2202 Alarm Inpection Job Center.pdf
PDF 224 KB Posted
- Solicitation number
- 2202
- Issued by
- Kenosha County, Kellnersville Village, Wisconsin
About this file
This is an NFPA 72 System Record of Inspection and Testing report for fire alarm and detection equipment at the Kenosha County Job Center located at 8600 Sheridan Road, Kenosha, Wisconsin. The inspection was conducted by Siemens Industry, Inc. on July 14, 2022, from 4:00 p.m. to 11:30 p.m., and covered the Edwards EST 2 fire alarm control panel designated as "01 - EST 3" located in the first-floor maintenance shop. The system includes five Notification Appliance Power Extender Panels distributed across electrical closets and rooms throughout the facility, with secondary battery backup systems providing 24-hour standby capacity and 10-minute alarm mode operation. The inspection and testing included 28 manual pull stations, 26 system smoke detectors, 3 duct smoke detectors, and 1 heat detector, with 27 of 28 manual pull stations functionally tested and all tested devices passing inspection.
All primary control unit components, secondary power systems, notification appliances, and supervising station monitoring functions passed functional testing on July 14, 2022. However, one deficiency was identified: the elevator did not shunt when equipment room heat was tripped, although elevator recall functionality otherwise passed testing. All smoke detectors passed sensitivity testing in accordance with NFPA 72 2016 standards. The system was restored to normal operation on July 14, 2022 at 11:30 p.m. Testing notifications were provided to the monitoring organization (ADS), building management (Patty Bilski), and building occupants prior to and upon completion of inspection. The report was certified by Siemens technicians Stanley Laitinen and James Kayler on July 15, 2022, and accepted by Patty Bilski on behalf of Kenosha County on July 18, 2022.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFPA 72 REPORT
© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 7
SYSTEM RECORD OF INSPECTION AND TESTING
System Name: JOB CENTER Panel Name: 01 - EST 3
Inspection/Test Start Date/Time: 14 Jul 2022 1600 Inspection/Test Completion Date/Time: 14 Jul 2022 2330
Contract Info: Kenosha County 2022 (2600149454) Notification Number: 5102270782
Supplemental Form(s) Attached: Yes
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY JOB CENTER (4433-53143-00002)
Address: 8600 SHERIDAN ROAD, KENOSHA WI.
Description of property: OFFICES
Name of property representative: KENOSHA COUNTY (30078447)
Address: 1010 56TH ST, KENOSHA, WI 53140-3738
Phone: None Fax: None E-mail: None
2. TESTING AND MONITORING INFORMATION
Testing organization: SIEMENS
Address: 6737 West Washington Street, Suite 2110, Milwaukee, WI 53215
Phone: 414-475-3700 Fax: NA E-mail: NA
Monitoring organization: ADS
Address: NA
Phone: 1-262-658-4499 Fax: NA E-mail: NA
Account number: 8600 KENOSHA ROAD Phone line 1: NA Phone line 2: NA
Means of transmission: None
Entity to which alarms are retransmitted: NA Phone: NA
3. DOCUMENTATION
On-site location of the required record documents and site-specific software:
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
System Name: JOB CENTER Panel Name: 01 - EST 3
Panel Location and Address: 1ST FLOOR MAINTENANCE SHOP, 8600 SHERIDAN ROAD, KENOSHA WI 53143
Manufacturer: EDWARDS Model number: EST 2
4.2 Software and Firmware
Firmware revision number:
4.3 System Power
4.3.1 Primary (Main) Power
Nominal voltage: Amps: Location: 1ST FLOOR MAINTENANCE SHOP
Overcurrent protection type: Amps:
Disconnecting means location:
4.3.2 Secondary Power
Type: Storage Battery Location: 1ST FLOOR MAINTENANCE SHOP
Battery type (if applicable): Sealed Lead Acid Manufactured Date: 28 Feb 2021
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24 In alarm mode (minutes): 10
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 7
4.4 Notification Appliance Power Extender Panels
4.4.1 Primary Power
ID Location Input Volts
Panel Amps
Over-current Type
Over-current Amps
Primary Supply Location
Disconnect Location
01:01-01:NP-001 1st Fl Child Care Electrical Closet
120 BREAKER
01:01-01:NP-002 1st Fl East Electrical Room 120 BREAKER
01:01-01:NP-003 1st Fl Electrical Room by Elevator
120 BREAKER
01:01-01:NP-004 1st Fl Mechanical Room 120 BREAKER
01:01-01:NP-005 1st Fl Southwest Electrical Room
120 BREAKER
4.4.2 Secondary Power
ID Location Battery Type
Manufactured Date
Voltage Rating
Amp Rating
Standby Hours
Alarm Minutes
01:01-01:NP-001 1st Fl Child Care Electrical Closet SLA 2018-08-30 12/12
VDC
24 10
01:01-01:NP-002 1st Fl East Electrical Room SLA 2018-08-30 12/12
VDC
24 10
01:01-01:NP-003 1st Fl Electrical Room by Elevator SLA 2018-08-30 12/12
VDC
24 10
01:01-01:NP-004 1st Fl Mechanical Room SLA 2018-08-30 12/12
VDC
24 10
01:01-01:NP-005 1st Fl Southwest Electrical Room SLA 2018-08-30 12/12
VDC
24 10
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: CYNTHIA Time: 0400
Building management Contact: PATTY BILSKI Time: 0400
Building occupants Contact: BY PATTY BILSKI Time: PRIOR TO
INSPECTION
Authority having jurisdiction (AHJ) Contact: Time:
Other, if required Contact: NA Time: NA
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection or Functional Test Comments
Control unit Functional None
Disconnect switches Functional None
Fuses Functional None
Ground-fault monitoring Functional None
Interface Equipment Functional None
Lamps/LEDs/LCDs Functional None
Local annunciator Functional None
Primary Power Functional None
Remote annunciators Functional None
Remote power panels Functional None
Supervision Functional None
Trouble signals Functional None
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 7
6.2 Secondary Power
Description Visual Inspection or Functional Test Comments
Battery condition Functional (2) 12 AH BATTERIES
Charger test Functional 27.26
Discharge test Functional 100%/100%
Load voltage Functional 13.77/13.81
Remote panel batteries Functional None
6.3 Notification Appliance Power Extender Panels Secondary Power
ID Location Battery Voltage
Battery Amps
Test Method
Pass/ Fail
01:01-01:NP-001 1st Fl Child Care Electrical Closet 13.24 /13.21
80%/80% Functional Pass
01:01-01:NP-002 1st Fl East Electrical Room 13.24/13.22 80%/80% Functional Pass
01:01-01:NP-003 1st Fl Electrical Room by Elevator 13.29/13.21 80%/80% Functional Pass
01:01-01:NP-004 1st Fl Mechanical Room 13.23/13.24 80%/80% Functional Pass
01:01-01:NP-005 1st Fl Southwest Electrical Room 13.18/13.27 80%/80% Functional Pass
6.4 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
6.5 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.6 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
6.7 Supervising Station Monitoring
Description Received Time / Elapsed
Time Pass/Fail Comments
Alarm signal Yes NA / NA Pass None
Alarm restoration Yes NA / NA Pass None
Trouble signal Yes NA / NA Pass None
Trouble restoration Yes NA / NA Pass None
Supervisory signal Yes NA / NA Pass None
Supervisory restoration Yes NA / NA Pass None
6.8 Public Emergency Alarm Reporting System
Description Yes No Time Comments
Alarm signal NA NA
Alarm restoration NA NA
Trouble signal NA NA
Trouble restoration NA NA
Supervisory signal NA NA
Supervisory restoration NA NA
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: LEANNA Time: 2300
Building management Contact: MATHEW Time: 2300
Building occupants Contact: BY MATHEW Time: 2300
Authority having jurisdiction (AHJ) Contact: Time:
Other, if required Contact: NA Time: NA
8. SYSTEM RESTORED TO NORMAL OPERATION
Date: 14 Jul 2022 Time: 2330
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 7
9. CERTIFICATION
This Testing Was Performed in Accordance with Applicable NFPA Standards.
Signed: Stanley Laitinen Date: 7-15-2022
Printed name: STANLEY LAITINEN,JAMES KAYLER Title: Technician License No.: SL#150654
Organization: SIEMENS Phone: 414-475-3700
Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service
10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED
ELEVATOR DID NOT SHUNT WHEN EQUIPMENT ROOM HEAT WAS TRIPPED.
11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE
The undersigned accepted the test report for the system as specified herein:
Signed: Printed name: PATTY BILSKI Date:
Organization: KENOSHA COUNTY (30078447) Phone: None
Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements. Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.
12. OTHER
12.1 Special Procedures
12.2 Comments
Reviewed the sensitivity of the Analog Smoke/Duct detectors with use of Fire Alarm Control Panel whereby the detector causes a signal at the control panel when its sensitivity is outside its listed sensitivity range. (NFPA 72 2016 Ver. Para 10.4.4.2.4.(4) ) (NFPA 72 1999 Ver. Para 7.3.2.1 (4) )
ALL SMOKE DETECTORS PASSED SENSITIVITY TESTING.
ELEVATOR RECALL PASSED FUNCTIONAL TESTING, ALTHOUGH ELEVATOR DID NOT SHUNT WHEN THE EQUIPMENT
ROOM HEAT WAS TRIPPED.
NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY JOB CENTER (4433-53143-00002)
Address: 8600 SHERIDAN ROAD, KENOSHA WI.
Patty Bilski 7/18/22
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 7
2. NOTIFICATION APPLIANCE TEST RESULTS
2.1 Notification Appliances Equipment Summary by Type
Total Qty
NO DEVICE
TYPE
SUMMARY
LISTING
AVAILABLE
Functionally Tested Qty
Functionally Tested %
100%
Visually Tested
Qty
Visually Tested %
Failed Qty
Failed % Device or System Type
2.2 Notification Appliances Testing Results by Type
ALL NOTIFICATION DEVICES PASSED FUNCTIONAL TESTING.
See main System Record of Inspection and Testing for additional information, certifications, and approvals.
INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
1. PROPERTY INFORMATION
Name of property: KENOSHA COUNTY JOB CENTER (4433-53143-00002)
Address: 8600 SHERIDAN ROAD, KENOSHA WI.
2. INITIATING DEVICE TEST RESULTS
2.1 Initiating Devices Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
3 2 66.6% 0 0% 0 0% Duct Smoke Detectors (P)
1 1 100% 0 0% 0 0% Heat Detectors
21 21 100% 0 0% 0 0% Manual Pull Stations
28 27 96.43% 0 0% 0 0% System Smoke Detectors (P)
The following device points exist in panel but were not on points list supplied from previous inspection. This explains the difference in total quantity and tested quantity of smoke detectors/duct detectors.. Unable to locate.
01:D1-028 2nd Fl Elevator Equipment Room Smoke Detector.-Not Tested, Unable to locate.
01:D1-029 2nd Fl Elevator Equipment Room Duct Detector.-Not Tested, Unable to locate.
2.2 Initiating Devices Testing Results by Type
Duct Smoke Detectors (P)
Row Date Dev.# Location Visual/ Functional
Pass/ Fail
1 07/14/22 01-01:D1-144 2nd Fl East Mechanical Room Functional Pass
2 07/14/22 01-01:D1-145 2nd Fl West Mechanical Room Functional Pass
Heat Detectors
Functional
Pass/ Fail
1 07/14/22 01-01:D1-027 2nd Fl Elevator Equipment Room Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 7
Manual Pull Stations
Functional
Pass/ Fail
1 07/14/22 01-01:D1-127 1st Fl North 2 Conference Room Exit Functional Pass
2 07/14/22 01-01:D1-128 1st Fl Main Entrance North Functional Pass
3 07/14/22 01-01:D1-129 1st Fl Child Care NW Door Functional Pass
4 07/14/22 01-01:D1-130 1st Fl Child Care East Door Functional Pass
5 07/14/22 01-01:D1-131 1st Fl Child Care SW Door Functional Pass
6 07/14/22 01-01:D1-132 1st Fl Main Entrance East Functional Pass
7 07/14/22 01-01:D1-133 1st Fl Director Area NE Door Functional Pass
8 07/14/22 01-01:D1-134 1st Fl Director Area SE Door Functional Pass
9 07/14/22 01-01:D1-135 1st Fl Health Service South Door Functional Pass
10 07/14/22 01-01:D1-136 2nd Fl East Stairwell Functional Pass
11 07/14/22 01-01:D1-137 1st Fl South West Door Functional Pass
12 07/14/22 01-01:D1-138 1st Fl West SW Door Functional Pass
13 07/14/22 01-01:D1-139 1st Fl West NW Door Functional Pass
14 07/14/22 01-01:D1-140 1st Fl NW Door by Maintenance Functional Pass
15 07/14/22 01-01:D1-141 1st Fl North Elevator Lobby Functional Pass
16 07/14/22 01-01:D1-142 1st Fl South Elevator Lobby Functional Pass
17 07/14/22 01-01:D1-143 2nd Fl Elevator Lobby Functional Pass
18 07/14/22 01-01:D1-160 2nd Fl South Exit Functional Pass
19 07/14/22 01-01:D1-161 2nd Fl Center Exit Functional Pass
20 07/14/22 01-01:D1-162 2nd Fl North Exit Functional Pass
21 07/14/22 01-01:D1-163 1st Fl South East Exit Functional Pass
System Smoke Detectors (P)
Functional
Pass/ Fail
1 07/14/22 01-01:D1-001 1st Fl By Fire Alarm Panel Functional Pass
2 07/14/22 01-01:D1-002 1st Fl Child Care NW Functional Pass
3 07/14/22 01-01:D1-003 1st Fl Child Care Infant Room Functional Pass
4 07/14/22 01-01:D1-004 1st Fl Child Care Men's Rest Rm N Functional Pass
5 07/14/22 01-01:D1-005 1st Fl Child Care Women's Rest Rm NE Functional Pass
6 07/14/22 01-01:D1-006 1st Fl Child Care Kitchen Functional Pass
7 07/14/22 01-01:D1-007 1st Fl Child Care Toddler Room Functional Pass
8 07/14/22 01-01:D1-008 1st Fl Child Care Main Area East Functional Pass
9 07/14/22 01-01:D1-009 1st Fl Child Care Eating Area Functional Pass
10 07/14/22 01-01:D1-010 1st Fl Child Care Center Office East Functional Pass
11 07/14/22 01-01:D1-011 1st Fl Child Care Center Office West Functional Pass
12 07/14/22 01-01:D1-012 1st Fl Child Care Aarea By Toddler Room Functional Pass
13 07/14/22 01-01:D1-013 1st Fl Child Area Main Area NW Functional Pass
14 07/14/22 01-01:D1-014 1st Fl Child Area Main Area SW Functional Pass
15 07/14/22 01-01:D1-015 1st Fl Child Care by Reception Functional Pass
16 07/14/22 01-01:D1-016 1st Fl Child Care Office South Functional Pass
17 07/14/22 01-01:D1-017 1st Fl Child Care SE Exit Functional Pass
18 07/14/22 01-01:D1-018 1st Fl Child Care Electrical Closet SE Functional Pass
19 07/14/22 01-01:D1-019 1st Fl Electrical Room East Functional Pass
20 07/14/22 01-01:D1-020 1st Fl Health Service Electrical Closet Functional Pass
21 07/14/22 01-01:D1-021 1st Fl SW Electrical Closet Functional Pass
22 07/14/22 01-01:D1-022 2nd Fl Storage Room Above NAC Functional Pass
23 07/14/22 01-01:D1-023 1st Fl South Elevator Lobby Functional Pass
24 07/14/22 01-01:D1-024 1st Fl North Elevator Lobby Functional Pass
25 07/14/22 01-01:D1-025 2nd Fl Elevator Lobby Functional Pass
26 07/14/22 01-01:D1-026 2nd Fl Elevator Equipment Room Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 7