NFPA 72 Fire Alarm System Inspection and Testing Report for Kenosha County Courthouse
This document is an NFPA 72 System Record of Inspection and Testing report for the Kenosha County Courthouse located at 912 56th Street, Kenosha, Wisconsin 53140. The inspection and testing was conducted by Siemens Industry, Inc., Smart Infrastructure Division, with service performed August 11-12, 2022. The courthouse fire alarm system consists of a Simplex 4100ES control panel located in the lower level electrical room, supplemented by four notification appliance power extender panels distributed throughout the facility. The system includes 311 smoke detectors, 20 manual pull stations, 7 heat detectors, 2 projected beam smoke detectors, 120 alarm speakers with strobe, 44 visual alarm devices, and various interface components for elevator recall and door release functions. Primary power is supplied at 120 volts, 20 amps, with secondary battery backup providing 24 hours of standby capacity and 15 minutes of alarm mode operation. Testing was completed on August 12, 2022 at 23:45 hours, with the system restored to normal operation the same date.
The testing organization, Siemens, and monitoring organization, Alarm Detection Systems (ADS), performed comprehensive functional and visual inspections of all system components in accordance with NFPA 72-2016 standards. Most system components passed testing; however, two notification appliance power extender panels failed load testing and battery performance requirements. Panel 01:T-02 (lower level paper room right) and Panel 01:T-03 (lower level victim witness back conference room left) required replacement batteries, specifically two 12VDC 10AH sealed lead acid units each, per NFPA 72 requirements. All 120 alarm speakers with strobe devices passed functional testing, and 310 of 311 smoke detectors passed testing (99.7% pass rate), with one detector unable to be tested due to ceiling work in progress. All 20 manual pull stations, 7 heat detectors, 2 projected beam detectors, and 5 relay interface components passed functional testing. Smoke detector sensitivity testing verified all units operated within listed sensitivity ranges. System alarm, restoration, and trouble signals were successfully verified as received by ADS monitoring station. The inspection was accepted by Kenosha County representative Rhonda Haidinger on August 12, 2022, with certification by technicians Stanley Laitinen, Jim Kayler, and Alexander Hanus holding appropriate NICET certifications.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFPA 72 REPORT
© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 26
SYSTEM RECORD OF INSPECTION AND TESTING
System Name: KENOSHA COURTHOUSE Panel Name: 01 - 4100ES - COURTHOUSE
Inspection/Test Start Date/Time: 11 Aug 2022 1630 Inspection/Test Completion Date/Time: 12 Aug 2022 2345
Contract Info: Kenosha County 2022 (2600149454) Notification Number: 5102240918
Supplemental Form(s) Attached: Yes
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY COURTHOUSE (4433-53140-00020)
Address: 912 56TH ST. KENOSHA, WI, 53140
Description of property:
Name of property representative: KENOSHA COUNTY (30078447), None
Address: 1010 56TH ST, KENOSHA, WI 53140-3738
Phone: None Fax: None E-mail: None
2. TESTING AND MONITORING INFORMATION
Testing organization: SIEMENS
Address: 6737 West Washington Street, Suite 2110, Milwaukee, WI 53215
Phone: 414-475-3700 Fax: NA E-mail: NA
Monitoring organization: ALARM DETECTION SYSTEMS
Address: LL ELECTRICAL ROOM
Phone: NA Fax: NA E-mail: NA
Account number: 41677 Phone line 1: NA Phone line 2: NA
Means of transmission: Digital
Entity to which alarms are retransmitted: NA Phone: NA
3. DOCUMENTATION
On-site location of the required record documents and site-specific software:
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
System Name: KENOSHA COURTHOUSE Panel Name: 01 - 4100ES - COURTHOUSE
Panel Location and Address: LL ELECTRICAL ROOM, 912 56TH. ST., KENOSHA, WI, 53140
Manufacturer: SIMPLEX Model number: 4100ES
4.2 Software and Firmware
Firmware revision number:
4.3 System Power
4.3.1 Primary (Main) Power
Nominal voltage: 120 Amps: 20 Location: LL ELECTRICAL ROOM
Overcurrent protection type: BREAKER Amps: 20
Disconnecting means location: Custodial Room - Panel BE
4.3.2 Secondary Power
Type: Storage Battery Location: LL ELECTRICAL ROOM
Battery type (if applicable): Sealed Lead Acid Manufactured Date: 15 Oct 2019
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24 In alarm mode (minutes): 15
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 26
4.4 Notification Appliance Power Extender Panels
4.4.1 Primary Power
ID Location Input Volts
Panel Amps
Over-current Type
Over-current Amps
Primary Supply Location
Disconnect Location
01:T-01 LL PAPER ROOM (LEFT) 120VAC BREAKER 20 PAPER ROOM
PNL BC
CKT # 11
01:T-02 LL PAPER ROOM (RIGHT) 120VAC BREAKER 20 PAPER ROOM
PNL BC
CKT # 11
01:T-03 LL VICTIM WITNESS BACK
CONFERENCE RM (LEFT)
120VAC BREAKER 20 MAIN COORIDOR
PNL BA
CKT # 17
01:T-04 LL VICTIM WITNESS BACK
CONFERENCE RM (RIGHT)
120VAC BREAKER 20 MAIN COORIDOR
PNL BA
CKT # 17
4.4.2 Secondary Power
ID Location Battery Type
Manufactured Date
Voltage Rating
Amp Rating
Standby Hours
Alarm Minutes
01:T-01 LL PAPER ROOM (LEFT) SLA 2019-04-30 12/12 7AH 24 15
01:T-02 LL PAPER ROOM (RIGHT) SLA 2016-09-15 12/12 10AH 24 15
01:T-03 LL VICTIM WITNESS BACK CONFERENCE
RM (LEFT)
SLA 2016-09-15 12/12 10AH 24 15
01:T-04 LL VICTIM WITNESS BACK CONFERENCE
RM (RIGHT)
SLA 2021-05-17 12/12 10AH 24 15
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact
ADS CALLED BY RHONDA HAIDINGER Tim e:
Building management Contact
RHONDA HAIDINGER Tim e:
Building occupants Contact
BY RHONDA HAIDINGER Tim e:
Authority having jurisdiction
(AHJ)
Contact
Tim e:
Other, if required Contact
NA Tim e:
NA
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection or Functional
Test
Comments
Control unit Functional None
Disconnect switches Functional None
Fuses Functional None
Ground-fault monitoring Functional None
Interface Equipment Functional None
Lamps/LEDs/LCDs Functional None
Local annunciator Functional None
Primary Power Functional None
Remote annunciators Functional None
Remote power panels Functional None
Supervision Functional None
Trouble signals Functional None
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 26
6.2 Secondary Power
Description Visual Inspection or Functional
Test
Comments
Battery condition Functional (2) 50 AH BATTERIES
Charger test Functional 27.21
Discharge test Functional 100%/100%
Load voltage Functional 13.59/13.61
Remote panel batteries Functional None
6.3 Notification Appliance Power Extender Panels Secondary Power
ID Location Battery Voltage Battery Amps Test Method Pass/ Fail
01:T-01 LL PAPER
ROOM (LEFT)
13.70/13.67 100%/100% Functional Pass
01:T-02 LL PAPER
ROOM
(RIGHT)
13.67/13.66 70%/70% Functional Fail
Comment: FAILED LOAD TEST AND BY DATE PER NFPA72 REQUIREMENTS. REPLACEMENT REQUIRED. USE
QTY. OF 2 @ 12VDC 10AH SLA
01:T-03 LL VICTIM
WITNESS
BACK
CONFERENCE
RM (LEFT)
13.48/13.55 40%/20% Functional Fail
Comment: FAILED LOAD TEST AND BY DATE PER NFPA72 REQUIREMENTS. REPLACEMENT REQUIRED. USE
QTY. OF 2 @ 12VDC 10AH SLA
01:T-04 LL VICTIM
WITNESS
BACK
CONFERENCE
RM (RIGHT)
13.74/13.72 100%/100% Functional Pass
6.4 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
6.5 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.6 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
6.7 Supervising Station Monitoring
Description Receive d
Time / Elapsed Time
Pass/Fail Comments
Alarm signal Yes NA / NA Pass VERIFIED SIGNALS RECEIVED ADS
Alarm restoration Yes NA / NA Pass VERIFIED SIGNALS RESTORED ADS
Trouble signal Yes NA / NA Pass VERIFIED SIGNALS RECEIVED ADS
Trouble restoration Yes NA / NA Pass VERIFIED SIGNALS RESTORED ADS
Supervisory signal No NA / NA None
Supervisory restoration No NA / NA None
6.8 Public Emergency Alarm Reporting System
Description Yes No Time Comments
Alarm signal NA NA
Alarm restoration NA NA
Trouble signal NA NA
Trouble restoration NA NA
Supervisory signal NA NA
Supervisory restoration NA NA
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 26
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact
ADS - CALLED BY RHONDA HAIDINGER Tim e:
Building management Contact
RHONDA HAIDINGER Tim e:
Building occupants Contact
BY RHONDA HAIDINGER Tim e:
Authority having jurisdiction
(AHJ)
Contact
Tim e:
Other, if required Contact
NA Tim e:
NA
8. SYSTEM RESTORED TO NORMAL OPERATION
Date: 12 Aug 2022 Time: 2345
9. CERTIFICATION
This Testing Was Performed in Accordance with Applicable NFPA Standards.
Signed:
Alexander Hanus Date: 08/12/2022
Printed name: STANLEY LAITINEN, JIM KAYLER, ALEXANDER HANUS Title: Technician License No.: NICET CERT. # SL
150654, AH 148912
Organization: SIEMENS Phone: 414-475-3700
Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service
10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED
NAC Panels
Address Location Model Comment:
01:T-02 LL PAPER ROOM (RIGHT) SIMPLEX/4100 FAILED LOAD TEST AND BY DATE PER NFPA72
REQUIREMENTS. REPLACEMENT REQUIRED. USE QTY. OF
2 @ 12VDC 10AH SLA
01:T-03 LL VICTIM WITNESS BACK
CONFERENCE RM (LEFT)
SIMPLEX/4100 FAILED LOAD TEST AND BY DATE PER NFPA72
REQUIREMENTS. REPLACEMENT REQUIRED. USE QTY. OF
2 @ 12VDC 10AH SLA
11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE
The undersigned accepted the test report for the system as specified herein:
Signed:
Printed name: RHONDA HAIDINGER Date:
Organization: KENOSHA COUNTY (30078447) Phone: None
Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements.
Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.
12. OTHER
12.1 Special Procedures
TO BYPASS PANEL CHANGE TO ACCESS LEVEL 3.
TO BYPASS EXTERIOR DOOR RELEASES:
08/15/22
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 26
LOG IN ACCESS LEVEL 3
PRESS DISABLE
PRESS #6 -ID NET
ENTER 1-111
REVERSE PROCESS TO ENABLE
12.2 Comments
*Reviewed the sensitivity of the Analog Smoke/Duct detectors with use of Fire Alarm Control Panel whereby the detector causes a signal at the control panel when its sensitivity is outside its listed sensitivity range.
NFPA 72-2016 14.4.3.2-17 (h)(4) states that *Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside it listed sensitivity range*
ALL SMOKE DETECTORS PASSED SENSITIVITY TESTING.
ELEVATOR RECALL FUNCTIONED PROPERLY.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 26
NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY COURTHOUSE (4433-53140-00020)
Address: 912 56TH ST. KENOSHA, WI, 53140
2. NOTIFICATION APPLIANCE TEST RESULTS
2.1 Notification Appliances Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
2 2 100% 0 0% 0 0% Alarm Speakers
120 120 100% 0 0% 0 0% Alarm Speakers w/Strobe
44 44 100% 0 0% 0 0% Visual Alarms
2.2 Notification Appliances Testing Results by Type
Alarm Speakers
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
1 08/12/22 01:SP-01:SP-
LL Lower Level Functional Pass
2 08/12/22 01:SP-01:SP-
LL Northwest Section: Basement Corridor Functional Pass
Alarm Speakers w/Strobe
Functional
Pass/ Fail
1 08/12/22 01:AV-01:AV-
LL Basement Corridor Functional Pass
2 08/12/22 01:AV-01:AV-
LL Basement Corridor Functional Pass
3 08/12/22 01:AV-01:AV-
LL Basement Corridor Functional Pass
4 08/12/22 01:AV-01:AV-
LL Basement Corridor Room E39 Functional Pass
5 08/12/22 01:AV-01:AV-
LL Basement Corridor Room E39 Functional Pass
6 08/12/22 01:AV-01:AV-
1st Fl Branch 2: Room 100 Functional Pass
7 08/12/22 01:AV-01:AV-
1st Fl Branch 2: Room 100 Functional Pass
8 08/12/22 01:AV-01:AV-
2nd Fl Branch 5 Functional Pass
9 08/12/22 01:AV-01:AV-
2nd Fl Branch 5 Courtroom Functional Pass
10 08/12/22 01:AV-01:AV-
2nd Fl Branch 5 Courtroom Functional Pass
11 08/12/22 01:AV-01:AV-
3rd Fl Branch 5 Courtroom Functional Pass
12 08/12/22 01:AV-01:AV-
3rd Fl Branch 5 Courtroom Functional Pass
13 08/12/22 01:AV-01:AV-
3rd Fl Branch 6 Courtroom Functional Pass
14 08/12/22 01:AV-01:AV-
3rd Fl Branch 6 Courtroom Functional Pass
15 08/12/22 01:AV-01:AV-
1st Fl Branch 7 Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 26
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
16 08/12/22 01:AV-01:AV-
1st Fl Branch 7 Functional Pass
17 08/12/22 01:AV-01:AV-
1st Fl Branch 7 Corridor Functional Pass
18 08/12/22 01:AV-01:AV-
2nd Fl Branch 8 Courtroom Functional Pass
19 08/12/22 01:AV-01:AV-
2nd Fl Branch 8 Courtroom Functional Pass
20 08/12/22 01:AV-01:AV-
2nd Fl Branch 8 - Judges Office/Chambers Functional Pass
21 08/12/22 01:AV-01:AV-
LL Center Hall Functional Pass
22 08/12/22 01:AV-01:AV-
LL Center Hall Functional Pass
23 08/12/22 01:AV-01:AV-
1st Fl Clerk of Courts: Room 119 Functional Pass
24 08/12/22 01:AV-01:AV-
2nd Fl Conference Room Functional Pass
25 08/12/22 01:AV-01:AV-
2nd Fl Conference Room Functional Pass
26 08/12/22 01:AV-01:AV-
LL Conference Room Functional Pass
27 08/12/22 01:AV-01:AV-
1st Fl Conference Room 104 Functional Pass
28 08/12/22 01:AV-01:AV-
1st Fl Conference Room 121 Functional Pass
29 08/12/22 01:AV-01:AV-
1st Fl Conference Room 123 Functional Pass
30 08/12/22 01:AV-01:AV-
1st Fl Family Court Room 124 Functional Pass
31 08/12/22 01:AV-01:AV-
LL File Storage Room E43 Functional Pass
32 08/12/22 01:AV-01:AV-
3rd Fl Northwest Corridor Functional Pass
33 08/12/22 01:AV-01:AV-
LL Generator Room Functional Pass
34 08/12/22 01:AV-01:AV-
LL Hall by Room 14 Functional Pass
35 08/12/22 01:AV-01:AV-
2nd Fl Hall by Room 203 Functional Pass
36 08/12/22 01:AV-01:AV-
LL IT Room Functional Pass
37 08/12/22 01:AV-01:AV-
LL IT Room Functional Pass
38 08/12/22 01:AV-01:AV-
1st Fl Judges Office: Room 101 Functional Pass
39 08/12/22 01:AV-01:AV-
LL Jury Duty Functional Pass
40 08/12/22 01:AV-01:AV-
LL Jury Duty Functional Pass
41 08/12/22 01:AV-01:AV-
1st Fl Jury Room 110 Functional Pass
42 08/12/22 01:AV-01:AV-
1st Fl Jury Room 110 Functional Pass
43 08/12/22 01:AV-01:AV-
2nd Fl Jury Room 210 Functional Pass
44 08/12/22 01:AV-01:AV-
2nd Fl Jury Room 210 Functional Pass
45 08/12/22 01:AV-01:AV-
1st Fl Main Entrance Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 8 of 26
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
46 08/12/22 01:AV-01:AV-
1st Fl Men's Restroom 112 Functional Pass
47 08/12/22 01:AV-01:AV-
LL Multipurpose Restroom Functional Pass
48 08/12/22 01:AV-01:AV-
LL Multipurpose Room Functional Pass
49 08/12/22 01:AV-01:AV-
1st Fl Northeast Conference Room Functional Pass
50 08/12/22 01:AV-01:AV-
2nd Fl Northeast Conference Room Functional Pass
51 08/12/22 01:AV-01:AV-
2nd Fl Northeast Corridor Functional Pass
52 08/12/22 01:AV-01:AV-
2nd Fl Northeast Corridor Functional Pass
53 08/12/22 01:AV-01:AV-
3rd Fl Northeast Corridor Functional Pass
54 08/12/22 01:AV-01:AV-
3rd Fl Northeast Corridor Functional Pass
55 08/12/22 01:AV-01:AV-
2nd Fl Northeast Corridor: Plaster Ceiling Functional Pass
56 08/12/22 01:AV-01:AV-
2nd Fl Northeast Corridor: Plaster Ceiling Functional Pass
57 08/12/22 01:AV-01:AV-
3rd Fl Northeast Hall Functional Pass
58 08/12/22 01:AV-01:AV-
3rd Fl Northeast Judges Chambers Functional Pass
59 08/12/22 01:AV-01:AV-
1st Fl Northeast Judges Office Functional Pass
60 08/12/22 01:AV-01:AV-
3rd Fl Northeast Jury Room Functional Pass
61 08/12/22 01:AV-01:AV-
2nd Fl Northeast Open Office Functional Pass
62 08/12/22 01:AV-01:AV-
2nd Fl Northeast Open Office Functional Pass
63 08/12/22 01:AV-01:AV-
3rd Fl Northeast Open Office Functional Pass
64 08/12/22 01:AV-01:AV-
3rd Fl Northeast Open Office Functional Pass
65 08/12/22 01:AV-01:AV-
2nd Fl Northeast Open Office Files Functional Pass
66 08/12/22 01:AV-01:AV-
2nd Fl Northeast Public Waiting Functional Pass
67 08/12/22 01:AV-01:AV-
3rd Fl Northeast Waiting Area Functional Pass
68 08/12/22 01:AV-01:AV-
1st Fl Northeast Women's Restroom 113 Functional Pass
69 08/12/22 01:AV-01:AV-
1st Fl Northeast Women's Restroom Lounge Functional Pass
70 08/12/22 01:AV-01:AV-
1st Fl Northwest Functional Pass
71 08/12/22 01:AV-01:AV-
2nd Fl Northwest Breakroom Functional Pass
72 08/12/22 01:AV-01:AV-
2nd Fl Northwest Conference Room Functional Pass
73 08/12/22 01:AV-01:AV-
3rd Fl Northwest Conference Room Functional Pass
74 08/12/22 01:AV-01:AV-
1st Fl Northwest Corridor Functional Pass
75 08/12/22 01:AV-01:AV-
2nd Fl Northwest Corridor Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 9 of 26
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
76 08/12/22 01:AV-01:AV-
3rd Fl Northwest Corridor Functional Pass
77 08/12/22 01:AV-01:AV-
3rd Fl Northwest Corridor Functional Pass
78 08/12/22 01:AV-01:AV-
1st Fl Northwest Hall: Room 103 Functional Pass
79 08/12/22 01:AV-01:AV-
3rd Fl Northwest Judges Office Functional Pass
80 08/12/22 01:AV-01:AV-
3rd Fl Northwest Jury Room Functional Pass
81 08/12/22 01:AV-01:AV-
3rd Fl Northwest Jury Room Functional Pass
82 08/12/22 01:AV-01:AV-
2nd Fl Northwest Office Functional Pass
83 08/12/22 01:AV-01:AV-
2nd Fl Northwest Office Functional Pass
84 08/12/22 01:AV-01:AV-
3rd Fl Northwest Reporters Office Functional Pass
85 08/12/22 01:AV-01:AV-
1st Fl Northwest Section Functional Pass
86 08/12/22 01:AV-01:AV-
3rd Fl Northwest Section Functional Pass
87 08/12/22 01:AV-01:AV-
1st Fl Northwest State Patrol/Trooper Office Functional Pass
88 08/12/22 01:AV-01:AV-
LL Office Functional Pass
89 08/12/22 01:AV-01:AV-
1st Fl Office 122 Functional Pass
90 08/12/22 01:AV-01:AV-
LL Office Room E40 Functional Pass
91 08/12/22 01:AV-01:AV-
LL Office Room E40 Functional Pass
92 08/12/22 01:AV-01:AV-
LL Open Office Functional Pass
93 08/12/22 01:AV-01:AV-
LL Open Office Functional Pass
94 08/12/22 01:AV-01:AV-
1st Fl Reception Room 114 Functional Pass
95 08/12/22 01:AV-01:AV-
1st Fl Reporters Office 106 Functional Pass
96 08/12/22 01:AV-01:AV-
LL Restroom Functional Pass
97 08/12/22 01:AV-01:AV-
LL Restroom Functional Pass
98 08/12/22 01:AV-01:AV-
1st Fl Southeast Functional Pass
99 08/12/22 01:AV-01:AV-
3rd Fl Southeast Conference Room Functional Pass
100 08/12/22 01:AV-01:AV-
3rd Fl Southeast Conference Room Functional Pass
101 08/12/22 01:AV-01:AV-
1st Fl Southeast Corridor Functional Pass
102 08/12/22 01:AV-01:AV-
1st Fl Southeast Corridor Functional Pass
103 08/12/22 01:AV-01:AV-
2nd Fl Southeast Corridor Functional Pass
104 08/12/22 01:AV-01:AV-
2nd Fl Southeast Corridor Functional Pass
105 08/12/22 01:AV-01:AV-
2nd Fl Southeast Corridor Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 10 of 26
Alarm Speakers w/Strobe
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
106 08/12/22 01:AV-01:AV-
3rd Fl Southeast Corridor Functional Pass
107 08/12/22 01:AV-01:AV-
3rd Fl Southeast Corridor Functional Pass
108 08/12/22 01:AV-01:AV-
3rd Fl Southeast Corridor Functional Pass
109 08/12/22 01:AV-01:AV-
3rd Fl Southeast Judges Office Functional Pass
110 08/12/22 01:AV-01:AV-
2nd Fl Southeast Office Functional Pass
111 08/12/22 01:AV-01:AV-
2nd Fl Southeast Resting Area Functional Pass
112 08/12/22 01:AV-01:AV-
3rd Fl Southeast Section Functional Pass
113 08/12/22 01:AV-01:AV-
1st Fl Southeast Supply Room Functional Pass
114 08/12/22 01:AV-01:AV-
3rd Fl Southeast Waiting Area Functional Pass
115 08/12/22 01:AV-01:AV-
LL Storage Room E46 Functional Pass
116 08/12/22 01:AV-01:AV-
LL Storage Room E46 Functional Pass
117 08/12/22 01:AV-01:AV-
LL Storage Room E47 Functional Pass
118 08/12/22 01:AV-01:AV-
3rd Fl Traffic Courtroom Functional Pass
119 08/12/22 01:AV-01:AV-
LL Waiting Area Functional Pass
120 08/12/22 01:AV-01:AV-
LL Waiting Room A16 Functional Pass
Visual Alarms
Functional
Pass/ Fail
1 08/12/22 01:ST-01:ST-
LL Center Hall Functional Pass
2 08/12/22 01:ST-01:ST-
LL Center Hall Functional Pass
3 08/12/22 01:ST-01:ST-
LL Center Hall Functional Pass
4 08/12/22 01:ST-01:ST-
LL Electrical Room 19 Functional Pass
5 08/12/22 01:ST-01:ST-
1st Fl Northeast Functional Pass
6 08/12/22 01:ST-01:ST-
2nd Fl Northeast Functional Pass
7 08/12/22 01:ST-01:ST-
3rd Fl Northeast Conference Room Functional Pass
8 08/12/22 01:ST-01:ST-
3rd Fl Northeast Conference Room Functional Pass
9 08/12/22 01:ST-01:ST-
1st Fl Northeast: Conference Toilet Functional Pass
10 08/12/22 01:ST-01:ST-
1st Fl Northeast: Conference Toilet Functional Pass
11 08/12/22 01:ST-01:ST-
1st Fl Northeast Corridor Functional Pass
12 08/12/22 01:ST-01:ST-
3rd Fl Northeast Corridor Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 11 of 26
Visual Alarms
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
13 08/12/22 01:ST-01:ST-
1st Fl Northeast: Judges Office Corridor Functional Pass
14 08/12/22 01:ST-01:ST-
1st Fl Northeast Office Functional Pass
15 08/12/22 01:ST-01:ST-
LL Northeast E38 Functional Pass
16 08/12/22 01:ST-01:ST-
LL Northeast E40 Functional Pass
17 08/12/22 01:ST-01:ST-
3rd Fl Northeast Restroom Functional Pass
18 08/12/22 01:ST-01:ST-
3rd Fl Northeast Restroom Functional Pass
19 08/12/22 01:ST-01:ST-
LL Northwest Corridor E39 Functional Pass
20 08/12/22 01:ST-01:ST-
2nd Fl Northwest Jury Corridor Functional Pass
21 08/12/22 01:ST-01:ST-
3rd Fl Northwest Jury Restroom Functional Pass
22 08/12/22 01:ST-01:ST-
3rd Fl Northwest Jury Restroom Functional Pass
23 08/12/22 01:ST-01:ST-
2nd Fl Northwest Jury Restroom 210 Functional Pass
24 08/12/22 01:ST-01:ST-
2nd Fl Northwest Jury Restroom 210 Functional Pass
25 08/12/22 01:ST-01:ST-
LL Northwest Multipurpose Room Functional Pass
26 08/12/22 01:ST-01:ST-
LL Northwest Multipurpose Room Restroom Functional Pass
27 08/12/22 01:ST-01:ST-
1st Fl Northwest: Restroom 107 Functional Pass
28 08/12/22 01:ST-01:ST-
1st Fl Northwest: Restroom 109 Functional Pass
29 08/12/22 01:ST-01:ST-
2nd Fl Southeast Functional Pass
30 08/12/22 01:ST-01:ST-
LL Southeast Basement Ramp Functional Pass
31 08/12/22 01:ST-01:ST-
1st Fl Southeast Clerk of Courts Office 119 Functional Pass
32 08/12/22 01:ST-01:ST-
LL Southeast Conference Room Functional Pass
33 08/12/22 01:ST-01:ST-
1st Fl Southeast Conference Room 115 Functional Pass
34 08/12/22 01:ST-01:ST-
1st Fl Southeast Financial Room 116 Functional Pass
35 08/12/22 01:ST-01:ST-
LL Southeast Office Functional Pass
36 08/12/22 01:ST-01:ST-
2nd Fl Southeast Restroom Functional Pass
37 08/12/22 01:ST-01:ST-
2nd Fl Southeast Restroom Functional Pass
38 08/12/22 01:ST-01:ST-
3rd Fl Southeast Restroom Functional Pass
39 08/12/22 01:ST-01:ST-
3rd Fl Southeast Restroom Functional Pass
40 08/12/22 01:ST-01:ST-
LL Southeast Restroom 13 Functional Pass
41 08/12/22 01:ST-01:ST-
LL Southeast Restroom 15 Functional Pass
42 08/12/22 01:ST-01:ST-
2nd Fl Southeast Waiting Room Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 12 of 26
Visual Alarms
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
43 08/12/22 01:ST-01:ST-
1st Fl Southeast Workroom 118 Functional Pass
44 08/12/22 01:ST-01:ST-
2nd Fl Southwest Corridor Functional Pass
See main System Record of Inspection and Testing for additional information, certifications, and approvals.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 13 of 26
INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY COURTHOUSE (4433-53140-00020)
Address: 912 56TH ST. KENOSHA, WI, 53140
2. INITIATING DEVICE TEST RESULTS
2.1 Initiating Devices Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
7 7 100% 0 0% 0 0% Heat Detectors
20 20 100% 0 0% 0 0% Manual Pull Stations
2 2 100% 0 0% 0 0% Projected Beam Smoke Detectors
311 310 99.7% 1 0.3% 0 0% System Smoke Detectors (P)
2.2 Initiating Devices Testing Results by Type
Heat Detectors
Functional
Pass/ Fail
1 08/12/22 01:M1-01:M1-
LL Generator Room 44 Functional Pass
2 08/12/22 01:M1-01:M1-
LL Generator Room 44 Functional Pass
3 08/12/22 01:M1-01:M1-
LL Boiler Room: Entrance Functional Pass
4 08/12/22 01:M1-01:M1-
LL Boiler Room: Entrance Functional Pass
5 08/12/22 01:M1-01:M1-
LL Boiler Room Functional Pass
6 08/12/22 01:M1-01:M1-
LL Boiler Room Functional Pass
7 08/12/22 01:M1-01:M1-
LL Boiler Room Functional Pass
Manual Pull Stations
Functional
Pass/ Fail
1 08/12/22 01:M1-01:M1-
LL Basement Hall Exit: East Functional Pass
2 08/12/22 01:M1-01:M1-
LL Basement Hall IT Door: East Functional Pass
3 08/12/22 01:M1-01:M1-
LL Center Stairs Functional Pass
4 08/12/22 01:M1-01:M1-
LL Basement Corridor Functional Pass
5 08/12/22 01:M1-01:M1-
1st Fl North Entrance Functional Pass
6 08/12/22 01:M1-01:M1-
1st Fl Center Hall Stairs - East Functional Pass
7 08/12/22 01:M1-01:M1-
2nd Fl Center Stairwell Functional Pass
8 08/12/22 01:M1-01:M1-
3rd Fl Center Stairwell Functional Pass
9 08/12/22 01:M2-01:M2-
1st Fl Center Hall Stairs - West Functional Pass
10 08/12/22 01:M2-01:M2-
2nd Fl Center Stairs Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 14 of 26
Manual Pull Stations
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
11 08/12/22 01:M2-01:M2-
3rd Fl Center Hall Functional Pass
12 08/12/22 01:M2-01:M2-
1st Fl West Main Hall Functional Pass
13 08/12/22 01:M2-01:M2-
2nd Fl Center Hall: West Functional Pass
14 08/12/22 01:M2-01:M2-
3rd Fl Center Hall: West Functional Pass
15 08/12/22 01:M2-01:M2-
2nd Fl Judges Stairwell Functional Pass
16 08/12/22 01:M2-01:M2-
3rd Fl Judges Stairwell Functional Pass
17 08/12/22 01:M3-01:M3-
3rd Fl Center Stairs Functional Pass
18 08/12/22 01:M3-01:M3-
1st Fl Main Entrance - Security Checkpoint Functional Pass
19 08/12/22 01:M3-01:M3-
1st Fl Center Hall: East Functional Pass
20 08/12/22 01:M3-01:M3-
2nd Fl Center Hall Functional Pass
Projected Beam Smoke Detectors
Functional
Pass/ Fail
1 08/12/22 01:M1-01:M1-
1st Fl East Beam Detector Functional Pass
2 08/12/22 01:M1-01:M1-
1st Fl West Beam Detector Functional Pass
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
1 08/12/22 01:M1-01:M1-
LL Tunnel Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
2 08/12/22 01:M1-01:M1-
LL Custodian Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
3 08/12/22 01:M1-01:M1-
LL Custodian Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
4 08/12/22 01:M1-01:M1-
LL Custodian Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
5 08/12/22 01:M1-01:M1-
LL Custodian Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
6 08/12/22 01:M1-01:M1-
LL Custodian Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
7 08/12/22 01:M1-01:M1-
LL Custodian Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
8 08/12/22 01:M1-01:M1-
LL Custodian Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
9 08/12/22 01:M1-01:M1-
LL Elevator Equipment Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
10 08/12/22 01:M1-01:M1-
LL Electrical Room: FACP Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
11 08/12/22 01:M1-01:M1-
LL Storage Room E46: Paper Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
12 08/12/22 01:M1-01:M1-
LL Storage Room E46 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
13 08/12/22 01:M1-01:M1-
LL Storage Room E46 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 15 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
14 08/12/22 01:M1-01:M1-
LL Storage Room E46 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
15 08/12/22 01:M1-01:M1-
LL Storage Room E46: Paper Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
16 08/12/22 01:M1-01:M1-
LL Probation File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
17 08/12/22 01:M1-01:M1-
LL Probation File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
18 08/12/22 01:M1-01:M1-
LL Probation Back Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
19 08/12/22 01:M1-01:M1-
LL Probation Juvenile Circuit Court 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
20 08/12/22 01:M1-01:M1-
LL Probation Managers Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
21 08/12/22 01:M1-01:M1-
LL Probation Office Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
22 08/12/22 01:M1-01:M1-
LL Probation Front Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
23 08/12/22 01:M1-01:M1-
LL East File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
24 08/12/22 01:M1-01:M1-
LL East Hall Ramp 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
25 08/12/22 01:M1-01:M1-
LL East Women's Restroom: Public 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
26 08/12/22 01:M1-01:M1-
LL East Men's Restroom: Public 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
27 08/12/22 01:M1-01:M1-
LL East I.T. Clsoet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
28 08/12/22 01:M1-01:M1-
LL Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
29 08/12/22 01:M1-01:M1-
LL Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
30 08/12/22 01:M1-01:M1-
LL Corporate Southeast Office Ramp 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
31 08/12/22 01:M1-01:M1-
LL Corporate Southeast Office Ramp 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
32 08/12/22 01:M1-01:M1-
LL Corporate Library 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
33 08/12/22 01:M1-01:M1-
LL Corporate Reception Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
34 08/12/22 01:M1-01:M1-
LL Corporate Center Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
35 08/12/22 01:M1-01:M1-
LL Corporate South Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
36 08/12/22 01:M1-01:M1-
LL Corporate File Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
37 08/12/22 01:M1-01:M1-
LL Corporate Clerks Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
38 08/12/22 01:M1-01:M1-
LL Corporate head Attorney Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
39 08/12/22 01:M1-01:M1-
LL Corporate Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
40 08/12/22 01:M1-01:M1-
LL Center Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
41 08/12/22 01:M1-01:M1-
LL Hall by Room LL13 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
42 08/12/22 01:M1-01:M1-
LL Hall by Room LL09 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
43 08/12/22 01:M1-01:M1-
LL Victim Witness Back Conference Room 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 16 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
44 08/12/22 01:M1-01:M1-
LL Victim Witness Back File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
45 08/12/22 01:M1-01:M1-
LL West IT Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
Comment: REMOVED TAPE
46 08/12/22 01:M1-01:M1-
LL Victim Witness Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
Comment: REMOVED TAPE
47 08/12/22 01:M1-01:M1-
LL Victim Witness Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
48 08/12/22 01:M1-01:M1-
LL Victim Witness Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
49 08/12/22 01:M1-01:M1-
LL Victim Witness File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
50 08/12/22 01:M1-01:M1-
LL Large File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
51 08/12/22 01:M1-01:M1-
LL Large File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
52 08/12/22 01:M1-01:M1-
LL Large File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
53 08/12/22 01:M1-01:M1-
LL Large File Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
54 08/12/22 01:M1-01:M1-
LL Jury Office Entrance/Waiting Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
55 08/12/22 01:M1-01:M1-
LL Jury Room Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
56 08/12/22 01:M1-01:M1- 065^1
LL Victim Witness Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
57 08/12/22 01:M1-01:M1- 065^2
LL Short Door Storage 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
58 08/12/22 01:M1-01:M1-
1st Fl Elevator Lobby 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
59 08/12/22 01:M1-01:M1-
LL Short Door Storage 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
60 08/12/22 01:M1-01:M1-
LL Center Hall by Stairs 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
61 08/12/22 01:M1-01:M1-
LL Hall by Room LL24 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
62 08/12/22 01:M1-01:M1-
LL Hall by Vending 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
63 08/12/22 01:M1-01:M1-
LL Mechanical Room: Gas/Water 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
64 08/12/22 01:M1-01:M1-
LL Custodian Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
65 08/12/22 01:M1-01:M1-
LL Mechanical Room: Gas/Water 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
66 08/12/22 01:M1-01:M1-
LL Mechanical Room: Gas/Water 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
67 08/12/22 01:M1-01:M1-
LL Mechanical Room: Gas/Water 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
68 08/12/22 01:M1-01:M1-
LL Mechanical Room: Gas/Water 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
69 08/12/22 01:M1-01:M1-
LL Jury Overflow Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
70 08/12/22 01:M1-01:M1-
LL Jury Overflow Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
71 08/12/22 01:M1-01:M1-
LL Jury Overflow Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
72 08/12/22 01:M1-01:M1-
LL Men's Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 17 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
73 08/12/22 01:M1-01:M1-
LL Jury Hall Between Rooms 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
74 08/12/22 01:M1-01:M1-
LL Womens Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
75 08/12/22 01:M1-01:M1-
LL Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
76 08/12/22 01:M1-01:M1-
LL Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
77 08/12/22 01:M1-01:M1-
LL Restraining Order Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
78 08/12/22 01:M1-01:M1-
LL Restraining Order Room: Storage 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
79 08/12/22 01:M1-01:M1-
LL Hall by Room LL36 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
80 08/12/22 01:M1-01:M1-
LL Victim Witness Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
81 08/12/22 01:M1-01:M1-
LL Victim Witness Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
82 08/12/22 01:M1-01:M1-
1st Fl North Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
83 08/12/22 01:M1-01:M1-
LL Elevator Lobby 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
84 08/12/22 01:M1-01:M1-
1st Fl East Emergency Exit 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
85 08/12/22 01:M1-01:M1-
1st Fl West Emergency Exit 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
Comment: REMOVED TAPE
86 08/12/22 01:M1-01:M1-
3rd Fl Elevator Lobby 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
87 08/12/22 01:M1-01:M1-
2nd Fl Elevator Lobby 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
88 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
89 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
90 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Judges Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
91 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
92 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Reporters Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
93 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
94 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
95 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Storage Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
96 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
97 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
98 08/12/22 01:M2-01:M2-
1st Fl Men's Public Restroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
99 08/12/22 01:M2-01:M2-
1st Fl Hall by Room 124 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
100 08/12/22 01:M2-01:M2-
1st Fl State Patrol 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
101 08/12/22 01:M2-01:M2-
1st Fl Middle Main Hall - Across from Custodian Closet 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 18 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
102 08/12/22 01:M2-01:M2-
1st Fl Hall by Room 116 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
103 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Center Door Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
104 08/12/22 01:M2-01:M2-
1st Fl Hall Near Room 120 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
105 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
106 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
107 08/12/22 01:M2-01:M2-
1st Fl Branch 2: Storage 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
108 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
109 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Judges Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
110 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
111 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
112 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Reporters Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
113 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
114 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
115 08/12/22 01:M2-01:M2-
2nd Fl NBR 8: Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
116 08/12/22 01:M2-01:M2-
2nd Fl Break Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
117 08/12/22 01:M2-01:M2-
2nd Fl Hall by Break Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
118 08/12/22 01:M2-01:M2-
2nd Fl Hall by Room 220 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
119 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Storage 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
120 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Jury Room Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
121 08/12/22 01:M2-01:M2-
2nd Fl Branch 7: Clerks Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
122 08/12/22 01:M2-01:M2-
2nd Fl Hall by Room 224 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
123 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
124 08/12/22 01:M2-01:M2-
2nd Fl Hall by Room 228 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
125 08/12/22 01:M2-01:M2-
2nd Fl Branch 6: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
126 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
127 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Judges Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
128 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
129 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
130 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Reporters Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
131 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 19 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
132 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
133 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
134 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
135 08/12/22 01:M2-01:M2-
3rd Fl Women's Restroom: Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
136 08/12/22 01:M2-01:M2-
3rd Fl Women's Restroom: Public 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
137 08/12/22 01:M2-01:M2-
3rd Fl Center Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
138 08/12/22 01:M2-01:M2-
3rd Fl Center Hall by Stairs 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
139 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Storage 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
140 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Center Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
141 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
142 08/12/22 01:M2-01:M2-
3rd Fl Branch 7: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
143 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
144 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Reporters Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
145 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Kitchenette 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
146 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Jury Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
147 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
148 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
149 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
150 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Judges Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
151 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Judges Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
152 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Back Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
153 08/12/22 01:M2-01:M2-
1st Fl Basement Stairwell to 3rd Floor 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
154 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
155 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
156 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
157 08/12/22 01:M2-01:M2-
1st Fl Custodian Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
158 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
159 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
160 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Clerks Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
161 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 20 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
162 08/12/22 01:M2-01:M2-
1st Fl Branch 4: Printer Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
163 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Judges Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
164 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Judges Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
165 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
166 08/12/22 01:M2-01:M2-
2ND FL 209 STORAGE SMOKE 1.5%-
3.7%
SIMPLEX/4098-
Functional Pass
167 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
168 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Clerks Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
169 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Reporters Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
170 08/12/22 01:M2-01:M2-
2nd Fl West Stairs 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
171 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Back Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
172 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Jury Room Stairs 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
173 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Hall to Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
174 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Kitchenette 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
175 08/12/22 01:M2-01:M2- 095^1
3rd Fl Branch 3: Hall to Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
176 08/12/22 01:M2-01:M2- 095^2
3rd Fl Branch 3: Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
177 08/12/22 01:M2-01:M2-
3rd Fl Branch 3: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
178 08/12/22 01:M2-01:M2-
3rd Fl Branch 3: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
179 08/12/22 01:M2-01:M2-
3rd Fl Hall to Roof 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
180 08/12/22 01:M2-01:M2-
3rd Fl Branch 3: To Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
181 08/12/22 01:M2-01:M2-
3rd Fl Room 317: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
182 08/12/22 01:M2-01:M2-
3rd Fl Room 317: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
183 08/12/22 01:M2-01:M2-
3rd Fl West Stairs 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
184 08/12/22 01:M2-01:M2-
3rd Fl Hall by Room 336 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
185 08/12/22 01:M2-01:M2-
3rd Fl Branch 3: Jury Room Stairs 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
186 08/12/22 01:M2-01:M2-
3rd Fl Hall by Room 332 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
187 08/12/22 01:M2-01:M2-
3rd Fl Hall by Room 328 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
188 08/12/22 01:M2-01:M2-
3rd Fl Center Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
189 08/12/22 01:M2-01:M2-
3rd Fl Custodian Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
190 08/12/22 01:M2-01:M2-
3rd Fl Atrium 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
191 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Courtroom - Northeast 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 21 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
192 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Courtroom - Southeast 1.5%- 3.7%
SIMPLEX/4098-
Visual Pass
Comment: UNABLE ABLE TO TEST DUE TO CEILING WORK
193 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Courtroom - Southwest 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
194 08/12/22 01:M2-01:M2-
2nd Fl Branch 3: Courtroom - Northwest 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
195 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Back Ramp to Bench 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
196 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Courtroom - Jury Box 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
197 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Courtroom - Center 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
198 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Courtroom - South 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
199 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Center Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
200 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
201 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Center Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
202 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Clerks Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
203 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
204 08/12/22 01:M3-01:M3-
1st Fl Women's Employee Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
205 08/12/22 01:M3-01:M3-
1st Fl Women's Employee Lounge 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
206 08/12/22 01:M3-01:M3-
1st Fl Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
207 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
208 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
209 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
210 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Judges Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
211 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
212 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Judges Office Hall 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
213 08/12/22 01:M3-01:M3-
1st Fl Branch 5: Judges Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
214 08/12/22 01:M3-01:M3-
2nd Fl Room 204: East Work Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
215 08/12/22 01:M3-01:M3-
2nd Fl Room 204: East Work Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
216 08/12/22 01:M3-01:M3-
2nd Fl Hall by Room 200 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
217 08/12/22 01:M3-01:M3-
2nd Fl Hall by Room 204 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
218 08/12/22 01:M3-01:M3-
2nd Fl Hall by Room 208 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
219 08/12/22 01:M3-01:M3-
2nd Fl Room 204: Kitchenette 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
220 08/12/22 01:M3-01:M3-
2nd Fl Room 204: Finance Office 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 22 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
221 08/12/22 01:M3-01:M3-
2nd Fl Room 204: West Work Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
222 08/12/22 01:M3-01:M3-
2nd Fl Room 204: Finance Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
223 08/12/22 01:M3-01:M3-
2nd Fl Room 204: Public Access Waiting Area 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
224 08/12/22 01:M3-01:M3-
2nd Fl Room 204: Payment Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
225 08/12/22 01:M3-01:M3-
2nd Fl Room 204: Copy Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
226 08/12/22 01:M3-01:M3-
2nd Fl Room 204: Supply Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
227 08/12/22 01:M3-01:M3-
2nd Fl Room 204: COC Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
228 08/12/22 01:M3-01:M3-
2nd Fl Room 204: COC Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
229 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
230 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
231 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Judges Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
232 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Jury Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
233 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Hall to Jury Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
234 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Hall to Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
235 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Reporters Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
236 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
237 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
238 08/12/22 01:M3-01:M3-
3rd Fl Upper Atrium 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
239 08/12/22 01:M3-01:M3-
3rd Fl Upper Atrium 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
240 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
241 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Courtroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
242 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Conference Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
243 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Jury Room Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
244 08/12/22 01:M3-01:M3-
3rd Fl Branch 1: Clerks Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
245 08/12/22 01:M3-01:M3-
3rd Fl Judges Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
246 08/12/22 01:M3-01:M3-
1st Fl Conference Room 115 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
247 08/12/22 01:M3-01:M3-
1st Fl Family Court: Community Officer 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
248 08/12/22 01:M3-01:M3-
1st Fl Conference Room 123 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
249 08/12/22 01:M3-01:M3-
1st Fl Court Services Manager: Room 120 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
250 08/12/22 01:M3-01:M3-
1st Fl Clerk of Courts: Room 119 1.5%- 3.7%
SIMPLEX/4098-
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 23 of 26
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
Comment: LOCATED IN 109
251 08/12/22 01:M3-01:M3-
1st Fl Room 109: Shredding Room 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
252 08/12/22 01:M3-01:M3-
1st Fl Room 109: Vault 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
253 08/12/22 01:M3-01:M3-
1st Fl E121: Custodian Closet 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
254 08/12/22 01:M3-01:M3-
1st Fl Coutroom 109: Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
255 08/12/22 01:M3-01:M3-
1st Fl Room 109: Financial Office 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
256 08/12/22 01:M3-01:M3-
1st Fl Clerk of Courts: Room 119 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
Comment: LOCATED IN 109
257 08/12/22 01:M3-01:M3-
1st Fl Conference Room 121 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
Comment: LOCATED IN 109
258 08/12/22 01:M3-01:M3-
1st Fl Clerk of Courts: Room 119 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
259 08/12/22 01:M3-01:M3-
1st Fl Hall by Room 109 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
260 08/12/22 01:M3-01:M3-
1st Fl Hall by Room 105 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
261 08/12/22 01:M3-01:M3-
1st Fl Hall by Room 101 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
262 08/12/22 01:M3-01:M3-
1st Fl Family Court: Bathroom 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
263 08/12/22 01:M3-01:M3-
1st Fl Room 109: Middle Entrance 1.5%- 3.7%
SIMPLEX/4098-
Functional Pass
264 08/12/22 01:M3-01:M3-
1st…