This federal contract opportunity announcement solicits proposals for construction rehabilitation services at the Belmont-Paul Women's Equality National Monument in Washington, D.C. The scope of work includes interior and exterior repairs, structural upgrades, fire suppression system improvements, site work, and mechanical, electrical and plumbing system replacements. Optional items such as chilled water piping replacement and additional fan coil unit work may be included pending available funds. Proposals are due through the SAM.gov website by the dates specified in the solicitation package, which is available in full on SAM.gov as of July 27, 2021. A pre-bid meeting will be held on July 30, 2021. The National Park Service is the contracting agency seeking these construction services at the Belmont-Paul Women's Equality National Monument located within the National Mall and Memorial Parks.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PHASE 2
PRODUCT DATA
FOR
REHABILITATION OF THE BELMONT-PAUL
WOMEN’S EQUALITY NATIONAL MONUMENT
WASHINGTON, D.C.
Prepared for:
UNITED STATES DEPARTMENT OF THE INTERIOR
NATIONAL PARK SERVICE – NATIONAL CAPITAL REGION
Prepared by:
ALPHA CORPORATION
1850 SOUTH LOUDOUN STREET
SUITE 200
WINCHESTER, VA 22601
(540) 723-0704
December 10, 2018
Final CD Phase 2 Submission
A D
V A
N C
ED
A
R C
H G
R
IL
LE
S
D e n to n
A v e n u e
N e w
H y d e
P a rk
N Y
V o ic e
-4
-0
F a x
-4
-0
E m a il sa le s@ a a g ri ll e s.
co m w w w .a ag ri lle s.
co
V A
N C
ED
A
R C
H G
R
IL
LE
S
D e n to n
A v e n u e
N e w
H y d e
P a rk
N Y
V o ic e
-4
-0 x
-4
-0 a il sa le s@ a a g ri ll e s.
co m w w w .a ag ri lle s.
V A
N C
ED
A
R C
H G
R
IL
LE
S
D e n to n
A v e n u e
N e w
H y d e
P a rk
N Y
V o ic e
-4
-0 x
-4
-0 a il sa le s@ a a g ri ll e s.
co m w w w .a ag ri lle s.
SCALE: FULL
SILL DETAIL3
SCALE: FULL
JAMB DETAIL2
STEEL TAPE
DEEP GUIDE
MAGNETIC SEAL TAPE
ALUMINUM EXTRUSION
MAGNETIC ONE LITE • MOL
SCALE: FULL
HEAD DETAIL1
DEEP GUIDE
ALUMINUM EXTRUSION
MAGNETIC ONE LITE • MOL
PRODUCT
MAGNETIC ONE LITE • MOL
MOUNT TO CHANNEL W / MUNTIN
DWG. NO.
M-2 Allied Window 11111 CANAL ROAD • CINCINNATI, OH 45241 • PH: 800-445-5411, 513-559-1212 • FAX: 513-559-1883 • www.alliedwindow.com • info@alliedwindow.com
NOTE: MAGNETIC SCREEN AVAILABLE
T-9 MUNTIN
OPTIONAL
MUNTIN DETAIL
D-46 HANDLE FRAME
SILL SEAL
WEATHERSTRIPPING
0" ½" 1"
Graphic Scale
1/27/15 Master Copy
Performance Panels ®
WALL
LARGO™
GLAZED CERAMIC
WHITE LR94
LIGHT GREY LR93
ALMOND LR95
WALL TILE
©2016 Dal-Tile Corporation (8/16)
SIZES
Thickness Sq. Ft.
per Carton
Pieces per
Carton
6 x 6
Wall Tile
(6" x 6")
(15.20 cm x 15.20 cm) 5/16" 12.50 50
4-1/4 x 4-1/4
Wall Tile
(4-1/4" x 4-1/4")
(10.80 cm x 10.80 cm) 5/16" 12.50 100
3 x 6
Wall Tile
(3" x 6")
(7.62 cm x 15.20 cm) 5/16" 12.50 100
INSTALLATION
Grout Joint Recommendation Shade Variation
1/16" Low (V1)
TEST RESULTS
ASTM#
Wall
Result
Water Absorption C373 < 20.0%
Breaking Strength C648 120-230 lbs
Scratch Hardness MOHS 4.0-6.0
Chemical Resistance C650 Resistant
NOTES
Since there are variations in all fired ceramic products, tile and trim supplied for your particular installation may not match these samples. Final color selection should be made from actual tiles and trim and not from tile samples or color reproductions. Manufactured in accordance with ANSI A137.1 standards.
For additional information refer to “Factors to Consider” at daltile.com/Factors.
APPLICATIONS
Suitable
Floors
Walls/Backsplashes
Countertops
Pool Linings
APPLICATION NOTES:
Suitable for exterior wall applications in non-freezing climates only when proper installation methods are followed.
TRIM
Type Number Size Pieces per
Carton
Wall Bullnose S-4369
(6" side) 3 x 6 100
Wall Bullnose
Corner SN-4339 3 x 3 24
Wall Bullnose S-4269
(6" side) 2 x 6 100
Wall Bullnose
Corner SN-4269 2 x 2 25
Radius Bullnose A-4200 2 x 6 64
Radius Bullnose
Corner AN-4200 2 x 2 18
Quarter Round A-106 1 x 6 180
Quarter Round
Corner UC-106 1 x 1 40
7834 C. F. Hawn Freeway, Dallas, Texas 75217 | 1.800.933.TILE
To view the complete collection of Daltile® products and information, visit our website at daltile.com.
DESIGNED TO HELP EARN LEED™
CREDITS. For more detailed information, visit daltilegreenworks.com. ©2016 Dal-Tile Corporation (10/16)
WALL
LARGO™
GLAZED CERAMIC
SCAN QR CODE
FOR PRODUCT
INFORMATION
Get a QR Code reader at:
GET.DALTILE.COM
6/18/2018 J-Bead Frame for Perforated Grilles - AAG http://aagrilles.com/j-bead/j-bead-frame-for-perforated-grilles/ 1/3
J-Bead Frame for Perforated Grilles
SEEMINGLY SIMPLE.
SIMPLY SEAMLESS.
Artistry in Architectural Grilles a/k/a AAG
Advanced Architectural Grilleworks, the innovator of the Plaster J-Bead frame for linear bar grilles has developed a similar product for perforated metal grilles that will improve installation speed and accuracy while providing a strong and seamless nished result.
“HVAC Industry standards were not satisfying our customers’ requirements so we undertook extensive testing and development with some of our key HVAC clients and engineers. The resulting solution is a J-Bead frame for perforated grilles with numerous unique features including multiple core mounting options.”
REQUEST A QUOTE
Home Grilles Plaster J-Bead® Request a Quote Resources Projects About Contact http://aagrilles.com/j-bead/j-bead-frame-for-perforated-grilles/ 2/3
CONTAC
T US
516-488-
516-488-0728 (fax)
149 Denton
TESTIMONIALS FOLLOW US
THE PERFORATED GRILLE WITH J-BEAD FRAME
FULLY WELDED – A SOLID, ONE PIECE UNIT
There are no unsightly rivets, welds or seams that can crack or pull-apart as is the current industry standard. The ange provides multiple recessed capture areas for plaster or “mud” and there is a step enabling the nishers to smoothly and cleanly apply an initial coat and a nal skim coat. Additionally, there are numerous pre-punched holes designed to accept standard wall board screws with spacing to accommodate any wall condition.
The perforated grille J-Bead style frame can be provided in any shape or con guration
( xed or removable; with or without a door) and will accommodate either lter slots or opposed blade dampers.
The frame is available in aluminum with a full range of nishes: satin #4, satin – clear anodized, mirror polish #8, prime painted, or powder coated.
http://aagrilles.com/j-bead/j-bead-frame-for-perforated-grilles/ 3/3
Ave New Hyde
Park, NY 11040
SALES@AAG
RILLES.COM
© AAG 2016 Advanced Architectural Grilleworks, Advanced Grille, Advanced Arch Grilles, Artistry in Architectural Grilles & Metal. *Plaster J-Bead Patent #9,765,988. Under license by Dan Roeper 149 Denton Ave. New Hyde Park, NY 11040. Ph:
516-488-0628; sales@aagrilles.com. All rights reserved. Use of any logos, images or text in this web site without full express, written permission is prohibited. Violaters will be prosecuted to the full extent of the law.
Site designed by 13PRIME
PO Box 1960 | Winston, Oregon 97496 | t: 541.679.6791 | f: 541.679.5063 | oregondoor.com
AWAC4901 Architectural Series Acoustic Core STC 49
Positive Pressure 5-Ply Thickness 2-¼” Only
Maximum Sizes Non-Rated: Single 40 x 80 Pairs not available Up to 20 minute: Single 40 x 80 Pairs not available
Core Proprietary NAF acoustic core
Edges Stiles: Minimum width 1-¼” SCL with matching or compatible edge band Rails: Minimum width 3-5/8” SCL
Edge Construction Category B: Frame applied intumescent required
Faces All commercially available species veneers per AWI 1300, G11. 1/50” minimum veneer thickness, medium density overlay (MDO), hardboard (1)
Cross Bands NAF high density fiberboard (HDF)
Adhesive Type 1—Waterproof Bond NAF
Core Bonding Stiles and rails are securely bonded utilizing type 1 adhesive in conjunction with superior RF bonding technology. To ensure freedom from telegraphing of core components, the core unit is then sanded before face veneers are applied.
Warranty (2) Interior Use—Life of installation Exterior Use—No Warranty
Construction Standards
Meet or Exceed WDMA I.S. 1-A NFPA 80 AWS Section 9 WH/ITS Labeling Service
UBC7-2-1997 UL10C
ASTM E 90 under Architectural Testing Inc.
Performance Standards Meets or exceeds WDMA I.S.1-A Heavy Duty performance
Factory Finish WDMA TR-8/AWS System 9 (UV Cured Acrylated Polyurethane) > Clear > Standard color selections > Custom color matching (3)
Factory Machining > Pre-fitting >Templated hardware prep > Lite cutouts (consult factory) Consult factory for full list of machining options
Gasketing Gasket system #103, supplied by others, required for approved STC rating.
Contact factory for hardware details and test report
Sustainability
CALGreen Compliant GREENGUARD and GREENGUARD Gold Certified No-Added Formaldehyde (NAF) Extracted: Clarksville, Iowa. Manufactured: Winston, Oregon
(1) Hardboard available in 3-ply construction only.
(2) See complete Oregon Door warranty for details.
(3) Set-up fee for custom matching applies. Approval of custom samples is required prior to finishing.
3_
S
3_
S_
CU
T R ev
.1 0.
AV
AI
LA
BL
E
FI
N
IS
H
ES
: A , B
D G
, D , G
, P W
, S N
W
ID
TH
: 1
/4
(6 .4 m m
PR
O
FI
LE
H
EI
G H
T:
/8
(2 2.
m m
TO
TA
L H
EI
G
H T
W
IT
H
IN
SE
RT
: 1 -1
/8
(2 8.
m m
A (M ill Fi ni sh
A lu m in um
BD
G
(B rig ht D ip G ol d
An od iz ed
A lu m in um
D (D ar k
Br on ze A no di ze d
Al um in um
G
(G ol d An od iz ed A lu m in um
PW
(P ai nt ed
W hi te A lu m in um
SN
(S at in N ic ke l A no di ze d Al um in um
Co py ri gh t ©
7, P em ko M an uf ac tu ri ng
C o.
, a n
A
SS
A
AB
LO
Y
G ro up c om pa ny . A ll ri gh ts re se rv ed
Re pr od uc ti on in w ho le o r i n pa rt w it ho ut th e ex pr es s w ri tt en p er m is si on o f P em ko M an uf ac tu ri ng
C o.
is p ro hi bi te d.
TI
TL
E:
PR
EP
AR
ED
F O
R:
PR
EP
AR
ED
B Y:
D
AT
E:
CO
M
M
EN
TS
Pe m ko P er im et er
G as ke tin g:
St an da rd P er im et er
G as ke tin g
Ar ch ite ct ur al oo r A cc es so rie s
_P K
_P
K_
CU
T R ev
.2 8.
AV
AI
LA
BL
E
FI
N
IS
H
ES
: A , D
W
ID
TH
: 4
(1
.6 m
H
EI
G H
T:
/2
(1 2.
m m
A (M ill Fi ni sh
A lu m in um
D (D ar k
Br on ze A no di ze d)
(3 9.
7)
(1 2.
7)
(6 .4
(6 .4
(1
.6
Co py ri gh t ©
7, P em ko M an uf ac tu ri ng
C o.
, a n
A
SS
A
AB
LO
Y
G ro up c om pa ny . A ll ri gh ts re se rv ed
Re pr od uc ti on in w ho le o r i n pa rt w it ho ut th e ex pr es s w ri tt en p er m is si on o f P em ko M an uf ac tu ri ng
C o.
is p ro hi bi te d.
TI
TL
E:
PR
EP
AR
ED
F O
R:
PR
EP
AR
ED
B Y:
D
AT
E:
CO
M
M
EN
TS
Pe m ko C om m er ci al T hr es ho ld s:
La tc hi ng P an ic
E xi t S ad dl es
Ar ch ite ct ur al oo r A cc es so rie s
Index
Sections 211313 – Automatic Sprinkler System
1. Schedule 40 Black Steel Sprinkler Pipe.
2. Upright Sprinkler.
3. Nitrogen generator
4. Wood Fasteners
1819 Clarkson Road, Chesterfield, MO 63017 US: 800.325.4467 | Canada: 800.882.4666 | sales@BullMooseIndustries.com
SCHEDULE 10 & 40 SPRINKLER PIPE SUBMITTAL DATA SHEET
APPROVALS AND SPECIFICATIONS
• ASTM A135, Grade A
• ASTM A795, Type E, Grade A
• Pressure rated to 300 psi
• Underwriters Laboratories— United States of America
• Underwriters Laboratories—Canada
• Factory Mutual
• NFPA-13
• NFPA-13R
• NFPA-14
• CIVIL DEFENSE APPROVAL—
United Arab Emirates
• Made in the United States of America
• UL, ULC & FM listed for roll-groove, plain-end and welded joints for wet, dry, preaction and deluge sprinkler systems.
• LEED v4 Certified
FINISHES AND COATINGS
• Schedule 10 & 40 Sprinkler Pipe receives an OD mill coating of water-based paint which has corrosion protection expected with a painted carbon steel product, i.e. it would be expected to resist corrosion for an extended and indefinite period in a clean and dry environment and, as environmental conditions deteriorate, the corrosion protection would also diminish.
• Schedule 10 & 40 Sprinkler Pipe (black) receives an ID mill coating of Eddy Guard II MIC preventative coating. EG2 has been tested at independent laboratories to resist bacterial growth and maintain minimal bacterial count after multiple flushes (25) of the pipe.
• Schedule 10 & 40 Sprinkler Pipe when Hot Dip Galvanized by ASTM A123 and supplied by Bull Moose Tube is UL listed and FM approved.
PRODUCT IDENTIFICATION
• Every length of Bull Moose fire sprinkler pipe features large, easy-to-read, continuous stenciling, clearly identifying the manufacturer, type of pipe, size, and length.
Nominal Pipe Size (inches) 1 1-1/4” 1-1/2” 2” 2-1/2” 3” 4” 6” 8” O.D. (in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 6.625 8.625
I.D. (in) 1.097 1.442 1.682 2.157 2.635 3.260 4.260 6.357 8.249
Empty Weight (lb/ft) 1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940
Water Filled Weight (lb/ft) 1.800 2.518 3.053 4.223 5.893 7.957 11.796 23.038 40.086
C.R.R.* 15.27 9.91 7.76 6.27 4.92 3.54 2.50 1.158 1.805
Pieces per Lift 91 61 61 37 30 19 19 10 7
O.D. (in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500
I.D. (in) 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Empty Weight (lb/ft) 1.680 2.270 2.720 3.660 5.800 7.580 10.800
Water Filled Weight (lb/ft) 2.055 2.918 3.602 5.114 7.875 10.783 16.316
C.R.R.* 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Pieces per Lift 70 51 44 30 30 19 19
*Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY
SUBMITTAL INFORMATION
Project
Contractor
Engineer
Specification Reference
Locations
Comments
System TypeDate
Schedule 10 - Black Schedule 40 - BlackSchedule 10 - Hot Dip Galvanized Schedule 40 - Hot Dip Galvanized
Sc he du le
Sc he du le microfast® quick response upright sprinkler Vk300 (k5.6) technical Data
Form No. F_052114 17.10.05 Rev 17.1 the Viking corporation, 210 n industrial park Drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. Description The Viking Microfast® Quick Response Upright Sprinkler VK300 is a small, thermosensitive, glass-bulb spray sprinkler available in several differ-ent finishes and temperature ratings to meet design requirements. The spe-cial Polyester and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coat-ings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: fm global approves the ent coating as corrosion resistant. FM Global has no approval classification Polyester coatings as corrosion resistant.)
2. listings anD approVals culus listed: Category VNIV fm approved: Classes 2002 and 2020
Refer to Approval Charts and Design Criteria for listing and approval requirements that must be followed.
3. technical Data Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: 1/2” NPT, 15 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 2-3/16” (56 mm)
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar).
material standards:
Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Brass UNS-C23000 or Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated ordering information: (Also refer to the current Viking price list.)
Order Viking Microfast® Quick Response Upright Sprinkler VK300 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2” NPT thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB available finishes and temperature ratings: Refer to Table 1.
accessories: (Also refer to the Viking website.)
sprinkler Wrench: Standard Wrench: Part No. 21475M/B (available since 2017) sprinkler cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. installation Refer to appropriate NFPA Installation Standards.
Replaces Form No. F_052114 Rev 15.2 (Replaced wrench 10896W/B with 21475M/B) mcpolley Highlight mcpolley Highlight mcpolley Highlight sprinkler Vk300 (k5.6) technical Data
Form No. F_052114 17.10.05 Rev 17.1 the Viking corporation, 210 n industrial park Drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
5. operation During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. inspections, tests anD maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. aVailability The Viking Microfast® Quick Response Upright Sprinkler VK300 is available through a network of domestic and international distributors.
See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. guarantee For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
table 1: aVailable sprinkler temperature ratings anD finishes sprinkler temperature classification sprinkler nominal temperature rating1 maximum ambient ceiling temperature2 bulb color
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue sprinkler finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT corrosion-resistant coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C) footnotes 1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only.
Note that the spring is exposed on sprinklers with Polyester, ENT, and PTFE coatings. For ENT coated automatic sprinklers, the waterway is coated.
figure 1:
standard sprinkler Wrench 21475m/b protective sprinkler cap
Wrench flat sprinkler Vk300 (k5.6) technical Data
Form No. F_052114 17.10.05 Rev 17.1 the Viking corporation, 210 n industrial park Drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com approval chart 1 (ul) microfast® quick response upright sprinkler Vk300 maximum 175 psi (12 bar) WWp base part number1 sin thread size nominal k-factor overall length listings and approvals3 npt bsp u.s. metric2 inches mm culus Vds lpcb nyc8
12978 VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A1, B2 -- -- See footnote 7. -- NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
06661B VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A1, B2 -- -- See footnote 7. --approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and
286 °F (141°C) B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) approved finishes 1 - Brass, Chrome, White Polyester5,6, and Black Polyester5,6
2 - ENT6
footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for us in the U.S. and Canada 5 Other colors are available on request with the same Listings and Approvals as the standard colors.
6 cULus Listed as corrosion resistant.
7 Meets New York City requirements, effective July 1, 2008 8 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA and City of New York Department of Buildings, MEA 89-92-E, Vol. 16.
Design criteria - ul (Also refer to Approval Chart 1 above.)
culus listing requirements:
The Viking Microfast® Quick Response Upright Sprinkler VK300 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers.
| • | Designed for use in Light and Ordinary Hazard occupancies. |
| • | The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. |
important: always refer to bulletin form no. f_091699 - care and handling of sprinklers. also refer to form
no. f_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of nfpa, fm global, lpcb, apsaD, Vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
mcpolley Highlight sprinkler Vk300 (k5.6) technical Data
Form No. F_052114 17.10.05 Rev 17.1 the Viking corporation, 210 n industrial park Drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Design criteria - fm (Also refer to Approval Chart 2 above.)
fm approval requirements:
The Microfast® Quick Response Upright Sprinkler VK300 is FM Approved as a quick response non-storage upright sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
note: the fm installation guidelines may differ from culus and/or nfpa criteria.
important: always refer to bulletin form no. f_091699 - care and handling of sprinklers. also refer to form
no. f_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of nfpa, fm global, lpcb, apsaD, Vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
approval chart 2 (fm) microfast® quick response upright sprinkler Vk300 maximum 175 psi (12 bar) WWp base part number1 sin thread size nominal k-factor overall length fm approvals3
(refer also to Design criteria below.)npt bsp u.s. metric2 inches mm 12978 VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A1, B2
NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 06661B VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A1, B2 approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) approved finishes 1 - Brass, Chrome, White Polyester5, and Black
Polyester5
2 - ENT6
footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals.
5 Other colors are available on request with the same Approvals as the standard colors.
6 FM approved as corrosion resistant.
Replaces Form No. F_052114 Rev 15.2 (Replaced wrench 10896W/B with 21475M/B)
ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E)
PGEN-5/(PGEN-5E)
Specifications
Dimensions: 24” (W) X 36” (H) X 9” (D) (610mm (W) X 914mm (H) X 229mm (D)) Weight 125 lbs (57kg) Power Supply: 120v/1 phase/60Hz (dedicated circuit) (230v/1 phase/50Hz (dedicated circuit)) Power Consumption: 6 Amps
Nitrogen/air connection: ½” NPT Female
Drain connection: ¼” NPT Female
FM Approved UL 508A Listed Industrial Control Panel
ECS Pre-Engineered Nitrogen Generator designed for fire sprinkler systems
ECS Pre-Engineered Nitrogen Generator PGEN-3/(3E)/PGEN-5/(5E) September 2017 - Rev 0
Engineered Corrosion Solutions 11336 Lackland Road St. Louis, MO 63146 Phone 1-314-432-1377 www.ecscorrosion.com
General Description
The ECS Pre-Engineered Wall Mount Nitrogen Generators are designed for use in facilitating the Dry Pipe Nitrogen Inerting (DPNI) process for controlling oxygen corrosion in dry and preaction fire sprinkler systems. The ECS Nitrogen Generators are designed for “plug and play” performance in a typical dry or preaction fire sprinkler system.
The ECS Pre-Engineered Nitrogen Generators can be used to provide DPNI for single or multiple zones depending on the number of systems, the volume of the largest system and the cumulative volume of all systems being supplied.
The ECS Nitrogen Generators are designed to nitrogen inert all of the zones being served within 14 days.
Thereafter, the ECS Nitrogen Generators continue to automatically provide supervisory nitrogen gas sufficient for pressure maintenance of the fire sprinkler system(s).
The ECS Nitrogen Generators facilitate the patented “fill and purge” breathing process in the fire sprinkler system when paired with a venting device installed on the sprinkler riser such as the ECS Protector Manual Vent (PAV-D) or the ECS Protector Dry SMART Vent
(PSV-D).
Ordering Information
Stock Number: PGEN-3(E)/PGEN-5(E)
Replacement Filters: PGEN-FKW (annual maintenance)
Replacement Membrane: PGEN-MW (20 year expected service life)
For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533
The ECS Pre-Engineered Nitrogen Generator is a self-contained wall mounted unit that includes the following components:
• Steel enclosure cabinet with membrane type nitrogen generator (no nitrogen gas storage) and manual bypass
• Power supply - 120v/1 phase/60Hz (230v/1 phase/50Hz)
• Single point nitrogen/air discharge – ½” NPT
• Oil less air compressor
• Hour Run Meter
• Cycle Counter
The ECS Nitrogen Generator includes the following function Indications:
• Bypass Alarm - Nitrogen generator is in the “By-Pass” mode (Flashing Indicator)
• Leak Monitoring - Nitrogen generator running excessively (Audible Signal)
The ECS Nitrogen Generator includes the following monitoring outputs:
• System Power (Digital Output)
• Bypass Mode Alarm (Digital Output)
• Nitrogen Generation Mode (Digital Output)
• Nitrogen Supply Line Pressure (Analog Output)
• Leak Monitoring (Digital Output)
The ECS Nitrogen Generator is designed to be used in conjunction with the following components as part of the complete ECS Dry Pipe Nitrogen Inerting (DPNI) system:
• Air maintenance device with on board adjustable regulator (recommend Victaulic Series 757, Tyco Model AMD– 1 or Reliable Model A-2)
• Riser-mounted ECS Protector Manual Vent (PAV-D) or ECS Protector Dry SMART Vent (PSV-D)
• ECS Protector SMART Gas Analyzer (SGA-1/(1E)) – one per nitrogen generator is recommended
• ECS In-Line Corrosion Detector (ILD-X) – monitoring at least one system is recommended
ECS Pre-Engineered Nitrogen Generator PGEN-3(3E)/PGEN-5(5E) September 2017 - Rev 0
Engineered Corrosion Solutions 11336 Lackland Road St. Louis, MO 63146 Phone 1-314-432-1377 www.ecscorrosion.com
Operating Performance
Model Number
Min. Supply Air
(SCFM)
Total System Capacity (Gallons)
Single System Capacity† @ 40 psig (Gallons)
Single System Capacity† @ 20 psig (Gallons)
Sound Level dBA @ 10’
PGEN-3 2.5 675 215 540 56
PGEN-5 3.3 950 265 590 57
Model Number
Min. Supply Air (L/min)
Total System Capacity (Liters)
Single System Capacity† @ 2.8 bar (Liters)
Single System Capacity† @ 1.4 bar (Liters)
Sound Level dBA @ 3m
PGEN-3E 71 2,555 814 2,044 56
PGEN-5E 94 3,596 1,003 2,233 57
† Capacity based on NFPA 13 30-minute fill requirement of largest single system
Nitrogen Quality
N2 Purity at Discharge: 98% or greater (maximum of 2.0% oxygen) N2 Pressure at Discharge: Min of 15 psig (1 bar); Max of feed air pressure minus 15 psig (1 bar) N2 Water Dew Point: Typically less than –70ºF (–57ºC)
Note: When connecting an ECS Protector Nitrogen Generator to an existing dry pipe/preaction fire sprinkler system, the existing fire sprinkler system(s) must be limited to a maximum leak rate of less than 3 psig (2 bar) within a 24 hour period, per system.
Installation Instructions
Installation of the ECS Nitrogen Generator requires five (5) steps:
1. Mount the Nitrogen Generator cabinet on the wall in the appropriate location within the riser room
2. Bring the dedicated power supply lines to the NEMA4 power supply box in the cabinet
3. Plumb the nitrogen/air supply line to the trim work on the dry or preaction zones being served
4. Plumb the drain line to floor drain or building exterior
5. Connect Nitrogen generator output signals to BMS or fire alarm system, where applicable
Step 1: Mounting the Wall Mounted Nitrogen Generator
The ECS Nitrogen Generator is designed to be mounted directly to the wall at the installation location.
Several factors should be considered in choosing the proper mounting location for the nitrogen generator:
• Access to the power supply (dedicated circuit as per above)
• Access to the sprinkler riser being supplied from the nitrogen generator
• Clearance at the front of the unit to open the cabinet door
• Ability to support cabinet weight at mounting location - 125 lbs (57kg)
The nitrogen generator cabinet assembly includes a mounting rail for wall mounting using standard anchors.
Step 2: Power Supply
The Nitrogen Generator requires a dedicated power supply line that ties into a single point in the generator cabinet.
Step 3: Plumb the Nitrogen/Air Supply Line
The nitrogen/air discharge plumbing from the Nitrogen Generator is to be connected directly to the dry or preaction valve trim work as per standard fire sprinkler compressed air supply lines using ½” black steel, galvanized steel or copper piping. The Nitrogen Generator requires an in-line Air Maintenance Device (AMD) that is equipped with an on board field adjustable pressure regulator for each zone being served. The preferred AMD is the Victaulic Series 757.
ECS Pre-Engineered Nitrogen Generator PGEN-3(3E)/PGEN-5(5E) September 2017 - Rev 0
Engineered Corrosion Solutions 11336 Lackland Road St. Louis, MO 63146 Phone 1-314-432-1377 www.ecscorrosion.com
120v/1 Phase Connections (230/1 Phase 50 Hz Connections)
G L1 N
Note: When both dry pipe and preaction fire sprinkler systems are connected to one nitrogen generator, additional equipment may be required if the fire sprinkler systems operate at different supervisory gas pressures.
Step 4: Plumb the Condensate Drain Line
The ECS Protector Nitrogen Generator will occasionally discharge a small amount of condensate water from the coalescing filters inside the cabinet. It is recommended that the 1/4” drain connection be plumbed to a floor drain or building exterior. When plumbing to a drain is not feasible an evaporative collection chamber can be used.
Step 5: System Signals and Monitoring, where used
The nitrogen generator cabinet has two (2) system signals and five (5) outputs that can be monitored by the facility’s BMS or fire alarm system.
• The nitrogen generator is operating in the bypass mode which is activated when the bypass valve is in the “fast fill” position to fast fill the fire sprinkler system and the air supplied directly from the air compressor has reached a pressure of 20 psig (1.4 bar). (Flashing amber light)
• The nitrogen generator is equipped with a leak monitor audible signal which is activated when the nitrogen generator runs excessively. (Audible signal)
The nitrogen generator cabinet includes system monitoring signals which can be monitored through a building monitoring system, if desired:
• Nitrogen Generator Loss of Power (Form C contacts)
• Bypass Mode Alarm (Form C contacts)
• Nitrogen Generation Mode (Form C contacts)
• Nitrogen System Supply Line Pressure (Analog Signal)
• Leak Monitoring (Form C contacts)
ECS Pre-Engineered Nitrogen Generator PGEN-3(3E)/PGEN-5(5E) September 2017 - Rev 0
Engineered Corrosion Solutions 11336 Lackland Road St. Louis, MO 63146 Phone 1-314-432-1377 www.ecscorrosion.com
By-Pass Alarm Monitoring Output
Nitrogen Generation Monitoring Output
Nitrogen Generator Power Monitoring Output
Leak Monitoring Output
Maintenance of the Nitrogen Generator
The nitrogen generator cabinet contains two (2) separate cartridge filters. It is recommended that each of the filter cartridges be replaced as part of an annual preventative maintenance program. In some environments it may be necessary to replace filters more frequently. The filter replacement kit for the nitrogen generator is part number PGEN-FKW. When maintained properly the nitrogen separation membrane will provide up to 20 years of service life. The membrane replacement part number is PGEN-MW.
Cartridge Filter Exchange Procedure
Preliminary Steps (taking the nitrogen generator out of service)
1. Turn the power supply to the unit off
2. Close the regulated and fast fill valves on fire sprinkler system’s air maintenance device(s)
3. Turn the bypass valve in the nitrogen generator to the “fast fill” position
4. The Nitrogen Generator is designed to depressurize the inlet piping through the permeate of the nitrogen separation membrane when the nitrogen generator automatically shuts off
ECS Pre-Engineered Nitrogen Generator PGEN-3(3E)/PGEN-5(5E) September 2017 - Rev 0
Engineered Corrosion Solutions 11336 Lackland Road St. Louis, MO 63146 Phone 1-314-432-1377 www.ecscorrosion.com
ECS PRE-ENGINEERED NITROGEN GENERATION SYSTEM
(typical installation schematic)
Engineered Corrosion Solutions 11336 Lackland Road St. Louis, MO 63146 Phone 1-314-432-1377 www.ecscorrosion.com
Coalescing Filter Cartridge Exchange Procedure
The two filters with the condensate drain tube extending from the bottom of the filter housing are coalescing filters.
To replace the filter cartridges follow Step 1 through Step 6.
Step 1: Grasp the ¼” clear drain tube on the bottom of the filter housing with the right hand. With the left hand, push upward on the grey retaining ring on the filter housing outlet fitting. This motion will allow for the ¼” clear drain tube to be removed from the fitting. Gently pull the ¼” clear drain tube downward out of the fitting and let it hang.
Step 2: Once the ¼” clear drain tube has been disconnected, the filter housing bowl may be unscrewed from the top portion of the filter housing which is connected to the internal system piping.
Step 3: Once the filter housing bowl has been removed, the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartridge and then pulling down on the cartridge.
Discard the old filter cartridge and replace it with the appropriately marked filter cartridge from the maintenance kit by pushing up so that it fits snugly onto the receiving stepped cylinder in the upper part of the filter housing. Screw the black retaining disc back onto the central metal threaded rod.
Important: HAND TIGHTEN ONLY!
Clear Drain Tube
Filter Cartridge
Step 4: Replace the filter housing bowl by screwing it onto the filter housing top.
Important: HAND TIGHTEN ONLY!
Step 5: Reconnect the ¼” clear drain tube into the fitting on the filter housing bowl. Make sure that it fully seats in the fitting and is retained snugly.
Step 6: Repeat Step 1 through Step 5 for the remaining coalescing filter.
Step 7: The Nitrogen Generator can now be placed back into service.
Return the Nitrogen Generator to Service
1. Turn the power supply to the unit on
2. Open the regulated valve on fire sprinkler system’s air maintenance device(s)
ECS Protector Nitrogen Generator Optional Monitoring Equipment
• ECS Protector Handheld Gas Analyzer (PHGA-1): portable handheld gas analyzer includes one-button calibration and enables user to measure nitrogen concentration at nitrogen generator cabinet or gas sampling ports on ECS venting devices
• ECS Protector SMART Gas Analyzer (SGA-1): permanently installed near an ECS Protector Manual/SMART Vent to continuously report nitrogen gas concentration to a building information or management system; includes digital display and provides 0-5V DC or 4-20mA output signals
• ECS In-Line Corrosion Detector (ILD-X): installed in-line within the fire sprinkler system piping at locations most susceptible to corrosion; provides either a local push-button test/indicator or control panel monitoring
Engineered Corrosion Solutions 11336 Lackland Road St. Louis, MO 63146 Phone 1-314-432-1377 www.ecscorrosion.com
Black Disc
Filter Cartridge
4 For the most up to date information, visit www.itwbuildex.com
Wood Flooring
Wood Joist
Double Sheetrock Ceiling
Approvals Rod Size
Part Number Model Screw
Descriptions Ultimate
Pullout (lbs) UL Test
Load (lbs) FM Test
Load (lbs) Box Qty
Case Qty
VERTICAL MOUNT
1/4" 8002957 GST 100 1/4 x 1" 210 (7/16” OSB) 670 (3/4” Ply) 25 125
1/4" 8003957 GST 200 1/4 x 2" 1760 (Fir) 25 125 1/4" 8004957 GST 300 1/4 x 3" 2060 (Fir) 25 125
3/8" 8007957 GST 10 1/4 x 1" 210 (7/16” OSB) 670 (3/4” Ply) 300 25 125
3/8" 8008957 GST 20 1/4 x 2" 1760 (Fir) 850 1475 25 125 3/8" 8068925 GST 20-SS 1/4 x 2" 1760 (Fir) 850 25 125 3/8" 8009925 GST 25-380 3/8 x 2-1/2" 2113 (Fir) 1500 25 125 3/8" 8010957 GST 30 1/4 x 3" 2060 (Fir) 1500 1475 25 125 3/8" 8069925 GST 30-SS 1/4 x 3" 2060 (Fir) 25 125 3/8" 8011925 GST 40 1/4 x 4" 2180 (Fir) 25 125 1/2" 8013925 GST 2 1/4 x 2" 1760 (Fir) 25 125 1/2" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113 (Fir) 25 125 1/2" 8015925 GST 3 1/4 x 3" 2275 (Fir) 25 125
Not less than 2” nominal width
(1-1/2”)
Not less than 3” nominal thickness (2-1/2”) (depth or side of vertical member)
#14 Black Nut Driver
Part # 8113910
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.
#14 SW Red Nut Driver
Part # 8114910
Composite / Truss Consult truss manufacturer for recommended installation point.
*Pre-drilling may be required for GST 25-380 . Tool available on page 11.
For vertical use -install in center of lower face.
Minimum 2” embedment into base material for NFPA 13 compliance.
• No pre-drilling required.
• Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver.
• Saves time from traditional methods.
• Reduces installation costs.
• Made in the U.S.A.
SAMMYS® FOR WOOD
Application Product Features
Watch a video demonstration at www.itwbuildex.com
SAMMYS® FOR WOOD - Vertical Application
5 To find a distributor near you, call 800-BUILDEX
S T
E E
L S
T E
E L
W O
O D
A P
P R
O V
A L
S A
C C
E S
S O
R
IE
S C
O N
C R
E T
E
Not less than 2” nominal width (1-1/2”) up to 3-1/2” pipe; not less than 3” (2-1/2”) nominal width 4” & 5” pipe
Minimum 2-1/2” from bottom for branch lines. Minimum 3” from bot-tom for main lines. Exception: This requirement shall not apply to 2” or thicker nailing strips resting on top of steel beams.
Floor Joist
Approvals Rod Size
Part Number Model Screw
Descriptions Ultimate
Pullout (lbs) UL Test
Load (lbs) Box Qty
Case Qty
HORIZONTAL MOUNT
1/4" 8019957 SWG 200 1/4 x 2" 1725 (Fir) 25 125 3/8" 8020957 SWG 10 1/4 x 1" 622 (Fir) 300 25 125 3/8" 8021957 SWG 20 1/4 x 2" 1725 (Fir) 1050 25 125 3/8" 8073925 SWG 20-SS 1/4 x 2" 1725 (Fir) 850 25 125
3/8"* 8022925 SWG 25-380 3/8 x 2-1/2" 2249 (Fir) 1500 25 125 3/8" 8023925 SWG 30 1/4 x 3" 1884 (Fir) 25 125#14 SW Red
Nut Driver Part # 8114910
• No pre-drilling required.
• Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver.
• Saves time from traditional methods.
• Reduces installation costs.
• Made in the U.S.A.
Approvals Rod Size
Part Number Model Screw
Descriptions Ultimate
Pullout (lbs) UL Test Load
(lbs) FM Test
Load (lbs) Min
Thickness Box Qty
Case Qty
SWIVEL MOUNT
3/8" 8139957 SH-GST 20 1/4 x 2" 1257 (Fir) 1050 1475 25 125 3/8" 8141957 SH-GST 30 1/4 x 3" 1720 (Fir) 1500 1475 25 125
3/8"* 8269957 SH-GST/CST 20 5/16 x 1-3/4” 1903 Dim. Lumber 1406 @ 45°off vertical Dim. Lumber
850 @ 45° 25 125
1/2” 8303957 SH-GST/CST 2.0 5/16 x 1-3/4” 903 Dim. Lumber 1406 @ 45°off vertical Dim. Lumber
25 125
#14 Black Nut Driver
Part # 8113910
• Eliminates distortion of threaded rod.
• Accommodates up to 3 ½” x 12 pitch roof.
• Allows 17° deflection from vertical.
• Saves time from traditional methods.
• Reduces installation costs.
• Made in the U.S.A.
Application Product Features
Application Product Features
Composite / Truss Consult truss manufacturer for recommended installation point.
*Pre-drilling may be required for Model SWG 25-380. Tool available on page 11.
Watch a video demonstration at www.itwbuildex.com
SIDEWINDER® FOR WOOD - Horizontal Application
SAMMYS SWIVEL HEAD™ FOR WOOD - Swivel Application
#14 SH Orange Nut Driver
Part # 8273910
* May require pre-drilling; consult joist manufacturer.
* May require pre-drilling; consult joist manufacturer.
Index
Section 283111 – Digital, Addressable Fire Alarm System
1. Notifier by Honeywell Addressable Monitor Module.
DN-6720:E • 07/30/2015 — Page 1 of 4
FMM-1(A), FMM-101(A),
FZM-1(A) & FDM-1(A)
Monitor Modules with FlashScan®
Intelligent/Addressable Devices
DN-6720:E
General Four different monitor modules are available for Notifier’s intelligent control panels for a variety of applications. Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors
(FZM-1(A)).
FMM-1(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices.
FMM-101(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.65" (1.651 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the FMM-101(A) to be mounted in a single-gang box behind the device it monitors.
FZM-1(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit.
FDM-1(A) is a standard-sized dual monitor module that mon-itors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems.
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER that greatly increases the speed of communication between analog intelligent devices.
Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other communication protocols.
FMM-1(A) Monitor Module
• Built-in type identification automatically identifies this device as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
• LED flashes green during normal operation (programma-ble option) and latches on steady red to indicate alarm.
The FMM-1(A) Monitor Module is intended for use in intelli-gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro-vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The FMM-1(A) can be used to replace MMX-1(A) modules in existing systems.
FMM-1(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit.
FMM-1(A) OPERATION
Each FMM-1(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limita-tions on the loop).
FMM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 375 μA (LED flashing), 1 com-munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
EOL resistance: 47K Ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box.
FMM-1(A) (Type H) co v.
jp g
Page 2 of 4 — DN-6720:E • 07/30/2015
FMM-101(A) Mini Monitor Module
• Built-in type identification automatically identifies this device as a monitor module to the panel.
• Powered directly by two-wire SLC loop. No additional power required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
The FMM-101(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The FMM-101(A) is intended for use in intelligent, two-wire systems where the individual address of each mod-ule is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm and security devices. The FMM-101(A) can be used to replace MMX-101(A) modules in existing systems.
FMM-101(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with spe-cial supervisory indication at the control panel. Monitored cir-cuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the circuit.
FMM-101(A) OPERATION
Each FMM-101(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC).
FMM-101(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 μA, 1 communication every 5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC Shorted).
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 450 μA.
EOL resistance: 47K Ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
FZM-1(A) Interface Module
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry entry of address: 01 – 159 on FlashScan loops, 01 – 99 on CLIP loops.
• LED flashes during normal operation; this is a program-mable option.
• LED latches steady to indicate alarm on command from control panel.
The FZM-1(A) Interface Module is intended for use in intelli-gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module.
The FZM-1(A) can be used to replace MMX-2(A) modules in existing systems.
FZM-1(A) APPLICATIONS
Use the FZM-1(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Cir-cuit. A 3.9 K Ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms). Install ELR across termi-nals 8 and 9 for Style D application.
FZM-1(A) OPERATION
Each FZM-1(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limita-tions on the loop).
FZM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 Ohms.
Average operating current: 270 μA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K Ohms.
External supply voltage (between Terminals T10 and T11):
• DC voltage: 24 volts power limited.
• Ripple voltage: 0.1 Vrms maximum.
• Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
6720m 101.w f
DN-6720:E • 07/30/2015 — Page 3 of 4
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm)…
This is the start of the file's text. The full file is on GovTribe.