14f- 578-20-002 100percent Bid Drawings -Part 6.pdf
PDF 8 MB Posted
- Attached to
- Z1DA--578-20-002 Renovations to Building 217 (CON) at Edward Hines Jr. VA Hospital, Hines, IL.
- Solicitation number
- 36C25225B0014
About this file
This document is an electrical bid drawing set for renovations to Building 217 at Edward Hines Jr. VA Hospital in Hines, Illinois. The comprehensive electrical drawings include detailed plans for demolition and new electrical work across multiple floors, covering areas such as the entrance lobby, dining rooms, conference rooms, patient rooms, electrical rooms, and mechanical spaces. The project involves extensive electrical system modifications, including replacing and relocating electrical panels, receptacles, lighting fixtures, fire alarm devices, wireless access points, and various low-voltage systems.
The electrical drawings specify technical requirements for conduit installation, wire sizing, equipment mounting heights, and electrical device placement, with particular attention to compliance with the National Electrical Code and VA design standards. The scope includes renovating electrical infrastructure for normal and emergency power systems, with specific focus on patient care areas like dementia units, high fall-risk patient rooms, and bariatric rooms. The project is part of VA Contract No. 36C25225B0014, with a projected completion time of 330 calendar days from the Notice to Proceed, and is designed to modernize and improve the electrical systems in Building 217.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL GENERAL NOTES GENERAL NOTES - DEMOLITION
NOTES:
1. ALL DIMENSIONS ARE CONSIDERED FROM FINISHED FLOOR AND, UNLESS NOTED OTHERWISE, SHALL NOT VARY. RAISED FLOORS SHALL BE
CONSIDERED FINISHED FLOOR.
2. ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND MAY BE ADJUSTED TO CONFORM WITH ARCHITECTURAL
REQUIREMENTS AS LONG AS NO CODE RESTRICTION IS VIOLATED.
3. OUTLETS INSTALLED LOWER THAN 15" AFF (FORWARD REACH) AND 9" AFF (SIDE REACH) ARE IN VIOLATION OF ADA.
AS NOTED ON DRAWINGS.
EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE
20"-25"D.
16" TO BOTTOM OF BOX OR AS NOTED ON DRAWINGS. EXCEPTION: 44"
MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE 20"-25"D.
48" TO HIGHEST OPERABLE PART (SIDE OR FORWARD ACCESS).
16" TO BOTTOM OF BOX.
EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS WHICH ARE
20"-25"D.
90" TO CENTERLINE OF SIGN OR CENTERED IN WALL
48" TO CENTERLINE OF BOX MINIMUM (TOILETS).
66" TO CENTERLINE OF BOX MAXIMUM (SHOWERS -
LOCATED OUT OF SPRAY AREA).
AREA BETWEEN TOP OF DOOR AND CEILING.
80" TO CENTERLINE OF DEVICE OR 6" BELOW CEILING, WHICHEVER IS
LOWER.
48" TO CENTERLINE OF BOX.
EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS
WHICH ARE 20"-25"D.
80" TO BOTTOM OF DEVICE OR NOT MORE THAN 96" TO TOP.FIRE ALARM VISUAL ONLY DEVICE OR A
COMBINATION AUDIBLE AND VISUAL DEVICE
NOT LESS THAN 90" TO TOP OR 6" BELOW CEILING, WHICH
EVER IS HIGHER.
48" TO HIGHEST OPERABLE PART - NOT MORE THAN 5'-0" FROM
EXIT.
54" TO DIAL CENTER (NON-ACCESSIBLE).
48" TO HIGHEST OPERABLE PART (ACCESSIBLE).
12" CEILING TO CENTERLINE OR 7'-0" TO CENTERLINE IF CEILING IS OVER
8'-0".
DISCONNECT SWITCHES, MOTOR STARTERS,
MOTOR PUSH BUTTON STATIONS
MOUNTING HEIGHTSDEVICE
"A" FT.
LIGHT SWITCHES, WALL MOUNTED OCCUPANCY
SENSORS
WALL MOUNTED EXIT SIGNS
CEILING MOUNTED EXIT SIGNS
RECEPTACLES
SPECIAL OUTLETS OR
RECEPTACLES
PLUGMOLD OR WIREMOLD
CLOCK OUTLETS
DATA/COMMUNICATION OR TELEPHONE OUTLETS
TELEPHONE OUTLETS - WALL TYPE
FIRE ALARM MANUAL PULL STATIONS
FIRE ALARM AUDIBLE ONLY DEVICE
WALL MOUNTED REMOTE INDICATOR LIGHT
AREA OF REFUGE TELEPHONE
CALL FOR AID SWITCH WITH PULL CHAIN TO FLOOR
CARD READER
INTERCOM STATION
SOUND SYSTEM VOLUME CONTROL
MICROPHONE OUTLETS
THERMOSTATS
TEMPERATURE/HUMIDITY SENSORS 60" TO CENTER LINE OF BOX.
54" TO HIGHEST OPERABLE PART (SIDE ACCESS).
48" HIGHEST OPERABLE PART (FORWARD ACCESS).
16" TO BOTTOM OF BOX.
54" TO HIGHEST OPERABLE PART (SIDE ACCESS).
48" HIGHEST OPERABLE PART (FORWARD ACCESS).
54" TO HIGHEST OPERABLE PART (SIDE ACCESS).
48" HIGHEST OPERABLE PART (FORWARD ACCESS).
SAME AS TELEPHONE - ACCESSIBLE.
16" TO BOTTOM OF BOX.
80" TO BOTTOM FIXTURE.
60" TO CENTERLINE.
IF DISTANCE (A+B) IN FEET IS:
(SEE DIAGRAMAT RIGHT)
FOR 120V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)
USE COPPER WIRE IN METALLIC CONDUIT,
AWG SIZE AS FOLLOWS ON ENTIRE CIRCUIT
AND SIZE CONDUIT ACCORDINGLY.
#12 AWG (MIN.)
#10 AWG
#8 AWG
#6 AWG (MAX.)
PANELBOARD
* RECEPTACLE OR LIGHTING LOAD
PANELBOARD
*LAST ON
CIRCUIT.
#12 AWG (MIN.)
#10 AWG
#8 AWG
#6 AWG (MAX.)
0' TO 100'
100' TO 175'
175' TO 300'
300' TO 450'
*FIRST ON
CIRCUIT.
"B" FT.
"A" FT.
0' TO 250'
250' TO 400'
400' TO 700'
700' TO 1000'
MOUNTING HEIGHTS FOR ELECTRICAL DEVICES
WIRE SIZING TABLE
SEE ALL PROJECT GENERAL NOTES AND OTHER REQUIREMENTS
INCLUDING THE LIFE SAFETY AND INFECTION CONTROL
REQUIREMENTS LOCATED WITHIN THE GENERAL DRAWINGS SECTION.
COMPLY WITH ALL REQUIREMENTS AS THEY ARE A DIRECT PART OF
THIS SECTION AND AS IF THEY WERE DIRECTLY INCLUDED AND
PROVIDED BELOW.
EQUIVALENCY SUBSTITUTIONS: THE "BASIS OF DESIGN (BOD)
PROTOCOLS": IS TO BE FOLLOWED FOR ALL EQUIPMENT, MATERIAL
AND ASSEMBLIES SPECIFIED AND DETAILED THROUGHOUT ALL
DRAWINGS AND SPECIFICATION SECTIONS, WHETHER THE BOD
DESIGNATE IS SPECIFICALLY REFERENCED THEREIN OR NOT. SEE THE
GENERAL DRAWINGS SECTION FOR THE FULL BOD EQUIVALENCY
SUBSTITUTION REQUIREMENTS AND PROTOCOLS TO BE FOLLOWED.
1. CODES
THE WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL,
MUNICIPAL, STATE, NATIONAL CODES, AND ALL VA APPLICABLE
DESIGN MANUALS STANDARDS REQUIREMENTS. WHERE THE
CONSTRUCTION DOCUMENTS INDICATE MORE RESTRICTIVE
REQUIREMENTS THE CONSTRUCTION DOCUMENTS SHALL
GOVERN. HOWEVER, THE CONSTRUCTION DOCUMENTS SHALL
NOT BE INTERPRETED AS AUTHORITY TO VIOLATE ANY CODE OR
REGULATION.
ALL WORK, MATERIAL, AND EQUIPMENT SHALL COMPLY WITH
ALL REQUIREMENTS OF THE LATEST EDITIONS AND INTERIM
AMENDMENTS OF THE NATIONAL ELECTRICAL CODE (N.E.C.),
NATIONAL ELECTRICAL SAFETY CODE, OSHA, AND ALL
APPLICABLE FEDERAL, STATE, AND LOCAL LAWS AND
ORDINANCES ALONG WITH ALL DESIGN CRITERIA STD AND
REQUIREMENTS. ALL ELECTRICAL EQUIPMENT PROVIDED
UNDER THIS CONTRACT SHALL BE NEW (UNLESS OTHERWISE
NOTED) AND SHALL BEAR THE MARK OF NATIONALLY
RECOGNIZED TESTING LABORATORY. ALL EQUIPMENT OF THE
SAME TYPE AND CAPACITY SHALL BE BY THE SAME
MANUFACTURER.
2. DRAWINGS AND SPECIFICATIONS
THE CONTRACTOR SHALL BE RESPONSIBLE FOR READING AND
COMPLYING WITH BOTH THE DRAWINGS AND SPECIFICATIONS.
IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN
THE DRAWINGS, NOTES, SPECIFICATIONS, OR CODES, THE
REFERENCE WHICH PROVIDES THE MORE COMPLETE OR
HIGHER STANDARD SHALL PREVAIL.
CONTRACTOR SHALL REVIEW ENTIRE SET OF CONTRACT
DOCUMENTS: INCLUDING BUT NOT NECESSARILY LIMITED TO
ALL ARCHITECTURAL, ALL STRUCTURAL, ALL MECHANICAL, ALL
ELECTRICAL, ALL PLUMBING, AND ENTIRE SPECIFICATIONS.
CONTRACTOR SHALL ACKNOWLEDGE AND INCLUDE IN THE
SCOPE OF WORK (CONTRACT) ALL CONDITIONS PERTINENT TO
THE COMPLETION OF THE ELECTRICAL WORK. CONTRACTOR
SHALL FULLY COORDINATE ELECTRICAL WORK WITH THE
INSTALLATION OF WORK BY ALL OTHER TRADES AND MAKE
NECESSARY FIELD ADJUSTMENTS AS REQUIRED TO
ACCOMMODATE THE ELECTRICAL INSTALLATION. ALL OF THE
ABOVE SHALL BE INCLUDED IN THE BASE SCOPE OF WORK AT
NO ADDITIONAL COST TO THE VA.
3. INTERPRETATION OF THE DOCUMENTS
CAREFULLY COMPARE THE DRAWINGS AND SPECIFICATIONS,
CHECKING MEASUREMENTS AND CONDITIONS UNDER WHICH
THIS INSTALLATION IS TO BE MADE. FOR CLARIFICATION
BETWEEN VARIOUS DRAWINGS, BETWEEN DRAWINGS OR
SPECIFICATION, OR BETWEEN SECTIONS OF THE
SPECIFICATION, THE MATTER SHALL BE REFERRED TO THE COR
BEFORE ANY WORK IS EXECUTED. THE CONTRACTOR SHALL
STATE IN THEIR PROPOSAL ANY EXCEPTIONS NECESSARY TO
MAKE THIS A COMPLETE, READY TO USE INSTALLATION. IF NOT
STATED IN THE BID, IT WILL NOT BE CONSIDERED EXTRA.
ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS, IN A NEAT AND WORKABLE MANNER
CONSISTENT WITH RECOGNIZED GOOD PRACTICE, AND SHALL
BE SUBJECT TO THE APPROVAL OF THE VA.
ANY CHANGES TO THE CONTRACT REQUIREMENTS MUST BE
APPROVED PRIOR TO CONSTRUCTION. THE CONTRACTOR
SHALL KEEP UP-TO-DATE DRAWINGS, ON-SITE, AVAILABLE,
INCLUDING ALLOWABLE DEVIATIONS FROM THE CONTRACT
DRAWINGS.
4. ELECTRICAL DRAWINGS
THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHALL
NOT BE SCALED. THE CONTRACTOR SHALL DETERMINE THE
EXACT LOCATION OF ALL DOORS, WALLS, FURNITURE,
EQUIPMENT, ETC. THE LOCATION OF RACEWAY SYSTEM
COMPONENTS IS SCHEMATIC. THE EXACT LOCATION OF
RACEWAY SYSTEM COMPONENTS SHALL BE DETERMINED BY
THE CONTRACTOR IN THE FIELD. THE CONTRACTOR SHALL
CONFIRM THE ACTUAL EQUIPMENT TO BE SUPPLIED FOR THIS
PROJECT, AND VERIFY CLEARANCES AND ROUGH-INS PRIOR TO
STARTING WORK.
5. SITE EXAMINATION
BEFORE SUBMITTING A BID, THE CONTRACTOR SHALL VISIT THE
SITE AND MAKE A THOROUGH SURVEY OF THE EXISTING
CONDITIONS. THIS VISIT SHALL ONLY BE ALLOWED AS PER THE
VA SCHEDULED WALKTHROUGH AND THE SUBMISSION OF A BID
WILL BE CONSTRUED AS EVIDENCE THAT SUCH A VISIT HAS
BEEN MADE. NO CONSIDERATION OR ALLOWANCE WILL BE
GRANTED FOR FAILURE TO VISIT THE SITE OR FOR LATER
CLAIMS FOR LABOR, EQUIPMENT, MATERIALS REQUIRED, OR
FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN
FORESEEN HAD SUCH VISIT BEEN MADE.
CONTRACTOR SHALL CAREFULLY EXAMINE THE DRAWINGS AND
SPECIFICATIONS, VISIT THE SITE OF THE WORK, AND FULLY
INFORM HIM/HER SELF AS TO ALL CONDITIONS AND MATTERS
THAT CAN, IN ANY WAY, AFFECT THE WORK OR THE COST
THEREOF, SHOULD THIS CONTRACTOR FIND DISCREPANCIES IN,
OR OMISSIONS FROM, THE DRAWINGS, SPECIFICATIONS OR
OTHER DOCUMENTS OR BE IN DOUBT AS TO THEIR MEANING,
NOTIFY THE VA AT ONCE, IN WRITING, OF ANY DISCREPANCIES
BETWEEN EXISTING CONDITIONS AND NEW WORK, OR BETWEEN
ELECTRICAL WORK AND THE WORK OF OTHER TRADES AND
OBTAIN CLARIFICATION PRIOR TO SUBMITTING ANY BID. LACK
OF SUCH NOTIFICATION SHALL BE CONSTRUED TO INDICATE NO
DISCREPANCIES OR CONFLICTS EXIST. ADDITIONAL
COMPENSATION WILL NOT BE GRANTED AFTER AWARD OF
CONTRACT FOR ANY WORK REQUIRED TO COMPLY WITH THESE
REQUIREMENTS.
6. COORDINATION WITH OTHER TRADES
THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COMPLETE SET
OF ARCHITECTURAL AND ENGINEERING DOCUMENTS AND
COORDINATE WITH MECHANICAL, PLUMBING, ARCHITECTURAL,
AND OTHER TRADES FOR EXACT DIMENSIONS, CLEARANCES,
ROUGH-IN LOCATIONS, AND OTHER ADDITIONAL SCOPE OF
WORK THAT MAY NOT BE SHOWN ON THE ELECTRICAL PLANS.
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
ALL 120 VOLT (AND HIGHER) AC POWER TO OTHER TRADES
EQUIPMENT AND HARDWARE. THIS SHALL INCLUDE, BUT NOT BE
LIMITED TO, CONTROLS, FIRE AND SECURITY SYSTEMS,
MOTORIZED DOORS, DAMPERS, LIFTS, AND OTHER SYSTEMS.
UNLESS SPECIFICALLY NOTED OTHERWISE ON THE ELECTRICAL
PLANS, THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL
SAFETY DISCONNECT SWITCHES TO MECHANICAL EQUIPMENT.
THE CONTRACTOR SHALL CHECK ALL ARCHITECTURAL,
STRUCTURAL, AND MECHANICAL TRADES WORK FOR POSSIBLE
INTERFERENCE CAUSED BY CONDITIONS IN THE FIELD BEFORE
THE BID IS MADE. NO ALLOWANCE SHALL SUBSEQUENTLY BE
MADE TO THE CONTRACTOR BY REASON OF HIS/HER FAILURE
TO HAVE MADE SUCH EXAMINATIONS OR OF ANY ERROR OF
HIS/HER PART.
7. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
SCHEDULING DELIVERY, RECEIVING, UNLOADING, UNCRATING,
STORING SETTING IN PLACE, AND PROTECTING FROM DAMAGE,
VANDALISM, THEFT OR WEATHER DURING CONSTRUCTION FOR
ALL NEW EQUIPMENT FURNISHED BY THE ELECTRICAL
CONTRACTOR.
CONTRACTOR SHALL PAY ALL PERMIT FEES, PLAN REVIEW
FEES, LICENSE FEES, INSPECTIONS AND TAXES APPLICABLE TO
THIS DIVISION IF NECESSARY. (FEDERAL GOVERNMENT IS NOT
SUBJECT TO LOCAL PERMITS OR FEE FOR THE PROJECT).
8. FIRE STOPPING
ALL PENETRATIONS IN WALL, FLOOR OR CEILINGS SHALL BE
SUITABLY CLOSED UP AND SEALED WITH AN INTUMESCENT FIRE
STOPPING COMPOUND LISTED IN THE MOST RECENT FACTORY
MUTUAL RESEARCH CORPORATION (FMRC) APPROVAL GUIDE.
FIRE STOPPING PRODUCTS SHALL BE MANUFACTURED BY 3M
CO OR APPROVED EQUAL.
9. PAINTING
ALL NEWLY INSTALLED EXPOSED PIPING SHALL BE PAINTED TO
MATCH THE EXISTING ADJACENT WALL OR CEILING SURFACE.
10. VA FURNISHED EQUIPMENT
EQUIPMENT THAT WILL BE FURNISHED BY THE VA SHALL BE
INDICATED ON A SEPARATE SCHEDULE. THE CONTRACTOR
SHALL COORDINATE WITH THE VA FOR DELIVERY SCHEDULES.
THE CONTRACTOR IS TO ASSUME THAT ON SITE STORAGE MAY
NOT BE AVAILABLE WHEN COORDINATING DELIVERY OF
EQUIPMENT. THE CONTRACTOR, IN COORDINATION WITH THE
COR, WILL INSPECT THE DELIVERY FOR ACCURACY AND
SHIPMENT DAMAGE AND ACCEPTING THE EQUIPMENT. THE
CONTRACTOR SHALL BE RESPONSIBLE TO STORE, PROTECT,
AND ULTIMATELY INSTALL THE EQUIPMENT.
11. ELECTRICAL SERVICE DISRUPTIONS
ANY WORK INVOLVING A TASK WHICH EXPOSES ACTIVE BUS
SHALL BE PERFORMED AFTER HOURS (11:00PM TO 5:00AM). THIS
RESTRICTION INCLUDES REMOVING THE COVER FROM ANY
PANEL BOARD, SWITCHBOARD, M.C.C. ETC. ALL WORK WHICH
EXPOSES ACTIVE BUS REQUIRES A WRITTEN NOTIFICATION TO
THE COR WHICH WILL OUTLINE THE METHOD OF PROCEDURE
FOR THE WORK. THE CONTRACTOR SHALL PROVIDE A MINIMUM
OF 2 WEEKS NOTICE TO THE COR BEFORE WORKING ON ANY
ENERGIZED ELECTRICAL SYSTEM. ALL POWER DISRUPTION
SHALL OCCUR AT TIMES AND OF DURATIONS ACCEPTABLE TO
THE COR.
12. EQUIPMENT
ALL MATERIALS AND EQUIPMENT USED IN THIS INSTALLATION
SHALL BE NEW, AND HAVE THE APPROPRIATE UL LISTING AND
LABEL.
THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL,
TOOLS, EQUIPMENT SERVICES, AND ACCESSORIES FOR
COMPLETE INSTALLATION OF ALL ELECTRICAL WORK AS NOTED.
ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE
DRAWINGS, BUT SHOWN OR DESCRIBED IN ONE OR THE OTHER,
AND ITEMS NECESSARY TO MAKE THE ELECTRICAL SYSTEM
COMPLETE AND WORKABLE SHALL FORM A PART OF THE WORK.
13. MISCELLANEOUS SUPPORTING MEMBERS
ALL ANGLES CHANNELS, AND OTHER MISCELLANEOUS STEEL,
BOLTS, RODS, ETC. REQUIRED TO SUPPORT LUMINAIRE,
CONDUIT, RACEWAY, LADDER TRAY, OR OTHER ELECTRICAL
EQUIPMENT OR DEVICES SHALL BE FURNISHED AND INSTALLED
BY THE CONTRACTOR.
ANY MENTION OF A SPECIFIC VOLTAGE ON THE ELECTRICAL
DRAWINGS SHALL NOT RELIEVE THE ELECTRICAL CONTRACTOR
OF THE RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR TO
PURCHASING OR ROUGH-IN WORK.
14. DISTRIBUTION PANELS AND PANELS BOARDS
ALL DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE
PROVIDED WITH TYPEWRITTEN DIRECTORIES. SEE PANEL
SCHEDULES ON THE DRAWINGS AND SPECIFICATION FOR
COMPLETE IDENTIFICATION AND LABELING REQUIREMENTS. ALL
DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE LABELED
ON THE PANEL CABINET WITH THE PANEL NAME AND THE
POWER SOURCE FEEDING THE PANEL AS PER THE ELECTRICAL
ONE LINE. ALL PANELS AND PANEL BOARDS SHALL BE PROVIDED
WITH HINGED DOOR WITH LOCK AND KEY.
15. SAFETY
THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO
ENSURE THE SAFETY OF THE VA'S EMPLOYEES, BUILDING
EMPLOYEES AND GUESTS, AS WELL AS THEIR OWN FORCES, BY
ADEQUATELY PROTECTING ANY EXPOSED LIVE CONDUCTORS,
OR DEVICES THROUGHOUT THE COURSE OF THIS WORK
16. EQUIPMENT CONNECTIONS
PROVIDE FINAL CONNECTIONS FOR ALL EQUIPMENT FURNISHED
UNDER OTHER DIVISIONS AND FOR ALL VA FURNISHED
EQUIPMENT. PROVIDE A FLEXIBLE LIQUID TIGHT CONNECTION
TO ALL VIBRATION PRODUCING EQUIPMENT.
17. TEMPORARY LIGHTING, POWER, FIRE, AND SAFETY
PROVIDE TEMPORARY LIGHTING AND POWER AS REQUIRED IN
AREAS UNDERGOING WORK DURING CONSTRUCTION. FURNISH
AND INSTALL ONE OSHA APPROVED PIGTAIL SOCKET WITH LED
EQUIVALENT 150-WATT LAMP FOR EVERY 500 SQUARE FEET OF
FLOOR SPACE AND A MINIMUM 1 PER ROOM. TEMPORARY
LIGHTING SHALL BE LEFT IN PLACE UNTIL PERMANENT LIGHTING
IS COMPLETELY OPERATIONAL.
FURNISH AND INSTALL POWER OUTLETS TO A TOTAL ONE FOR
EVERY 2,000 SQUARE FEET OR PART THEREOF OF FLOOR AREA
AND THESE SHALL BE 20 AMP, SINGLE PHASE RECEPTACLES
FOR EITHER 110 VOLTS OR AS INDICATED ON THE DRAWINGS.
COORDINATE ADDITIONAL TEMPORARY POWER AND
REQUIREMENTS WITH OTHER TRADES TO PROVIDE AN
ADEQUATE INSTALLATION.
COMPLY WITH NFPA 241 FOR SAFEGUARDING DURING
CONSTRUCTION AND ALTERATION OPERATIONS. IN ADDITION,
ANY OPENINGS IN FIRE RATED SEPARATIONS BETWEEN
OCCUPIED AND UNOCCUPIED (OR OPERATIONAL AND NON-
OPERATIONAL) AREAS SHALL BE SEALED AT THE END OF EACH
WORK DAY WITH AN APPROPRIATE FIRE RATED ENCLOSURE OR
SEALANT. DO NOT COMPROMISE EXISTING SECURITY OR FIRE
ALARM SYSTEMS SERVING THE OCCUPIED OR OPERATIONAL
AREAS.
DURING CONSTRUCTION THE CONTRACTOR SHALL MAINTAIN
ELECTRICAL SERVICE TO THE BUILDING WITHOUT ANY POWER
OUTAGES OR INTERRUPTION AT ALL TIMES. SHOULD IT BE
NECESSARY TO INTERRUPT ANY ELECTRICAL SERVICE OR
UTILITY, THE CONTRACTOR SHALL REQUIRED PERMISSION IN
WRITING FROM THE COR FOR SUCH INTERRUPTION AT LEAST 2
WEEKS IN ADVANCE. ANY INTERRUPTION SHALL BE MADE WITH
A MINIMUM AMOUNT OF DOWNTIME TO THE VA. ANY SHUT-DOWN
TIME SHALL HAVE TO BE ON A PREMIUM TIME BASIS AND SUCH
TIME TO BE INCLUDED IN THE CONTRACTOR'S BID.
CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES
FOR THE PROTECTION OF THE WORKMEN IN ALL PHASES OF
WORK, COMPLYING WITH THE APPLICABLE PROVISIONS OF ALL
CITY, STATE, AND FEDERAL SAFETY LAWS (OSHA), AND AS
RECOMMENDED IN THE "MANUAL OF ACCIDENT PREVENTION IN
CONSTRUCTION" AS ISSUED BY THE ASSOCIATION OF GENERAL
CONTRACTORS OF AMERICA, INC., 20TH AND E. STREETS, N.W.
WASHINGTON, D.C.
18. POWER COORDINATION
THE CONTRACTOR SHALL PERFORM ALL COORDINATION AND
SCHEDULING OF LOCAL POWER OUTAGES REQUIRED WITH THE
COR. ALL NEEDED POWER OUTAGES TO BE SCHEDULED WITH
THE COR TWO WEEKS IN ADVANCE.
19. CABLING
BRANCH CIRCUITS TO RECEPTACLES, LIGHTING AND MISC.
SMALL LOADS (15 OR 20 AMP CIRCUITS), UNLESS SPECIFICALLY
NOTED OTHERWISE, SHALL BE 2 - #12, 1 - #12 GRD., 3/4" C. A
SEPARATE NEUTRAL SHALL BE RUN FOR EACH CIRCUIT. SEE
WIRE SIZING TABLE ON THIS SHEET.
ALL WIRE SIZE #12 AWG AND LARGER SHALL BE STRANDED AND
SOLID FOR #14 AND SMALLER.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL
HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING
CONDUCTOR. ALL CONDUCTORS SHALL BE COPPER TYPE
THWN / XHHW.
20. CABLING SIZES
BRANCH CIRCUIT CABLE SIZING SHALL BE ADJUSTED BASED ON
THE VALUES INDICATED IN THE WIRE SIZING TABLE PER THIS
SHEET.
21. SPECIAL LUG REQUIREMENTS
ANY CABLE WHICH TERMINATES DIRECTLY ON TO A BUS BAR
SHALL BE 2 BOLT LONG BARREL TYPE WITH INSPECTION HOLES
PRODUCED WITH NON FLASHING TYPE DYES AS
MANUFACTURED BY THOMAS AND BETTS, OR EQUAL MINIMUM
10 TONS OF COMPRESSION, HEX CRIMP. THE USE OF HEAT
SHRINK TUBING IS EXPLICITLY FORBIDDEN. THERE SHALL BE NO
"SHINERS" AT THE LUGS.
22. RACEWAYS
ALL WIRE SHALL BE INSTALLED IN THIN WALL (E.M.T.) CONDUIT
UNLESS OTHERWISE NOTED. MINIMUM SIZE SHALL BE 3/4"
EXCEPT FOR DROPS FOR DEVICES, SWITCH LEGS,
TEMPERATURE CONTROL CONDUITS, WHERE INDICATED OR AS
CALLED FOR ON DRAWINGS. ALL THINWALL FITTINGS SHALL BE
OF THE STEEL COMPRESSION GLAND TYPE.
ALL UNDERFLOOR, UNDERGROUND OR EXPOSED-TO-WEATHER
CONDUIT SHALL BE HEAVYWALL GALVANIZED RIGID STEEL.
(G.R.S.), MINIMUM 3/4".
ALL CONDUIT FASTENERS, STRAPS, SUPPORTS ETC. MUST BE
"BOLT-ON" GALVANIZED STEEL ON EXPOSED CONSTRUCTION
AND IN WET AREAS. SNAP-ON BLACK METAL "CADDY" CLIPS IN
METAL PARTITION WALLS AND ABOVE SUSPENDED CEILINGS
WILL BE PERMITTED. ALL FASTENERS, STRAPS, CLIPS, ETC.
SHALL BE UL LISTED FOR THEIR USE.
SUPPORT CONDUIT WITH P1000 UNISTRUT OR APPROVED
EQUAL WITH 3/8" THREADED ROD 8'-0" O.C. MAX.
PROVIDE MYERS HUBS OR EQUAL FOR ALL CONDUIT TO
ENCLOSURE CONNECTIONS.
ALL CONDUIT RACEWAYS SHALL BE CONCEALED IN OR WITHIN:
WALLS, CEILING CAVITY, ROOF CONSTRUCTION (WHERE
APPROVED), SLAB, GRADE, ETC. UNLESS OTHERWISE NOTED.
ANY RACEWAY THAT IS TO BE ROUTED EXPOSED SHALL BE
APPROVED BY THE VA/COR AND SUCCESSFULLY REVIEWED BY
THE ARCHITECT/ENGINEER. PRIOR TO INSTALLATION. ALL
CONDUIT SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO
WALLS AND STRUCTURAL MEMBERS WITH 90° BENDS WHERE
REQUIRED AND SHALL BE RACKED. PULL AND JUNCTION BOXES
SHALL BE HELD TO A MINIMUM. CONTRACTOR SHALL INSTALL
ALL WORK IN NEAT & WORK LIKE MANNER.
GROUND ALL CONDUITS, MOTORS, AND EXPOSED NON-
CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT
IN ACCORDANCE WITH ALL PROVISIONS WITH THE LATEST
EDITION OF THE NATIONAL ELECTRICAL CODE. VA
SPECIFICATION SECTION 26 05 26 "GROUNDING AND BONDING
FOR ELECTRICAL SYSTEM".
CONTRACTOR SHALL PROVIDE BOXES, JUNCTION BOXES,
SPLICE BOXES AND FITTINGS WHERE NECESSARY OR
REQUIRED BY THE NEC.
ALL ELECTRICAL CONDUITS TO A MINIMUM OF 3/4". MULTI-GANG
BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL
HAVE DIVIDERS BETWEEN DEVICES.
PROVIDE COLOR RED CONDUIT FOR FIRE ALARM. WHERE CORE
DRILLING AND CUTTING OF FLOORS OR WALLS IS REQUIRED, X
RAY THE AREAS PRIOR TO DRILLING. AVOID INTERFERENCE
WITH EXISTING CONCEALED ELECTRICAL, PLUMBING
INSTALLATIONS REINFORCING STEEL. REFINISH DAMAGED AND
CUT SURFACES TO MATCH ADJACENT FINISHES.
CONTRACTOR SHALL FIREPROOF ALL CONDUIT OPENINGS
BETWEEN FLOORS AND ANY INTERSPACE FIRE SEPARATION
BLOCK WALLS WITH AN COR APPROVED U.L. LISTED FIRE
RETARDANT MATERIAL. AS SUCCESSFULLY REVIEWED BY
ARCHITECT/ENGINEER.
23. LIGHTING
ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING
FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL
REFLECTED CEILING PLAN.
24. RECEPTACLES
CONTRACTOR SHALL VERIFY ALL OUTLET MOUNTING
ARRANGEMENTS, HEIGHTS AND LOCATIONS WITH THE
ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. ANY
MENTION OF A SPECIFIC MOUNTING ARRANGEMENT, HEIGHT OR
LOCATION SHALL NOT RELIEVE THE CONTRACTOR OF THE
RESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT WITH
THE EQUIPMENT FURNISHED OR THE OTHER TRADES WORKING
IN THE SAME AREA. NO ADDITIONS TO THE CONTRACT SUM
WILL BE PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN
CONFLICT WITH OTHER WORK ETC. THE VA RESERVES THE
RIGHT TO RELOCATE ANY DEVICE 10'-0" PRIOR TO ROUGH-IN
WITHOUT ANY ADDITIONAL CHARGES BY THE CONTRACTOR.
OUTLET BOXES MOUNTED BACK-TO-BACK IN THE SAME WALL
ARE PROHIBITED. A MINIMUM 24" CENTER-TO-CENTER LATERAL
SPACING SHALL BE MAINTAINED BETWEEN BOXES.
ALL DUPLEX RECEPTACLES SHALL BE HOSPITAL GRADE
NEMA 5-20R.
ALL EMERGENCY POWER OUTLETS SHALL BE RED IN COLOR. IN
ROOMS WITHOUT GENERAL ILLUMINATION ON EMERGENCY
POWER, EMERGENCY RECEPTACLES SHALL BE OF THE SELF
ILLUMINATED TYPE.
25. GUARANTEE
ALL EQUIPMENT FURNISHED AND WORK PERFORMED UNDER
THE CONTRACT DOCUMENTS SHALL BE GUARANTEED AGAINST
DEFECTS IN MATERIALS OR WORKMANSHIP FOR A PERIOD AS
PER VA SPECIFICATION, UNLESS OTHERWISE NOTED. ANY
FAILURE OF EQUIPMENT OR WORK DUE TO DEFECTS IN
MATERIALS OR WORKMANSHIP SHALL BE CORRECTED BY THE
CONTRACTOR AT NO COST TO THE VA.
26. FINAL INSPECTION
ALL THE ITEMS AND WORK SHALL BE TESTED FOR SAFE,
PROPER OPERATIONS.
UPON COMPLETION OF THE WORK, THE ELECTRICAL
CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE PORTION
OF WORK, CLEAN EQUIPMENT AND DEVICES, REMOVE SURPLUS
MATERIALS AND RUBBISH FROM THE VA'S PROPERTY, LEAVING
THE WORK IN NEAT AND CLEAN ORDER AND IN COMPLETE
WORKING CONDITION. THE ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR REMOVAL OF ANY CARTON, DEBRIS, ETC.
FOR EQUIPMENT INSTALLED BY THIS CONTRACTOR INCLUDING
EQUIPMENT FURNISHED BY THE VA. THE ABOVE SHALL ALSO
APPLY TO ALL EQUIPMENT FURNISHED BY OTHERS AND
UNPACKED OR REMOVED FROM CARTON, BY THE CONTRACTOR.
1. EXAMINATION
A. THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE AREAS UNDERWHICH THE WORK IS
TO BE PERFORMED AND NOTIFY THE VA IN WRITING OF ANY CONDITIONS DETRIMENTAL TO
THE PROPER AND TIMELY COMPLETION OF THE WORK. CONTRACTOR SHALL NOT
PROCEED WITH WORK UNTIL SATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
B. VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS FOR DEVICES SHOWN
ON DRAWINGS.
C. DEMOLITION DRAWINGS ARE BASED ON FIELD OBSERVATION AND EXISTING RECORD
DRAWINGS. REPORT DISCREPANCIES TO COR BEFORE DISTURBING EXISTING
INSTALLATION. CONTRACTOR SHALL COORDINATE WITH COR FOR ANY
HIDDEN/UNFORESEEN WORK FOUND AFTER COMMENCEMENT OF WORK THAT NEEDS TO
BE REWORKED/RELOCATED TO COMPLETE THE NEW WORK.
D. COMMENCEMENT OF DEMOLITION MEANS ACCEPTANCE OF EXISTING CONDITIONS.
E. REVIEW MECHANICAL AND ARCHITECTURAL DEMOLITION DRAWINGS FOR FOR ANY OTHER
ELECTRICAL REQUIREMENTS.
2. PREPARATION
A. DISCONNECT ELECTRICAL ACCESSORIES IN WALLS, FLOORS, AND CEILINGS SCHEDULED
FOR REMOVAL.
3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK.
A. REMOVE, RELOCATE, AND EXTEND EXISTING ELECTRICAL WORK AS INDICATED ON THE
DRAWINGS AND AS NOTED HEREIN.
B. ABANDONED WIRING BACK TO SOURCE OF SUPPLY AND REMOVE ABANDONED CONDUIT
BACK TO NEAREST ACCESSIBLE JUNCTION BOX FOR ALL EQUIPMENT SHOWN TO BE
REMOVED.
C. ALL DEMOLISHED EQUIPMENT FROM PANELBOARD SHALL BE, RE-LABELED (TYPE WRITTEN)
AS "SPARE". AFTER DEMOLITION IS COMPLETE, SUBMIT REVISED PANELBOARD
SCHEDULES INDICATING "SPARE" CIRCUIT BREAKER.
D. REMOVE EXPOSED ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES. CUT
CONDUIT FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES. CONDUIT MAY BE
ABANDONED IN WALLS TO REMAIN EXISTING WIRING WITHIN THESE CONDUITS SHALL BE
REMOVED COMPLETELY.
E. DISCONNECT AND REMOVE ABANDONED OUTLETS AND ASSOCIATED DEVICES.
F. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND DISTRIBUTION EQUIPMENT.
G. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT THAT IS NO LONGER IN
USE.
H. DISCONNECT AND REMOVE ABANDONED LUMINARIES, BRACKETS, STEMS, HANGERS, AND
ACCESSORIES, ETC.
I. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABEL IN
JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE.
J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND
EXTENSION OF WORK.
K. IF INTERRUPTED MAINTAIN AND RESTORE, ALL WALL AND CEILING FINISHES PASSING
THROUGH UN-RENOVATED AREAS.
4. CLEANING, REPAIR, AND REPLACEMENT
A. GENERAL: CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT THAT WILL REMAIN
OR ARE TO BE REUSED.
B. PANELBOARDS: CLEAN EXPOSED SURFACES AND TIGHTEN ALL ELECTRICAL
CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE PLATES
FOR VACANT POSITIONS. PROVIDE TYPED SCHEDULES SHOWING REVISED CIRCUITING
INFORMATION.
C. LUMINARIES: REMOVE EXISTING LUMINARIES AS NOTED.
5. DISPOSAL
A. VA SHALL HAVE RIGHT TO RETAIN ANY EQUIPMENT OR MATERIALS THAT HAVE BEEN
DEMOLISHED PRIOR TO DISPOSAL OR REMOVAL FROM SITE.
B. ANY EQUIPMENT OR MATERIALS NOT WANTED BY THE VA SHALL BECOME THE PROPERTY
OF THE CONTRACTOR AND REMOVED FROM SITE.
C. CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL LAWS AND REGULATIONS FOR
DISPOSAL OF DEMOLISHED MATERIALS AND EQUIPMENT.
SPECIAL NOTES:
1. EXIT SIGNS SHALL NOT BE INSTALLED IN A MANNER THAT THE SIGN WILL BLOCK FIRE ALARM VISUAL DEVICES.
2. FOR LIGHTING FIXTURES MOUNTING HEIGHTS SEE SCHEDULE AND DRAWINGS.
NOTES:
1. TABLES ARE BASED ON EVENLY DISTRIBUTED LOAD ALLOWING A 3% VOLTAGE DROP AT LAST OUTLET.
2. 480V MOTOR BRANCH CIRCUIT CONDUCTORS SHALL BE #12 AWG IN 3/4" C UNLESS OTHERWISE NOTED.
3. SIZE OF CONDUCTORS ARE BASED UPON EACH MOTOR BEING FED WITH SEPARATE CONDUIT. IF CONDUCTORS FOR TWO MOTORS (MAX.) ARE TO BE
COMBINED IN ONE CONDUIT, INCREASE THE SIZE OF CONDUCTORS AND CONDUITS PER NATIONAL ELECTRICAL CODE (NEC), TO COMPENSATE FOR
CONDUCTOR DE-RATING.
4. PROVIDE DEDICATED NEUTRAL FOR EACH CIRCUIT.
USE COPPER WIRE IN METALLIC CONDUIT,
AWG SIZE AS FOLLOWS ON ENTIRE CIRCUIT
AND SIZE CONDUIT ACCORDINGLY.
*LAST ON
CIRCUIT.
*FIRST ON
CIRCUIT.
IF DISTANCE (A+B) IN FEET IS:
(SEE DIAGRAMAT RIGHT)
TEMPERATURE/HUMIDITY SENSORS 60" TO CENTER LINE OF BOX.
FOR 277V-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE)
WIRE SIZE CONDUIT SIZE
WIRE SIZE CONDUIT SIZE
3/4"
3/4"
3/4"
1"
3/4"
3/4"
3/4"
1"
"B" FT.
* LIGHTING LOAD
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
Bancroft Project No. VA CONTRACT NO.
12/06/2024
ELECTRICAL - GENERAL NOTES RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
WG JC
578-20-002
E001
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
DRAWING INDEX - ELECTRICAL
NUMBER TITLE
E001 ELECTRICAL - GENERAL NOTES
E002 ELECTRICAL - SYMBOLS AND ABBREVIATIONS
EPD101 ELECTRICAL - OVERALL DEMO PLAN, FIRST FLOOR
EPD102 ELECTRICAL - OVERALL DEMO PLAN, SECOND FLOOR
EPD401.1 ELECTRICAL - DEMOLITION PLAN, ENTRANCE LOBBY, VESTIBULE, RCC108R & 1A3
EPD401.2 ELECTRICAL - DEMOLITION PLAN, DINING ROOM
EPD401.3 ELECTRICAL - DEMOLITION PLAN, DINING ROOM
EPD401.4 ELECTRICAL - DEMOLITION PLAN, SECOND FLOOR CONFERANCE ROOMS
EPD401.5 ELECTRICAL - DEMOLITION PLAN, BARIATRIC ROOMS
EPD401.6 ELECTRICAL - POWER DEMOLITION PLAN, DEMENTIA UNIT
EPD401.7 ELECTRICAL - LIGHTING DEMOLITION PLAN, DEMENTIA UNIT
EPD401.8 ELECTRICAL - DEMOLITION PLAN, HIGH FALL-RISK PATIEN ROOMS
EPD401.9 ELECTRICAL - DEMOLITION PLAN, EASY STREET
EPD401.10 ELECTRICAL - POWER DEMOLITION PLAN, ELECTRICAL ROOMS
EPD401.11 ELECTRICAL - DEMOLITION PLAN, SMOKE SHELTER
EP101 ELECTRICAL - OVERALL PLAN, FIRST FLOOR
EP102 ELECTRICAL - OVERALL PLAN, SECOND FLOOR
EP401.1 ELECTRICAL - PLANS, PRIMARY & ENTRANCE LOBBY
EP401.2 ELECTRICAL - PLANS, DINING ROOMS 1A118
EP401.3 ELECTRICAL - PLANS, DINING ROOM 2A26
EP401.4 ELECTRICAL - PLANS, LIBRARY
EP401.5 ELECTRICAL - PLANS, BARIATRIC ROOMS
EP401.6 ELECTRICAL - POWER PLAN, DEMENTIA UNIT
ET401.7 ELECTRICAL - TELECOM PLAN, DEMENTIA UNIT
EL401.8 ELECTRICAL - LIGHTING PLAN, DEMENTIA UNIT
EP401.9 ELECTRICAL - PLANS, HIGH FALL-RISK ROOMS
EP401.10 ELECTRICAL - PLANS, EQUIPMENT STORAGE
EP401.11 ELECTRICAL - POWER PLAN, ELECTRICAL ROOMS
EP401.12 ELECTRICAL - PLANS, EASY STREET
EP401.13 ELECTRICAL - POWER PLAN, ROOF
E501 ELECTRICAL - DETAILS
E502 ELECTRICAL - DETAILS
E503 ELECTRICAL - DETAILS
E504 ELECTRICAL - DETAILS
E505 ELECTRICAL - DETAILS
E601 ELECTRICAL - LUMINAIRE AND CONTROLS SCHEDULES
E602 ELECTRICAL - SCHEDULES
E701 ELECTRICAL - DEMOLITION NORMAL POWER SINGLE LINE DIAGRAM
E702 ELECTRICAL - DEMOLITION EMERGENCY POWER SINGLE LINE DIAGRAM
E703 ELECTRICAL - NEW WORK NORMAL POWER SINGLE LINE DIAGRAM
E704 ELECTRICAL - NEW WORK EMERGENCY POWER SINGLE LINE DIAGRAM
E801 ELECTRICAL - PANEL SCHEDULES
E802 ELECTRICAL - PANEL SCHEDULES
E803 ELECTRICAL - PANEL SCHEDULES
E804 ELECTRICAL - PANEL SCHEDULES
E805 ELECTRICAL - PANEL SCHEDULES
E806 ELECTRICAL - PANEL SCHEDULES
Revisions: Date:
30% DESIGN DEVELOPMENT 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
90% CONSTRUCTION DOCUMENT 08/23/2024
100% CONSTRUCTION DOCUMENTS 12/06/2024
T
H
B
FR
PP
N P
N D
N BI
N SA
N DS
N ST
N CB
D
N MS
S PA
C
C
P A
DC
CR
ES
ML
CR/K
REX
KP
AIP
DC
RX
ES
ML
CCP
RTLS
QTS
MID
GB
SD
SSD
HD
HD135
SPS
SP
ST
HS
P
F SP
F SPS
STF
HSF
TS
FS
PS
FACP
MM
CM
RTS/I
Z
I
VSS
VTS
LS
XX
XX
GF
TVSS
M
CM
KWH
V
AS
VS
A
ST
T
TV TV
TVTV
TVTV
1/4
1/8
J
1. THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY APPEAR ON THIS SHEET AND NOT ON THE
PLANS.
ELECTRICAL ABBREVIATIONSELECTRICAL SYMBOLS - DIAGRAM
MOTORS AND CONTROLS
ELECTRICAL SYMBOLS - LIGHTING PLAN
ELECTRONIC SAFETY AND SECURITY SYMBOLS
ELECTRICAL SYMBOLS - COMM. / DATA PLAN
FIRE ALARM SYMBOLSELECTRICAL SYMBOL - POWER PLAN
ELECTRICAL SYMBOL - HVAC POWER PLAN
GENERAL NOTES
NURSE CALL SYMBOLS
PC
OS
S
S
S
S
DH
PB
TC
T
PB
A/V
VFD
GFCI
GFCI
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CB CODE BLUE
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST, EX EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX, JB JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT MICROWAVE
NA NOT APPLICABLE
NAC NOTIFICATION APPLIANCES CIRCUIT PANEL
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
EARTH GROUND
PULL BOX
TIME CLOCK
POWER JUNCTION BOX
TRANSFORMER, PLAN
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
WYE CONNECTION
EARTH GROUND
LADDER CABLE TRAY
PULL BOX
WIREWAY
REGULAR POWER
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON CRITICAL POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT
CIRCUIT INTERRUPTER
RECEPTACLE, QUADRAPLEX
LIFE SAFETY POWER
CRITICAL POWER
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS
DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA
& RECEPTACLE.
DOUBLE GANG DEEP AUDIO/VISUAL JUNCTION BOX
SWITCH
BLANK = SINGLE POLE 3 = THREE-WAY
4 = FOUR-WAY K = KEY OPERATED
DM= DIMMER P = WITH PILOT LIGHT
LV= LOW VOLTAGE TM = TIMER OPERATED
WP=WEATHER PROOF X = EXPLOSION PROOF
T= THERMAL OVERLOAD PROTECTION OS= OCCUPANCY SENSOR
SWITCH, LAMP HOLDER POLE
LIGHT FIXTURE RECESSED ROUND CEILING MOUNTED DOWNLIGHT
LIGHT FIXTURE, RECESSED LED, 2'x4'
LIGHT FIXTURE, RECESSED LED 1'x4'
LIGHT FIXTURE, LED, 2'x4' LETTER INDICATES MOUNTING TYPE i.e. LETTER "S" INDICATES SURFACE MOUNTED.
LIGHT FIXTURE, LED LIFE SAFETY
LIGHT FIXTURE, RECESSED LED, 2'x2'
LIGHT TRACK WITH HEADS AS SHOWN
LIGHT FIXTURE, STRIP/INDUSTRIAL LED; LETTER INDICATES TYPE.
LIGHT FIXTURE RECESSED SQUARE CEILING MOUNTED DOWNLIGHT
SWITCH, EXTERIOR PHOTO CELL FOR CONTROL OF EXTERIOR LIGHTING
LIGHTING, UNDERCABINET LIGHT/COVE LIGHT
SWITCH, OCCUPANCY SENSOR REFER TO FIXTURE SCHEDULE FOR TYPE
FIRE ALARM LINE = FA
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
EMERGENCY BATTERY BACK-UP EGRESS LIGHT
CEILING MOUNTED RECEPTACLE ON CRITICAL POWER
DOUBLE FACED CEILING OR WALL MOUNTED EXIT SIGN. ARROW INDICATES DIRECTION
SINGLE FACED CEILING OR WALL MOUNTED EXIT
SIGN.
ARROW INDICATES DIRECTION
HOMERUN TO PANELBOARDS. 4#10 + 1#12 GROUND IN 3/4" CONDUIT
THREE PORT TELEPHONE DATA OUTLET - MOUNTED 18"
AFF UNLESS OTHERWISE NOTED.
SECURITY / DURESS-ALARM BUTTON MOUNTED 3" ABOVE COUNTER
TOP
/ COUNTER TOP BACK SPLAH.
JUNCTION BOX WITH DISCONNECT SWITCH AND
FLEXIBLE CONDUIT CONNECTION
AUTOMATIC DOOR OPERATOR PUSH PLATE
CEILING MOUNTED RECEPTACLE
FLOOR RECEPTACLE, DUPLEX
FOUR PORT TELEPHONE/DATA OUTLET -
MOUNTED 18" AFF UNLESS OTHERWISE
NOTED. CABLE AND JACK COLOR AS FOLLOW
VOICE - WHITE, GREEN - VOIP,
BLUE - DATA, RED - DATA
TELEPHONE OUTLET - WALL MOUNTED
CEILING MOUNTED DATA OUTLET
GETWELL NETWORK DATA OUTLET
DUCT SMOKE DETECTOR W/REMOTE TEST STATION
WP INDICATES WEATHERPROOF HOUSING FOR
BOTH
TEMPER SWITCH
FLOW SWITCH
PRESSURE SWITCH
FIRE ALARM CONTROL PANEL
MONITOR MODULE
CONTROL MODULE
REMOTE TEST SWITCH W/INDICATOR
FIRE FIGHTERS TELEPHONE JACK
CEILING MOUNTED SECURITY CAMERA
WALL MOUNTED CARD READER
KEYPAD LOCK
AIPHONE
ACCESS CONTROL PANEL
ROOF POLE MOUNTED SECURITY CAMERA
CAMERA CONTROL PANEL
RECEPTACLE, QUADRAPLEX ON CRITICAL POWER
TV OUTLET - +84" A.F.F. OTHERWISE NOTED
AND EXISTING WORK
POINT OF CONNECTION BETWEEN NEW
LIMIT OF DEMOLITION
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER MOUNTED AT 44"
WIRELESS ACCESS POINT
INCOMING LINE
GROUND
FUSIBLE SWITCH
CURRENT TRANSFORMER
CONTROL OR POTENTIAL TRANSFORMER
SURGE AND LIGHTNING ARRESTER
CONTACTOR
SHUNT TRIP
AMMETER
AMMETER SELECTOR SWITCH
VOLTMETER
VOLTMETER SELECTOR SWITCH
UTILITY METER
OWNER METER
KILOWATT HOUR METER
TRANSIENT VOLTAGE SURGE SUPPRESSOR
GROUND FAULT
CABLE AND CONDUIT TAG
SEE
SCHEDULE
EQUIPMENT TAG SEE
EQUIPMENT
SCHEDULE
CONDUIT STUBBED DOWN
CONDUIT STUBBED UP
FLEXIBLE CONDUIT
EQUIPMENT CONNECTION
EMERGENCY POWER OFF PUSHBUTTON
BELL
BUZZER
DISCONNECT SWITCH, FUSED (SWITCH/FUSE RATING)
DISCONNECT SWITCH, UNFUSED (SWITCH RATING)
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
VARIABLE FREQUENCY DRIVE
30A/20A
30A
SINGLE PHASE MOTOR (HP AS INDICATED)
THREE PHASE (HP AS INDICATED)
VAV BOX
UNIT HEATER (ELECTRIC
COIL)
UNIT HEATER (GAS OR HOT
WATER
TYPE)
FAN POWERED BOX
CP
CPFP
11/8HP
2KW
UH
10KW
1/8HP
EUH
VAV
CP
CP
SPEAKER FOR PUBLIC ANNOUNCEMENT
L6-30R TWIST LOCK RECEPTACLE ON CRITICAL POWER, 250V,
TWO-POLE, 3W GROUNDED
L6-30R TWIST LOCK RECEPTACLE ON NORMAL POWER,
250V, TWO-POLE, 3W GROUNDED
FLOOR RECEPTACLE, DUPLEX ON CRITICAL POWER
F.A. INDIVIDUAL ADDRESSABLE MODULE
F.A. DOOR HOLDER
F.A. DOOR CLOSER
FIRE ALARM SHUT DOWN RELAY
F.A. ZONE ADDRESSABLE MODULE
WALL MOUNTED CARD READER WITH KEYPAD
DOCK DOOR POSITION INDICATOR LIGHT
HDMI OUTLET - CEILING/WALL
COAXIAL OUTLET - CEILING/WALL
TELEVISION ANTENNA SYSTEM OUTLET - CEILING/WALL
FCU
XX
CCT. XX
30A/1P
CONDENSATE PUMP
LIGHT FIXTURE, LED, 1'x4' LETTER INDICATES MOUNTING TYPE i.e. LETTER "S" INDICATES SURFACE MOUNTED.
LIGHT FIXTURE, LED, 2'x2' LETTER INDICATES MOUNTING TYPE i.e. LETTER "S" INDICATES SURFACE MOUNTED.
CHIME
FLOOR MOUNTED
FOUR PORT TELEPHONE/DATA OUTLET
LIGHT FIXTURE, LED CRITICAL POWER
WALL MOUNTED SECURITY CAMERA
CEILING MOUNTED HORN/STROBE (A/V)
CEILING MOUNTED STROBE
CEILING MOUNTED FIRE ALARM SPEAKER
WALL MOUNTED HORN/STROBE
WALL MOUNTED STROBE
WALL MOUNTED FIRE ALARM SPEAKER
CEILING MOUNTED FIRE ALARM SPEAKER/STROBE
WALL MOUNTED FIRE ALARM SPEAKER/STROBE
MANUAL PULL STATION WP-WEATHERPROOF HOUSING
STANDARD, CEILING MOUNTED SMOKE DETECTOR
NURSE CALL, WALL MOUNTED DOME LIGHT
NURSE CALL, WALL MOUNTED BED INTERFACE
NURSE CALL, WALL MOUNTED STAFF ASSIST
NURSE CALL, WALL MOUNTED DUTY STATION
NURSE CALL, CEILING MOUNTED DOME LIGHT
NURSE CALL, WALL MOUNTED PULL CORD
NURSE CALL, WALL MOUNTED STAFF TERMINAL
SOUNDER BASE, CEILING MOUNTED SMOKE DETECTOR
FIXED TEMP (135°), CEILING MOUNTED HEAT DETECTOR
RATE-OF-RISE STD, CEILING MOUNTED HEAT DETECTOR
MEDIUM-VOLTAGE OIL CIRCUIT BREAKER
MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
POTHEAD
STRESS CONE
LIGHT POLE, ONE MAST ARM, ONE LUMINAIRE
LIGHT POLE, TWO MAST ARMS, TWO LUMINAIRES
LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHT POLE, ONE LUMINAIRE
LIGHTING WALL PACK - EXTERIOR BUILDING
LIGHT FIXTURE, BOLLARD, SQAURE
LIGHT FIXTURE, DIRECTIONAL
LIGHT POLE, TWO LUMINAIRES
FLOOR RECEPTACLE, QUADRAPLEX ON CRITICAL POWER
FLOOR RECEPTACLE, QUADRAPLEX
NURSE CALL, COUNTER MOUNTED MASTER STATION
NURSE CALL, WALL MOUNTED CODE BLUE
DOOR CONTACT/DOOR POSITION SWITCH
REQUEST TO EXIT MOTION
DOOR LOCKING MECHANISM/ELECT STRIKE
DOOR LOCKING MECHANISM/MAG LOCK
ACCESS CONTROL PANEL (LNL-AL400ULX)
ACCESS CONTROL POWER SULLPY (AL600ULACMCB)
HUMIDISTAT, WALL MOUNTED
THERMOSTAT, WALL MOUNTED PULL CORD
REQUEST TO EXIT PUSH BUTTON
REAL TIME LOCATING SYSTEM
MOTION INTRUSION DETECTOR
GLASS BREAK SENSOR
DOOR CONTACT (SN-CSD80-W)
ELECTRIC STRIKE (DS160I)
MAG LOCK
CENTRAX EQUIPMENT TRACKING SYSTEM
UNIT HEATER
LIGHT FIXTURE, BOLLARD, ROUND
LIGHTING LANDSCAPE WALL
VALVE TAMPER SWITCH
VALVE SUPERVISORY SWITCH
LEVEL SWITCH
PANELBOARD
J
J
J
WAP
N
F
F
F
F
F
F
F
F
ACP
ACP
ACPS
FA
RECEPTACLE, DUPLEX MOUNTED AT 44"
RECEPTACLE, QUADRAPLEX MOUNTED AT 44"
S
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
Bancroft Project No. VA CONTRACT NO.
12/06/2024
ELECTRICAL - SYMBOLS AND
ABBREVIATIONS
RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
WG JC
578-20-002
E002
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
Revisions: Date:
30% DESIGN DEVELOPMENT 11/23/2023
60% DESIGN DEVELOPMENT 05/08/2024
ELEVATOR
1C268
ELEVATOR MACHINE RM.
1A40
ELECTRICAL
1A39
TELE.
1A137A
MECHANICAL
1A32
SOILED LINEN HOLDING
1A130
BUILDING MANAGEMENT
1A128
DIETICIAN
1A125
P.T. OFFICE
1A124
STORAGE
1A23A
HYDRO THERAPY
1A-26
MECHANICAL
1A114
O.T. OFFICE
1A116 O.T. OFFICE
1A-17
TOILET
1A119
MECHANICAL
1A121
STORAGE
1A137
H.A.C.
1A134
NON FOOD STORAGE
1A135
KITCHEN
1A127
DINING ROOM
1A118
LAUNDRY
1A110
NURSING HOME
SUPERVISOR
1A105
LOUNGE
1A104
OFFICE
1A106
OFFICE
1A107
C O
N F
E R
E N
C E
C
L A
S S
A
WOMEN
1A142
MEN
1A141
RECREATION ROOM
1A108
WOMEN
1A113
MEN
1A112
H.A.C.
1A111
NOURISH. KITCHEN
1A115
BATH
1B119
2 BEDROOM
1B120
TOILET
1B121
1 BEDROOM
1B122
2 BEDROOM
1B162
BATH
1B163
PANTRY
1B136
SOILED UTILITY
1B146
HAC
1B147
SHOWER
1B135
CONFERENCE ROOM
1B133
CLEAN UTILITY
1C133
WARD SUPPLY
1C134
H.A.C.
1B-4
SOILED UTILITY
1C146
TEL. CL.
1C43
CONGREGATE BATH
1C135
TOILET
1B-8
LOUNGE / TV ROOM
1C137
OFFICE
1C138
EXAM / TREATMENT
1C139
W/C STORAGE
1C140
NOURISHMENT KITCHEN
1C141
QUIET ROOM
1C142
STORAGE
1C136
ELECTRICAL
1C45
NURSE'S TOILET
1C181
MED.
1C180
BEDROOM
1B123
TOILET
1B124
BEDROOM
1B126
BEDROOM
1B127
TOILET
1B128
BEDROOM
1B130
BEDROOM
1B131
TOILET
1B132 TOILET
1B148
BEDROOM
1B149
TOILET
1B150
SOILED UTILITY
1B151
BEDROOM
1B152
TOILET
1B153
BEDROOM
1B155
BEDROOM
1B156
TOILET
1B157
BEDROOM
1B159
TOILET
1B161
BEDROOM
1B160
BEDROOM
1B164
TOILET
1B165
BATH
1B166
BEDROOM
1B167
BEDROOM
1B168
TOILET
1B169
BEDROOM
1B171
BEDROOM
1B172
BEDROOM
1B175
BEDROOM
1B176
TOILET
1B177
BEDROOM
1B178
TOILET
1B179
TOILET
B103
BEDROOM
B104
TOILET
1B105
BEDROOM
1B106
BEDROOM
1B107
TOILET
1B108
BEDROOM
1B110
BEDROOM
1B111
TOILET
1B112
BEDROOM
1B114
CORRIDOR
1B-84
CLEAN LINEN
1B115BTOILET
1B117
BEDROOM
1B118
TOILET
1C103
PATIENT ROOM
1C104
TOILET
1C105
BEDROOM
1C106
BEDROOM
1C107
TOILET
1C108
BEDROOM
1C110
BEDROOM
1C111
TOILET
1C112
BEDROOM
1C114
BEDROOM
1C115
BATH
1C116
TOILET
1C117
BEDROOM
1C118
BATH
1C119
BEDROOM
1C120
BEDROOM
1C122
TOILET
1C121
BEDROOM
1C123
TOILET
1C125
BEDROOM
1C126
BEDROOM
1C127
TOILET
1C129
BEDROOM
1C130
BEDROOM
1C131
TOILET
1C132
BEDROOM
1C149
TOILET
1C148
TOILET
1C150
BEDROOM
1C151
BEDROOM
1C152 TOILET
1C154
BEDROOM
1C155
BEDROOM
1C156
TOILET
1C158
BEDROOM
1C159
TOILET
1C161
BEDROOM
1C160
BEDROOM
1C162
TOILET
1C163
BEDROOM
1C164
TOILET
1C165
BEDROOM
1C167
BEDROOM
1C168
TOILET
1C170
BEDROOM
1C171
BEDROOM
1C172
TOILET
1C174
BEDROOM
1C175
BEDROOM
1C176
TOILET
1C177
TOILET
1C179
TOILET
1B173
TOILET
1C166
TOILET
1A138 TOILET
1A136
STORAGE
1A108A
REHABILITATION
THERAPY ROOM
1A43
PHYSICAL THERAPY
1A123
TOILET
1C173
PATIENT ROOM
1C178
TOILET
1C169
TOILET
1C157
TOILET
1C153
TOILET
1C128
TOILET
1C124
TOILET
1C113
TOILET
1C109
TOILET
1B174
TOILET
1B170
TOILET
1B158
TOILET
1B154
EQUIP. ROOM
1B151A
TOILET
1B129
TOILET
1B125
STORAGE
1B115A
TOILET
1B113
TOILET
1B109
OFFICE
1B139
OFFICE
1B141
MEDS
1B138
ELECT.
1B143
SUPPLY
1B142
STORAGE
1B145
EMS
1B145A
LOUNGE
1B80
SOILED UTILITY
1A131
ELEVATOR
1C268
J
K
H
M
L
N
O
P
Q
S
R
G
F1
E
D
C
B
A
234567
1010.11111.111.21213141515.11617
1920212223242526
S16
S15
S14
S13
S12
S11
S10
S9
S8
S7
S6
S5
S4
S3
S2
S1
N19
N17
N15.1N14.1
N16N15 S19
S18
S17
S16.1
S15.1
S14.1
N14
N13
N12
N11
N10
N9
N8
N7
N6
N5
N4
N3
N2
N1
EPD401.6
EPD401.8
EPD401.5
EPD401.8
EPD401.2
EPD401.9
EPD401.1
EPD401.11
EPD401.10
EPD401.10
EPD401.10
EPD401.1
EPD401.9
EPD401.2
EPD401.8
EPD401.8
EPD401.7
EPD401.5
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
Bancroft Project No. VA CONTRACT NO.
BUILDING 217 KEY PLAN
12/06/2024
ELECTRICAL - OVERALL DEMO PLAN, FIRST
FLOOR
RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
WG BX
578-20-002
EPD101
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
N 1/16" = 1'-0"
ELECTRICAL - DEMOLITION OVERALL PLAN, FIRST FLOOR
A. REFER TO E-001 ELECTRICAL GENERAL CONSTRUCTION NOTES.
B. ANY EXISTING CEILING MOUNTED SPEAKER, STROBE, AND SMOKE
DETECTORS TO BE RE-USED UNLESS OTHERWISE NOTED.
ELECTRICAL DEMOLITION GENERAL NOTES
Revisions: Date:
60% DESIGN DEVELOPMENT 05/08/2024
DN
LAUNDRY
2A32
WOMEN'S TOILET
2A27
MEN'S TOILET
2A28
OFFICE
2A33
OFFICE
2A34
ELECTRICAL
2A3
MECHANICAL
2A5
STORAGE
2A6
OFFICE
2A14
OFFICE
2A15
OFFICE
2A16
KINESIOTHER
2A17
STORAGE
2A18
PATIO
2APATIO
OFFICE
2A1
TOILET
2A9
TOILET
2A10
H.A.C.
2A11
SANCTUARY ROOM
2A12
CONFERENCE ROOM
2A13
OFFICE
2A25
DINING
2A26
NOURISHMENT KITCHEN
2A31
H.A.C.
2A39
MECHANICAL
2A24
PHARMACY
2A23 OFFICE
2A22 TOILET
2C2
MEDS
2C80
PATIENT ROOM
2C4
PATIENT ROOM
2C6
PATIENT ROOM
2C7
PATIENT ROOM
2C10
TOILET
2C9
TOILET
2C13
PATIENT ROOM
2C11
PATIENT ROOM
2C14
PATIENT ROOM
2C15
PATIENT ROOM
2C18
PATIENT ROOM
2C20
TOILET
2C61
TOILET
2B81
MEDS
2B80
TOILET
2B3
OFFICE
B26
OFFICE
2B20
TOILET
2B25
TOILET
2B21
TOILET
2B32
TOILET
2B50
TOILET
2B48
TOILET
2B35A
TOILET
2B54
TOILET
2B58 TOILET
2B61
TOILET
2B63
TOILET
2B65
TOILET
2B66
TOILET
2B69
TOILET
2B73
TOILET
2B77
TOILET
2B79
OFFICE
2B22
OFFICE
2B49
PATIENT RM.
2B59
PATIENT RM.
2B60
PATIENT RM.
2B62
PATIENT RM.
2B64
PATIENT RM.
2B67
PATIENT RM.
2B68
PATIENT RM.
2B71
PATIENT RM.
2B72
PATIENT RM.
2B75
TWO PATIENT RM.
2B76
SPD
2B33
STORAGE
2B34
H.A.C.
2B47
SOILED LINEN
2B46
SHOWER / BATHROOM
2B35
BREAK ROOM
2B42 NOURISH.
2B41
CLEAN SUPPLY
2B40
COPIER/MAIL RM.
2B39
OFFICE
2B38
CONFERENCE ROOM
2B37
SMOKING ROOM
2C37
OFFICE
2C39
STORAGE
2C40
NOURISH.
1C259
LOUNGE
2C42
ELECTRICAL
2C43
SHOWER / BATHROOM
2C35
TEL.
2C45
SOILED LINEN
2C46
WARD SUPPLY
2C34
CLEAN LINEN
2C33
TOILET
2C17
TOILET
2C16
TEL CLOSET
2A4
TOILET
2C79
TOILET
2C77
TOILET
2C74
TOILET
2C70
TOILET
2C66
TOILET
2C65
TOILET
2C63
TOILET
2C58
TOILET
2C53
TOILET
2C50
TOILET
2C48
TOILET
2C32
TOILET
2C29
TOILET
2C25
TOILET
2C19
TOILET
2C5
TOILET
2C3
TOILET
2B74
TOILET
2B70
TOILET
2B57
TOILET
2B53
TOILET
2B29
TOILET
2B24
TOILET
2B19
TOILET
2B17
TOILET
2B16
TOILET
2B13
TOILET
2B9 TOILET
2B5
PATIENT ROOM
2C76
PATIENT ROOM
2C75
PATIENT ROOM
2C78
OFFICE
2A19
PATIENT ROOM
2C72
PATIENT ROOM
2C71
PATIENT ROOM
2C68
PATIENT ROOM
2C67 PATIENT ROOM
2C64
PATIENT ROOM
2C62
PATIENT ROOM
2C60
PATIENT ROOM
2C59
PATIENT ROOM
2C56
PATIENT ROOM
2C55
PATIENT ROOM
2C52
PATIENT ROOM
2C51
HAC
2C47
EQUIP STORAGE
2C49
PATIENT ROOM
2C31
PATIENT ROOM
2C30
PATIENT ROOM
2C27
PATIENT ROOM
2C26
PATIENT ROOM
2C23
PATIENT ROOM
2C22
TOILET
2C21
MECHANICAL
2A20
OFFICE
2C38
TOILET
2C44
2C36
TOILET
2A21
CLEAN LINEN
2A2
OCCUPATION THERAPY
RM.
2A34A
STORAGE
2A35
OFFICE
2A36
OFFICE
2B4
OFFICE
2B7
OFFICE
2B10
OFFICE
2B11
OFFICE
2B14
OFFICE
2B15
OFFICE
2B18
OFFICE
2B23
OFFICE
2B26
OFFICE
2B27
OFFICE
2B30
OFFICE
2B31
PATIENT ROOM
2B51
PATIENT ROOM
2B52
PATIENT ROOM
2B55
PATIENT ROOM
2B56
FAMILY ROOM
2B78
J
K
H
M
L
N
O
P
Q
S
R
G
F1
E
D
C
B
A
234567
1010.11111.111.21213141515.11617
1920212223242526
S16
S15
S14
S13
S12
S11
S10
S9
S8
S7
S6
S5
S4
S3
S2
S1
N19
N17
N15.1N14.1
N16N15 S19
S18
S17
S16.1
S15.1
S14.1
N14
N13
N12
N11
N10
N9
N8
N7
N6
N5
N4
N3
N2
N1
EPD401.3
EPD401.8
EPD401.4
EPD401.8
EPD401.10
EPD401.10
EPD401.10
EPD401.3
EPD401.4
EPD401.8
EPD401.5
EPD401.8
EPD401.5
EPD401.8
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
Bancroft Project No. VA CONTRACT NO.
BUILDING 217 KEY PLAN
12/06/2024
ELECTRICAL - OVERALL DEMO PLAN,
SECOND FLOOR
RENOVATIONS TO
BUILDING 217
EDWARD J. HINES JR. VAMC
WG BX
578-20-002
EPD102
100% CONSTRUCTION
DOCUMENTS
23-00936C25223C0071
N 1/16" = 1'-0"
ELECTRICAL - DEMOLITION OVERALL PLAN, SECOND FLOOR
A. REFER TO E-001 ELECTRICAL GENERAL CONSTRUCTION NOTES.
B. ANY EXISTING CEILING MOUNTED SPEAKER, STROBE, AND SMOKE
DETECTORS TO BE RE-USED UNLESS OTHERWISE NOTED.
ELECTRICAL DEMOLITION GENERAL NOTES
Revisions: Date:
60% DESIGN DEVELOPMENT 05/08/2024
R e fr ig e ra to r
WAP
N S S
F
S S
N
F
F
P
F
F
WAP
WAP
F
F
F
F
WAP
F
W A
P
TV
F
W A
P
J
FA
A
P
C R
/K
C R
/K
N
F
MIDMID
CR
WAP
J
C R
C R
P P
S
N
J
F
DH
DH
DAS
F
F
N
N
WAP
F
WAP
F
JJ
R e fr ig e ra to r
K
M
L
N
O
P
Q
S
R
1515.11617
SP
SD
SPS
SPS
SP
ST
SD
SP
HS
ST
SP
SD
D
SD
D
SP
D
D
SP
A. REMOVE VAV POWER SUPPLIES NO LONGER IN USE.
B. RECEPTACLES NOTED AS DEMOLISH, REMOVE CONDUITS, PULL BOXES
AND CONDUCTORS BACK TO PANEL SOURCE. UPDATE TYPEWRITTEN
DIRECTORY TO REFLECT CHANGES.
C. LOW VOLTAGE DEVICES NOTED AS DEMOLISH, REMOVE CONDUITS, PULL
BOXES AND CONDUCTORS BACK TO SOURCE.
D. REMOVE ALL ABANDONED WIRING AND CONDUIT BACK TO SOURCE.
E. EXISTING CIRCUITS OUTSIDE OF SCOPE OF WORK SHALL BE EXISTING TO
REMAIN. IF CIRCUITS ARE AFFECTED FROM NEW CONSTRUCTION,
CONTRACTOR SHALL CIRCUIT TRACE AS NECESSARY. CIRCUITS FOR
THESE INTERRUPTED CIRCUITS SHALL BE NEW WIRING. ALL CIRCUITS
THAT ARE SHARED WITH DEVICES OUTSIDE THE AREA OF DEMOLITION
SHALL REMAIN POWERED AND SHALL BE RECONNECTED TO THE EXISTING
ASSOCIATED PANEL FEEDING THESE ITEMS. CONTINUITY SHALL BE
CHECKED FOR ALL LIGHTING, OUTLETS, COMM/DATA OUTLETS, FIRE
ALARM DEVICES IN THE AREAS NOT BEING REMODELED TO ENSURE
PROPER FUNCTIONING.
F. ALL ELECTRICAL DEVICES/EQUIPMENT SHOWN WITH DARK DASH LINES
SHALL BE REMOVED AND DEMOLISHED INCLUDING WIRING, BOXES AND
CONDUIT BACK TO SOURCE, UNLESS OTHERWISE NOTED.
G. ALL ELECTRICAL LUMINAIRES AND LIGHTING CONTROLS SHOWN WITH
DARK DASH LINES SHALL BE REMOVED AND DEMOLISHED, UNLESS
OTHERWISE NOTED.
H. NORMAL POWER AND LIFE SAFETY LIGHTING BRANCH CIRCUITS SHALL BE
RE-USED IN THE RENOVATED AREA.
I. EMERGENCY EXIT SIGN BRANCH CIRCUITS SHALL BE RE-USED IN THE
RENOVATED AREA.
J. WIRELESS ACCESS POINTS SHALL BE CAREFULLY REMOVED AND STORED
IN A VA DESIGNATED SECURED SITE.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .