This document provides details for a federal contract opportunity with the FBI for continued Job Order Contract (JOC) services at Quantico, Virginia. The FBI requires JOC services to support construction, alteration, and repair projects at various FBI facilities in Quantico, including project management, planning, estimating, labor, transportation, materials, equipment, tools, supervision, design, and other associated tasks. The contract will have a one-year base period and four option periods for a total period of up to 60 months. The NAICS code is 236220 and the solicitation will be a 100% small business set-aside utilizing best value source selection. Interested small businesses must submit a completed VR 219 form by March 30, 2022 to be approved to attend an Industry Day on April 5, 2022 to learn more about the opportunity.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL STRUCTURAL NOTES:
A. GENERAL:
1. THE CONTRACTOR SHALL REVIEW ALL SUBMITTALS REQUIRED BY TEH SCOPE OF WORK BEFORE
THEY ARE PROVIDED TO THE OWNER AND STRUCTURAL ENGINEER. THE CONTRACTOR’S REVIEW
SHALL BE DOCUMENTED WITHIN THE SUBMITTAL. THE OWNER AND STRUCTURAL ENGINEER
RESERVE THE RIGHT TO REJECT SUBMITTALS THAT HAVE NOT BEEN FIRST REVIEWED BY THE
CONTRACTOR. THE ACCURACY AND COMPLETENESS OF THE SUBMITTALS IS THE SOLE
RESPONSIBILITY OF THE CONTRACTOR, INCLUDING ALL ERRORS AND OMISSIONS. IN ADDITION, THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL MEANS, METHODS, AND SEQUENCING OF
CONSTRUCTION.
2. THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL BE EXPERIENCED AND
QUALIFIED TO PERFORM THE TYPE OF CONSTRUCTION REQUIRED TO COMPLETE THE WORK
PRESCRIBED BY THE CONTRACT DOCUMENTS. IT IS THE GENERAL CONTRACTOR’S
RESPONSIBILITY TO COORDINATE ALL EXISTING ARCHITECTURAL, MECHANICAL, AND ELECTRICAL
ITEMS WITH THE PROVIDED DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR SHALL NOTIFY
THE OWNER AND ARCHITECT/ENGINEER IMMEDIATELY OF ANY CONFLICTS, OMISSIONS, OR
DISCREPANCIES. THIS COORDINATION SHALL BE PERFORMED BEFORE THE PROCUREMENT OF
MATERIALS AND/OR FABRICATION OF ANY PROJECT COMPONENTS.
3. WHERE SECTION IS SHOWN AND DETAILED, OTHER SECTIONS OF SIMILAR CONDITION SHALL BE
DETAILED THE SAME OR OPPOSITE HAND, WHETHER SPECIFICALLY NOTED OR NOT.
4. CONTRACTOR SHALL VERIFY EXISTING DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE
BEGINNING CONSTRUCTION. NOTIFY OWNER AND ENGINEER OF RECORD OF ANY
DISCREPANCIES.
5. OWNER'S AND ENGINEER'S APPROVAL MUST BE SECURED FOR ALL SUBSTITUTIONS. SUCH
APPROVAL MAY ALSO BE WITHHELD AT THE SOLE DISCRETION OF THE OWNER AND ENGINEER.
6. THE STRUCTURES HAVE BEEN ANALYZED AND DESIGNED IN ACCORDANCE WITH THE PROVISIONS
OF THE FOLLOWING:
a. INTERNATIONAL BUILDING CODE, 2018 EDITION (IBC 2018).
b. AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMUM DESIGN LOADS FOR BUILDINGS AND
OTHER STRUCTURES," 2016 EDITION (ASCE 7-16).
7. THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING REQUIRED TO ERECT
AND HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL PERMANENT SUPPORTS AND LATERAL
BRACING ARE IN PLACE.
8. DO NOT SCALE DRAWINGS, USE DIMENSIONS.
9. DESIGN LOADS USED IN THE ANALYSIS AND DESIGN OF THE STRUCTURAL SYSTEMS IN THIS
PROJECT ARE AS FOLLOWS:
a. RISK CATEGORY II
b. DEAD LOAD:
ROOF (NOT INCLUDING FRAMING SELF WT.) 5 psf
c. LIVE LOAD:
ROOF 20 psf (REDUCIBLE) CATWALKS 60 psf
d. ROOF SNOW LOAD:
GROUND SNOW LOAD, pg 25 psf SNOW EXPOSURE FACTOR, Ce 0.9 IMPORTANCE FACTOR, Is 1.0 THERMAL FACTOR, Ct 1.2 FLAT ROOF SNOW LOAD, pf 18.9 psf FROST PENETRATION DEPTH 22 inches
e. WIND DESIGN CRITERIA:
EXPOSURE CATEGORY C
BASIC WIND SPEED, V 111 mph (FACTORED, ULTIMATE LOAD)
f. SEISMIC DESIGN CRITERIA:
SPECTRAL RESPONSE ACCELERATION:
Ss (SHORT PERIOD (0.2 SECOND)) 0.155 g S1 (LONG PERIOD (1.0 SECOND)) 0.046 g SDS (SHORT PERIOD (0.2 SECOND)) 0.165 g SD1 (LONG PERIOD (1.0 SECOND)) 0.074 g
SITE CLASS CLASS D (ASSUMED)
SEISMIC DESIGN CATEGORY B
LATERAL FORCE RESISTING SYSTEM CANTILEVER COLUMN SYSTEM - TIMBER
FRAMES (ASSUMED)
IMPORTANCE FACTOR, Ie 1.0
RESPONSE MODIFICATION COEFFICIENT, R 1.5
SEISMIC RESPONSE COEFFICIENT, Cs 0.11
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
SEISMIC BASE SHEAR, V 4.94 K
10. ALL VERTICAL ELEVATIONS ARE BASED ON EXISTING INFORMATION PROVIDED BY OTHERS.
1. FOUNDATIONS FOR THIS STRUCTURE HAVE BEEN DESIGNED IN ACCORDANCE WITH AN ASSUMED ALLOWABLE BEARING CAPACITY OF 2,500 psf BASED ON EXISTING DESIGN INFORMATION.
2. SUBGRADE SHALL BE COMPACTED TO 95% STANDARD PROCTOR.
3. IF THE SUBGRADE HAS LESS THAN THE STATED ALLOWABLE BEARING CAPACITY (SEE NOTE 1
ABOVE) THE WEAK SUBGRADE SHALL BE REMOVED, RECOMPACTED, AND RETESTED UNTIL IT IS
SATISFACTORY AT NO ADDITIONAL COST TO THE OWNER.
4. WATER SHALL NOT BE ALLOWED TO ACCUMULATE IN EXCAVATIONS. CONTRACTOR SHALL
PROVIDE ALL CONSTRUCTION DEWATERING REQUIREMENTS NECESSARY.
B. FOUNDATION
1. CAST-IN-PLACE CONCRETE FOR THIS PROJECT SHALL COMPLY WITH THE AMERICAN CONCRETE
INSTITUTE (ACI) "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND
COMMENTARY" ACI 318-14 AND ACI 318R-14.
2. CONCRETE SHALL HAVE THE FOLLOWING PROPERTIES:
3. ALL EXPOSED CONCRETE EDGES SHALL HAVE 3/4" CHAMFER, WHETHER SPECIFICALLY NOTED OR
NOT.
4. CONCRETE FORMWORK SHALL COMPLY WITH ACI 347, LATEST EDITION. CONTRACTOR SHALL BE
RESPONSIBLE FOR THE DESIGN OF ALL FORMWORK.
5. DURING AND IMMEDIATELY AFTER PLACING, CONCRETE SHALL BE THOROUGHLY COMPACTED BY
SPADING OR MECHANICAL VIBRATING TO PROVIDE DENSE CONCRETE FREE OF HONEYCOMBING.
6. DIRECTLY AFTER FORMS HAVE BEEN REMOVED, ALL EXPOSED TIE WIRES AND STAPLED ENDS
SHALL BE REMOVED FROM CONCRETE SURFACES TO BE EXPOSED. CUT TIES FLUSH WITH
FINISHED SURFACES FOR ALL OTHER CONCRETE. RUB SMOOTH OR CUT OFF FINS AND ROUGH
PLACES. REMOVE ALL LOOSE CONCRETE AND OTHER IRREGULARITIES. PATCH AND FILL VOIDS
WITH BONDING AGENT AS REQUIRED.
7. ROUGHEN ALL CONSTRUCTION JOINTS TO A MINIMUM OF 1/4" AMPLITUDE UNLESS NOTED
OTHERWISE.
8. CONCRETE MATERIALS:
A. FINE AGGREGATES: ASTM C33
B. COARSE AGGREGATES: ASTM C33, MAX. AGGREGATE SIZE 1" FOR NWC
C. CEMENT: ASTM C150, TYPE I OR II (ONE SOURCE)
D. FLY ASH: ASTM C818, CLASS F (20% MAX. CEMENTITITIOUS)
E. WATER: POTABLE
DO NOT USE FINE OR COARSE AGGREGATES THAT CONTAIN SUBSTANCES THAT CAUSE SPALLING.
11. CHEMICAL ADMIXTURES:
A. WATER REDUCER: ASTM C494, TYPE A
B. RETARDER: ASTM C94, TYPE B
C. AIR ENTRAINER: ASTM C26
12. READY-MIXED CONCRETE: MEASURE, BATCH, MIX, AND DELIVER CONCRETE IN ACCORDANCE
WITH ASTM C494. FURNISH BATCH TICKET INFORMATION AT TIME OF DELIVERY.
13. DEPOSIT CONCRETE CONTINUOUSLY IN ONE LAYER. CONCRETE PLACEMENT SHALL COMPLY
WITH ACI 304 AND ASTM C94.
14. CONCRETE SHALL BE CURED IN ACCORDANCE WITH ACI 301 AND ACI 306.1 FOR COLD WEATHER
PROTECTION OR ACI 305.1 FOR HOT WEATHER PROTECTION.
AREA
FOUNDATIONS
STRENGTH @ 28 DAYS AIR CONTENT MAX. W/C RATIO
4,500 psi < 6% 0.45
C. CAST-IN-PLACE CONCRETE
SLUMP
4" ± 1"
1. STRUCTURAL STEEL FOR THIS PROJECT HAS BEEN DESIGNED IN ACCORDANCE WITH THE
FIFTHTEENTH EDITION OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "STEEL
CONSTRUCTION MANUAL."
2. STRUCTURAL STEEL SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS:
3. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1, "STRUCTURAL WELDING CODE - STEEL," LATEST EDITION. WELD ELECTRODES SHALL BE E70XX. PROVIDE 1/4" CONTINUOUS FILLET WELDS
UNLESS NOTED OTHERWISE.
4. EXPOSED EXTERIOR METAL INCLUDING ALL EXTERIOR METAL FABRICATIONS SHALL BE SHOP
FABRICATED, PRIMED, AND PAINTED.
COMPONENT TYPE STANDARD YIELD STRENGTH
a. STRUCTURAL STEEL PLATES AND BARS:
b. ANCHOR RODS:
ASTM A36
ASTM F1554
Fy = 36 ksi
Fy = 36 ksi
D. STRUCTURAL STEEL:
1. ALL TIMBER HAS BEEN DESIGNED ACCORDING TO THE NATIONAL DESIGN SPECIFICATION FOR
WOOD STRUCTURES, 2018 EDITION WITH SUPPLEMENT.
2. ALL TIMBER SHALL BE CONSTRUCTED USING PRE-MANUFACTURED ATTACHMENTS AS SHOWN
PROVIDING EQUAL OR GREATER STRENGTH THAN THE REFERENCE PRODUCT INDICATED IN
THESE DRAWINGS.
3. TIMBER SHALL BE AS FOLLOWS:
A. POSTS: SOUTHERN YELLOW PINE NO.1 GRADE OR BETTER.
OR SPRUCE PINE FIR NO. 1 OR BETTER
OR DOUGLAS FIR NO. 1 GRADE OR BETTER
B. BEAMS & JOISTS: SOUTHERN YELLOW PINE NO. 1 GRADE OR BETTER
OR SPRUCE PINE FIR NO. 2 STRUCTURAL OR BETTER
OR DOUGLAS FIR NO. 2 GRADE OR BETTER
4. UNLESS NOTED OTHERWISE, CONNECT ALL MULTIWOOD MEMBERS TOGETHER WITH 16d NAILS @
12" OC (STAGGERED APPROX 1" FROM EA FACE).
5. ALL WOOD SHALL BE APWA UC3B USE CATEGORY PRESSURE TREATED.
E. WOOD:
1. QUALIFIED SPECIAL INSPECTORS SHALL BE RETAINED BY THE OWNER TO PERFORM
INSPECTIONS REQUIRED BY THE BUILDING CODE.
2. ANY FIELD OBSERVATIONS OR OTHER WORK PROGRESS REVIEW PERFORMED BY THE
STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS A SPECIAL INSPECTION.
3. SPECIAL INSPECTIONS FOR THE FOLLOWING TYPES OF WORK IN ACCORDANCE WITH IBC 2018
SECTIONS AS NOTED BELOW SHALL BE PROVIDED:
1705.2 STEEL CONSTRUCTION
1705.3 CONCRETE CONSTRUCTION
1705.5 WOOD CONSTRUCTION
1705.6 SOILS
F. SPECIAL INSPECTIONS:
ABBREVIATION KEY
AT
ARCHITECTURAL
BUILDING
BEAM
BOTTOM
CENTERLINE
CAST-IN-PLACE
CONTRACTION JOINT
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
DEAD LOAD
DRAWING
DOWEL
EACH END
EACH FACE
ENGINEER OF RECORD
EDGE OF SLAB
EXPANSION
FOUNDATION
FINISH FLOOR
FOOTING
HORIZONTAL
HEIGHT
INCH
INTERIOR
1,000 POUNDS PER SQUARE INCH
EXTERIOR
FEET
DIAMETER
ELEVATION
CLEAR
POUNDS
LIVE LOAD
MAXIMUM
MANUFACTURER
MINIMUM
MILES PER HOUR
NOT APPLICABLE
OUT TO OUT
ON CENTER
OPENING
OPPOSITE
PLATE
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
REQUIRED
SQUARE FOOT
SIMILAR
STANDARD
STEEL
SELF-WEIGHT
TOP AND BOTTOM
TOP OF
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
WITH
WATER TO CEMENT
WIDE FLANGE
WIND LOAD
WORKING POINT
WEIGHT
SQUARE
THREADED
PRE-MOLDED JOINT FILLER
REINFORCEMENT
NOT TO SCALE
ARCH.
BLDG.
BM
BTM.
C/L
CIP
CJ
CLR.
COL.
CONC.
CONST.
CONT.
DIA.
D.L.
DWG.
DWL.
E.E.
E.F.
ELEV.
E.O.R.
E.O.S.
EXP.
EXT.
FDN.
F.F.
FT.
FTG
HOR.
HT.
IN.
INT.
ksi lb
L.L.
MAX.
MFR.
MIN.
mph
N/A
N.T.S.
O/O
O.C.
OPN'G
OPP.
PL.
PJF
psf psi
REINF.
REQ'D
S.F.
SIM.
SQ.
STD.
STL.
S.W.
T&B
T/
THRD'D
TYP.
U.N.O.
VERT.
w/
W/C
WF
W.L.
W.P.
WT.
KIPSK
EQUALEQ.
EXISTINGEXIST.
BOTTOM OFB/
DEGREEDEG.
TOP OF STEELTOS
GAUGEga
GALVANIZEDGALV.
HOOKHK.
NOTE: NOT ALL ABBREVIATIONS ARE APPLICABLE TO THIS PROJECT.
Copyright © 2021 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond &
Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
/1
/2
:2
:2
A
M C
U s e rs \w h it e m a n b
\D o c u m e n ts
\1
F B
I R a n g e
S
T R v
W h it e m a n B
.r v t
S-001
GENERAL
STRUCTURAL
NOTES
AMB
EAW
EAW
MWH
DEC 17 2021
PROJECT # - 1210567
RANGE 7
SHOOTHOUSE
REPAIRS
US DEPARTMENT OF
JUSTICE
FEDERAL BUREAU
OF INVESTIGATION
STAFFORD, VA
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
SEE SHEET S-001 FOR GENERAL STRUCTURAL NOTES AND
ABBREVIATION KEY.
DEMOLISH AND OFFSITE DISPOSE OF ALL EXISTING WOOD
CATWALKS PRIOR TO START OF ANY WORK.
PLYWOOD SHALL BE 23/32" THICK APA RATED, MARINE
GRADE. ATTACH PLYWOOD FLOOR TO CATWALK BEAM
MEMBERS USING 12d NAILS AT 12" O.C. AT ALL PLYWOOD
EDGES. LOCATE PLYWOOD EDGES ALONG CENTERLINE OF
2x6 BEAM MEMBERS.
PROVIDE AND INSTALL PROTECTIVE CLOSED-CELL FOAM (2"
THICK) COVERING ALONG EACH VERTICAL FACE AND BOTTOM
EDGE OF BOTTOM CHORD OF ALL OVERHEAD TRUSSES
WITHIN LIMITS OF CATWALK. THE INTENT IS TO PROVIDE
SOME PROTECTION AGAINST HEAD-HEIGHT OBSTRUCTIONS.
ADHERE FOAM TO TRUSS USING PL400 (OR EQUAL) EXTERIOR
RATED CONSTRUCTION ADHESIVE ADN DUCT TAPE WRAP
AROUND BOTTOM CHORD ONCE EVERY 3'-0".
TYPICAL GIRDER CONNECTION TO EXIST. BALLISTIC WALL AS
SHOWN IN DETAIL . ALL GIRDERS SHALL BE
CONNECTED AT THEIR END TO THE BALLISTIC WALL BELOW.
ATTACH SIMPSON CAPS TO EXISTING STEEL PLATE AT TOP
OF WALL USING 3/16" FILLET WELD, MINIMUM LENGTH OF 3",
AT EACH SIDE. STRUCTURAL CAPACITY OF EXISTING
BALLISTIC WALLS IS EXCLUDED FROM THE SCOPE OF THESE
MODIFICATIONS.
MODIFY EXISTING STEEL CATWALK GUARDRAILS AS
REQUIRED TO ALLOW FOR ENTRANCE TO WOOD CATWALKS.
DO NOT MODIFY EXISTING STEEL SUPPORT MEMBERS FOR
STEEL GRATING.
BUILT-UP (2)2X12 GIRDERS SHALL BE CONNECTED WITH (3)
10d BOX NAILS @ 2'-0" O.C. AT TOP AND BOTTOM STAGGERED ON OPPOSTE SIDES AND (3) 10d BOX NAILS AT ENDS.
ADJUST LOCATION OF EXISTING LIGHT FIXTURES AS
REQUIRED TO ELIMINATE OVERHEAD HAZARD AT CATWALK
AREAS. MOUNTING OF THE RELOCATED OVERHEAD LIGHT
FIXTURES SHALL RESTORE THEM TO THE SAME CONDITION
AS EXISTING LIGHT FIXTURES.
/A4 S-302
A
2 3 4
16'-5"± 19'-8"± 16'-5"±
B
C
D
E
52'-6"±
A1
S-301
S-301
C1
10"± 17'-0"± 12'-6"± 5'-8"± 15'-8"±
A3
S-301
TYP
C/L GIRDERC/L GIRDER
C/L WALL C/L WALL C/L WALLC/L WALL
C/L
GIRDER
C/L
GIRDER
2x6 BEAM
(TYP.)
2'-9"
2'-9"
/2
C /L
G
IR
D
E R
D
E R
D
E R
D
E R
5'-10"±
2'-6" ± 9" ±
EXISTING CATWALK
28'-2"±
C L R
5'-8"
C/L GIRDERC/L GIRDER
A3
S-301
TYP
W
A L L
L L
L L
L L
L L
C/L
WALL
S-301
C3
AT CATWALK LEVEL
AT GROUND LEVEL
SEE
NOTE 6
EXIST. STAIRS
EXIST. BALLISTIC
WALL (TYP.)
A3
S-301
TYP. AT
END
(2 )2 x
S E
E N
O T
E
T
Y P
(2 )2 x
(2 )2 x
(2 )2 x
(2)2x12
(2)2x12
(2 )2 x
(2 )2 x
(2 )2 x
(2 )2 x
(2 )2 x
(2)2x12
(2)2x12
A4
S-302
TYP AT GIRDER
TO WALL CXN
LEGEND:
23/32" PLYWOOD, SEE NOTE 3
EXIST. BALLISTIC WALL
SLOPE
ROOF SLOPE DOWN DIRECTION
A
2 3 4
B
C
D
E
16'-5"± 19'-8"± 16'-5"±
A1
S-301
EDGE OF
ROOF
5'-0"±5'-0"±
EDGE OF
ROOF
E D
G E
O F
R
O
F E
D G
E
F
O F
SLOPE SLOPE
C3
S-302
EXIST. ROOF
TRUSS (TYP.)
EXIST. EDGE
BEAM (TYP.)
2x6 BLOCKING
Copyright © 2021 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond &
Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
/1
/2
:2
:2
A
M C
U s e rs \w h it e m a n b
\D o c u m e n ts
\1
F B
I R a n g e
S
T R v
W h it e m a n B
.r v t
S-101
CATWALK
AND ROOF
FRAMING
PLANS
AMB
EAW
EAW
MWH
DEC 17 2021
PROJECT # - 1210567
RANGE 7
SHOOTHOUSE
REPAIRS
US DEPARTMENT OF
JUSTICE
FEDERAL BUREAU
OF INVESTIGATION
STAFFORD, VA
SCALE: 1/8" = 1'-0"C1
CATWALK FRAMING PLAN
SCALE: = 1'-0"
0 8 168
1/8"
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SCALE: N.T.S.A1
ROOF FRAMING PLAN
N
CD
7 EQ SPA = 14'-0"±
EXISTING ROOF TRUSS
(TYP.)
EXISTING BUILT-UP
(3) 2x12 EDGE BEAM
EXISTING 10" DIA.
TIMBER POLE (TYP.)
EXISTING BALLISTIC
WALL (BEYOND)
SEE NOTE 1
NOTES:
1. REMOVE PORTION OF EXISTING EDGE BEAM AFTER 6x6 POSTS ARE
SECURELY IN PLACE AND ALL CONNECTIONS ARE COMPLETED.
EXISTING EDGE BEAM
SUPPORT AT COLUMN
S-302
C1
EXISTING STEEL
CATWALK
2'-4" 3'-10"
C/L POST C/L POST
S-302
A1
B/ TRUSS
ELEV. = 16'-6"±
T/ EXISTING WALL
ELEV. = 10'-0"±
T/ EXISTING GROUND
FLOOR SLAB
ELEV. = 0'-0"
C
6"FACE OF EXISTING
BALLISTIC WALL
A1
S-301
6x6 TIMBER POST
(TYP.)
E D
G E
O F
E X
IS
T
IN
S
E
E L C
A T
W A
L K
A
T
E D
G E
O F
E X
IS
T
S
E
E L C
A T
W A
K
A
T
X
IS
T
IN
G
S T
E
T W
A L K
B E
M
CUT OPENING IN EXIST.
STEEL GRATING (TYP.)
PROVIDE SUPPORT FOR
MODIFIED STEEL GRATING
OR REPLACE PORTION OF
GRATING AS REQUIRED.
EXISTING STEEL
CATWALK BEAM
T Y
P
/2
C
L R
EXIST. 10" DIA.
COLUMN
2x4 SUPPORT BEAM
AT UNDERSIDE OF
EXISTING STEEL
GRATING. ATTACH
TO TIMBER POST AT
EACH END USING
LU24 HANGER
(2)2x12 GIRDER, SEE PLAN
FOR LOCATIONS
2x6 BEAM @ 16" O.C.
23/32" PLYWOOD WITH APPLIED
NON-SKID COATING (GRANITE
GRIP PAINT, OR EQUIVALENT)
AT WALKING SURFACE
T/ EXISTING WALL
10'-0"±
CLEAR DISTANCE
C/L GIRDER
C/L GIRDER
4x4 GUARDRAIL POST @ 5'-0" O.C.
(2) 1/2" DIA. CARRIAGE BOLTS WITH
2"x2" PLATE WASHER ON NUT SIDE
2x4 x CONT. GUARDRAIL TOP
RAIL, CXN TO POST USING
(2) 1/2" DIA. LAG SCREWS
2x4 x CONT. GUARDRAIL MID-RAIL, CXN TO POST SAME AS TOP RAIL
SEE PLAN
BEAM TO GIRDER CXN USING SIMPSON LU26
FACE MOUNT HANGER. CXN TO BEAM WITH (4)
12d NAILS x 1-1/2" LG. AND CXN TO GIRDER WITH (6) 16d NAILS x 3-1/2" LG. (TYP. EACH END)
/2
TYP.
2 1/2"
/2
C
6"FACE OF EXISTING
BALLISTIC WALL
A1
S-301
EXIST. 10" DIA.
COLUMN
4'-7"
EXIST. STEEL CATWALK
POST - SHORE AS
REQUIRED FOR
CONSTRUCTION OF
FOOTING AT TIMBER POSTS
(TYP.)
6x6 TIMBER POST
(TYP.)
1"
Copyright © 2021 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond &
Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
/1
/2
:2
:2
A
M C
U s e rs \w h it e m a n b
\D o c u m e n ts
\1
F B
I R a n g e
S
T R v
W h it e m a n B
.r v t
S-301
STRUCTURAL
SECTIONS &
DETAILS
AMB
EAW
EAW
MWH
DEC 17 2021
PROJECT # - 1210567
RANGE 7
SHOOTHOUSE
REPAIRS
US DEPARTMENT OF
JUSTICE
FEDERAL BUREAU
OF INVESTIGATION
STAFFORD, VA
SCALE: N.T.S.A1
SECTION AT EAST EDGE BEAM
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SCALE: N.T.S.C1
ENLARGED PLAN
SCALE: N.T.S.A3
SECTION AT CATWALK
SCALE: N.T.S.C3
ENLARGED PLAN
1/2" ISOLATION JOINT
ABU66Z POST BASE, CXN TO
POST USING (12) 12d NAILS
AND CXN TO CONCRETE USING
5/8" DIA. ANCHOR BOLT T/ EXIST.
PAVEMENT
ELEV. = 0'-0"±
C/L POST
2'-4"
EXIST. CONC. PAVEMENT, REMOVE
AND REPLACE AS REQUIRED FOR
FOOTING INSTALLATION
C/L POST
2'-4" 2'-4"
E M
B E
D
6" LAYER OF FREE-DRAINING FILL
HELIX GROUND ANCHOR MI2H64 (OR
EQUIVALENT PRODUCT WITH WORKING
CAPACITY OF 3,150 LBS). ATTACH STRAP
TO DOUBLE TENSION HEAD USING STRAP
BOLTS PER MANUFACTURER GUIDANCE.
INSTALL HELIX GROUND ANCHOR PRIOR
TO FOUNDATION. (TYP.)
SWIVEL TIE PLATE ASSEMBLY.
ATTACH TO TIMBER POST USING
8d NAILS x 1-1/2" LG. IN AT LEAST
50% OF PRE-PUNCHED HOLES
TIMBER POST, SEE PLAN
(TYP.)
GALVANIZED G-60
STEEL STRAP
EXIST. 7/16" PLYWOOD
WITH ASPHALT SHINGLES
2x6 BLOCKING, ATTACH TO EXIST.
ROOF TRUSS USING SIMPSON A34
CLIP ANGLE OR EQUIVALENT
SIMPSON STEEL STRAP MSTA48,
ATTACH WITH (26) 16d NAILS
PER MFR REQUIREMENTS
SIMPSON A34 CLIP ANGLE
B/ TRUSS
ELEV. = 16'-6"±
SIMPSON COLUMN CAP
ECCU5 1/4-8
EXIST. (3) 2x12 EDGE BEAM
6x6 TIMBER POST
(4) 3/4" DIA. BOLTS
TO EDGE BEAM
(2) 3/4" DIA. CARRIAGE
BOLTS TO COLUMN
EXIST. ROOF TRUSS
BOTTOM CHORD
EXIST. ROOF TRUSS TOP
CHORD
C3
S-302
SIMPSON A34 CLIP
ANGLE (TYP.)
2x6 BLOCKING, ADD AT TOP CHORD LEVEL IN
INTERRUPTED EDGE BEAM BAY AND ONE
ADJACENT BAY EACH SIDE OF INTERRUPTED BAY
STRAP, SEE /C3 S-302
B/ TRUSS
16'-6"±
(2)2x12 GIRDER
T/ EXISTING WALL
4x4 GUARDRAIL POST
2x4 GUARDRAIL TOP RAIL
2x4 GUARDRAIL MID-RAIL
2x4 GUARDRAIL MID-RAIL
(BEYOND)
NOTE: FOR DETAILS NOT SHOWN SEE .
2x4 GUARDRAIL TOP RAIL
(BEYOND)
/A3 S-301
E
T/ EXISTING WALL
10'-0"
10"±
C/L EXIST.
BALLISTIC WALL
SIMPSON CCO3 1/4-6 AT GIRDERS
PARALLEL TO BALLISTIC WALL
AND SIMPSON ECCO3 1/4-6 AT
GIRDERS PERPENDICULAR TO
BALLISTIC WALL
EXIST. STEEL
PLATE AT WALL
3/16
3/16
Copyright © 2021 by Pond & Company. All rights reserved. No copying or duplication of these documents is allowed without the expressed written agreement of Pond &
Company.
1 2
D
SHEET NUMBER
SUBMITTED BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
SHEET TITLE
DRAWING ISSUE
EOR/AOR SEAL
CLIENT INFORMATION
3500 Parkway Lane Suite 500
Peachtree Corners Georgia 30092
ORIGINAL SHEET SIZE:
22" X 34"
PROJECT NAME
3 4 5
C
B
A
/1
/2
:2
:2
A
M C
U s e rs \w h it e m a n b
\D o c u m e n ts
\1
F B
I R a n g e
S
T R v
W h it e m a n B
.r v t
S-302
STRUCTURAL
SECTIONS &
DETAILS
AMB
EAW
EAW
MWH
DEC 17 2021
PROJECT # - 1210567
RANGE 7
SHOOTHOUSE
REPAIRS
US DEPARTMENT OF
JUSTICE
FEDERAL BUREAU
OF INVESTIGATION
STAFFORD, VA
SCALE: N.T.S.A1
DETAIL AT POST FOUNDATION
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SCALE: N.T.S.C3
SECTION AT TRUSS
SCALE: N.T.S.C1
DETAIL AT EDGE BEAM
SCALE: N.T.S.C4
SECTION AT CATWALK END
SCALE: N.T.S.A4
SECTION AT GIRDER TO BALLISTIC WALL
| Sheets |
| S-001 - GENERAL STRUCTURAL NOTES |
| S-101 - CATWALK AND ROOF FRAMING PLANS |
| S-301 - STRUCTURAL SECTIONS & DETAILS |
| S-302 - STRUCTURAL SECTIONS & DETAILS |