2202 Alarm Inspection Parking Ramp.pdf

PDF 242 KB Posted

Attached to
KENOSHA COUNTY RFB #2202 COUNTYWIDE FIRE INSPECTION
Solicitation number
2202
Issued by
Kenosha County, Kellnersville Village, Wisconsin

About this file

This is an NFPA 72 System Record of Inspection and Testing Report for Kenosha County, Wisconsin, documenting the alarm inspection and testing of the fire alarm system installed at the Kenosha County Park & Ride facility located at 920 54th Street, Kenosha, Wisconsin. The inspection and testing was conducted by Siemens Industry, Inc., Smart Infrastructure Division on August 10, 2022, beginning at 12:00 PM and completing at 1:30 PM. The system under inspection is a Simplex 4010 fire alarm control panel (FACP) located in the parking garage elevator lobby. The testing included functional and visual inspections of the control unit, secondary power systems, notification appliance power extender panels, initiating devices, and interface equipment. All tested components passed inspection, including three heat detectors on floors one through three, one system smoke detector located above the FACP in the elevator equipment room, and three remote relay interface components for elevator recall functions. The system is powered by a 120-volt, 20-amp primary power supply with a sealed lead acid battery backup (manufactured April 30, 2019) providing 24 hours of standby capacity and 15 minutes of alarm mode capacity.

The inspection was performed by certified technicians Stanley Laitinen (License No. SL#150654) and Alexander Hanus (License No. AH#148912) in accordance with applicable NFPA standards. Notifications of the testing were made to building management, building occupants, and the monitoring organization (Alarm Detection Service) prior to and upon completion of testing. The smoke detector sensitivity testing passed in accordance with NFPA 72-2016 standards, and elevator recall functionality operated properly. The system was restored to normal operation at 1:30 PM on August 10, 2022. Acceptance of the test report was signed by Kenosha County representative Rhonda Haidinger on August 15, 2022. No equipment failures were identified during inspection or testing. The property owner is responsible for proper maintenance and care of the system, and Siemens retains the right to report any code deficiencies to the local Authority Having Jurisdiction if corrective actions are not completed within required timeframes.

View the file

Other files

File Type Posted
2202D Kitchen hoods.pdf PDF
2202 PSB suppression.pdf PDF
2202 Brookside suppression 2.pdf PDF
2202 Alarm Inspection Brighton Dale Links.pdf PDF
2202 Alarm Inspection Courthouse.pdf PDF
2202 KCDC suppression.pdf PDF
2202 Pets suppression.pdf PDF
2202 Alarm Inspection Admin Bldg.pdf PDF
2202 KCJC ext.pdf PDF
2202 Alarm Inspection Public Safety Bldg.pdf PDF
2202 KCAB ext.pdf PDF
2202 PSB suppression 2.pdf PDF
2202 Alarm Inspection KCDC.pdf PDF
2202 Alarm Inspection Kemper.pdf PDF
2202 Addendum 3.pdf PDF
2202 Addendum 1.pdf PDF
2202 Alarm Inspection Pre-Trail Bldg.pdf PDF
2202D Offer Form.xlsx XLSX spreadsheet
2202B Sprinklers, Hydrants, Backflow preventers.pdf PDF
2202A2 Offer Form.xlsx XLSX spreadsheet
2202 Pets ext 2.pdf PDF
2202 KCDC ext.pdf PDF
2202 Courthouse ext.pdf PDF
Vendor Responsibility Form.pdf PDF
2202A Fire extinguishers hoses.pdf PDF
2202 Fire Inspection Bid.pdf PDF
2202 KCC ext.pdf PDF
2202C Offer Form.xlsx XLSX spreadsheet
2202 Brookside suppression.pdf PDF
2202 Pets ext.pdf PDF
2202C Alarm panels inc elevator shafts.pdf PDF
2202 Alarm Inspection Fleet Maintenance.pdf PDF
2202B Offer Form.xlsx XLSX spreadsheet
2202 Alarm Inspection Brookside.pdf PDF
2202 PT ext.pdf PDF
2202 Alarm Inpection Job Center.pdf PDF
2202 PSB ext.pdf PDF
2202 Alarm Inspection KCDC E Storage Bldg.pdf PDF
2202 Alarm Inspection Kenosha County Center.pdf PDF
2202A Offer Form.xlsx XLSX spreadsheet
2202 Addendum 2.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NFPA 72 REPORT

© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 7

SYSTEM RECORD OF INSPECTION AND TESTING

System Name: KENOSHA PARK & RIDE Panel Name: 01 - PARK & RIDE 4010

Inspection/Test Start Date/Time: 10 Aug 2022 1200 Inspection/Test Completion Date/Time: 10 Aug 2022 1330

Contract Info: Kenosha County 2022 (2600149454) Notification Number: 5102270779

Supplemental Form(s) Attached: Yes

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY PARK RIDE (4433-53140-00023)

Address: 920 54TH ST. KENOSHA, WI. 53140

Description of property:

Name of property representative: KENOSHA COUNTY (30078447), None

Address: 1010 56TH ST, KENOSHA, WI 53140-3738

Phone: None Fax: None E-mail: None

2. TESTING AND MONITORING INFORMATION

Testing organization: SIEMENS

Address: 6737 West Washington Street, Suite 2110, Milwaukee, WI 53215

Phone: 414-475-3700 Fax: NA E-mail: NA

Monitoring organization: ALARM DETECTION SERVICE

Address: NA

Phone: NA Fax: NA E-mail: NA

Account number: NA Phone line 1: NA Phone line 2: NA

Means of transmission: Digital

Entity to which alarms are retransmitted: NA Phone: NA

3. DOCUMENTATION

On-site location of the required record documents and site-specific software:

4. DESCRIPTION OF SYSTEM OR SERVICE

4.1 Control Unit

System Name: KENOSHA PARK & RIDE Panel Name: 01 - PARK & RIDE 4010

Panel Location and Address: PARKING GARAGE ELEVATOR LOBBY, 920 54TH ST., KENOSHA WI. 53140

Manufacturer: SIMPLEX Model number: 4010

4.2 Software and Firmware

Firmware revision number:

4.3 System Power

4.3.1 Primary (Main) Power

Nominal voltage: 120 Amps: 20 Location: PARKING GARAGE ELEVATOR LOBBY

Overcurrent protection type: BREAKER Amps: 20

Disconnecting means location: UNKNOWN

4.3.2 Secondary Power

Type: Storage Battery Location: PARKING GARAGE ELEVATOR LOBBY

Battery type (if applicable): Sealed Lead Acid Manufactured Date: 30 Apr 2019

Calculated capacity of batteries to drive the system:

In standby mode (hours): 24 In alarm mode (minutes): 15

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 7

4.4 Notification Appliance Power Extender Panels

4.4.1 Primary Power

ID Location Input Volts

Panel Amps

Over-current Type

Over-current Amps

Primary Supply Location

Disconnect Location

01:DIALER-01 FL1 ELEV. EQUIPMENT

RM

UNKNOWN

4.4.2 Secondary Power

ID Location Battery Type

Manufactured Date

Voltage Rating

Amp Rating

Standby Hours

Alarm Minutes

01:DIALER-01 FL1 ELEV. EQUIPMENT RM 2018-08-11 12 8AH 24 10

5. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: CALLED BY RHONDA HAIDINGER Time: 1145

Building management Contact: RHONDA HAIDINGER Time: 1145

Building occupants Contact: BY RHONDA HAIDINGER Time: 1145

Authority having jurisdiction (AHJ) Contact: Time:

Other, if required Contact: NA Time: NA

6. TESTING RESULTS

6.1 Control Unit and Related Equipment

Description Visual Inspection or Functional Test Comments

Control unit Functional None

Disconnect switches Functional None

Fuses Functional None

Ground-fault monitoring Functional None

Interface Equipment Functional None

Lamps/LEDs/LCDs Functional None

Local annunciator Functional None

Primary Power Functional None

Remote annunciators Not Tested N/A

Remote power panels Not Tested None

Supervision Functional None

Trouble signals Functional None

6.2 Secondary Power

Description Visual Inspection or Functional Test Comments

Battery condition Functional (2) 7AH BATTERIES

Charger test Functional 27.24

Discharge test Functional 100%/100%

Load voltage Functional 13.68/13.64

Remote panel batteries Not Tested None

6.3 Notification Appliance Power Extender Panels Secondary Power

ID Location Battery Voltage

Battery Amps

Test Method

Pass/ Fail

01:DIALER-01 FL1 ELEV. EQUIPMENT RM 13.77 100% Functional Pass

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 7

6.4 Alarm and Supervisory Alarm Initiating Device

Attach supplementary device test sheets for all initiating devices.

6.5 Notification Appliances

Attach supplementary appliance test sheets for all notification appliances.

6.6 Interface Equipment

Attach supplementary interface component test sheets for all interface components.

6.7 Supervising Station Monitoring

Description Received Time / Elapsed

Time Pass/Fail Comments

Alarm signal Yes NA / NA Pass None

Alarm restoration Yes NA / NA Pass None

Trouble signal Yes NA / NA Pass None

Trouble restoration Yes NA / NA Pass None

Supervisory signal No NA / NA None

Supervisory restoration No NA / NA None

6.8 Public Emergency Alarm Reporting System

Description Yes No Time Comments

Alarm signal NA NA

Alarm restoration NA NA

Trouble signal NA NA

Trouble restoration NA NA

Supervisory signal NA NA

Supervisory restoration NA NA

7. NOTIFICATIONS THAT TESTING IS COMPLETE

Monitoring organization Contact: CALLED BY RHONDA HAIDINGER Time: 1330

Building management Contact: RHONDA HAIDINGER Time: 1330

Building occupants Contact: BY RHONDA HAIDINGER Time: 1330

Authority having jurisdiction (AHJ) Contact: Time:

Other, if required Contact: NA Time: NA

8. SYSTEM RESTORED TO NORMAL OPERATION

Date: 10 Aug 2022 Time: 1330

9. CERTIFICATION

This Testing Was Performed in Accordance with Applicable NFPA Standards.

Signed:

Alexander Hanus Date: 08/10/2022

Printed name: STANLEY LAITINEN,ALEXANDER HANUS Title: Technician License No.: SL#150654 AH#148912

Organization: SIEMENS Phone: 414-475-3700

Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service

10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED

11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE

The undersigned accepted the test report for the system as specified herein:

Signed:

Printed name: RHONDA HAIDINGER Date:

Organization: KENOSHA COUNTY (30078447) Phone: None

08/15/22

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 7

Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements.

Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.

12. OTHER

12.1 Special Procedures

12.2 Comments

SMOKE DETECTOR PASSED SENSITIVITY TESTING.

*Reviewed the sensitivity of the Analog Smoke/Duct detectors with use of Fire Alarm Control Panel whereby the detector causes a signal at the control panel when its sensitivity is outside its listed sensitivity range.

NFPA 72-2016 14.4.3.2-17 (h)(4) states that *Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside it listed sensitivity range*

ELEVATOR RECALL FUNCTIONED PROPERLY.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 7

NOTIFICATION APPLIANCE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY PARK RIDE (4433-53140-00023)

Address: 920 54TH ST. KENOSHA, WI. 53140

2. NOTIFICATION APPLIANCE TEST RESULTS

2.1 Notification Appliances Equipment Summary by Type

Total Qty Functionally Tested Qty

Functionally Tested %

Visually Tested

Qty

Visually Tested %

Failed Qty Failed % Device or System Type

THERE ARE

NO

NOTIFICATION

DEVICES ON

THIS SYSTEM.

N/A N/A N/A N/A N/A N/A N/A

2.2 Notification Appliances Testing Results by Type

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 7

INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY PARK RIDE (4433-53140-00023)

Address: 920 54TH ST. KENOSHA, WI. 53140

2. INITIATING DEVICE TEST RESULTS

2.1 Initiating Devices Equipment Summary by Type

Total Qty Functionally Tested Qty

Functionally Tested %

Visually Tested

Qty

Visually Tested %

Failed Qty Failed % Device or System Type

3 3 100% 0 0% 0 0% Heat Detectors

1 1 100% 0 0% 0 0% System Smoke Detectors (P)

2.2 Initiating Devices Testing Results by Type

Heat Detectors

Row Date Dev.# Location Model Visual/ Functional

Pass/ Fail

1 08/10/22 01:M1-004 FL1 PARKING GARAGE ELEV. LOBBY SIMPLEX Functional Pass

2 08/10/22 01:M1-005 FL2 PARKING GARAGE ELEV. LOBBY SIMPLEX Functional Pass

3 08/10/22 01:M1-006 FL3 PARKING GARAGE ELEV. LOBBY SIMPLEX Functional Pass

System Smoke Detectors (P)

Row Date Dev.# Location Factory Setting

Model Visual/ Functional

Pass/ Fail

1 08/10/22 01:M1-007 ABOVE FACP - ELEVATOR EQUIPMENT RM 1.5-3.7 SIMPLEX

4098-9757

Functional Pass

See main System Record of Inspection and Testing for additional information, certifications, and approvals.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 7

INTERFACE COMPONENT SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

1. PROPERTY INFORMATION

Name of property: KENOSHA COUNTY PARK RIDE (4433-53140-00023)

Address: 920 54TH ST. KENOSHA, WI. 53140

2. INTERFACE COMPONENT TEST RESULTS

2.1 Equipment Summary by Type

Total Qty Functionally Tested Qty

Functionally Tested %

Visually Tested

Qty

Visually Tested %

Failed Qty Failed % Device or System Type

3 3 100% 0 0% 0 0% Remote Relays

2.2 Equipment Testing Results by Type

Remote Relays

Row Date Dev.# Location Model Visual/ Functional

Pass/ Fail

1 08/10/22 01:M1-001 FL1 ELEV. MECH RM PRIMARY RECALL SIMPLEX Functional Pass

2 08/10/22 01:M1-002 FL1 ELEV. MECH RM ALT RECALL SIMPLEX Functional Pass

3 08/10/22 01:M1-003 FL1 ELEV. MECH RM RED HAT SIMPLEX Functional Pass

2.3 Additional Equipment Testing Results

Interface Component Type Address Location Test Results

See main System Record of Inspection and Testing for additional information, certifications, and approvals.