Pass
180 05/25/22 01-01:SV-010 2nd Fl Hall by Room R217 Functional Pass
181 05/25/22 01-01:SV-011 2nd Fl Nurses Station Functional Pass
182 05/25/22 01-01:SV-012 2nd Fl R-2 by Entrance Functional Pass
183 05/25/22 01-01:SV-013 2nd Fl R-2 Entrance Functional Pass
184 05/25/22 01-01:SV-014 2nd Fl Activities Room Functional Pass
185 05/25/22 01-01:SV-015 2nd Fl Sitting Area Functional Pass
186 05/25/22 01-01:SV-016 2nd Fl TV Room Functional Pass
187 05/25/22 01-01:SV-017 2nd Fl TV Room Functional Pass
Visual Alarms
Functional
Pass/ Fail
1 05/25/22 01-01:ST-001 1st Fl 100's Restrooms Functional Pass
2 05/25/22 01-01:ST-002 1st Fl 200's Restrooms Functional Pass
3 05/25/22 01-01:ST-003 1st Fl 400's Restrooms Functional Pass
4 05/25/22 01-01:ST-004 1st Fl 500 Restrooms Functional Pass
5 05/25/22 01-01:ST-005 1st Fl 600's Restrooms Functional Pass
6 05/25/22 01-01:ST-006 1st Fl 700's Restrooms Functional Pass
7 05/25/22 01-01:ST-007 Bsmnt Boiler Room Functional Pass
8 05/25/22 01-01:ST-008 1st Fl Business Office Restrooms Functional Pass
9 05/25/22 01-01:ST-009 1st Fl Corridor by Room 723 Functional Pass
10 05/25/22 01-01:ST-010 1st Fl Corridor by Tub Room Functional Pass
11 05/25/22 01-01:ST-011 1st Fl Corridor by Tub Room Functional Pass
12 05/25/22 01-01:ST-012 1st Fl East Entrance Men's Restroom Functional Pass
13 05/25/22 01-01:ST-013 1st Fl East Entrance Women's Restroom Functional Pass
14 05/25/22 01-01:ST-014 Bsmnt East Restrooms Functional Pass
15 05/25/22 01-01:ST-015 1st Fl East Restrooms by 02 Storage Functional Pass
16 05/25/22 01-01:ST-016 1st Fl Exam Room Functional Pass
17 05/25/22 01-01:ST-017 1st Fl Hall by Emergency Exit Functional Pass
18 05/25/22 01-01:ST-018 1st Fl Hall by O2 Storage Functional Pass
19 05/25/22 01-01:ST-019 1st Fl Hall by Room 106 Functional Pass
20 05/25/22 01-01:ST-020 1st Fl Hall by Room 115 Functional Pass
21 05/25/22 01-01:ST-021 1st Fl Hall by Room 201 Functional Pass
22 05/25/22 01-01:ST-022 1st Fl Hall by Room 501 Functional Pass
23 05/25/22 01-01:ST-023 1st Fl Hall by Room 526 Functional Pass
24 05/25/22 01-01:ST-024 1st Fl Hall by Room 602 Functional Pass
25 05/25/22 01-01:ST-025 1st Fl Hall by Room 612 Functional Pass
26 05/25/22 01-01:ST-026 1st Fl Hall by Room 619 Functional Pass
27 05/25/22 01-01:ST-027 1st Fl Hall by Room 705 Functional Pass
28 05/25/22 01-01:ST-028 1st Fl Hall by Room 712 Functional Pass
29 05/25/22 01-01:ST-029 1st Fl Hall by West Kitchen Functional Pass
30 05/25/22 01-01:ST-030 Bsmnt Laundry Room: East Functional Pass
31 05/25/22 01-01:ST-031 Bsmnt Laundry Room: West Functional Pass
32 05/25/22 01-01:ST-032 Bsmnt Locker Room/Changing Room: East Functional Pass
33 05/25/22 01-01:ST-033 Bsmnt Locker Room/Changing Room: West Functional Pass
34 05/25/22 01-01:ST-034 1st Fl Massage Room Functional Pass
35 05/25/22 01-01:ST-035 Bsmnt Men's Restrooms Functional Pass
36 05/25/22 01-01:ST-036 1st Fl Middle Restrooms Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 16 of 36
Visual Alarms
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
37 05/25/22 01-01:ST-037 1st Fl Middle Staff Restrooms Functional Pass
38 05/25/22 01-01:ST-038 1st Fl Middle Staff Restrooms Functional Pass
39 05/25/22 01-01:ST-039 1st Fl Mother's Room Functional Pass
40 05/25/22 01-01:ST-040 1st Fl North Restrooms Functional Pass
41 05/25/22 01-01:ST-041 1st Fl North Restrooms by Tub Room Functional Pass
42 05/25/22 01-01:ST-042 Bsmnt Nurses Central Supply: East Functional Pass
43 05/25/22 01-01:ST-043 1st Fl Restrooms Functional Pass
44 05/25/22 01-01:ST-044 1st Fl Restrooms Functional Pass
45 05/25/22 01-01:ST-045 1st Fl Restrooms by East Activity Room Functional Pass
46 05/25/22 01-01:ST-046 1st Fl Restrooms by Therapy Conference Room Functional Pass
47 05/25/22 01-01:ST-047 1st Fl Room 408 Functional Pass
48 05/25/22 01-01:ST-048 1st Fl Room 415 Functional Pass
49 05/25/22 01-01:ST-049 1st Fl Room 420 Functional Pass
50 05/25/22 01-01:ST-050 1st Fl South Restrooms Functional Pass
51 05/25/22 01-01:ST-051 1st Fl South Restrooms by Tub Room Functional Pass
52 05/25/22 01-01:ST-052 1st Fl Therapy Gym Restrooms Functional Pass
53 05/25/22 01-01:ST-053 1st Fl Tub Room Functional Pass
54 05/25/22 01-01:ST-054 1st Fl Tub Room Functional Pass
55 05/25/22 01-01:ST-055 Bsmnt West Restrooms Functional Pass
56 05/25/22 01-01:ST-056 Bsmnt Women's Restrooms Functional Pass
57 05/25/22 01-01:VN-001 1st Fl Visible Notification Device 1 100's Restroom Functional Pass
58 05/25/22 01-01:VN-002 1st Fl Visible Notification Device 1 200's Restroom Functional Pass
59 05/25/22 01-01:VN-003 1st Fl Visible Notification Device 1 400 Restroom Functional Pass
60 05/25/22 01-01:VN-004 1st Fl Visible Notification Device 1 500 Restroom Functional Pass
61 05/25/22 01-01:VN-005 1st Fl Visible Notification Device 1 600 Restroom Functional Pass
62 05/25/22 01-01:VN-006 1st Fl Visible Notification Device 1 700 Restroom Functional Pass
63 05/25/22 01-01:VN-007 1st Fl Visible Notification Device 1 Business Ofc Restrm Functional Pass
64 05/25/22 01-01:VN-008 1st Fl Visible Notification Device 1 Corr by 02 Storage Functional Pass
65 05/25/22 01-01:VN-009 1st Fl Visible Notification Device 1 Corr by Emer Exit Functional Pass
66 05/25/22 01-01:VN-010 1st Fl Visible Notification Device 1 Corr by Room 106 Functional Pass
67 05/25/22 01-01:VN-011 1st Fl Visible Notification Device 1 Corr by Room 115 Functional Pass
68 05/25/22 01-01:VN-012 1st Fl Visible Notification Device 1 Corr by Room 201 Functional Pass
69 05/25/22 01-01:VN-013 1st Fl Visible Notification Device 1 Corr by Room 501 Functional Pass
70 05/25/22 01-01:VN-014 1st Fl Visible Notification Device 1 Corr by Room 526 Functional Pass
71 05/25/22 01-01:VN-015 1st Fl Visible Notification Device 1 Corr by Room 602 Functional Pass
72 05/25/22 01-01:VN-016 1st Fl Visible Notification Device 1 Corr by Room 612 Functional Pass
73 05/25/22…
This is the start of the file's text. The full file is on GovTribe.