2202 Alarm Inpection Job Center.pdf

PDF 224 KB Posted

Attached to
KENOSHA COUNTY RFB #2202 COUNTYWIDE FIRE INSPECTION
Solicitation number
2202
Issued by
Kenosha County, Kellnersville Village, Wisconsin

About this file

This is an NFPA 72 System Record of Inspection and Testing report for fire alarm and detection equipment at the Kenosha County Job Center located at 8600 Sheridan Road, Kenosha, Wisconsin. The inspection was conducted by Siemens Industry, Inc. on July 14, 2022, from 4:00 p.m. to 11:30 p.m., and covered the Edwards EST 2 fire alarm control panel designated as "01 - EST 3" located in the first-floor maintenance shop. The system includes five Notification Appliance Power Extender Panels distributed across electrical closets and rooms throughout the facility, with secondary battery backup systems providing 24-hour standby capacity and 10-minute alarm mode operation. The inspection and testing included 28 manual pull stations, 26 system smoke detectors, 3 duct smoke detectors, and 1 heat detector, with 27 of 28 manual pull stations functionally tested and all tested devices passing inspection.

All primary control unit components, secondary power systems, notification appliances, and supervising station monitoring functions passed functional testing on July 14, 2022. However, one deficiency was identified: the elevator did not shunt when equipment room heat was tripped, although elevator recall functionality otherwise passed testing. All smoke detectors passed sensitivity testing in accordance with NFPA 72 2016 standards. The system was restored to normal operation on July 14, 2022 at 11:30 p.m. Testing notifications were provided to the monitoring organization (ADS), building management (Patty Bilski), and building occupants prior to and upon completion of inspection. The report was certified by Siemens technicians Stanley Laitinen and James Kayler on July 15, 2022, and accepted by Patty Bilski on behalf of Kenosha County on July 18, 2022.

View the file

Other files

File Type Posted
2202D Kitchen hoods.pdf PDF
2202 PSB suppression.pdf PDF
2202 Brookside suppression 2.pdf PDF
2202 Alarm Inspection Brighton Dale Links.pdf PDF
2202 Alarm Inspection Courthouse.pdf PDF
2202 Alarm Inspection Parking Ramp.pdf PDF
2202 KCDC suppression.pdf PDF
2202 Pets suppression.pdf PDF
2202 Alarm Inspection Admin Bldg.pdf PDF
2202 KCJC ext.pdf PDF
2202 Alarm Inspection Public Safety Bldg.pdf PDF
2202 KCAB ext.pdf PDF
2202 PSB suppression 2.pdf PDF
2202 Alarm Inspection KCDC.pdf PDF
2202 Alarm Inspection Kemper.pdf PDF
2202 Addendum 3.pdf PDF
2202 Addendum 1.pdf PDF
2202 Alarm Inspection Pre-Trail Bldg.pdf PDF
2202D Offer Form.xlsx XLSX spreadsheet
2202B Sprinklers, Hydrants, Backflow preventers.pdf PDF
2202A2 Offer Form.xlsx XLSX spreadsheet
2202 Pets ext 2.pdf PDF
2202 KCDC ext.pdf PDF
2202 Courthouse ext.pdf PDF
Vendor Responsibility Form.pdf PDF
2202A Fire extinguishers hoses.pdf PDF
2202 Fire Inspection Bid.pdf PDF
2202 KCC ext.pdf PDF
2202C Offer Form.xlsx XLSX spreadsheet
2202 Brookside suppression.pdf PDF
2202 Pets ext.pdf PDF
2202C Alarm panels inc elevator shafts.pdf PDF
2202 Alarm Inspection Fleet Maintenance.pdf PDF
2202B Offer Form.xlsx XLSX spreadsheet
2202 Alarm Inspection Brookside.pdf PDF
2202 PT ext.pdf PDF
2202 PSB ext.pdf PDF
2202 Alarm Inspection KCDC E Storage Bldg.pdf PDF
2202 Alarm Inspection Kenosha County Center.pdf PDF
2202A Offer Form.xlsx XLSX spreadsheet
2202 Addendum 2.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NFPA 72 REPORT

© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 7

SYSTEM RECORD OF INSPECTION AND TESTING

System Name: JOB CENTER Panel Name: 01 - EST 3

Inspection/Test Start Date/Time: 14 Jul 2022 1600 Inspection/Test Completion Date/Time: 14 Jul 2022 2330

Contract Info: Kenosha County 2022 (2600149454) Notification Number: 5102270782

Supplemental Form(s) Attached: Yes

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY JOB CENTER (4433-53143-00002)

Address: 8600 SHERIDAN ROAD, KENOSHA WI.

Description of property: OFFICES

Name of property representative: KENOSHA COUNTY (30078447)

Address: 1010 56TH ST, KENOSHA, WI 53140-3738

Phone: None Fax: None E-mail: None

2. TESTING AND MONITORING INFORMATION

Testing organization: SIEMENS

Address: 6737 West Washington Street, Suite 2110, Milwaukee, WI 53215

Phone: 414-475-3700 Fax: NA E-mail: NA

Monitoring organization: ADS

Address: NA

Phone: 1-262-658-4499 Fax: NA E-mail: NA

Account number: 8600 KENOSHA ROAD Phone line 1: NA Phone line 2: NA

Means of transmission: None

Entity to which alarms are retransmitted: NA Phone: NA

3. DOCUMENTATION

On-site location of the required record documents and site-specific software:

4. DESCRIPTION OF SYSTEM OR SERVICE

4.1 Control Unit

System Name: JOB CENTER Panel Name: 01 - EST 3

Panel Location and Address: 1ST FLOOR MAINTENANCE SHOP, 8600 SHERIDAN ROAD, KENOSHA WI 53143

Manufacturer: EDWARDS Model number: EST 2

4.2 Software and Firmware

Firmware revision number:

4.3 System Power

4.3.1 Primary (Main) Power

Nominal voltage: Amps: Location: 1ST FLOOR MAINTENANCE SHOP

Overcurrent protection type: Amps:

Disconnecting means location:

4.3.2 Secondary Power

Type: Storage Battery Location: 1ST FLOOR MAINTENANCE SHOP

Battery type (if applicable): Sealed Lead Acid Manufactured Date: 28 Feb 2021

Calculated capacity of batteries to drive the system:

In standby mode (hours): 24 In alarm mode (minutes): 10

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 7

4.4 Notification Appliance Power Extender Panels

4.4.1 Primary Power

ID Location Input Volts

Panel Amps

Over-current Type

Over-current Amps

Primary Supply Location

Disconnect Location

01:01-01:NP-001 1st Fl Child Care Electrical Closet

120 BREAKER

01:01-01:NP-002 1st Fl East Electrical Room 120 BREAKER

01:01-01:NP-003 1st Fl Electrical Room by Elevator

120 BREAKER

01:01-01:NP-004 1st Fl Mechanical Room 120 BREAKER

01:01-01:NP-005 1st Fl Southwest Electrical Room

120 BREAKER

4.4.2 Secondary Power

ID Location Battery Type

Manufactured Date

Voltage Rating

Amp Rating

Standby Hours

Alarm Minutes

01:01-01:NP-001 1st Fl Child Care Electrical Closet SLA 2018-08-30 12/12

VDC

24 10

01:01-01:NP-002 1st Fl East Electrical Room SLA 2018-08-30 12/12

VDC

24 10

01:01-01:NP-003 1st Fl Electrical Room by Elevator SLA 2018-08-30 12/12

VDC

24 10

01:01-01:NP-004 1st Fl Mechanical Room SLA 2018-08-30 12/12

VDC

24 10

01:01-01:NP-005 1st Fl Southwest Electrical Room SLA 2018-08-30 12/12

VDC

24 10

5. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: CYNTHIA Time: 0400

Building management Contact: PATTY BILSKI Time: 0400

Building occupants Contact: BY PATTY BILSKI Time: PRIOR TO

INSPECTION

Authority having jurisdiction (AHJ) Contact: Time:

Other, if required Contact: NA Time: NA

6. TESTING RESULTS

6.1 Control Unit and Related Equipment

Description Visual Inspection or Functional Test Comments

Control unit Functional None

Disconnect switches Functional None

Fuses Functional None

Ground-fault monitoring Functional None

Interface Equipment Functional None

Lamps/LEDs/LCDs Functional None

Local annunciator Functional None

Primary Power Functional None

Remote annunciators Functional None

Remote power panels Functional None

Supervision Functional None

Trouble signals Functional None

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 7

6.2 Secondary Power

Description Visual Inspection or Functional Test Comments

Battery condition Functional (2) 12 AH BATTERIES

Charger test Functional 27.26

Discharge test Functional 100%/100%

Load voltage Functional 13.77/13.81

Remote panel batteries Functional None

6.3 Notification Appliance Power Extender Panels Secondary Power

ID Location Battery Voltage

Battery Amps

Test Method

Pass/ Fail

01:01-01:NP-001 1st Fl Child Care Electrical Closet 13.24 /13.21

80%/80% Functional Pass

01:01-01:NP-002 1st Fl East Electrical Room 13.24/13.22 80%/80% Functional Pass

01:01-01:NP-003 1st Fl Electrical Room by Elevator 13.29/13.21 80%/80% Functional Pass

01:01-01:NP-004 1st Fl Mechanical Room 13.23/13.24 80%/80% Functional Pass

01:01-01:NP-005 1st Fl Southwest Electrical Room 13.18/13.27 80%/80% Functional Pass

6.4 Alarm and Supervisory Alarm Initiating Device

Attach supplementary device test sheets for all initiating devices.

6.5 Notification Appliances

Attach supplementary appliance test sheets for all notification appliances.

6.6 Interface Equipment

Attach supplementary interface component test sheets for all interface components.

6.7 Supervising Station Monitoring

Description Received Time / Elapsed

Time Pass/Fail Comments

Alarm signal Yes NA / NA Pass None

Alarm restoration Yes NA / NA Pass None

Trouble signal Yes NA / NA Pass None

Trouble restoration Yes NA / NA Pass None

Supervisory signal Yes NA / NA Pass None

Supervisory restoration Yes NA / NA Pass None

6.8 Public Emergency Alarm Reporting System

Description Yes No Time Comments

Alarm signal NA NA

Alarm restoration NA NA

Trouble signal NA NA

Trouble restoration NA NA

Supervisory signal NA NA

Supervisory restoration NA NA

7. NOTIFICATIONS THAT TESTING IS COMPLETE

Monitoring organization Contact: LEANNA Time: 2300

Building management Contact: MATHEW Time: 2300

Building occupants Contact: BY MATHEW Time: 2300

Authority having jurisdiction (AHJ) Contact: Time:

Other, if required Contact: NA Time: NA

8. SYSTEM RESTORED TO NORMAL OPERATION

Date: 14 Jul 2022 Time: 2330

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 7

9. CERTIFICATION

This Testing Was Performed in Accordance with Applicable NFPA Standards.

Signed: Stanley Laitinen Date: 7-15-2022

Printed name: STANLEY LAITINEN,JAMES KAYLER Title: Technician License No.: SL#150654

Organization: SIEMENS Phone: 414-475-3700

Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service

10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED

ELEVATOR DID NOT SHUNT WHEN EQUIPMENT ROOM HEAT WAS TRIPPED.

11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE

The undersigned accepted the test report for the system as specified herein:

Signed: Printed name: PATTY BILSKI Date:

Organization: KENOSHA COUNTY (30078447) Phone: None

Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements. Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.

12. OTHER

12.1 Special Procedures

12.2 Comments

Reviewed the sensitivity of the Analog Smoke/Duct detectors with use of Fire Alarm Control Panel whereby the detector causes a signal at the control panel when its sensitivity is outside its listed sensitivity range. (NFPA 72 2016 Ver. Para 10.4.4.2.4.(4) ) (NFPA 72 1999 Ver. Para 7.3.2.1 (4) )

ALL SMOKE DETECTORS PASSED SENSITIVITY TESTING.

ELEVATOR RECALL PASSED FUNCTIONAL TESTING, ALTHOUGH ELEVATOR DID NOT SHUNT WHEN THE EQUIPMENT

ROOM HEAT WAS TRIPPED.

NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY JOB CENTER (4433-53143-00002)

Address: 8600 SHERIDAN ROAD, KENOSHA WI.

Patty Bilski 7/18/22

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 7

2. NOTIFICATION APPLIANCE TEST RESULTS

2.1 Notification Appliances Equipment Summary by Type

Total Qty

NO DEVICE

TYPE

SUMMARY

LISTING

AVAILABLE

Functionally Tested Qty

Functionally Tested %

100%

Visually Tested

Qty

Visually Tested %

Failed Qty

Failed % Device or System Type

2.2 Notification Appliances Testing Results by Type

ALL NOTIFICATION DEVICES PASSED FUNCTIONAL TESTING.

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY JOB CENTER (4433-53143-00002)

Address: 8600 SHERIDAN ROAD, KENOSHA WI.

2. INITIATING DEVICE TEST RESULTS

2.1 Initiating Devices Equipment Summary by Type

Total Qty Functionally Tested Qty

Functionally Tested %

Visually Tested

Qty

Visually Tested %

Failed Qty Failed % Device or System Type

3 2 66.6% 0 0% 0 0% Duct Smoke Detectors (P)

1 1 100% 0 0% 0 0% Heat Detectors

21 21 100% 0 0% 0 0% Manual Pull Stations

28 27 96.43% 0 0% 0 0% System Smoke Detectors (P)

The following device points exist in panel but were not on points list supplied from previous inspection. This explains the difference in total quantity and tested quantity of smoke detectors/duct detectors.. Unable to locate.

01:D1-028 2nd Fl Elevator Equipment Room Smoke Detector.-Not Tested, Unable to locate.

01:D1-029 2nd Fl Elevator Equipment Room Duct Detector.-Not Tested, Unable to locate.

2.2 Initiating Devices Testing Results by Type

Duct Smoke Detectors (P)

Row Date Dev.# Location Visual/ Functional

Pass/ Fail

1 07/14/22 01-01:D1-144 2nd Fl East Mechanical Room Functional Pass

2 07/14/22 01-01:D1-145 2nd Fl West Mechanical Room Functional Pass

Heat Detectors

Functional

Pass/ Fail

1 07/14/22 01-01:D1-027 2nd Fl Elevator Equipment Room Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 7

Manual Pull Stations

Functional

Pass/ Fail

1 07/14/22 01-01:D1-127 1st Fl North 2 Conference Room Exit Functional Pass

2 07/14/22 01-01:D1-128 1st Fl Main Entrance North Functional Pass

3 07/14/22 01-01:D1-129 1st Fl Child Care NW Door Functional Pass

4 07/14/22 01-01:D1-130 1st Fl Child Care East Door Functional Pass

5 07/14/22 01-01:D1-131 1st Fl Child Care SW Door Functional Pass

6 07/14/22 01-01:D1-132 1st Fl Main Entrance East Functional Pass

7 07/14/22 01-01:D1-133 1st Fl Director Area NE Door Functional Pass

8 07/14/22 01-01:D1-134 1st Fl Director Area SE Door Functional Pass

9 07/14/22 01-01:D1-135 1st Fl Health Service South Door Functional Pass

10 07/14/22 01-01:D1-136 2nd Fl East Stairwell Functional Pass

11 07/14/22 01-01:D1-137 1st Fl South West Door Functional Pass

12 07/14/22 01-01:D1-138 1st Fl West SW Door Functional Pass

13 07/14/22 01-01:D1-139 1st Fl West NW Door Functional Pass

14 07/14/22 01-01:D1-140 1st Fl NW Door by Maintenance Functional Pass

15 07/14/22 01-01:D1-141 1st Fl North Elevator Lobby Functional Pass

16 07/14/22 01-01:D1-142 1st Fl South Elevator Lobby Functional Pass

17 07/14/22 01-01:D1-143 2nd Fl Elevator Lobby Functional Pass

18 07/14/22 01-01:D1-160 2nd Fl South Exit Functional Pass

19 07/14/22 01-01:D1-161 2nd Fl Center Exit Functional Pass

20 07/14/22 01-01:D1-162 2nd Fl North Exit Functional Pass

21 07/14/22 01-01:D1-163 1st Fl South East Exit Functional Pass

System Smoke Detectors (P)

Functional

Pass/ Fail

1 07/14/22 01-01:D1-001 1st Fl By Fire Alarm Panel Functional Pass

2 07/14/22 01-01:D1-002 1st Fl Child Care NW Functional Pass

3 07/14/22 01-01:D1-003 1st Fl Child Care Infant Room Functional Pass

4 07/14/22 01-01:D1-004 1st Fl Child Care Men's Rest Rm N Functional Pass

5 07/14/22 01-01:D1-005 1st Fl Child Care Women's Rest Rm NE Functional Pass

6 07/14/22 01-01:D1-006 1st Fl Child Care Kitchen Functional Pass

7 07/14/22 01-01:D1-007 1st Fl Child Care Toddler Room Functional Pass

8 07/14/22 01-01:D1-008 1st Fl Child Care Main Area East Functional Pass

9 07/14/22 01-01:D1-009 1st Fl Child Care Eating Area Functional Pass

10 07/14/22 01-01:D1-010 1st Fl Child Care Center Office East Functional Pass

11 07/14/22 01-01:D1-011 1st Fl Child Care Center Office West Functional Pass

12 07/14/22 01-01:D1-012 1st Fl Child Care Aarea By Toddler Room Functional Pass

13 07/14/22 01-01:D1-013 1st Fl Child Area Main Area NW Functional Pass

14 07/14/22 01-01:D1-014 1st Fl Child Area Main Area SW Functional Pass

15 07/14/22 01-01:D1-015 1st Fl Child Care by Reception Functional Pass

16 07/14/22 01-01:D1-016 1st Fl Child Care Office South Functional Pass

17 07/14/22 01-01:D1-017 1st Fl Child Care SE Exit Functional Pass

18 07/14/22 01-01:D1-018 1st Fl Child Care Electrical Closet SE Functional Pass

19 07/14/22 01-01:D1-019 1st Fl Electrical Room East Functional Pass

20 07/14/22 01-01:D1-020 1st Fl Health Service Electrical Closet Functional Pass

21 07/14/22 01-01:D1-021 1st Fl SW Electrical Closet Functional Pass

22 07/14/22 01-01:D1-022 2nd Fl Storage Room Above NAC Functional Pass

23 07/14/22 01-01:D1-023 1st Fl South Elevator Lobby Functional Pass

24 07/14/22 01-01:D1-024 1st Fl North Elevator Lobby Functional Pass

25 07/14/22 01-01:D1-025 2nd Fl Elevator Lobby Functional Pass

26 07/14/22 01-01:D1-026 2nd Fl Elevator Equipment Room Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 7