NFPA 72 Fire Alarm System Inspection and Testing Report for Kenosha County Courthouse

This document is an NFPA 72 System Record of Inspection and Testing report for the Kenosha County Courthouse located at 912 56th Street, Kenosha, Wisconsin 53140. The inspection and testing was conducted by Siemens Industry, Inc., Smart Infrastructure Division, with service performed August 11-12, 2022. The courthouse fire alarm system consists of a Simplex 4100ES control panel located in the lower level electrical room, supplemented by four notification appliance power extender panels distributed throughout the facility. The system includes 311 smoke detectors, 20 manual pull stations, 7 heat detectors, 2 projected beam smoke detectors, 120 alarm speakers with strobe, 44 visual alarm devices, and various interface components for elevator recall and door release functions. Primary power is supplied at 120 volts, 20 amps, with secondary battery backup providing 24 hours of standby capacity and 15 minutes of alarm mode operation. Testing was completed on August 12, 2022 at 23:45 hours, with the system restored to normal operation the same date.

The testing organization, Siemens, and monitoring organization, Alarm Detection Systems (ADS), performed comprehensive functional and visual inspections of all system components in accordance with NFPA 72-2016 standards. Most system components passed testing; however, two notification appliance power extender panels failed load testing and battery performance requirements. Panel 01:T-02 (lower level paper room right) and Panel 01:T-03 (lower level victim witness back conference room left) required replacement batteries, specifically two 12VDC 10AH sealed lead acid units each, per NFPA 72 requirements. All 120 alarm speakers with strobe devices passed functional testing, and 310 of 311 smoke detectors passed testing (99.7% pass rate), with one detector unable to be tested due to ceiling work in progress. All 20 manual pull stations, 7 heat detectors, 2 projected beam detectors, and 5 relay interface components passed functional testing. Smoke detector sensitivity testing verified all units operated within listed sensitivity ranges. System alarm, restoration, and trouble signals were successfully verified as received by ADS monitoring station. The inspection was accepted by Kenosha County representative Rhonda Haidinger on August 12, 2022, with certification by technicians Stanley Laitinen, Jim Kayler, and Alexander Hanus holding appropriate NICET certifications.

View the file

Other files

File Type Posted
Vendor Responsibility Form.pdf PDF
2202 Courthouse ext.pdf PDF
2202 KCAB ext.pdf PDF
2202 KCDC ext.pdf PDF
2202D Kitchen hoods.pdf PDF
2202 Alarm Inspection KCDC.pdf PDF
2202 PSB suppression 2.pdf PDF
2202 Pets suppression.pdf PDF
2202C Alarm panels inc elevator shafts.pdf PDF
2202 Fire Inspection Bid.pdf PDF
2202 Alarm Inspection Pre-Trail Bldg.pdf PDF
2202 Pets ext 2.pdf PDF
2202 Pets ext.pdf PDF
2202 Brookside suppression.pdf PDF
2202 Alarm Inspection Brighton Dale Links.pdf PDF
2202A2 Offer Form.xlsx XLSX spreadsheet
2202 Brookside suppression 2.pdf PDF
2202C Offer Form.xlsx XLSX spreadsheet
2202A Fire extinguishers hoses.pdf PDF
2202 Addendum 1.pdf PDF
2202 Alarm Inspection Parking Ramp.pdf PDF
2202 PSB ext.pdf PDF
2202 Addendum 2.pdf PDF
2202 Alarm Inspection Kenosha County Center.pdf PDF
2202 PSB suppression.pdf PDF
2202 Alarm Inspection Fleet Maintenance.pdf PDF
2202B Offer Form.xlsx XLSX spreadsheet
2202 Alarm Inspection KCDC E Storage Bldg.pdf PDF
2202 Alarm Inspection Admin Bldg.pdf PDF
2202A Offer Form.xlsx XLSX spreadsheet
2202 Alarm Inpection Job Center.pdf PDF
2202 Alarm Inspection Brookside.pdf PDF
2202 KCDC suppression.pdf PDF
2202 PT ext.pdf PDF
2202 Addendum 3.pdf PDF
2202D Offer Form.xlsx XLSX spreadsheet
2202 Alarm Inspection Kemper.pdf PDF
2202 Alarm Inspection Public Safety Bldg.pdf PDF
2202B Sprinklers, Hydrants, Backflow preventers.pdf PDF
2202 KCJC ext.pdf PDF
2202 KCC ext.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NFPA 72 REPORT

© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 26

SYSTEM RECORD OF INSPECTION AND TESTING

System Name: KENOSHA COURTHOUSE Panel Name: 01 - 4100ES - COURTHOUSE

Inspection/Test Start Date/Time: 11 Aug 2022 1630 Inspection/Test Completion Date/Time: 12 Aug 2022 2345

Contract Info: Kenosha County 2022 (2600149454) Notification Number: 5102240918

Supplemental Form(s) Attached: Yes

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY COURTHOUSE (4433-53140-00020)

Address: 912 56TH ST. KENOSHA, WI, 53140

Description of property:

Name of property representative: KENOSHA COUNTY (30078447), None

Address: 1010 56TH ST, KENOSHA, WI 53140-3738

Phone: None Fax: None E-mail: None

2. TESTING AND MONITORING INFORMATION

Testing organization: SIEMENS

Address: 6737 West Washington Street, Suite 2110, Milwaukee, WI 53215

Phone: 414-475-3700 Fax: NA E-mail: NA

Monitoring organization: ALARM DETECTION SYSTEMS

Address: LL ELECTRICAL ROOM

Phone: NA Fax: NA E-mail: NA

Account number: 41677 Phone line 1: NA Phone line 2: NA

Means of transmission: Digital

Entity to which alarms are retransmitted: NA Phone: NA

3. DOCUMENTATION

On-site location of the required record documents and site-specific software:

4. DESCRIPTION OF SYSTEM OR SERVICE

4.1 Control Unit

System Name: KENOSHA COURTHOUSE Panel Name: 01 - 4100ES - COURTHOUSE

Panel Location and Address: LL ELECTRICAL ROOM, 912 56TH. ST., KENOSHA, WI, 53140

Manufacturer: SIMPLEX Model number: 4100ES

4.2 Software and Firmware

Firmware revision number:

4.3 System Power

4.3.1 Primary (Main) Power

Nominal voltage: 120 Amps: 20 Location: LL ELECTRICAL ROOM

Overcurrent protection type: BREAKER Amps: 20

Disconnecting means location: Custodial Room - Panel BE

4.3.2 Secondary Power

Type: Storage Battery Location: LL ELECTRICAL ROOM

Battery type (if applicable): Sealed Lead Acid Manufactured Date: 15 Oct 2019

Calculated capacity of batteries to drive the system:

In standby mode (hours): 24 In alarm mode (minutes): 15

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 26

4.4 Notification Appliance Power Extender Panels

4.4.1 Primary Power

ID Location Input Volts

Panel Amps

Over-current Type

Over-current Amps

Primary Supply Location

Disconnect Location

01:T-01 LL PAPER ROOM (LEFT) 120VAC BREAKER 20 PAPER ROOM

PNL BC

CKT # 11

01:T-02 LL PAPER ROOM (RIGHT) 120VAC BREAKER 20 PAPER ROOM

PNL BC

CKT # 11

01:T-03 LL VICTIM WITNESS BACK

CONFERENCE RM (LEFT)

120VAC BREAKER 20 MAIN COORIDOR

PNL BA

CKT # 17

01:T-04 LL VICTIM WITNESS BACK

CONFERENCE RM (RIGHT)

120VAC BREAKER 20 MAIN COORIDOR

PNL BA

CKT # 17

4.4.2 Secondary Power

ID Location Battery Type

Manufactured Date

Voltage Rating

Amp Rating

Standby Hours

Alarm Minutes

01:T-01 LL PAPER ROOM (LEFT) SLA 2019-04-30 12/12 7AH 24 15

01:T-02 LL PAPER ROOM (RIGHT) SLA 2016-09-15 12/12 10AH 24 15

01:T-03 LL VICTIM WITNESS BACK CONFERENCE

RM (LEFT)

SLA 2016-09-15 12/12 10AH 24 15

01:T-04 LL VICTIM WITNESS BACK CONFERENCE

RM (RIGHT)

SLA 2021-05-17 12/12 10AH 24 15

5. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact

ADS CALLED BY RHONDA HAIDINGER Tim e:

Building management Contact

RHONDA HAIDINGER Tim e:

Building occupants Contact

BY RHONDA HAIDINGER Tim e:

Authority having jurisdiction

(AHJ)

Contact

Tim e:

Other, if required Contact

NA Tim e:

NA

6. TESTING RESULTS

6.1 Control Unit and Related Equipment

Description Visual Inspection or Functional

Test

Comments

Control unit Functional None

Disconnect switches Functional None

Fuses Functional None

Ground-fault monitoring Functional None

Interface Equipment Functional None

Lamps/LEDs/LCDs Functional None

Local annunciator Functional None

Primary Power Functional None

Remote annunciators Functional None

Remote power panels Functional None

Supervision Functional None

Trouble signals Functional None

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 26

6.2 Secondary Power

Description Visual Inspection or Functional

Test

Comments

Battery condition Functional (2) 50 AH BATTERIES

Charger test Functional 27.21

Discharge test Functional 100%/100%

Load voltage Functional 13.59/13.61

Remote panel batteries Functional None

6.3 Notification Appliance Power Extender Panels Secondary Power

ID Location Battery Voltage Battery Amps Test Method Pass/ Fail

01:T-01 LL PAPER

ROOM (LEFT)

13.70/13.67 100%/100% Functional Pass

01:T-02 LL PAPER

ROOM

(RIGHT)

13.67/13.66 70%/70% Functional Fail

Comment: FAILED LOAD TEST AND BY DATE PER NFPA72 REQUIREMENTS. REPLACEMENT REQUIRED. USE

QTY. OF 2 @ 12VDC 10AH SLA

01:T-03 LL VICTIM

WITNESS

BACK

CONFERENCE

RM (LEFT)

13.48/13.55 40%/20% Functional Fail

Comment: FAILED LOAD TEST AND BY DATE PER NFPA72 REQUIREMENTS. REPLACEMENT REQUIRED. USE

QTY. OF 2 @ 12VDC 10AH SLA

01:T-04 LL VICTIM

WITNESS

BACK

CONFERENCE

RM (RIGHT)

13.74/13.72 100%/100% Functional Pass

6.4 Alarm and Supervisory Alarm Initiating Device

Attach supplementary device test sheets for all initiating devices.

6.5 Notification Appliances

Attach supplementary appliance test sheets for all notification appliances.

6.6 Interface Equipment

Attach supplementary interface component test sheets for all interface components.

6.7 Supervising Station Monitoring

Description Receive d

Time / Elapsed Time

Pass/Fail Comments

Alarm signal Yes NA / NA Pass VERIFIED SIGNALS RECEIVED ADS

Alarm restoration Yes NA / NA Pass VERIFIED SIGNALS RESTORED ADS

Trouble signal Yes NA / NA Pass VERIFIED SIGNALS RECEIVED ADS

Trouble restoration Yes NA / NA Pass VERIFIED SIGNALS RESTORED ADS

Supervisory signal No NA / NA None

Supervisory restoration No NA / NA None

6.8 Public Emergency Alarm Reporting System

Description Yes No Time Comments

Alarm signal NA NA

Alarm restoration NA NA

Trouble signal NA NA

Trouble restoration NA NA

Supervisory signal NA NA

Supervisory restoration NA NA

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 26

7. NOTIFICATIONS THAT TESTING IS COMPLETE

Monitoring organization Contact

ADS - CALLED BY RHONDA HAIDINGER Tim e:

Building management Contact

RHONDA HAIDINGER Tim e:

Building occupants Contact

BY RHONDA HAIDINGER Tim e:

Authority having jurisdiction

(AHJ)

Contact

Tim e:

Other, if required Contact

NA Tim e:

NA

8. SYSTEM RESTORED TO NORMAL OPERATION

Date: 12 Aug 2022 Time: 2345

9. CERTIFICATION

This Testing Was Performed in Accordance with Applicable NFPA Standards.

Signed:

Alexander Hanus Date: 08/12/2022

Printed name: STANLEY LAITINEN, JIM KAYLER, ALEXANDER HANUS Title: Technician License No.: NICET CERT. # SL

150654, AH 148912

Organization: SIEMENS Phone: 414-475-3700

Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service

10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED

NAC Panels

Address Location Model Comment:

01:T-02 LL PAPER ROOM (RIGHT) SIMPLEX/4100 FAILED LOAD TEST AND BY DATE PER NFPA72

REQUIREMENTS. REPLACEMENT REQUIRED. USE QTY. OF

2 @ 12VDC 10AH SLA

01:T-03 LL VICTIM WITNESS BACK

CONFERENCE RM (LEFT)

SIMPLEX/4100 FAILED LOAD TEST AND BY DATE PER NFPA72

REQUIREMENTS. REPLACEMENT REQUIRED. USE QTY. OF

2 @ 12VDC 10AH SLA

11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE

The undersigned accepted the test report for the system as specified herein:

Signed:

Printed name: RHONDA HAIDINGER Date:

Organization: KENOSHA COUNTY (30078447) Phone: None

Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements.

Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.

12. OTHER

12.1 Special Procedures

TO BYPASS PANEL CHANGE TO ACCESS LEVEL 3.

TO BYPASS EXTERIOR DOOR RELEASES:

08/15/22

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 26

LOG IN ACCESS LEVEL 3

PRESS DISABLE

PRESS #6 -ID NET

ENTER 1-111

REVERSE PROCESS TO ENABLE

12.2 Comments

*Reviewed the sensitivity of the Analog Smoke/Duct detectors with use of Fire Alarm Control Panel whereby the detector causes a signal at the control panel when its sensitivity is outside its listed sensitivity range.

NFPA 72-2016 14.4.3.2-17 (h)(4) states that *Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside it listed sensitivity range*

ALL SMOKE DETECTORS PASSED SENSITIVITY TESTING.

ELEVATOR RECALL FUNCTIONED PROPERLY.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 26

NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY COURTHOUSE (4433-53140-00020)

Address: 912 56TH ST. KENOSHA, WI, 53140

2. NOTIFICATION APPLIANCE TEST RESULTS

2.1 Notification Appliances Equipment Summary by Type

Total Qty Functionally Tested Qty

Functionally Tested %

Visually Tested

Qty

Visually Tested %

Failed Qty Failed % Device or System Type

2 2 100% 0 0% 0 0% Alarm Speakers

120 120 100% 0 0% 0 0% Alarm Speakers w/Strobe

44 44 100% 0 0% 0 0% Visual Alarms

2.2 Notification Appliances Testing Results by Type

Alarm Speakers

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

1 08/12/22 01:SP-01:SP-

LL Lower Level Functional Pass

2 08/12/22 01:SP-01:SP-

LL Northwest Section: Basement Corridor Functional Pass

Alarm Speakers w/Strobe

Functional

Pass/ Fail

1 08/12/22 01:AV-01:AV-

LL Basement Corridor Functional Pass

2 08/12/22 01:AV-01:AV-

LL Basement Corridor Functional Pass

3 08/12/22 01:AV-01:AV-

LL Basement Corridor Functional Pass

4 08/12/22 01:AV-01:AV-

LL Basement Corridor Room E39 Functional Pass

5 08/12/22 01:AV-01:AV-

LL Basement Corridor Room E39 Functional Pass

6 08/12/22 01:AV-01:AV-

1st Fl Branch 2: Room 100 Functional Pass

7 08/12/22 01:AV-01:AV-

1st Fl Branch 2: Room 100 Functional Pass

8 08/12/22 01:AV-01:AV-

2nd Fl Branch 5 Functional Pass

9 08/12/22 01:AV-01:AV-

2nd Fl Branch 5 Courtroom Functional Pass

10 08/12/22 01:AV-01:AV-

2nd Fl Branch 5 Courtroom Functional Pass

11 08/12/22 01:AV-01:AV-

3rd Fl Branch 5 Courtroom Functional Pass

12 08/12/22 01:AV-01:AV-

3rd Fl Branch 5 Courtroom Functional Pass

13 08/12/22 01:AV-01:AV-

3rd Fl Branch 6 Courtroom Functional Pass

14 08/12/22 01:AV-01:AV-

3rd Fl Branch 6 Courtroom Functional Pass

15 08/12/22 01:AV-01:AV-

1st Fl Branch 7 Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 26

Alarm Speakers w/Strobe

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

16 08/12/22 01:AV-01:AV-

1st Fl Branch 7 Functional Pass

17 08/12/22 01:AV-01:AV-

1st Fl Branch 7 Corridor Functional Pass

18 08/12/22 01:AV-01:AV-

2nd Fl Branch 8 Courtroom Functional Pass

19 08/12/22 01:AV-01:AV-

2nd Fl Branch 8 Courtroom Functional Pass

20 08/12/22 01:AV-01:AV-

2nd Fl Branch 8 - Judges Office/Chambers Functional Pass

21 08/12/22 01:AV-01:AV-

LL Center Hall Functional Pass

22 08/12/22 01:AV-01:AV-

LL Center Hall Functional Pass

23 08/12/22 01:AV-01:AV-

1st Fl Clerk of Courts: Room 119 Functional Pass

24 08/12/22 01:AV-01:AV-

2nd Fl Conference Room Functional Pass

25 08/12/22 01:AV-01:AV-

2nd Fl Conference Room Functional Pass

26 08/12/22 01:AV-01:AV-

LL Conference Room Functional Pass

27 08/12/22 01:AV-01:AV-

1st Fl Conference Room 104 Functional Pass

28 08/12/22 01:AV-01:AV-

1st Fl Conference Room 121 Functional Pass

29 08/12/22 01:AV-01:AV-

1st Fl Conference Room 123 Functional Pass

30 08/12/22 01:AV-01:AV-

1st Fl Family Court Room 124 Functional Pass

31 08/12/22 01:AV-01:AV-

LL File Storage Room E43 Functional Pass

32 08/12/22 01:AV-01:AV-

3rd Fl Northwest Corridor Functional Pass

33 08/12/22 01:AV-01:AV-

LL Generator Room Functional Pass

34 08/12/22 01:AV-01:AV-

LL Hall by Room 14 Functional Pass

35 08/12/22 01:AV-01:AV-

2nd Fl Hall by Room 203 Functional Pass

36 08/12/22 01:AV-01:AV-

LL IT Room Functional Pass

37 08/12/22 01:AV-01:AV-

LL IT Room Functional Pass

38 08/12/22 01:AV-01:AV-

1st Fl Judges Office: Room 101 Functional Pass

39 08/12/22 01:AV-01:AV-

LL Jury Duty Functional Pass

40 08/12/22 01:AV-01:AV-

LL Jury Duty Functional Pass

41 08/12/22 01:AV-01:AV-

1st Fl Jury Room 110 Functional Pass

42 08/12/22 01:AV-01:AV-

1st Fl Jury Room 110 Functional Pass

43 08/12/22 01:AV-01:AV-

2nd Fl Jury Room 210 Functional Pass

44 08/12/22 01:AV-01:AV-

2nd Fl Jury Room 210 Functional Pass

45 08/12/22 01:AV-01:AV-

1st Fl Main Entrance Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 8 of 26

Alarm Speakers w/Strobe

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

46 08/12/22 01:AV-01:AV-

1st Fl Men's Restroom 112 Functional Pass

47 08/12/22 01:AV-01:AV-

LL Multipurpose Restroom Functional Pass

48 08/12/22 01:AV-01:AV-

LL Multipurpose Room Functional Pass

49 08/12/22 01:AV-01:AV-

1st Fl Northeast Conference Room Functional Pass

50 08/12/22 01:AV-01:AV-

2nd Fl Northeast Conference Room Functional Pass

51 08/12/22 01:AV-01:AV-

2nd Fl Northeast Corridor Functional Pass

52 08/12/22 01:AV-01:AV-

2nd Fl Northeast Corridor Functional Pass

53 08/12/22 01:AV-01:AV-

3rd Fl Northeast Corridor Functional Pass

54 08/12/22 01:AV-01:AV-

3rd Fl Northeast Corridor Functional Pass

55 08/12/22 01:AV-01:AV-

2nd Fl Northeast Corridor: Plaster Ceiling Functional Pass

56 08/12/22 01:AV-01:AV-

2nd Fl Northeast Corridor: Plaster Ceiling Functional Pass

57 08/12/22 01:AV-01:AV-

3rd Fl Northeast Hall Functional Pass

58 08/12/22 01:AV-01:AV-

3rd Fl Northeast Judges Chambers Functional Pass

59 08/12/22 01:AV-01:AV-

1st Fl Northeast Judges Office Functional Pass

60 08/12/22 01:AV-01:AV-

3rd Fl Northeast Jury Room Functional Pass

61 08/12/22 01:AV-01:AV-

2nd Fl Northeast Open Office Functional Pass

62 08/12/22 01:AV-01:AV-

2nd Fl Northeast Open Office Functional Pass

63 08/12/22 01:AV-01:AV-

3rd Fl Northeast Open Office Functional Pass

64 08/12/22 01:AV-01:AV-

3rd Fl Northeast Open Office Functional Pass

65 08/12/22 01:AV-01:AV-

2nd Fl Northeast Open Office Files Functional Pass

66 08/12/22 01:AV-01:AV-

2nd Fl Northeast Public Waiting Functional Pass

67 08/12/22 01:AV-01:AV-

3rd Fl Northeast Waiting Area Functional Pass

68 08/12/22 01:AV-01:AV-

1st Fl Northeast Women's Restroom 113 Functional Pass

69 08/12/22 01:AV-01:AV-

1st Fl Northeast Women's Restroom Lounge Functional Pass

70 08/12/22 01:AV-01:AV-

1st Fl Northwest Functional Pass

71 08/12/22 01:AV-01:AV-

2nd Fl Northwest Breakroom Functional Pass

72 08/12/22 01:AV-01:AV-

2nd Fl Northwest Conference Room Functional Pass

73 08/12/22 01:AV-01:AV-

3rd Fl Northwest Conference Room Functional Pass

74 08/12/22 01:AV-01:AV-

1st Fl Northwest Corridor Functional Pass

75 08/12/22 01:AV-01:AV-

2nd Fl Northwest Corridor Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 9 of 26

Alarm Speakers w/Strobe

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

76 08/12/22 01:AV-01:AV-

3rd Fl Northwest Corridor Functional Pass

77 08/12/22 01:AV-01:AV-

3rd Fl Northwest Corridor Functional Pass

78 08/12/22 01:AV-01:AV-

1st Fl Northwest Hall: Room 103 Functional Pass

79 08/12/22 01:AV-01:AV-

3rd Fl Northwest Judges Office Functional Pass

80 08/12/22 01:AV-01:AV-

3rd Fl Northwest Jury Room Functional Pass

81 08/12/22 01:AV-01:AV-

3rd Fl Northwest Jury Room Functional Pass

82 08/12/22 01:AV-01:AV-

2nd Fl Northwest Office Functional Pass

83 08/12/22 01:AV-01:AV-

2nd Fl Northwest Office Functional Pass

84 08/12/22 01:AV-01:AV-

3rd Fl Northwest Reporters Office Functional Pass

85 08/12/22 01:AV-01:AV-

1st Fl Northwest Section Functional Pass

86 08/12/22 01:AV-01:AV-

3rd Fl Northwest Section Functional Pass

87 08/12/22 01:AV-01:AV-

1st Fl Northwest State Patrol/Trooper Office Functional Pass

88 08/12/22 01:AV-01:AV-

LL Office Functional Pass

89 08/12/22 01:AV-01:AV-

1st Fl Office 122 Functional Pass

90 08/12/22 01:AV-01:AV-

LL Office Room E40 Functional Pass

91 08/12/22 01:AV-01:AV-

LL Office Room E40 Functional Pass

92 08/12/22 01:AV-01:AV-

LL Open Office Functional Pass

93 08/12/22 01:AV-01:AV-

LL Open Office Functional Pass

94 08/12/22 01:AV-01:AV-

1st Fl Reception Room 114 Functional Pass

95 08/12/22 01:AV-01:AV-

1st Fl Reporters Office 106 Functional Pass

96 08/12/22 01:AV-01:AV-

LL Restroom Functional Pass

97 08/12/22 01:AV-01:AV-

LL Restroom Functional Pass

98 08/12/22 01:AV-01:AV-

1st Fl Southeast Functional Pass

99 08/12/22 01:AV-01:AV-

3rd Fl Southeast Conference Room Functional Pass

100 08/12/22 01:AV-01:AV-

3rd Fl Southeast Conference Room Functional Pass

101 08/12/22 01:AV-01:AV-

1st Fl Southeast Corridor Functional Pass

102 08/12/22 01:AV-01:AV-

1st Fl Southeast Corridor Functional Pass

103 08/12/22 01:AV-01:AV-

2nd Fl Southeast Corridor Functional Pass

104 08/12/22 01:AV-01:AV-

2nd Fl Southeast Corridor Functional Pass

105 08/12/22 01:AV-01:AV-

2nd Fl Southeast Corridor Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 10 of 26

Alarm Speakers w/Strobe

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

106 08/12/22 01:AV-01:AV-

3rd Fl Southeast Corridor Functional Pass

107 08/12/22 01:AV-01:AV-

3rd Fl Southeast Corridor Functional Pass

108 08/12/22 01:AV-01:AV-

3rd Fl Southeast Corridor Functional Pass

109 08/12/22 01:AV-01:AV-

3rd Fl Southeast Judges Office Functional Pass

110 08/12/22 01:AV-01:AV-

2nd Fl Southeast Office Functional Pass

111 08/12/22 01:AV-01:AV-

2nd Fl Southeast Resting Area Functional Pass

112 08/12/22 01:AV-01:AV-

3rd Fl Southeast Section Functional Pass

113 08/12/22 01:AV-01:AV-

1st Fl Southeast Supply Room Functional Pass

114 08/12/22 01:AV-01:AV-

3rd Fl Southeast Waiting Area Functional Pass

115 08/12/22 01:AV-01:AV-

LL Storage Room E46 Functional Pass

116 08/12/22 01:AV-01:AV-

LL Storage Room E46 Functional Pass

117 08/12/22 01:AV-01:AV-

LL Storage Room E47 Functional Pass

118 08/12/22 01:AV-01:AV-

3rd Fl Traffic Courtroom Functional Pass

119 08/12/22 01:AV-01:AV-

LL Waiting Area Functional Pass

120 08/12/22 01:AV-01:AV-

LL Waiting Room A16 Functional Pass

Visual Alarms

Functional

Pass/ Fail

1 08/12/22 01:ST-01:ST-

LL Center Hall Functional Pass

2 08/12/22 01:ST-01:ST-

LL Center Hall Functional Pass

3 08/12/22 01:ST-01:ST-

LL Center Hall Functional Pass

4 08/12/22 01:ST-01:ST-

LL Electrical Room 19 Functional Pass

5 08/12/22 01:ST-01:ST-

1st Fl Northeast Functional Pass

6 08/12/22 01:ST-01:ST-

2nd Fl Northeast Functional Pass

7 08/12/22 01:ST-01:ST-

3rd Fl Northeast Conference Room Functional Pass

8 08/12/22 01:ST-01:ST-

3rd Fl Northeast Conference Room Functional Pass

9 08/12/22 01:ST-01:ST-

1st Fl Northeast: Conference Toilet Functional Pass

10 08/12/22 01:ST-01:ST-

1st Fl Northeast: Conference Toilet Functional Pass

11 08/12/22 01:ST-01:ST-

1st Fl Northeast Corridor Functional Pass

12 08/12/22 01:ST-01:ST-

3rd Fl Northeast Corridor Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 11 of 26

Visual Alarms

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

13 08/12/22 01:ST-01:ST-

1st Fl Northeast: Judges Office Corridor Functional Pass

14 08/12/22 01:ST-01:ST-

1st Fl Northeast Office Functional Pass

15 08/12/22 01:ST-01:ST-

LL Northeast E38 Functional Pass

16 08/12/22 01:ST-01:ST-

LL Northeast E40 Functional Pass

17 08/12/22 01:ST-01:ST-

3rd Fl Northeast Restroom Functional Pass

18 08/12/22 01:ST-01:ST-

3rd Fl Northeast Restroom Functional Pass

19 08/12/22 01:ST-01:ST-

LL Northwest Corridor E39 Functional Pass

20 08/12/22 01:ST-01:ST-

2nd Fl Northwest Jury Corridor Functional Pass

21 08/12/22 01:ST-01:ST-

3rd Fl Northwest Jury Restroom Functional Pass

22 08/12/22 01:ST-01:ST-

3rd Fl Northwest Jury Restroom Functional Pass

23 08/12/22 01:ST-01:ST-

2nd Fl Northwest Jury Restroom 210 Functional Pass

24 08/12/22 01:ST-01:ST-

2nd Fl Northwest Jury Restroom 210 Functional Pass

25 08/12/22 01:ST-01:ST-

LL Northwest Multipurpose Room Functional Pass

26 08/12/22 01:ST-01:ST-

LL Northwest Multipurpose Room Restroom Functional Pass

27 08/12/22 01:ST-01:ST-

1st Fl Northwest: Restroom 107 Functional Pass

28 08/12/22 01:ST-01:ST-

1st Fl Northwest: Restroom 109 Functional Pass

29 08/12/22 01:ST-01:ST-

2nd Fl Southeast Functional Pass

30 08/12/22 01:ST-01:ST-

LL Southeast Basement Ramp Functional Pass

31 08/12/22 01:ST-01:ST-

1st Fl Southeast Clerk of Courts Office 119 Functional Pass

32 08/12/22 01:ST-01:ST-

LL Southeast Conference Room Functional Pass

33 08/12/22 01:ST-01:ST-

1st Fl Southeast Conference Room 115 Functional Pass

34 08/12/22 01:ST-01:ST-

1st Fl Southeast Financial Room 116 Functional Pass

35 08/12/22 01:ST-01:ST-

LL Southeast Office Functional Pass

36 08/12/22 01:ST-01:ST-

2nd Fl Southeast Restroom Functional Pass

37 08/12/22 01:ST-01:ST-

2nd Fl Southeast Restroom Functional Pass

38 08/12/22 01:ST-01:ST-

3rd Fl Southeast Restroom Functional Pass

39 08/12/22 01:ST-01:ST-

3rd Fl Southeast Restroom Functional Pass

40 08/12/22 01:ST-01:ST-

LL Southeast Restroom 13 Functional Pass

41 08/12/22 01:ST-01:ST-

LL Southeast Restroom 15 Functional Pass

42 08/12/22 01:ST-01:ST-

2nd Fl Southeast Waiting Room Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 12 of 26

Visual Alarms

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

43 08/12/22 01:ST-01:ST-

1st Fl Southeast Workroom 118 Functional Pass

44 08/12/22 01:ST-01:ST-

2nd Fl Southwest Corridor Functional Pass

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 13 of 26

INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY COURTHOUSE (4433-53140-00020)

Address: 912 56TH ST. KENOSHA, WI, 53140

2. INITIATING DEVICE TEST RESULTS

2.1 Initiating Devices Equipment Summary by Type

Total Qty Functionally Tested Qty

Functionally Tested %

Visually Tested

Qty

Visually Tested %

Failed Qty Failed % Device or System Type

7 7 100% 0 0% 0 0% Heat Detectors

20 20 100% 0 0% 0 0% Manual Pull Stations

2 2 100% 0 0% 0 0% Projected Beam Smoke Detectors

311 310 99.7% 1 0.3% 0 0% System Smoke Detectors (P)

2.2 Initiating Devices Testing Results by Type

Heat Detectors

Functional

Pass/ Fail

1 08/12/22 01:M1-01:M1-

LL Generator Room 44 Functional Pass

2 08/12/22 01:M1-01:M1-

LL Generator Room 44 Functional Pass

3 08/12/22 01:M1-01:M1-

LL Boiler Room: Entrance Functional Pass

4 08/12/22 01:M1-01:M1-

LL Boiler Room: Entrance Functional Pass

5 08/12/22 01:M1-01:M1-

LL Boiler Room Functional Pass

6 08/12/22 01:M1-01:M1-

LL Boiler Room Functional Pass

7 08/12/22 01:M1-01:M1-

LL Boiler Room Functional Pass

Manual Pull Stations

Functional

Pass/ Fail

1 08/12/22 01:M1-01:M1-

LL Basement Hall Exit: East Functional Pass

2 08/12/22 01:M1-01:M1-

LL Basement Hall IT Door: East Functional Pass

3 08/12/22 01:M1-01:M1-

LL Center Stairs Functional Pass

4 08/12/22 01:M1-01:M1-

LL Basement Corridor Functional Pass

5 08/12/22 01:M1-01:M1-

1st Fl North Entrance Functional Pass

6 08/12/22 01:M1-01:M1-

1st Fl Center Hall Stairs - East Functional Pass

7 08/12/22 01:M1-01:M1-

2nd Fl Center Stairwell Functional Pass

8 08/12/22 01:M1-01:M1-

3rd Fl Center Stairwell Functional Pass

9 08/12/22 01:M2-01:M2-

1st Fl Center Hall Stairs - West Functional Pass

10 08/12/22 01:M2-01:M2-

2nd Fl Center Stairs Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 14 of 26

Manual Pull Stations

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

11 08/12/22 01:M2-01:M2-

3rd Fl Center Hall Functional Pass

12 08/12/22 01:M2-01:M2-

1st Fl West Main Hall Functional Pass

13 08/12/22 01:M2-01:M2-

2nd Fl Center Hall: West Functional Pass

14 08/12/22 01:M2-01:M2-

3rd Fl Center Hall: West Functional Pass

15 08/12/22 01:M2-01:M2-

2nd Fl Judges Stairwell Functional Pass

16 08/12/22 01:M2-01:M2-

3rd Fl Judges Stairwell Functional Pass

17 08/12/22 01:M3-01:M3-

3rd Fl Center Stairs Functional Pass

18 08/12/22 01:M3-01:M3-

1st Fl Main Entrance - Security Checkpoint Functional Pass

19 08/12/22 01:M3-01:M3-

1st Fl Center Hall: East Functional Pass

20 08/12/22 01:M3-01:M3-

2nd Fl Center Hall Functional Pass

Projected Beam Smoke Detectors

Functional

Pass/ Fail

1 08/12/22 01:M1-01:M1-

1st Fl East Beam Detector Functional Pass

2 08/12/22 01:M1-01:M1-

1st Fl West Beam Detector Functional Pass

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

1 08/12/22 01:M1-01:M1-

LL Tunnel Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

2 08/12/22 01:M1-01:M1-

LL Custodian Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

3 08/12/22 01:M1-01:M1-

LL Custodian Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

4 08/12/22 01:M1-01:M1-

LL Custodian Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

5 08/12/22 01:M1-01:M1-

LL Custodian Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

6 08/12/22 01:M1-01:M1-

LL Custodian Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

7 08/12/22 01:M1-01:M1-

LL Custodian Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

8 08/12/22 01:M1-01:M1-

LL Custodian Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

9 08/12/22 01:M1-01:M1-

LL Elevator Equipment Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

10 08/12/22 01:M1-01:M1-

LL Electrical Room: FACP Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

11 08/12/22 01:M1-01:M1-

LL Storage Room E46: Paper Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

12 08/12/22 01:M1-01:M1-

LL Storage Room E46 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

13 08/12/22 01:M1-01:M1-

LL Storage Room E46 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 15 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

14 08/12/22 01:M1-01:M1-

LL Storage Room E46 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

15 08/12/22 01:M1-01:M1-

LL Storage Room E46: Paper Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

16 08/12/22 01:M1-01:M1-

LL Probation File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

17 08/12/22 01:M1-01:M1-

LL Probation File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

18 08/12/22 01:M1-01:M1-

LL Probation Back Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

19 08/12/22 01:M1-01:M1-

LL Probation Juvenile Circuit Court 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

20 08/12/22 01:M1-01:M1-

LL Probation Managers Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

21 08/12/22 01:M1-01:M1-

LL Probation Office Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

22 08/12/22 01:M1-01:M1-

LL Probation Front Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

23 08/12/22 01:M1-01:M1-

LL East File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

24 08/12/22 01:M1-01:M1-

LL East Hall Ramp 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

25 08/12/22 01:M1-01:M1-

LL East Women's Restroom: Public 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

26 08/12/22 01:M1-01:M1-

LL East Men's Restroom: Public 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

27 08/12/22 01:M1-01:M1-

LL East I.T. Clsoet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

28 08/12/22 01:M1-01:M1-

LL Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

29 08/12/22 01:M1-01:M1-

LL Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

30 08/12/22 01:M1-01:M1-

LL Corporate Southeast Office Ramp 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

31 08/12/22 01:M1-01:M1-

LL Corporate Southeast Office Ramp 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

32 08/12/22 01:M1-01:M1-

LL Corporate Library 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

33 08/12/22 01:M1-01:M1-

LL Corporate Reception Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

34 08/12/22 01:M1-01:M1-

LL Corporate Center Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

35 08/12/22 01:M1-01:M1-

LL Corporate South Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

36 08/12/22 01:M1-01:M1-

LL Corporate File Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

37 08/12/22 01:M1-01:M1-

LL Corporate Clerks Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

38 08/12/22 01:M1-01:M1-

LL Corporate head Attorney Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

39 08/12/22 01:M1-01:M1-

LL Corporate Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

40 08/12/22 01:M1-01:M1-

LL Center Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

41 08/12/22 01:M1-01:M1-

LL Hall by Room LL13 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

42 08/12/22 01:M1-01:M1-

LL Hall by Room LL09 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

43 08/12/22 01:M1-01:M1-

LL Victim Witness Back Conference Room 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 16 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

44 08/12/22 01:M1-01:M1-

LL Victim Witness Back File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

45 08/12/22 01:M1-01:M1-

LL West IT Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

Comment: REMOVED TAPE

46 08/12/22 01:M1-01:M1-

LL Victim Witness Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

Comment: REMOVED TAPE

47 08/12/22 01:M1-01:M1-

LL Victim Witness Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

48 08/12/22 01:M1-01:M1-

LL Victim Witness Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

49 08/12/22 01:M1-01:M1-

LL Victim Witness File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

50 08/12/22 01:M1-01:M1-

LL Large File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

51 08/12/22 01:M1-01:M1-

LL Large File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

52 08/12/22 01:M1-01:M1-

LL Large File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

53 08/12/22 01:M1-01:M1-

LL Large File Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

54 08/12/22 01:M1-01:M1-

LL Jury Office Entrance/Waiting Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

55 08/12/22 01:M1-01:M1-

LL Jury Room Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

56 08/12/22 01:M1-01:M1- 065^1

LL Victim Witness Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

57 08/12/22 01:M1-01:M1- 065^2

LL Short Door Storage 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

58 08/12/22 01:M1-01:M1-

1st Fl Elevator Lobby 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

59 08/12/22 01:M1-01:M1-

LL Short Door Storage 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

60 08/12/22 01:M1-01:M1-

LL Center Hall by Stairs 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

61 08/12/22 01:M1-01:M1-

LL Hall by Room LL24 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

62 08/12/22 01:M1-01:M1-

LL Hall by Vending 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

63 08/12/22 01:M1-01:M1-

LL Mechanical Room: Gas/Water 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

64 08/12/22 01:M1-01:M1-

LL Custodian Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

65 08/12/22 01:M1-01:M1-

LL Mechanical Room: Gas/Water 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

66 08/12/22 01:M1-01:M1-

LL Mechanical Room: Gas/Water 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

67 08/12/22 01:M1-01:M1-

LL Mechanical Room: Gas/Water 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

68 08/12/22 01:M1-01:M1-

LL Mechanical Room: Gas/Water 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

69 08/12/22 01:M1-01:M1-

LL Jury Overflow Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

70 08/12/22 01:M1-01:M1-

LL Jury Overflow Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

71 08/12/22 01:M1-01:M1-

LL Jury Overflow Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

72 08/12/22 01:M1-01:M1-

LL Men's Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 17 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

73 08/12/22 01:M1-01:M1-

LL Jury Hall Between Rooms 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

74 08/12/22 01:M1-01:M1-

LL Womens Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

75 08/12/22 01:M1-01:M1-

LL Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

76 08/12/22 01:M1-01:M1-

LL Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

77 08/12/22 01:M1-01:M1-

LL Restraining Order Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

78 08/12/22 01:M1-01:M1-

LL Restraining Order Room: Storage 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

79 08/12/22 01:M1-01:M1-

LL Hall by Room LL36 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

80 08/12/22 01:M1-01:M1-

LL Victim Witness Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

81 08/12/22 01:M1-01:M1-

LL Victim Witness Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

82 08/12/22 01:M1-01:M1-

1st Fl North Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

83 08/12/22 01:M1-01:M1-

LL Elevator Lobby 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

84 08/12/22 01:M1-01:M1-

1st Fl East Emergency Exit 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

85 08/12/22 01:M1-01:M1-

1st Fl West Emergency Exit 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

Comment: REMOVED TAPE

86 08/12/22 01:M1-01:M1-

3rd Fl Elevator Lobby 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

87 08/12/22 01:M1-01:M1-

2nd Fl Elevator Lobby 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

88 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

89 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

90 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Judges Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

91 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

92 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Reporters Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

93 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

94 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

95 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Storage Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

96 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

97 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

98 08/12/22 01:M2-01:M2-

1st Fl Men's Public Restroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

99 08/12/22 01:M2-01:M2-

1st Fl Hall by Room 124 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

100 08/12/22 01:M2-01:M2-

1st Fl State Patrol 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

101 08/12/22 01:M2-01:M2-

1st Fl Middle Main Hall - Across from Custodian Closet 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 18 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

102 08/12/22 01:M2-01:M2-

1st Fl Hall by Room 116 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

103 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Center Door Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

104 08/12/22 01:M2-01:M2-

1st Fl Hall Near Room 120 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

105 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

106 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

107 08/12/22 01:M2-01:M2-

1st Fl Branch 2: Storage 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

108 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

109 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Judges Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

110 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

111 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

112 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Reporters Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

113 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

114 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

115 08/12/22 01:M2-01:M2-

2nd Fl NBR 8: Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

116 08/12/22 01:M2-01:M2-

2nd Fl Break Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

117 08/12/22 01:M2-01:M2-

2nd Fl Hall by Break Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

118 08/12/22 01:M2-01:M2-

2nd Fl Hall by Room 220 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

119 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Storage 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

120 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Jury Room Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

121 08/12/22 01:M2-01:M2-

2nd Fl Branch 7: Clerks Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

122 08/12/22 01:M2-01:M2-

2nd Fl Hall by Room 224 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

123 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

124 08/12/22 01:M2-01:M2-

2nd Fl Hall by Room 228 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

125 08/12/22 01:M2-01:M2-

2nd Fl Branch 6: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

126 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

127 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Judges Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

128 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

129 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

130 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Reporters Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

131 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 19 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

132 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

133 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

134 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

135 08/12/22 01:M2-01:M2-

3rd Fl Women's Restroom: Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

136 08/12/22 01:M2-01:M2-

3rd Fl Women's Restroom: Public 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

137 08/12/22 01:M2-01:M2-

3rd Fl Center Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

138 08/12/22 01:M2-01:M2-

3rd Fl Center Hall by Stairs 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

139 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Storage 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

140 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Center Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

141 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

142 08/12/22 01:M2-01:M2-

3rd Fl Branch 7: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

143 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

144 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Reporters Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

145 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Kitchenette 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

146 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Jury Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

147 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

148 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

149 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

150 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Judges Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

151 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Judges Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

152 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Back Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

153 08/12/22 01:M2-01:M2-

1st Fl Basement Stairwell to 3rd Floor 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

154 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

155 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

156 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

157 08/12/22 01:M2-01:M2-

1st Fl Custodian Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

158 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

159 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

160 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Clerks Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

161 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 20 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

162 08/12/22 01:M2-01:M2-

1st Fl Branch 4: Printer Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

163 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Judges Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

164 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Judges Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

165 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

166 08/12/22 01:M2-01:M2-

2ND FL 209 STORAGE SMOKE 1.5%-

3.7%

SIMPLEX/4098-

Functional Pass

167 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

168 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Clerks Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

169 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Reporters Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

170 08/12/22 01:M2-01:M2-

2nd Fl West Stairs 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

171 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Back Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

172 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Jury Room Stairs 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

173 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Hall to Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

174 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Kitchenette 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

175 08/12/22 01:M2-01:M2- 095^1

3rd Fl Branch 3: Hall to Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

176 08/12/22 01:M2-01:M2- 095^2

3rd Fl Branch 3: Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

177 08/12/22 01:M2-01:M2-

3rd Fl Branch 3: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

178 08/12/22 01:M2-01:M2-

3rd Fl Branch 3: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

179 08/12/22 01:M2-01:M2-

3rd Fl Hall to Roof 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

180 08/12/22 01:M2-01:M2-

3rd Fl Branch 3: To Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

181 08/12/22 01:M2-01:M2-

3rd Fl Room 317: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

182 08/12/22 01:M2-01:M2-

3rd Fl Room 317: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

183 08/12/22 01:M2-01:M2-

3rd Fl West Stairs 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

184 08/12/22 01:M2-01:M2-

3rd Fl Hall by Room 336 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

185 08/12/22 01:M2-01:M2-

3rd Fl Branch 3: Jury Room Stairs 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

186 08/12/22 01:M2-01:M2-

3rd Fl Hall by Room 332 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

187 08/12/22 01:M2-01:M2-

3rd Fl Hall by Room 328 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

188 08/12/22 01:M2-01:M2-

3rd Fl Center Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

189 08/12/22 01:M2-01:M2-

3rd Fl Custodian Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

190 08/12/22 01:M2-01:M2-

3rd Fl Atrium 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

191 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Courtroom - Northeast 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 21 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

192 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Courtroom - Southeast 1.5%- 3.7%

SIMPLEX/4098-

Visual Pass

Comment: UNABLE ABLE TO TEST DUE TO CEILING WORK

193 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Courtroom - Southwest 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

194 08/12/22 01:M2-01:M2-

2nd Fl Branch 3: Courtroom - Northwest 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

195 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Back Ramp to Bench 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

196 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Courtroom - Jury Box 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

197 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Courtroom - Center 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

198 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Courtroom - South 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

199 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Center Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

200 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

201 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Center Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

202 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Clerks Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

203 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

204 08/12/22 01:M3-01:M3-

1st Fl Women's Employee Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

205 08/12/22 01:M3-01:M3-

1st Fl Women's Employee Lounge 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

206 08/12/22 01:M3-01:M3-

1st Fl Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

207 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

208 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

209 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

210 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Judges Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

211 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

212 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Judges Office Hall 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

213 08/12/22 01:M3-01:M3-

1st Fl Branch 5: Judges Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

214 08/12/22 01:M3-01:M3-

2nd Fl Room 204: East Work Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

215 08/12/22 01:M3-01:M3-

2nd Fl Room 204: East Work Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

216 08/12/22 01:M3-01:M3-

2nd Fl Hall by Room 200 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

217 08/12/22 01:M3-01:M3-

2nd Fl Hall by Room 204 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

218 08/12/22 01:M3-01:M3-

2nd Fl Hall by Room 208 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

219 08/12/22 01:M3-01:M3-

2nd Fl Room 204: Kitchenette 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

220 08/12/22 01:M3-01:M3-

2nd Fl Room 204: Finance Office 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 22 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

221 08/12/22 01:M3-01:M3-

2nd Fl Room 204: West Work Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

222 08/12/22 01:M3-01:M3-

2nd Fl Room 204: Finance Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

223 08/12/22 01:M3-01:M3-

2nd Fl Room 204: Public Access Waiting Area 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

224 08/12/22 01:M3-01:M3-

2nd Fl Room 204: Payment Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

225 08/12/22 01:M3-01:M3-

2nd Fl Room 204: Copy Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

226 08/12/22 01:M3-01:M3-

2nd Fl Room 204: Supply Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

227 08/12/22 01:M3-01:M3-

2nd Fl Room 204: COC Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

228 08/12/22 01:M3-01:M3-

2nd Fl Room 204: COC Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

229 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

230 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

231 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Judges Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

232 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Jury Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

233 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Hall to Jury Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

234 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Hall to Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

235 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Reporters Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

236 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

237 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

238 08/12/22 01:M3-01:M3-

3rd Fl Upper Atrium 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

239 08/12/22 01:M3-01:M3-

3rd Fl Upper Atrium 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

240 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

241 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Courtroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

242 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Conference Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

243 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Jury Room Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

244 08/12/22 01:M3-01:M3-

3rd Fl Branch 1: Clerks Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

245 08/12/22 01:M3-01:M3-

3rd Fl Judges Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

246 08/12/22 01:M3-01:M3-

1st Fl Conference Room 115 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

247 08/12/22 01:M3-01:M3-

1st Fl Family Court: Community Officer 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

248 08/12/22 01:M3-01:M3-

1st Fl Conference Room 123 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

249 08/12/22 01:M3-01:M3-

1st Fl Court Services Manager: Room 120 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

250 08/12/22 01:M3-01:M3-

1st Fl Clerk of Courts: Room 119 1.5%- 3.7%

SIMPLEX/4098-

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 23 of 26

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

Comment: LOCATED IN 109

251 08/12/22 01:M3-01:M3-

1st Fl Room 109: Shredding Room 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

252 08/12/22 01:M3-01:M3-

1st Fl Room 109: Vault 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

253 08/12/22 01:M3-01:M3-

1st Fl E121: Custodian Closet 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

254 08/12/22 01:M3-01:M3-

1st Fl Coutroom 109: Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

255 08/12/22 01:M3-01:M3-

1st Fl Room 109: Financial Office 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

256 08/12/22 01:M3-01:M3-

1st Fl Clerk of Courts: Room 119 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

Comment: LOCATED IN 109

257 08/12/22 01:M3-01:M3-

1st Fl Conference Room 121 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

Comment: LOCATED IN 109

258 08/12/22 01:M3-01:M3-

1st Fl Clerk of Courts: Room 119 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

259 08/12/22 01:M3-01:M3-

1st Fl Hall by Room 109 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

260 08/12/22 01:M3-01:M3-

1st Fl Hall by Room 105 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

261 08/12/22 01:M3-01:M3-

1st Fl Hall by Room 101 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

262 08/12/22 01:M3-01:M3-

1st Fl Family Court: Bathroom 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

263 08/12/22 01:M3-01:M3-

1st Fl Room 109: Middle Entrance 1.5%- 3.7%

SIMPLEX/4098-

Functional Pass

264 08/12/22 01:M3-01:M3-

1st…