This document is an NFPA 72 fire alarm system inspection and testing report for Kenosha County, Wisconsin, detailing the results of comprehensive testing performed on the alarm system at the Kenosha County Admin Building located at 1010 56th Street, Kenosha, Wisconsin 53140. The inspection and testing was conducted by Siemens Industry, Inc. on August 10, 2022, beginning at 5:45 a.m. and completing at 10:45 a.m. The system consists of a Simplex 4100ES fire alarm control panel located in the lower level electrical room, supplemented by two notification appliance power extender panels (NAC-01 and NAC-02), both utilizing sealed lead acid batteries manufactured in April 2019. The system was tested to verify compliance with NFPA 72 standards and includes 4 heat detectors, 14 manual pull stations, and 13 system smoke detectors, all of which functioned properly with the exception of one strobe-only device in the lower level Register of Deeds Northeast Conference Room.
All primary and secondary power systems, control unit components, initiating devices, remote relays, and supervising station monitoring functioned as designed during the inspection, with battery backup providing 24 hours of standby capacity and 10 to 15 minutes of alarm mode operation. Testing included functional verification of all notification appliances, smoke detector sensitivity testing using the Fire Alarm Control Panel, and confirmation of alarm signal transmission and reception through the monitoring organization, Alarm Detection Service. The inspection was completed and documented by Siemens technicians Stanley Laitinen (License #SL#150654) and Alexander Hanus (License #AH#148912), with acceptance of the test report signed by Rhonda Haidinger on behalf of Kenosha County on August 10, 2022. The owner assumes responsibility for correcting the identified deficiency with the failed strobe device and for ongoing system maintenance in accordance with applicable codes and standards.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFPA 72 REPORT
© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 8
SYSTEM RECORD OF INSPECTION AND TESTING
System Name: ADMIN 4100ES Panel Name: 01 - ADMIN 4100ES
Inspection/Test Start Date/Time: 10 Aug 2022 0545 Inspection/Test Completion Date/Time: 10 Aug 2022 1045
Contract Info: Kenosha County 2022 (2600149454) Notification Number: 5102270780
Supplemental Form(s) Attached: Yes
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY ADMIN BUILDING (4433-53140-00026)
Address: 1010 56TH ST. KENOSHA, WI. 53140
Description of property:
Name of property representative: KENOSHA COUNTY (30078447), None
Address: 1010 56TH ST, KENOSHA, WI 53140-3738
Phone: None Fax: None E-mail: None
2. TESTING AND MONITORING INFORMATION
Testing organization: SIEMENS
Address: 6737 West Washington Street, Suite 2110, Milwaukee, WI 53215
Phone: 414-475-3700 Fax: NA E-mail: NA
Monitoring organization: ALARM DETECTION SERVICE
Address: NA
Phone: NA Fax: NA E-mail: NA
Account number: NA Phone line 1: NA Phone line 2: NA
Means of transmission: Digital
Entity to which alarms are retransmitted: NA Phone: NA
3. DOCUMENTATION
On-site location of the required record documents and site-specific software:
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
System Name: ADMIN 4100ES Panel Name: 01 - ADMIN 4100ES
Panel Location and Address: LL ELECTRICAL ROOM, 1010 56TH ST., KENOSHA, WI. 53140
Manufacturer: SIMPLEX Model number: 4100ES
4.2 Software and Firmware
Firmware revision number:
4.3 System Power
4.3.1 Primary (Main) Power
Nominal voltage: 120 Amps: 20 Location: LL ELECTRICAL ROOM
Overcurrent protection type: BREAKER Amps: 20
Disconnecting means location: LL ELECTRICAL ROOM ACROSS FROM FACP
4.3.2 Secondary Power
Type: Storage Battery Location: LL ELECTRICAL ROOM
Battery type (if applicable): Sealed Lead Acid Manufactured Date: 22 Feb 2019
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24 In alarm mode (minutes): 15
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 8
4.4 Notification Appliance Power Extender Panels
4.4.1 Primary Power
ID Location Input Volts
Panel Amps
Over-current Type
Over-current Amps
Primary Supply Location
Disconnect Location
01:NAC-01 LL ELECTRICAL BY
FACP
120 FUSED
DISCONNECT
SWITCH
20AMP LL ELECTRICAL RM
ACROSS
MARKED FIRE
ALARM
01:NAC-02 LL ELECTRICAL BY
FACP
120 FUSED
DISCONNECT
SWITCH
20AMP LL ELECTRICAL RM
ACROSS
MARKED FIRE
ALARM
4.4.2 Secondary Power
ID Location Battery Type
Manufactured Date
Voltage Rating
Amp Rating
Standby Hours
Alarm Minutes
01:NAC-01 LL ELECTRICAL BY FACP SLA 2019-04-30 12/12 7AH 24 10
01:NAC-02 LL ELECTRICAL BY FACP SLA 2019-04-30 12/12 7AH 24 10
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: CALLED BY RHONDA HAIDINGER Time: 0600
Building management Contact: RHONDA HAIDINGER Time: 0600
Building occupants Contact: BY RHONDA HAIDINGER Time: 0600
Authority having jurisdiction (AHJ) Contact: Time:
Other, if required Contact: NA Time: NA
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection or Functional Test Comments
Control unit Functional None
Disconnect switches Functional None
Fuses Functional None
Ground-fault monitoring Functional None
Interface Equipment Functional None
Lamps/LEDs/LCDs Functional None
Local annunciator Functional None
Primary Power Functional None
Remote annunciators Functional None
Remote power panels Functional None
Supervision Functional None
Trouble signals Functional None
6.2 Secondary Power
Description Visual Inspection or Functional Test Comments
Battery condition Functional (2) 35AH BATTERIES
Charger test Functional 27.59
Discharge test Functional 100%/100%
Load voltage Functional 13.72/13.85
Remote panel batteries Not Tested N/A
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 8
6.3 Notification Appliance Power Extender Panels Secondary Power
ID Location Battery Voltage
Battery Amps
Test Method
Pass/ Fail
01:NAC-01 LL ELECTRICAL BY FACP 13.75/13.70 100%/100% Functional Pass
01:NAC-02 LL ELECTRICAL BY FACP 13.77/13.75 100%/100% Functional Pass
6.4 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
6.5 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.6 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
6.7 Supervising Station Monitoring
Description Received Time / Elapsed
Time Pass/Fail Comments
Alarm signal Yes NA / NA Pass VERIFIED BY MONITORING THRU RHONDA HAIDINGER
Alarm restoration Yes NA / NA Pass VERIFIED BY MONITORING THRU RHONDA HAIDINGER
Trouble signal Yes NA / NA Pass VERIFIED BY MONITORING THRU RHONDA HAIDINGER
Trouble restoration Yes NA / NA VERIFIED BY MONITORING THRU RHONDA HAIDINGER
Supervisory signal No NA / NA None
Supervisory restoration No NA / NA None
6.8 Public Emergency Alarm Reporting System
Description Yes No Time Comments
Alarm signal NA NA
Alarm restoration NA NA
Trouble signal NA NA
Trouble restoration NA NA
Supervisory signal NA NA
Supervisory restoration NA NA
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: CALLED BY RHONDA HAIDINGER Time: 1130
Building management Contact: RHONDA HAIDINGER Time: 1130
Building occupants Contact: BY RHONDA HAIDINGER Time: 1130
Authority having jurisdiction (AHJ) Contact: Time:
Other, if required Contact: NA Time: NA
8. SYSTEM RESTORED TO NORMAL OPERATION
Date: 10 Aug 2022 Time: 1045
9. CERTIFICATION
This Testing Was Performed in Accordance with Applicable NFPA Standards.
Signed:
Alexander Hanus Date: 08/10/2022
Printed name: STANLEY LAITINEN,ALEXANDER HANUS Title: Technician License No.: SL#150654 AH#148912
Organization: SIEMENS Phone: 414-475-3700
Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service
10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 8
1) STROBE ONLY – LL REGISTOR OF DEEDS N.E. CONFERENCE ROOM. MAKE: SIMPLEX, MODEL: 4906-9101
11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE
The undersigned accepted the test report for the system as specified herein:
Signed:
Printed name: RHONDA HAIDINGER Date:
Organization: KENOSHA COUNTY (30078447) Phone: None
Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements.
Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.
12. OTHER
12.1 Special Procedures
12.2 Comments
DEVICE LOCATIONS ON REPORT REFLECT ACCURATE AND MOST IDENTIFIABLE DECRIPTIONS. COMMENTS FOR THE
DEVICES, IF NOTED, REFLECT DESCRIPTIONS AS THEY REPORT TO THE PANEL.
ALL SMOKE DETECTORS PASSED SENSITIVITY TESTING.
*Reviewed the sensitivity of the Analog Smoke/Duct detectors with use of Fire Alarm Control Panel whereby the detector causes a signal at the control panel when its sensitivity is outside its listed sensitivity range.
NFPA 72-2016 14.4.3.2-17 (h)(4) states that *Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside it listed sensitivity range*
08/15/22
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 8
NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY ADMIN BUILDING (4433-53140-00026)
Address: 1010 56TH ST. KENOSHA, WI. 53140
2. NOTIFICATION APPLIANCE TEST RESULTS
2.1 Notification Appliances Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
NO DEVICE
LISTING OR
COUNTS
AVAILABLE.
100% 100% 1
2.2 Notification Appliances Testing Results by Type
ALL NOTIFICATION DEVICES WERE FUCNTIONALLY TESTED AND PASSED WITH EXCEPTION TO THE LISTED BELOW
FAILURES:
1) STROBE ONLY – LL REGISTOR OF DEEDS N.E. CONFERENCE ROOM. MAKE: SIMPLEX, MODEL: 4906-9101
See main System Record of Inspection and Testing for additional information, certifications, and approvals.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 8
INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY ADMIN BUILDING (4433-53140-00026)
Address: 1010 56TH ST. KENOSHA, WI. 53140
2. INITIATING DEVICE TEST RESULTS
2.1 Initiating Devices Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
4 4 100% 0 0% 0 0% Heat Detectors
14 14 100% 0 0% 0 0% Manual Pull Stations
13 13 100% 0 0% 0 0% System Smoke Detectors (P)
2.2 Initiating Devices Testing Results by Type
Heat Detectors
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
1 08/10/22 01:M1-003 LL Elevator Equipment Room L14 Functional Pass
Comment: PANEL SHOWS: LL L14
2 08/10/22 01:M1-009 LL Elevator Equipment Room #2 L27 Functional Pass
3 08/10/22 01:M1-037 3rd Fl Elevator 1 Top of Shaft Functional Pass
4 08/10/22 01:M1-042 3rd Fl Elevator 2 Top of Shaft Functional Pass
Manual Pull Stations
Functional
Pass/ Fail
1 08/10/22 01:M1-001 LL Lobby By Stairs Functional Pass
Comment: PANEL SHOWS: LL LOBBY L11
2 08/10/22 01:M1-008 LL Stair 5 Functional Pass
3 08/10/22 01:M1-013 LL Mechanical Room L33 Functional Pass
4 08/10/22 01:M1-014 LL Map Area L38 Functional Pass
5 08/10/22 01:M1-018 1st Fl Lobby by Elevator 1 Functional Pass
6 08/10/22 01:M1-020 1st Fl Lobby by Vestibule Main Entrance Functional Pass
Comment: PANEL SHOWS: 1ST FL LOBBY 112 NEAR VESTIBULE 111
7 08/10/22 01:M1-022 1st Fl Mailroom Room 125 Functional Pass
Comment: PANEL SHOWS: 1ST MAIL 125 PULL
8 08/10/22 01:M1-023 1st Fl Clerical 103 Stair 1 Functional Pass
9 08/10/22 01:M1-027 2nd Fl Elevator #1 Lobby Functional Pass
10 08/10/22 01:M1-029 2nd FL Elevator #2 Lobby Functional Pass
Comment: PANEL SHOWS: 2ND BREAK RM 218
11 08/10/22 01:M1-031 2nd Fl Office Area 202 Stair 1 Functional Pass
12 08/10/22 01:M1-035 3rd Fl Elevator #2 Lobby Functional Pass
Comment: PANEL SHOWS: 3RD FL ELEVATOR LOBBY 310 PULL
13 08/10/22 01:M1-039 3rd FL Elevator #2 Lobby Functional Pass
Comment: PANEL SHOWS: 3RD FL WAITING 322 PULL
14 08/10/22 01:M1-043 3rd Fl Hallway by Stair 1 Functional Pass
Comment: PANEL SHOWS: COORIDOR 302 BY STAIR 1
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 8
System Smoke Detectors (P)
Row Date Dev.# Location Factory Setting
Model Visual/ Functional
Pass/ Fail
1 08/10/22 01:M1-002 LL Elevator #1 Lobby 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: LL LOBBY L09
2 08/10/22 01:M1-004 LL Elevator Equipment Room #1 L14 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: LL L14 SMOKE
3 08/10/22 01:M1-005 LL Above FACP 1.5%- 3.7%
SIMPLEX 4098-
Functional Pass
4 08/10/22 01:M1-007 LL Elevator 2 Lobby 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: LL L25 SMOKE
5 08/10/22 01:M1-010 LL Elevator Equipment Room #2 L27 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
6 08/10/22 01:M1-019 1st Fl Elevator #1 Lobby 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: 1ST FL LOBBY 112 SMOKE
7 08/10/22 01:M1-021 1st Fl Rear Elevator #2 Lobby 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: 1ST MAIL 125 SMOKE
8 08/10/22 01:M1-028 2nd Fl Elevator #1 Lobby 209 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
9 08/10/22 01:M1-030 2nd FL Elevator #2 Lobby 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: 2ND FL BREAK RM 218 SMOKE
10 08/10/22 01:M1-036 3rd Fl Elevator 1 Lobby: Top of Shaft 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
11 08/10/22 01:M1-038 3rd Fl Elevator #1 Lobby 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: 3RD FL ELEVATOR LOBBY 310 SMOKE
12 08/10/22 01:M1-040 3rd Fl Rear Elevator #2 Lobby 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
Comment: PANEL SHOWS: 3RD FL WAITING 322 SMOKE
13 08/10/22 01:M1-041 3rd Fl Elevator 2 Top of Shaft 1.5%- 3.59%
SIMPLEX/2098-
Functional Pass
See main System Record of Inspection and Testing for additional information, certifications, and approvals.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 8 of 8
INTERFACE COMPONENT SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY ADMIN BUILDING (4433-53140-00026)
Address: 1010 56TH ST. KENOSHA, WI. 53140
2. INTERFACE COMPONENT TEST RESULTS
2.1 Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
6 6 100% 0 0% 0 0% Remote Relays
2.2 Equipment Testing Results by Type
Remote Relays
Functional
Pass/ Fail
1 08/10/22 01:M1-005^1 LL ELEVATOR #1 PRIMARY Functional Pass
2 08/10/22 01:M1-006^1 LL ELEVATOR #1 ALTERNATE Functional Pass
3 08/10/22 01:M1-011 LL ELEVATOR #2 PRIMARY Functional Pass
4 08/10/22 01:M1-012 LL ELEVATOR #2 ALTERNATE Functional Pass
5 08/10/22 01:M2-003 LL ELECTRICAL NAC-01 TROUBLE Functional Pass
6 08/10/22 01:M2-004 LL ELECTRICAL NAC-02 TROUBLE Functional Pass
2.3 Additional Equipment Testing Results
Interface Component Type Address Location Test Results
See main System Record of Inspection and Testing for additional information, certifications, and approvals.