2202A Fire extinguishers hoses.pdf

PDF 163 KB Posted

Attached to
KENOSHA COUNTY RFB #2202 COUNTYWIDE FIRE INSPECTION
Solicitation number
2202
Issued by
Kenosha County, Kellnersville Village, Wisconsin

About this file

This is a Request for Bid (RFB) document from Kenosha County, Wisconsin for Bid #2202, specifically for countywide fire inspection services covering fire extinguishers and hoses. The County seeks a vendor to provide comprehensive fire extinguisher services for all types of extinguishers located in County facilities, including structures, vehicles, and buildings. Required services include annual inspections, recharges, six- and 12-year maintenance checks, hydrostatic testing, repair, and replacement as needed, all in strict compliance with the latest NFPA standards. Additionally, the vendor must perform periodic inspections, tests, and maintenance on fire hoses at County facilities in accordance with NFPA standards for inspection, testing, and maintenance. The vendor is required to document and identify all fire extinguishers by facility and location, provide replacement extinguishers within 24 hours when units are removed for service, maintain at least 75 percent of extinguishers on premises at all times, and attach maintenance tags indicating inspection dates and company information. For fire hoses, the vendor must inspect hose stations, check hose condition and placement, exercise hoses, conduct hydrostatic testing as required, and perform physical and pressure testing in accordance with NFPA 1962 standards.

The document does not specify pricing terms, bid submission deadlines, contract award dates, or the contract term. No information is provided regarding set-asides, incumbent vendors, funding sources or amounts, or renewal options. The vendor is responsible for pickup and delivery of extinguishers at no additional charge or must conduct services on-site. The vendor must follow specific maintenance procedures, including a detailed recharge checklist for dry chemical extinguishers and must return all replaced defective parts to the County for inspection. Hydrostatic testing shall be performed every 12 years for dry chemical extinguishers and every five years for CO2 extinguishers, with testing intervals to follow NFPA 10 recommendations.

View the file

Other files

File Type Posted
2202D Kitchen hoods.pdf PDF
2202 PSB suppression.pdf PDF
2202 Brookside suppression 2.pdf PDF
2202 Alarm Inspection Brighton Dale Links.pdf PDF
2202 Alarm Inspection Courthouse.pdf PDF
2202 Alarm Inspection Parking Ramp.pdf PDF
2202 KCDC suppression.pdf PDF
2202 Pets suppression.pdf PDF
2202 Alarm Inspection Admin Bldg.pdf PDF
2202 KCJC ext.pdf PDF
2202 Alarm Inspection Public Safety Bldg.pdf PDF
2202 KCAB ext.pdf PDF
2202 PSB suppression 2.pdf PDF
2202 Alarm Inspection KCDC.pdf PDF
2202 Alarm Inspection Kemper.pdf PDF
2202 Addendum 3.pdf PDF
2202 Addendum 1.pdf PDF
2202 Alarm Inspection Pre-Trail Bldg.pdf PDF
2202D Offer Form.xlsx XLSX spreadsheet
2202B Sprinklers, Hydrants, Backflow preventers.pdf PDF
2202A2 Offer Form.xlsx XLSX spreadsheet
2202 Pets ext 2.pdf PDF
2202 KCDC ext.pdf PDF
2202 Courthouse ext.pdf PDF
Vendor Responsibility Form.pdf PDF
2202 Fire Inspection Bid.pdf PDF
2202 KCC ext.pdf PDF
2202C Offer Form.xlsx XLSX spreadsheet
2202 Brookside suppression.pdf PDF
2202 Pets ext.pdf PDF
2202C Alarm panels inc elevator shafts.pdf PDF
2202 Alarm Inspection Fleet Maintenance.pdf PDF
2202B Offer Form.xlsx XLSX spreadsheet
2202 Alarm Inspection Brookside.pdf PDF
2202 PT ext.pdf PDF
2202 Alarm Inpection Job Center.pdf PDF
2202 PSB ext.pdf PDF
2202 Alarm Inspection KCDC E Storage Bldg.pdf PDF
2202 Alarm Inspection Kenosha County Center.pdf PDF
2202A Offer Form.xlsx XLSX spreadsheet
2202 Addendum 2.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KENOSHA COUNTY BID #2202A

WISCONSIN PAGE 1 OF 4

COUNTY OF KENOSHA

REQUEST FOR BID (RFB) #2202

COUNTYWIDE FIRE INSPECTION –

2202A – FIRE EXTINGUISHERS & HOSES

FIRE EXTINGUISHER INSPECTION

Vendor shall be required to provide fire extinguisher services for all types of extinguishers in County facilities, including extinguishers used in structures, vehicles and buildings. The services, which include annual inspection, required recharges, six- and 12-year maintenance check, hydrostatic testing, repair, or replacement at the County’s discretion, are to be provided in strict conformance to the latest NFPA code.

Vendor Requirements

Vendor shall be required to:

• Document and identify all fire extinguishers. This shall include facility, location within the facility, fire extinguisher type, and advising the County of any needed additions.

• Provide a replacement, suitable for the type of hazard being protected and of equal or better rating, for any fire extinguisher removed from service for maintenance and/or recharge. Extinguisher(s) must be replaced within 24 hours.

Annual Inspection/Testing

• All extinguishers shall be subject to a maintenance inspection not more than one year apart or when specifically indicated in accordance with the latest NFPA Standard #10. All extinguishers shall be maintained in strict accordance with the name plate instructions.

• The annual maintenance inspection is intended to give maximum assurance that an extinguisher will operate effectively and safely.

• Each extinguisher shall have a tag securely attached that indicates the month and year that the maintenance inspection was performed and shall identify the company name, phone number and the name of the person performing the service. The County shall notify the vendor if weatherproof tags are required.

• Fire Extinguishers may be located in vehicles. Inspection of these extinguishers must be scheduled in advance with the County designee.

Inspections must verify

• Fire extinguisher information and location against records and develop a map of extinguishers if not available.

• Equipment is in the designated location and properly marked.

• Access to or visibility of fire extinguisher is not obstructed.

• Seals or tamper indicators are not broken. Fire extinguishers without seals or indicators should be lifted or weighted to determine if full.

• Fire extinguisher has not been physically damaged.

• Fire extinguisher does not have other obvious defects.

• The maintenance record tag is up to date.

Vendor shall:

WISCONSIN PAGE 2 OF 4

• Examine for physical damage.

• Check to assure pressure gauge is in proper range.

• Check wall hood or bracket for proper type, fit and that is secure.

• Brush and lubricate hose threads.

• Remove and inspect pull pin.

• Check for most recent hydrostatic test and maintenance dates.

• Check agent container for dents, abrasions and corrosion.

• Check weight and inspect expellant gas.

• Replace tamper seal in pull pin.

• Attach new maintenance tag.

• Check for proper DOT and HMIS labeling.

• Clean and wipe down equipment.

Six Year Maintenance Inspection

• Every six (6) years, stored pressure dry chemical extinguishers shall be emptied and subjected to the applicable maintenance procedures. At the time of this maintenance inspection, a NFPA approved identification collar that indicates the inspector, month and year the maintenance check was performed shall be securely attached to the extinguisher.

The vendor shall pick-up and deliver all extinguishers at no additional charge or services shall be conducted on site.

Recharging

• All extinguishers shall only be recharged after use or as indicated by an inspection. The recharging instructions on the name plate shall always be followed. The vendor shall pick-up and deliver all extinguishers at no additional charge or services shall be conducted on site.

• Only the materials specified on the nameplate or materials to have equal chemical composition and physical characteristics shall be used. No extinguisher shall be converted from one type to another, nor shall any extinguisher be converted to use a different type of extinguishing agent.

Vendor shall be responsible to:

• Return fire extinguishers being recharged within twenty-four (24) hours after removal or the vendor must provide loaded fire extinguisher coverage and return the original extinguisher within 24 hours.

• Allow the County to keep no less than 75% of fire extinguishers on the premises of each facility at all times or vendor must provide coverage of equal rating.

• Return fire extinguishers to the same location after completion of recharge or inspection/testing.

• When requested by the County it is recommended that the vendor provide on-site recharging services otherwise the vendor must provide a replacement extinguisher. The original extinguisher must be returned within 24 hours of being taken out of service.

• Advise the County if replacement parts are needed, and if so, what parts and cost.

• Record the date of inspection check and/or recharge and initial tag or label affixed to the fire extinguisher. Metal stamping will not be accepted.

• Repair and obtaining parts shall be at the County's discretion. If the County authorizes the vendor to repair, all replaced defective parts will be returned to the County for inspection.

WISCONSIN PAGE 3 OF 4

Recharge Checklist

• Vendors shall be required to follow the following checklist when completing recharges:

o Discharge remaining dry chemical from canister.

o Remove valve from canister.

o Remove valve stem, siphon tube and spring from valve body.

o Clean all parts along with valve body thoroughly removing all packed dry chemicals from vital areas.

o Refill canister with correct dry chemical.

o Examine "O" rings for wear and replace when necessary.

o Lubricate "O" rings, sealing surfaces and moving parts.

o Reassemble valve.

o Replace valve into canister and pressurize to correct operating pressure using moisture trap with nitrogen.

o Submerge entire canister into water to check for leaks.

o Replace nozzle or hose assembly, seal valve and tag fire extinguisher indicating date and type of fire extinguisher with durable plastic tag.

Hydrostatic Testing

• All hydrostatic testing shall be performed in accordance with the latest NFPA Standards.

This test will be performed every 12 years for dry chemical fire extinguishers and every five for CO2 extinguishers. The contractor shall pick-up and deliver all extinguishers at no additional charge or conduct services on site.

• Extinguishers shall be hydro-statically tested at intervals recommended by the current version of NFPA 10.

FIRE HOSE INSPECTION

• The vendor shall perform periodic inspections, tests, and maintenance to ensure fire hoses are in proper operating condition and shall correct any defects or impairments revealed.

Inspection, testing, and maintenance shall be at frequencies and in accordance with procedures meeting or exceeding those established in the latest NFPA standard for the inspection, testing, and maintenance for fire hoses and in accordance with the manufacturer’s instructions.

Inspection Services

• Record location of fire hose stations.

• Check date, location and length of hose at each station.

• Visually check hose for damage and make sure it is properly racked in cabinet and that the nozzle is attached.

• Rerack fire hose to prevent creases.

• Check condition of hose muzzle and make sure is it in the closed position.

• Exercise each hose.

• Inspect hose cabinet signs.

• Clean hose and cabinet of cobwebs, dust and debris.

• Inspect locks for functionally.

• Tag all inspected units and install new sated tamper seal.

• Report any problems and missing or damaged units to the County’s designee to the facility.

WISCONSIN PAGE 4 OF 4

• Perform hydrotest service when applicable.

Maintenance and Hydrotest Services

• Hydrotest of all fire hoses in the facilities must be performed as per NFPA 1962 2-5, Standard for the Care, Use, Inspection, Service Testing, and Replacement of Fire Hose, Couplings, Nozzles, and Fire Hose Appliances. Pricing for the three and five year hydrotest and after usage test shall include:

o Physical inspection shall determine that the hose, couplings and any nozzles have not been vandalized; are free of debris and exhibit no evidence of mildew, rot or damage by chemicals, burns, cuts, abrasion and vermin. If the hose fails the physical inspection, it shall be removed from service, repaired as necessary and service tested or condemned.

o Pressure test fire hose to check for structural weakness or flaws.

o Coupling Inspection, after each use and during each service test, visually inspect for the flowing: damaged threads, corrosion, slippage in the hose, out-of–round, swivel not rotating freely, missing lugs, loose external collar, internal gasket and other defects that impair operation.

o Nozzle Inspection, after each use and during each service test shall include verification of the following, nozzle valves attached to in-service hose is in the closed position, waterway clear of obstructions, no damage to tip, full operation of adjustments such as pattern selection and so forth, proper operation of shutoff valve if so equipped, no missing parts, thread gasket in good condition.