14b- 578-20-002 100percent Bid Drawings -Part 2.pdf

PDF 13 MB Posted

Attached to
Z1DA--578-20-002 Renovations to Building 217 (CON) at Edward Hines Jr. VA Hospital, Hines, IL.
Solicitation number
36C25225B0014
Issued by

About this file

This document is a comprehensive set of architectural drawings for renovations to Building 217 at Edward Hines Jr. VA Hospital in Hines, Illinois. The 100% construction documents detail extensive renovations across multiple floors and functional areas, including a Primary Care Clinic, Dining Rooms, Conference Rooms, Dementia Unit, High Fall-Risk Patient Rooms, Bariatric Patient Rooms, and support spaces. The drawings, dated December 6, 2024, provide detailed floor plans, equipment layouts, finish schedules, wayfinding plans, and equipment specifications for a project with the contract number 578-20-002.

The renovation project encompasses approximately 1,623 square feet of multipurpose space, multiple patient rooms, dining areas, clinical spaces, and support facilities. Key design elements include specialized room configurations for dementia and high fall-risk patients, medical equipment placement, finish materials selections, and comprehensive architectural details. The project is set to be completed within 330 calendar days from the Notice to Proceed, with the work to be performed for the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 12. The architectural drawings provide extensive technical specifications for construction, including partition types, equipment mounting details, ceiling configurations, and room-specific design requirements.

View the file

Other files

File Type Posted
HINES VA SITE PLAN - Contractor Parking.pdf PDF
578-20-002_Addendum2_06102025.pdf PDF
578-20-002_Addendum1_Specifications_060225.pdf PDF
RFI FINAL QUESTIONS AND RESPONSES -IFB SOLICITATION 36C25225B0014.docx DOCX document
36C25225B0014 0004.docx DOCX document
36C25225B0014 0003.docx DOCX document
RFI QUESTIONS AND ANSWERS FOR PROJECT 578-20-002 IFB SOLICITATION 36C25225B0014.docx DOCX document
SOW Requirements for AC Shop 4-13-2023.docx DOCX document
36C25225B0014 0002.docx DOCX document
18- Building 217 - Clinic Details.pdf PDF
36C25225B0014 0001.docx DOCX document
P09 - 578-20-002 Construction SOW Rev2 5-12-25.docx DOCX document
16c- 578-20-002 Basis of Design -BOD Part 3.pdf PDF
16b- 578-20-002 Basis of Design -BOD Part 2.pdf PDF
14d- 578-20-002 100percent Bid Drawings -Part 4.pdf PDF
2- Contractor Badging - Fingerprint Request Form 2025.pdf PDF
1- Contractor Parking.pdf PDF
14c- 578-20-002 100percent Bid Drawings -Part 3.pdf PDF
12- Interim Life Safety Measures -ILSM.pdf PDF
13- VHA ICRA-1.3 -Dec 9 2024.pdf PDF
P07 Wage determination IL20250009 03-07-2025.pdf PDF
16- 578-20-002 Basis of Design -BOD Part 1.pdf PDF
14e- 578-20-002 100percent Bid Drawings -Part 5.pdf PDF
36C25225B0014.docx DOCX document
16d- 578-20-002 Basis of Design -BOD Part 4.pdf PDF
6- Infection Control Barrier Sample.pdf PDF
9- OIT Horizontal Cable Requirements.pdf PDF
14f- 578-20-002 100percent Bid Drawings -Part 6.pdf PDF
4- No Smoking Policy 10-1-19.pdf PDF
3- Emergency Contact List - Template.docx DOCX document
17- Building 217 Colored Space Drawings.pdf PDF
P01 - 578-20-002 Construction SOW Rev1 5-1-25.docx DOCX document
5- Safety and Health During Construction Activities.pdf PDF
15- 57820002_100CD_Specifications_12092024 r1.pdf PDF
7- Cutting Welding and Other Hot Work.pdf PDF
11- VHA PCRA-1.1 -May 21 2024.pdf PDF
14- 578-20-002 100percent Bid Drawings -Part 1.pdf PDF
10- Pre-Construction Checklist.pdf PDF
8- Above Ceiling Entry and Wall Construction Permits.pdf PDF
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEC

FE

C

FEC

FE

C

FE

C

FECFEC

FEC

J

K

H

M

L

N

O

P

Q

S

R

G

F1

E

D

C

B

A

23456789

1010.11111.111.21213141515.11617

181920212223242526

S16

S15

S14

S13

S12

S11

S10

S9

S8

S7 S6

S5

S4

S3

S2

S1

N19

N17

N15.1

N14.1

N16 N15

S19

S18

S17

S16.1

S15.1

S14.1

N14

N13

N12

N11

N10

N9

N8

N7 N6

N5

N4

N3

N2

N1

AE401

1 AE410

AE402

AE407

AE405

AE405

AE408

AE408

AE409

BEDROOM

B120

BEDROOM

B122

BEDROOM

B123

BEDROOM

B126

BEDROOM

B127

BEDROOM

B130

BEDROOM

1B131

BEDROOM

B118

LINEN

B115

STR

B115A

BEDROOM

B114

BEDROOM

B111

BEDROOM

B110

BEDROOM

B107

BEDROOM

B106 4

BEDROOM

B104

Room

CONFERENCE

ROOM

B133

OFFICE

B139

SOILED

UTILITY

B146

SHOWER

ROOM

1B135

MED

ROOM

B138

OFFICE

B141

STAFF

WORK

AREA

1B142

ELECTRICAL

BEDROOM

1C106

BEDROOM

1C107

BEDROOM

1C110

BEDROOM

1C111

BEDROOM

1C114

BEDROOM

1C115

BEDROOM

1C118

TOILET

1C119

BEDROOM

1C120

BEDROOM

1C122

BEDROOM

1C123

BEDROOM

1C126

BEDROOM

1C127

BEDROOM

1C130

BEDROOM

1C131

BEDROOM

1C151

BEDROOM

1C152

BEDROOM

1C155

BEDROOM

1C156

BEDROOM

1C159 1

BEDROOM

C160

BEDROOM

C162

BEDROOM

1C164

BEDROOM

1C167

BEDROOM

1C168

BEDROOM

1C171

BEDROOM

1C172

BEDROOM

1C175

BEDROOM

1C176

PHYSICAL

THERAPY

A123

P.T.

OFFICE

A124

DIETICIAN

A125

SATELLITE

DENTAL

CLINIC

A128

MECHANICAL

A132

ELECTRICAL

A139

ELEVATOR

MACHINE

ROOM

A140

SOILED

LAUNDRY

HOLDING

A130

TRASH

ROOM

A131

CLEAN

LINEN

STORAGE

1B151

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - FIRST FLOOR - FLOOR

PLAN

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE101

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/16" = 1'-0"

ARCHITECTURAL - FIRST FLOOR - OVERALL PLAN

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

90% CONSTRUCTION DOCUMENTS 08/23/2024

100% CONSTRUCTION DOCUMENTS 12/06/2024

DN

FEC

FECFEC

J

K

H

M

L

N

O

P

Q

S

R

G

F1

E

D

C

B

A

23456789

1010.11111.111.21213141515.11617

181920212223242526

S16

S15

S14

S13

S12

S11

S10

S9

S8

S7

S6

S5

S4

S3

S2

S1

N19

N17

N15.1

N14.1

N16 N15

S19

S18

S17

S16.1

S15.1

S14.1

N14

N13

N12

N11

N10

N9

N8

N7N6

N5

N4

N3

N2

N1

AE403

AE406

AE408

AE408

AE404

AE409

AE409

TOILET

2C79

HIGH

FALL-RISK

PATIENT

ROOM

2C78

OFFICE

2B20

OFFICE

2B22

OFFICE

2B23

OFFICE

2B26

OFFICE

2B27

OFFICE

2B30

OFFICE

2B31

OFFICE

2B49

BEDROOM

2B51

BEDROOM

2B52

BEDROOM

2B55

BEDROOM

2B56

BEDROOM

2B59

BEDROOM

2B60

BEDROOM

2B62

OFFICE

2B64

BEDROOM

2B67

BEDROOM

2B68

BEDROOM

2B71

BEDROOM

2B72

BEDROOM

2B75

BEDROOM

2B76

OFFICE

2B18

OFFICE

2B15

OFFICE

2B14

OFFICE

2B11

OFFICE

2B10

OFFICE

2B7

OFFICE

2B6

OFFICE

FELLOWS

2B4

LAUNDRY

A232

PSYCH

OFFICE

A233

OFFICE

A234

OCCUPATIONAL

THERAPY

A234A

O.T.

STORAGE

C211

OFFICE

A236

CLEAN

LINEN

STORAGE

A202

ELECTRICAL

A203

MECHANICAL

A205

HAC

SUPPLIES

A206

STORAGE

A207

OFFICE

A208

BUILDING

MANAGEMENT

A214

SOCIAL

OFFICE

A215

P.T.

OFFICE

A216

KINESIO

THERAPY

A217

OFFICE

A225

BEDROOM

2C76

BEDROOM

2C75

BEDROOM

2C72

BEDROOM

2C71

BEDROOM

2C68

BEDROOM

2C67

BEDROOM

2C64

BEDROOM

2C62

BEDROOM

2C60

BEDROOM

2C59

BEDROOM

2C56

BEDROOM

2C55

BEDROOM

2C52

BEDROOM

2C51

CLEAN

STORAGE

C231

BEDROOM

2C30

BEDROOM

2C27

BEDROOM

2C26

BEDROOM

2C23

BEDROOM

2C22

BEDROOM

2C20

HOSPICE

SUPPORT

2C18

BEDROOM

2C15

BEDROOM

2C14

BEDROOM

2C11

BEDROOM

2C10

BEDROOM

2C7

BEDROOM

2C6

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - SECOND FLOOR - FLOOR

PLAN

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE102

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/16" = 1'-0"

ARCHITECTURAL - SECOND FLOOR - OVERALL PLAN

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

C

FE

C

FEC

FEC

K

M

L

N

O

P

Q

S

R

1515.11617

179 SF

EXAM

1A109

178 SF

EXAM

1A108

168 SF

EXAM

1A107

182 SF

EXAM

1A106

179 SF

EXAM

1A105

253 SF

WAITING

ROOM/LIBRARY

1A104

127 SF

VITALS

1A142

113 SF

SOCIAL

WORKER

1A111

77 SF

TOILET

1A112

0"

0"

0"

0"

0"

130 SF

WORK

ROOM

1A141

A E

.3

187 SF

RECEPTION

1A104A

7'

- 3

/16

9'

- 7

0"

7'

- 7

5/ 8"

8' - 6 3/4"

5'

- 1

1 1 /16

5'

- 1 1 1

/8"

9'

- 9

7/

8'

- 7

1A105

1A106

1A104C

1A104A

1A142

1A107 1A141

1A111

1A108

1A109 1A112

1A

3B

/3 AE401.2

2' - 0 5/8"

A E

.2

A E

.2

A E

.3

/5 AE401.2

A E

.2

AE401.1

AE401.1

AE401.4

AE551

A E

.3

1A103E

1A103D

1A103C

1A104B

1A

6' - 1 3/4"

A E

8'

- 6

1/

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CONSTRUCTION.

M. PROVIDE METAL BACKING PLATE AT ALL WALL MOUNTED ITEMS, SEE

EQUIPMENT PLANS AND SCHEDULES.

N. NEW SUBSURFACE FLOOR PREPARATION: THE EXISTING CONCRETE

FLOOR SUB-SURFACES RESULTING FROM THE REMOVAL OF OLD

FLOOR FINISHES (I.E., CERAMIC TILE, VCT, MASTICS, VINYL SHEETS,

ABATEMENTS, CARPETING, ETC.) OR GOING OVER CONCRETE FLOOR

REPAIRS OR INFILLS SHALL BE ENTIRELY SKIM COATED TO A

SMOOTH AND LEVEL FINISH, TO BE LEVEL WITH ALL ADJACENT

FLOOR SURFACES REQUIRING EXISTING FLOOR FINISH REMOVALS

AND/OR NEW FLOOR FINISHES, SUCH THAT THE FINAL FINISHED

FLOORS ARE SMOOTH AND LEVEL AND HAVE FINISH TRANSITIONS AS

SHOWN AND INTENDED. FOR BIDDING PURPOSES, FLOOR SKIM

COATING SHALL BE FIGURED AT 3/4” THICKNESS AVERAGE

O. FURRED PARTITIONS EXTEND TO STRUCTURE ABOVE, UNLESS

NOTED OTHERWISE.

GENERAL NOTES FLOOR PLAN

EXISTING

CONSTRUCTION

TO REMAIN

NEW PARTITION

WALL

MATCHLINE

LIMITS OF NEW

CONSTRUCTION

FIRE

EXTINGUISHER

CABINET - REFER

TO DETAIL AE561

FLOOR PLAN LEGEND

4'

- 0

4'

- 0

4' - 0" 2" 4' - 0" 2"

AE542

Sim

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO.

BUILDING 217 KEY PLANN

12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

PRIMARY CARE CLINIC & ENTRANCE LOBBY

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE401

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/8" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - PRIMARY CARE CLINIC & ENTRANCE LOBBY

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

90% CONSTRUCTION DOCUMENTS 08/23/2024

100% CONSTRUCTION DOCUMENTS 12/06/2024

1/2" = 1'-0"2

WHEELCHAIR CORRAL ELEVATION

R e fr ig e ra to r

EXAM

1A108

E0224 F0206

F0340

M1801

A1015

M8810

M4925 M4116

A5106

M4200

M4100 F0205

F2010

A5082

A5075

M2050

M1801 A5145

3' - 0"3' - 0"

2'

- 6

/16

1'

- 8

3' - 0" 3' - 0"

A5082 A5075

F2010

F0205

4" 2'

- 8 7/

8" 1"

SS-2

PL-1

PL-1

AE541

Typ.1A

AE541

Typ.

AE541

Typ.

AE541

Typ.

SLOPED TOP

WP-10

PL-1

F0206

F2010

F0340

M1801

E0224

A1015

RB-1

A5145

WP-10

AE551

SimM4925

M8810 F0340

M1801

E0224

A1015

RB-1

SS-1

AE531

WP-10

M4925M4116M4200 M4100A5106

F0205A5075

RB-1

WP-10

WP-17

TOILET

1A112

A5082

F2010

A5075

A1067 A5200

A5090

A1067

A5082

F2010

PT-8

WP-16

A5200

A5090

F2010

A5082

A5075

A1067

PT-8

WP-16

A5200

A5090

PT-8

WP-16

A5090

L1200

PT-8

WP-16

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

PRIMARY CARE CLINIC & ENTRANCE LOBBY

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE401.1

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - TYP EXAM ROOM

1/2" = 1'-0"

ELEVATION - 1A108 SOUTH 1/2" = 1'-0"

ELEVATION - 1A108 EAST

1/2" = 1'-0"

ELEVATION - 1A108 NORTH

1/2" = 1'-0"

ELEVATION - 1A108 WEST

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - TOILET 1A112

1/2" = 1'-0"

ELEVATION - 1A112 NORTH

1/2" = 1'-0"

ELEVATION - 1A112 EAST

1/2" = 1'-0"

ELEVATION - 1A112 SOUTH

1/2" = 1'-0"

ELEVATION - 1A112 WEST

Revisions: Date:

AE541

Typ.

A5106

M1830

A5075

A5082

WP-2

RB-1WP-3

WP-2

RB-1WP-3

WP-2

RB-1WP-3

WP-2

RB-1WP-3

WP-2

RB-1WP-3

WP-1

SS-2

AE611

Sim

AE611

Sim

AE611

Sim

AE611

Sim2

AE611

Sim

AE611

Sim

AE611

Sim1

AE611

Sim1

AE611

Sim

WP-10

WP-10 WP-10 WP-10 WP-10

WP-10

PNL-1 PNL-1 PNL-1

L1200

AE611

Sim

AE611

Sim

AE611

Sim

4' - 2"

3'

- 8

6' - 1 7/16" 5' - 5" 10' - 6 7/8"

PNL-1

M4020

E0954

WP-1RB-1 WP-1RB-1 RB-1 WP-1

AE531

Typ.

AE531

Typ.

AE531

Typ.

WP-10 WP-10

WP-10

WP-2

WP-3

WP-2

WP-3

WP-2

WP-3

F0305 F0206 F0305

AE611

Typ.

AE611

Typ.

RB-1 WP-11

AE552

Sim

PNL-3

17' - 0"

4'

- 6

F0305 F0305

WP-1

RB-1 RB-1

RB-1

AE551

Sim

WP-11 WP-11

WP-11

WP-1 WP-1 WP-1 WP-1

RB-1

WP-11

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS - PRIMARY

CARE CLINIC & ENTRANCE LOBBY

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE401.2

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - C104B SOUTH

1/2" = 1'-0"

ELEVATION - C104B NORTH

1/2" = 1'-0"

ELEVATION - 1A104A EAST

1/2" = 1'-0"

ELEVATION - 1A104A NORTH

1/2" = 1'-0"

ELEVATION - 1A104A SOUTH

Revisions: Date:

WP-2

RB-1WP-3 RB-1

WP-1 WP-1

AE611

Typ.

AE611

Typ.

AE611

Typ.

WP-11

RB-1

WP-11

WP-11

PNL-2 PNL-2 PNL-2

PNL-2 PNL-2

PNL-2

WP-2WP-2

WP-3 WP-3

WP-2

RB-1WP-3

WP-2

RB-1WP-3

WP-2

RB-1

WP-3

AE611

Typ.

AE611

Typ.

AE611

Typ.

AE611

Typ.

AE611

Typ.

AE611

Typ.

WP-11 WP-11

BRICK

WP-2

RB-1WP-3

WP-1

WP-11

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS - PRIMARY

CARE CLINIC & ENTRANCE LOBBY

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE401.3

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - 1A104A NORTH CORRIDOR

1/2" = 1'-0"

ELEVATION - 1A104A SOUTH CORRIDOR - A

1/2" = 1'-0"

ELEVATION - 1A104A SOUTH CORRIDOR - B

Revisions: Date:

O

15.116 /2 AE401.4

/3 AE401.4

A E

.4

A E

.4 RECEPTION

1A104A

A

E .4

/7 AE401.4

A E

.4

/9 AE401.4

2'

- 1

1"

2'

- 7

2' - 2 3/4"

1' - 0"

R 2' - 7"

R 2' - 7"

105.00°

R 1' - 0"

9'

- 4

9/

2' - 1"

9' - 7 1/16"

R 1' - 7"

2' - 6 3/16"

2"

2' - 10 3/16" 2' - 9 7/8" 2' - 2 3/16"

2"

2' - 0 3/16" 1"

2'

- 0

3/

2"

2'

- 0

3/

2"

2'

- 0

3/

5 3 /8"

1'

- 6

3/

TY

P.2'

- 0

4"

15.00°

AE542

Sim

SS-3

PL-1

SS-3

AE542

Sim

AE542

Sim

SS-3

M1801

PNL-1 PNL-1

4'

- 1

0"

AE542

Sim

WP-2

RB-1WP-3

SS-3

PL-1

RB-1

PNL-3 PNL-3 PNL-3

WP-11

AE542

Sim

SS-3

PL-1

RB-1

PNL-3PNL-3 PNL-3 PNL-3 PNL-3 PNL-3

8" 2'

- 1 0"

SS-3

PL-1

M1801

F0280

M1840

2'

- 1

0"

SS-3

M1840

M1801

F0280

AE542

Sim

3'

- 6

2'

- 1

0"

SS-3

PL-1

RB-1

SS-3

M1801

F0280 F0280

SS-3

PL-1

SS-3

PL-1

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

PRIMARY CARE CLINIC & ENTRANCE LOBBY

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE401.4

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - RECEPTION 1A104A

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - EXTERIOR - WEST

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - EXTERIOR - EAST

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - EXTERIOR - SOUTH

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - EXTERIOR - NORTH

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - INTERIOR - NORTH

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - INTERIOR - EAST

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - INTERIOR - SOUTH

1/2" = 1'-0"

ELEVATION - RECEPTION DESK - INTERIOR - WEST

Revisions: Date:

FECFEC

K

M

L

N

1111.111.212131415

15' - 7 1/8" 22' - 5 7/8"

1585 SF

DINING

ROOM

1A118

504 SF

KITCHEN

SUPPORT

1A127A

167.16°

5' - 6 11/16" 19' - 4"

5' - 0"

3'

- 0

24' - 7 1/16"

1A118A

1A118B

1A127AA

4' - 3"

81.64°

/3 AE402.1

8' - 4 11/16"

/1 AE402.1

A E

.1

3' - 0"

4'

- 6

1A118C

.8

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CONSTRUCTION.

M. PROVIDE METAL BACKING PLATE AT ALL WALL MOUNTED ITEMS, SEE

EQUIPMENT PLANS AND SCHEDULES.

N. NEW SUBSURFACE FLOOR PREPARATION: THE EXISTING CONCRETE

FLOOR SUB-SURFACES RESULTING FROM THE REMOVAL OF OLD

FLOOR FINISHES (I.E., CERAMIC TILE, VCT, MASTICS, VINYL SHEETS,

ABATEMENTS, CARPETING, ETC.) OR GOING OVER CONCRETE FLOOR

REPAIRS OR INFILLS SHALL BE ENTIRELY SKIM COATED TO A

SMOOTH AND LEVEL FINISH, TO BE LEVEL WITH ALL ADJACENT

FLOOR SURFACES REQUIRING EXISTING FLOOR FINISH REMOVALS

AND/OR NEW FLOOR FINISHES, SUCH THAT THE FINAL FINISHED

FLOORS ARE SMOOTH AND LEVEL AND HAVE FINISH TRANSITIONS AS

SHOWN AND INTENDED. FOR BIDDING PURPOSES, FLOOR SKIM

COATING SHALL BE FIGURED AT 3/4” THICKNESS AVERAGE

O. FURRED PARTITIONS EXTEND TO STRUCTURE ABOVE, UNLESS

NOTED OTHERWISE.

GENERAL NOTES FLOOR PLAN

EXISTING

CONSTRUCTION

TO REMAIN

NEW PARTITION

WALL

MATCHLINE

LIMITS OF NEW

CONSTRUCTION

FIRE

EXTINGUISHER

CABINET - REFER

TO DETAIL AE561

FLOOR PLAN LEGEND

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO.

BUILDING 217 KEY PLANN

12/06/2024

ARCHITECTURAL - ENLARGED PLAN - DINING

ROOM 1A118

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE402

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - DINING 1A118

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

F0780

F0225

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0780

WP-1

RB-1

WP-1

RB-1

RB-1

WP-12 WP-12

PNL-2 PNL-2 PNL-2 PNL-2 PNL-2 PNL-2 PNL-2 PNL-2

SS-3

RB-1

WP-6

WP-12

F0225

F0225

F0225

F0225

F0225

RB-1

WP-1

AE531

Typ.

AE541

Typ.3

AE541

Typ.

2'

- 1

0"

WP-12SS-3

WP-12

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS - DINING

ROOM 1A118

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE402.1

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - 1A118 EAST

1/2" = 1'-0"

ELEVATION - 1A118 NORTH

1/2" = 1'-0"

ELEVATION - 1A118 WEST

Revisions: Date:

FECFEC

K

M

L

N

1111.111.21213141515.1

2247 SF

DINING

ROOM

2A18

2A18A

/1 AE403.1

A E

.1

A E

.1

/4 AE403.1

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CONSTRUCTION.

M. PROVIDE METAL BACKING PLATE AT ALL WALL MOUNTED ITEMS, SEE

EQUIPMENT PLANS AND SCHEDULES.

N. NEW SUBSURFACE FLOOR PREPARATION: THE EXISTING CONCRETE

FLOOR SUB-SURFACES RESULTING FROM THE REMOVAL OF OLD

FLOOR FINISHES (I.E., CERAMIC TILE, VCT, MASTICS, VINYL SHEETS,

ABATEMENTS, CARPETING, ETC.) OR GOING OVER CONCRETE FLOOR

REPAIRS OR INFILLS SHALL BE ENTIRELY SKIM COATED TO A

SMOOTH AND LEVEL FINISH, TO BE LEVEL WITH ALL ADJACENT

FLOOR SURFACES REQUIRING EXISTING FLOOR FINISH REMOVALS

AND/OR NEW FLOOR FINISHES, SUCH THAT THE FINAL FINISHED

FLOORS ARE SMOOTH AND LEVEL AND HAVE FINISH TRANSITIONS AS

SHOWN AND INTENDED. FOR BIDDING PURPOSES, FLOOR SKIM

COATING SHALL BE FIGURED AT 3/4” THICKNESS AVERAGE

O. FURRED PARTITIONS EXTEND TO STRUCTURE ABOVE, UNLESS

NOTED OTHERWISE.

GENERAL NOTES FLOOR PLAN

EXISTING

CONSTRUCTION

TO REMAIN

NEW PARTITION

WALL

MATCHLINE

LIMITS OF NEW

CONSTRUCTION

FIRE

EXTINGUISHER

CABINET - REFER

TO DETAIL AE561

FLOOR PLAN LEGEND

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO.

BUILDING 217 KEY PLANN

12/06/2024

ARCHITECTURAL - ENLARGED PLAN - DINING

ROOM 2A18

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE403

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - DINING 2A26

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

AE551

Sim

RB-1

WP-1

RB-1 RB-1

WP-1

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0780

WP-13 WP-13 WP-13

PNL-2 PNL-2 PNL-2 PNL-2 PNL-2 PNL-2 PNL-2 PNL-2

SS-3

AE551

Sim

RB-1

WP-1

RB-1

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0780

F0225

F0225 F0225

F0225

F0225 F0780

F0225WP-1

WP-13

AE551

Sim

AE551

Sim

F0225

F0225

F0780

F0225

F0225 F0225 F0225 F0225 F0225

SS-3

WP-1

WP-1

WP-1

F0225 F0225 F0225

RB-1WP-13

SS-3

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ENLARGED PLAN - DINING

ROOM 2A18

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE403.1

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - 2A18 EAST

1/2" = 1'-0"

ELEVATION - 2A18 NORTH

1/2" = 1'-0"

ELEVATION - 2A18 WEST

1/2" = 1'-0"

ELEVATION - 2A18 SOUTH

Revisions: Date:

O

P

1111.111.212

MOVABLE PARTITION

31' - 7 5/16"

463 SF

CONFERENCE

ROOM

2A12A

309 SF

CONFERENCE

ROOM

2A12B

A E

.1

/3 AE404.1

A E

.1

/1 AE404.1

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CONSTRUCTION.

M. PROVIDE METAL BACKING PLATE AT ALL WALL MOUNTED ITEMS, SEE

EQUIPMENT PLANS AND SCHEDULES.

N. NEW SUBSURFACE FLOOR PREPARATION: THE EXISTING CONCRETE

FLOOR SUB-SURFACES RESULTING FROM THE REMOVAL OF OLD

FLOOR FINISHES (I.E., CERAMIC TILE, VCT, MASTICS, VINYL SHEETS,

ABATEMENTS, CARPETING, ETC.) OR GOING OVER CONCRETE FLOOR

REPAIRS OR INFILLS SHALL BE ENTIRELY SKIM COATED TO A

SMOOTH AND LEVEL FINISH, TO BE LEVEL WITH ALL ADJACENT

FLOOR SURFACES REQUIRING EXISTING FLOOR FINISH REMOVALS

AND/OR NEW FLOOR FINISHES, SUCH THAT THE FINAL FINISHED

FLOORS ARE SMOOTH AND LEVEL AND HAVE FINISH TRANSITIONS AS

SHOWN AND INTENDED. FOR BIDDING PURPOSES, FLOOR SKIM

COATING SHALL BE FIGURED AT 3/4” THICKNESS AVERAGE

O. FURRED PARTITIONS EXTEND TO STRUCTURE ABOVE, UNLESS

NOTED OTHERWISE.

GENERAL NOTES FLOOR PLAN

EXISTING

CONSTRUCTION

TO REMAIN

NEW PARTITION

WALL

MATCHLINE

LIMITS OF NEW

CONSTRUCTION

FIRE

EXTINGUISHER

CABINET - REFER

TO DETAIL AE561

FLOOR PLAN LEGEND

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO.

BUILDING 217 KEY PLANN

12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

CONFERENCE ROOMS

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE404

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - CONFERENCE ROOMS

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

WP-1

RB-1

WP-1

WP-1

RB-1

MOVABLE WALL PARTITION

WP-1

RB-1 RB-1

MOVABLE WALL PARTITION

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS -

CONFERENCE ROOMS

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE404.1

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - 2A12 EAST

1/2" = 1'-0"

ELEVATION - 2A12 NORTH

1/2" = 1'-0"

ELEVATION - 2A12 WEST

1/2" = 1'-0"

ELEVATION - 2A12 SOUTH

Revisions: Date:

E

D

S19

S18

S17

N9N8

308 SF

BARIATRIC

PATIENT

ROOM

B149

72 SF

TOILET

B148

8' - 0"

B148

B149

A E

.1

/1 AE405.1

A E

.1

A E

.1

/4 AE405.1

/5 AE405.1

A E

.1

/8

AE405.1

2' - 0"

E

DS9 S8

N19

N17

8' - 0"

8'

- 0

298 SF

BARIATRIC

PATIENT

ROOM

C149

73 SF

TOILET

C148

4 1 3/1

6"

C149

C148

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CONSTRUCTION.

M. PROVIDE METAL BACKING PLATE AT ALL WALL MOUNTED ITEMS, SEE

EQUIPMENT PLANS AND SCHEDULES.

N. NEW SUBSURFACE FLOOR PREPARATION: THE EXISTING CONCRETE

FLOOR SUB-SURFACES RESULTING FROM THE REMOVAL OF OLD

FLOOR FINISHES (I.E., CERAMIC TILE, VCT, MASTICS, VINYL SHEETS,

ABATEMENTS, CARPETING, ETC.) OR GOING OVER CONCRETE FLOOR

REPAIRS OR INFILLS SHALL BE ENTIRELY SKIM COATED TO A

SMOOTH AND LEVEL FINISH, TO BE LEVEL WITH ALL ADJACENT

FLOOR SURFACES REQUIRING EXISTING FLOOR FINISH REMOVALS

AND/OR NEW FLOOR FINISHES, SUCH THAT THE FINAL FINISHED

FLOORS ARE SMOOTH AND LEVEL AND HAVE FINISH TRANSITIONS AS

SHOWN AND INTENDED. FOR BIDDING PURPOSES, FLOOR SKIM

COATING SHALL BE FIGURED AT 3/4” THICKNESS AVERAGE

O. FURRED PARTITIONS EXTEND TO STRUCTURE ABOVE, UNLESS

NOTED OTHERWISE.

GENERAL NOTES FLOOR PLAN

EXISTING

CONSTRUCTION

TO REMAIN

NEW PARTITION

WALL

MATCHLINE

LIMITS OF NEW

CONSTRUCTION

FIRE

EXTINGUISHER

CABINET - REFER

TO DETAIL AE561

FLOOR PLAN LEGEND

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO.

BUILDING 217 KEY PLANN

12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

BARIATRIC ROOMS

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE405

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - BARIATRIC B149

N

1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - BARIATRIC C149

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

F0400 F0315

RB-1

SS-1

AE541

Typ.

AE541

Typ.

AE541

Typ.

RB-1

A5082 A5075

M7010

F0400SS-3

PL-2

PL-2

RB-1

M0506

F0315

RB-1

PT-2

PT-3

P-17

PT-2

PT-3

P-17

AE541

Typ.

A5082 A5075

A1067

SS-3

PT-2

PT-3

P-17

PL-2

A5082

PT-2

PT-3

P-17

308 SF

BARIATRIC

PATIENT

ROOM

B149

72 SF

TOILET

B148

8' - 0"

B148

B149

2' - 0"

F0400 F0315

M7010

M0506

A5082

A1067

A5075

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

BARIATRIC ROOMS

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE405.1

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - B149 EAST

1/2" = 1'-0"

ELEVATION - B149 NORTH

1/2" = 1'-0"

ELEVATION - B149 SOUTH

1/2" = 1'-0"

ELEVATION - B149 WEST

1/2" = 1'-0"

ELEVATION - B148 WEST

1/2" = 1'-0"

ELEVATION - B148 NORTH

1/2" = 1'-0"

ELEVATION - B148 SOUTH

1/2" = 1'-0"

ELEVATION - B148 EAST

N

1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - BARIATRIC B149

Revisions: Date:

N

O

1515.116

PEDASTAL MOUNTED

ENGINEERED WOOD

DECKING

PLANTER BOX

PLANTER BOX

AE521

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CONSTRUCTION.

M. PROVIDE METAL BACKING PLATE AT ALL WALL MOUNTED ITEMS, SEE

EQUIPMENT PLANS AND SCHEDULES.

N. NEW SUBSURFACE FLOOR PREPARATION: THE EXISTING CONCRETE

FLOOR SUB-SURFACES RESULTING FROM THE REMOVAL OF OLD

FLOOR FINISHES (I.E., CERAMIC TILE, VCT, MASTICS, VINYL SHEETS,

ABATEMENTS, CARPETING, ETC.) OR GOING OVER CONCRETE FLOOR

REPAIRS OR INFILLS SHALL BE ENTIRELY SKIM COATED TO A

SMOOTH AND LEVEL FINISH, TO BE LEVEL WITH ALL ADJACENT

FLOOR SURFACES REQUIRING EXISTING FLOOR FINISH REMOVALS

AND/OR NEW FLOOR FINISHES, SUCH THAT THE FINAL FINISHED

FLOORS ARE SMOOTH AND LEVEL AND HAVE FINISH TRANSITIONS AS

SHOWN AND INTENDED. FOR BIDDING PURPOSES, FLOOR SKIM

COATING SHALL BE FIGURED AT 3/4” THICKNESS AVERAGE

O. FURRED PARTITIONS EXTEND TO STRUCTURE ABOVE, UNLESS

NOTED OTHERWISE.

GENERAL NOTES FLOOR PLAN

EXISTING

CONSTRUCTION

TO REMAIN

NEW PARTITION

WALL

MATCHLINE

LIMITS OF NEW

CONSTRUCTION

FIRE

EXTINGUISHER

CABINET - REFER

TO DETAIL AE561

FLOOR PLAN LEGEND

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO.

BUILDING 217 KEY PLANN

12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

SECOND FLOOR PATIO

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE406

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - SECOND FLOOR PATIO

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

C

FEC

FEC

H

G

F1

E

D

C

B

A

1515.11617

N16

N15 S19

S18

S17

S16.1

S15.1

S14.1

N14

N13

N12

N11

N10

N9

N8

N6

109 SF

CLEAN

UTILITY

1B152

240 SF

DEMENTIA

PATIENT

ROOM

1B155

239 SF

DEMENTIA

PATIENT

ROOM

1B156

245 SF

DEMENTIA

PATIENT

ROOM

1B159

149 SF

MULTIPURPOSE

ROOM

1B160

238 SF

DEMENTIA

PATIENT

ROOM

1B162

236 SF

DEMENTIA

PATIENT

ROOM

1B164

232 SF

DEMENTIA

PATIENT

ROOM

1B167

238 SF

DEMENTIA

PATIENT

ROOM

1B168

235 SF

DEMENTIA

PATIENT

ROOM

1B171

239 SF

DEMENTIA

PATIENT

ROOM

1B172

235 SF

DEMENTIA

PATIENT

ROOM

1B175

8' -

3/4

242 SF

DEMENTIA

PATIENT

ROOM

1B176

0"

8' - 5 7/16"

14'

- 1

1 9 /16

14'

- 1

0 1 1/1

6"

15'

- 2

/16

0 1 /8"

1/

8"

0 1

1/1 6"

9 9 /16

1' - 0"

72 SF

BATHROOM

1B165

64 SF

BATHROOM

1B166

66 SF

BATHROOM

1B169

65 SF

BATHROOM

1B170

67 SF

BATHROOM

1B173

65 SF

BATHROOM

1B174

75 SF

BATHROOM

1B177

67 SF

BATHROOM

1B154

65 SF

BATHROOM

1B157

67 SF

BATHROOM

1B158

60 SF

PUBLIC

TOILET

1B161

78 SF

BATHROOM

1B163

1B135A

1B80B

1B80A

1B176

1B175

1B171

1B168

1B167

1B164

1B158

1B

1B154

1B180C

1B172

AE

7.

AE

7.

110 SF

SOILED

UTILITY

1B153

27 SF

CLEAN

LINEN

1B151

1B151

3' - 6"

5' - 6"

7' - 8 1

/4"

6' - 9 9

/16

13'

- 4

7/1 6"

16'

- 9

/16

6' - 8 1

5/1 6"

A E

.3

7 5 /16

3'

- 0

3'

- 0

3'

- 0

3'

- 0

3'

- 0

3'

- 0

3'

- 0

1' - 6 7/16"

1' - 2 9/16"

1' - 3 1/8"

1' - 0 5/16" 3' -

0"

3' - 0"

3' - 0"

3' - 0"

1' - 0 1/4"

1' - 0 1/4"

44 SF

STAFF

TOILET

1B135A

347 SF

STAFF

WORK

AREA

1B142

210 SF

SHOWER

ROOM

1B135

6' - 7 1/8"

AE

7.

AE407.1

AE407.2

AE407.6

A E

.2

A E

.2

1B159 1B156

1B155

1B

1B153

1B162

1B

1B165

1B

1B169

1B

1B173

1B

1B177

AE

7.

8 3 /4"

9 5 /8"

7 3 /4"

5/

8"

1/ 8"

7'

- 1

1/ 8"

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CONSTRUCTION.

M. PROVIDE METAL BACKING PLATE AT ALL WALL MOUNTED ITEMS, SEE

EQUIPMENT PLANS AND SCHEDULES.

N. NEW SUBSURFACE FLOOR PREPARATION: THE EXISTING CONCRETE

FLOOR SUB-SURFACES RESULTING FROM THE REMOVAL OF OLD

FLOOR FINISHES (I.E., CERAMIC TILE, VCT, MASTICS, VINYL SHEETS,

ABATEMENTS, CARPETING, ETC.) OR GOING OVER CONCRETE FLOOR

REPAIRS OR INFILLS SHALL BE ENTIRELY SKIM COATED TO A

SMOOTH AND LEVEL FINISH, TO BE LEVEL WITH ALL ADJACENT

FLOOR SURFACES REQUIRING EXISTING FLOOR FINISH REMOVALS

AND/OR NEW FLOOR FINISHES, SUCH THAT THE FINAL FINISHED

FLOORS ARE SMOOTH AND LEVEL AND HAVE FINISH TRANSITIONS AS

SHOWN AND INTENDED. FOR BIDDING PURPOSES, FLOOR SKIM

COATING SHALL BE FIGURED AT 3/4” THICKNESS AVERAGE

O. FURRED PARTITIONS EXTEND TO STRUCTURE ABOVE, UNLESS

NOTED OTHERWISE.

GENERAL NOTES FLOOR PLAN

EXISTING

CONSTRUCTION

TO REMAIN

NEW PARTITION

WALL

MATCHLINE

LIMITS OF NEW

CONSTRUCTION

FIRE

EXTINGUISHER

CABINET - REFER

TO DETAIL AE561

FLOOR PLAN LEGEND

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO.

BUILDING 217 KEY PLANN

12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

DEMENTIA UNIT

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE407

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/8" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - DEMENTIA UNIT

Revisions: Date:

30% SCHEMATIC DESIGN 11/23/2023

60% DESIGN DEVELOPMENT 05/08/2024

DEMENTIA

PATIENT

ROOM

1B168

BATHROOM

1B1692' - 0"

M7010

F0400

M7040 F0315

A5075 A1067

F2010

A5082

M0506

F2010

A5082

A5075

AE543

M7040

M7010

F0400 F0315

RB-1

AE551

SimF0315

RB-1

SS-1

AE542

Typ.

2'

- 9

1/ 2"

SS-3

PL-2

RB-1

F2010

M0506

AE541

Typ.

AE541

Typ.

AE541

Typ.

RB-1

F2010

A5075

A5082

SS-3

PL-2

PL-2

2' - 11"

2' - 10"

F2010

A5170

PT-2

PT-3

P-17

PT-2

PT-2

PT-3

PT-2

A5082

F2010

PT-2

PT-3

P-17

AE541

Typ.

A1067

A5170

A5075

SS-3 PL-2

3' - 0"

2'

- 1

0"

PT-2

PT-3

P-17

PT-2

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

DEMENTIA UNIT

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE407.1

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - TYP DEMENTIA PATIENT ROOM

1/2" = 1'-0"

ELEVATION - 1B168 NORTH

1/2" = 1'-0"

ELEVATION - 1B168 SOUTH

1/2" = 1'-0"

ELEVATION - 1B168 WEST

1/2" = 1'-0"

ELEVATION - 1B168 EAST

1/2" = 1'-0"

ELEVATION - 1B169 EAST

1/2" = 1'-0"

ELEVATION - 1B169 SOUTH

1/2" = 1'-0"

ELEVATION - 1B169 NORTH

1/2" = 1'-0"

ELEVATION - 1B169 WEST

Revisions: Date:

WP-1 WP-2

WP-3

WP-6

RB-1

WP-1

RB-1

WP-1 WP-2

WP-3 RB-1

WP-1WP-9 WP-9

WP-9

WP-9

PL-1 PL-1 PL-1

WP-1 WP-2

WP-3 RB-1

WP-1 WP-1 WP-2

WP-3 RB-1

/3 AE407.2

AE531

Typ.

WP-9

WP-9

PL-1

PL-1 PL-1PL-1

PL-1PL-1

/2 AE407.2

WP-2

WP-3 RB-1

WP-1

WP-9

STAFF

TOILET

1B135A

A5090 A5200

A5082

A1067

A5075

A5075

A5082

A1067

PT-6

WP-14

A5200

PT-6

WP-14

A1067

A5082A5075

A5200

PT-6

WP-14

A5082

A5090 A5200

PT-6

WP-14

WP-2

WP-3RB-1

WP-9

PL-1

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS - DEMENTIA

UNIT

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE407.2

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - DEMENTIA UNIT CORRIDOR C150 - NORTH

1/2" = 1'-0"

ELEVATION - DEMENTIA UNIT CORRIDOR C150 - SOUTH A

1/2" = 1'-0"

ELEVATION - DEMENTIA UNIT CORRIDOR C150 - SOUTH B

Revisions: Date:

90% CONSTRUCTION DOCUMENTS 08/23/2024

100% CONSTRUCTION DOCUMENTS 12/06/2024

N 1/2" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - STAFF TOILET 1B135A

1/2" = 1'-0"

ELEVATION - 1B135A WEST

1/2" = 1'-0"

ELEVATION - 1B135A SOUTH

1/2" = 1'-0"

ELEVATION - 1B135A NORTH

1/2" = 1'-0"

ELEVATION - 1B135A EAST

1/2" = 1'-0"9

ELEVATION - DEMENTIA UNIT CORRIDOR C150 - SOUTH C

F0780

F0225 F0225

F0780

PT-9

M0506

SS-5

PL-1

AE542

FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1

FLM-1

FLM-1 FLM-1 FLM-1

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS - DEMENTIA

UNIT

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE407.3

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - DEMENTIA UNIT COMMUNITY SPACE - SOUTH

Revisions: Date:

F0780

SS-5

PL-1

FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS - DEMENTIA

UNIT

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE407.4

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - DEMENTIA UNIT COMMUNITY SPACE - NORTH

Revisions: Date:

SS-5

PL-1

FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1 FLM-1FLM-1

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ELEVATIONS - DEMENTIA

UNIT

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE407.5

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

1/2" = 1'-0"

ELEVATION - DEMENTIA UNIT COMMUNITY SPACE - FACING SOUTH CORRIDOR

Revisions: Date:

E

D

S18

S17

S16.1

N11

A E 407.6

A E

7.

/ 3

A E 407.6

AE

7.

/ 2

A E 407.6

AE

7.

2' - 9"

2' - 9"

12' - 10 1/16"

3' - 6 5/8"

R 1 ' - 0"

R 6 ' - 0

1' - 3 15/16"

19' - 4 1/2"

21.52°

141.66°

A E

.2

A E

.2

AE542

Typ.

AE542

Typ.

AE542

Typ.

F0225F0225F0225F0225

SS-5

PL-1

WP-7 WP-7

WP-20

WP-20

RB-1

F0225F0225F0225F0225 F0280 F0225 F0280F0280

SS-5

PL-1

WP-7 WP-7 WP-7

WP-20

WP-20

WP-20

F0280 F0280

WP-20

WP-7

F0225 F0225 F0225 WP-20

WP-7

AE541

Typ.

AE541

Typ.

AE541

Typ.

1A

AE541

Typ.5

AE541

Typ. 5

AE541

Typ.

2' - 0" 4' - 0" 4' - 0"

4' - 0"

SLOPED TOP

PL-1

PL-1

2' - 0"2' - 0"2' - 0"

SS-1

3' - 0"3' - 0"

PT-5

RB-1

F0225

WP-20

WP-7

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

REVIEW ONLY - NOT FOR CONSTRUCTION

Bancroft Project No. VA CONTRACT NO. 12/06/2024

ARCHITECTURAL - ENLARGED PLAN -

DEMENTIA UNIT

RENOVATIONS TO

BUILDING 217

EDWARD J. HINES JR. VAMC

CZ CR

578-20-002

AE407.6

100% CONSTRUCTION

DOCUMENTS

23-00936C25223C0071

N 1/4" = 1'-0"

ARCHITECTURAL - ENLARGED PLAN - NURSE STATION AND NOURISHMENT

1/2" = 1'-0"2

ELEVATION - NURSE STATION - FRONT OF NURSE STATION

1/2" = 1'-0"3

ELEVATION - NURSE STATION - LOOKING BEHIND NURSE STATION

1/2" = 1'-0"4

ELEVATION - NURSE STATION - RIGHT

1/2" = 1'-0"5

ELEVATION - NURSE STATION - LEFT

1/2" = 1'-0"6

ELEVATION - NURSE STATION - BEHIND NURSE STATION

1/2" = 1'-0"7

ELEVATION - NURSE STATION - LEFT LOOKING OUT OF NURSE STATION

SS-5

Revisions: Date:

H

G

11.212

442 SF

HIGH

FALL-RISK

PATIENT

ROOM

1C104

71 SF

TOILET

1C105

1C105

1C104

9'

- 4

1/ 8"

7"

7' - 5 3/8"

11' - 9 11/16"

/2 AE408.1

A E

.1

/5 AE408.1

A E

.1

A E

.1

/8 AE408.1

/6 AE408.1

A E

.1

2'

- 0

K

M

L

N14.1

465 SF

HIGH

FALL-RISK

PATIENT

ROOM

1C178

67 SF

TOILET

1C179

1C179

1C178

9' - 4 1/8"

7'

- 8

3/

2 1 /4"

7"

H

G

11.212

441 SF

HIGH

FALL-RISK

PATIENT

ROOM

2C4

72 SF

TOILET

2C5

2C4

2C5

9'

- 4

1/ 8"

7' - 5 3/8"

11' - 9 5/8"

7"

K

M

L

N14.1

454 SF

HIGH

FALL-RISK

PATIENT

ROOM

2C78

67 SF

TOILET

2C79

9' - 4 1/8"

7'

- 8

1/ 4"

2C78

2C79

2 1 /4"

7"

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK –

GENERAL NOTES” REGARDING THE VA’S DISCRETION IN SELECTING

WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK

C. REFER TO GENERAL NOTES ON GI001 AND GI002.

D. REFER TO SHEET SERIES AF AND QH FOR FINISHES AND EQUIPMENT.

E. REFER TO SHEET ANNN FOR DETAILS FOR WALL GUARDS, CRASH

RAILS, HANDRAILS, INTEGRAL COVE BASE, CORNER GUARDS.

F. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING

FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL

DRAWINGS FOR FULL SCOPE OF CONSTRUCTION WORK.

G. UNLESS OTHERWISE NOTED ALL WALLS TO BE TYPE '1'. REFER TO

SHEET AE501 FOR PARTITION TYPES.

H. REFER TO SHEET AE601 FOR DOOR AND WINDOW SCHEDULES.

I. ALL DIMENSIONS ARE TO THE FINISHED FACE.

J. SEAL/FIRESTOP ALL OPENINGS IN ALL FIRE RATED WALLS TO

CREATE A CONTINUOUS SYSTEM. INCLUDES ALL EXPOSED CONDUIT

AND PIPING.

K. EACH PARTITION NOTED TO CARRY AN ACOUSTIC RATING SHALL

CARRY THAT RATING IN THE ENTIRETY OF ITS CONSTRUCTION TO

CREATE A CONTINUOUS SYSTEM. INCLUDES PLACEMENT AND

SEALING OF PENETRATIONS, JUNCTION BOXES, ETC. UNLESS NOTED

OTHERWISE, PARTITIONS SHALL EXTEND TO THE STRUCTURE ABOVE

AND ACCOMMODATE ITS PROFILE.

L. NEW DOOR INSTALLATIONS SHALL COMPLY WITH THE FOLLOWING

UNLESS OTHERWISE NOTED: (A) ON THE PUSH SIDE OF DOORS:

PROVIDE A MINIMUM CLEARANCE OF 12" AT THE LOCK/LATCH SIDE

FACE OF DOOR FRAME OPENING TO ANY FIXED CONSTRUCTION

THAT WOULD BE ADJACENT TO THE FACE OF PARTITION. (B) ON THE

PULL SIDE OF DOORS: PROVIDE A MINIMUM CLEARANCE OF 18" AT

THE LOCK/LATCH SIDE FACE OF DOOR FRAME OPENING TO ANY

FIXED CONSTRUCTION THAT WOULD BE ADJACENT TO THE FACE OF

PARTITION. (C) IN METAL FRAMED GYPSUM BOARD PARTITIONS

TYPICALLY ON THE PULL SIDE OF DOORS WHERE THE HINGE SIDE OF

A DOOR FRAME IS PLACED ADJACENT TO ANY FIXED CONSTRUCTION,

LOCATE THE DOOR SIDE FRAME OPENING 4" FROM THE FIXED

CO…