E602-E602_0006.pdf
PDF 239 KB Posted
- Attached to
- GRCA 318719_Temporary WWTP at North Rim Federal contract opportunity
- Solicitation number
- 140P2026R0075
About this file
This is an electrical single-line diagram for a temporary wastewater treatment facility (WWTP) located at North Rim, Grand Canyon National Park. The diagram illustrates the complete electrical infrastructure and power distribution system required for the facility's operations.
The system comprises two 30kVA dry-type transformers (T1B and T2B) stepping down from 480V to 208/120V service with NEMA 3R weathershields, each feeding separate distribution panels (PB1-PB4). The facility includes multiple electrical loads distributed across several functional areas: hypochlorite and citric acid chemical storage rooms, caustic storage, and membrane storage containers, each equipped with 6,000 BTUH fan coil/condensing units, chemical injection pumps rated at 350 VA and 110V, and associated receptacles and lighting. The system also supplies power to screening channel equipment (2.5kW at 480V), influent and filtrate lift stations (4HP, 3kW each at 480V), immersion water heaters (72kW at 480V), unit heaters (5kW each at 480V), and a 2HP booster pump operating at 240V single-phase. All circuits are protected by appropriate breakers ranging from 20A to 200A, with main distribution panels rated at 35 KAIC and 22 KAIC. The cabling schedule specifies PVC conduit runs with appropriately sized copper conductors, including ground wires, connecting all components with detailed cable identification from source to destination.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T1B 30kVA DRY TYPE 480 - 208/120V
NEMA 3R WITH WEATHERSHIELDS
T2B 30kVA DRY TYPE 480 - 208/120V
NEMA 3R WITH WEATHERSHIELDS
UH-4
Heater
5KW
480V/3PH
IWH-2
Water Heater 72kW
480V/3PH
110A 3P
200A 3P
50A 3P
MCB3
480/277 VAC
3Ø, 4W 200A
NEMA 3R
35KAIC
20A 3P
20A 1P
20A 1P
20A 1P
20A 2P
CU-4
FAN COIL / CONDENSING UNIT
6000 BTUH : 208-230V/1PH
PMP-6213
CITRIC ROOM PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
PMP-6214
CITRIC ROOM PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
AREA LIGHT : 120V
CITRIC ROOM
RECEPTACLES
20AMP, 120V
100A 3P
20A 1P
20A 1P
20A 1P
20A 1P
UH-1
Heater
5KW
480V/3PH
20A 3P
200A 3P
20A 3P
MCB4
480/277 VAC
3Ø, 4W 200A
NEMA 3R
35 KAIC
50A 3P
110A 3P
IWH-1
Water Heater 72kW
480V/3PH
UH-2
Heater
5KW
480V/3PH
20A 1P
20A 1P
20A 1P
20A 2P
CU-1
FAN COIL / CONDENSING UNIT
6000 BTUH : 208-230V/1PH
PMP-6111
SODIUM HYPO PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
EMERGENCY LIGHT: 120V
AREA LIGHT: 120V
HYPOCHLORITE
ROOM RECEPTACLES
20AMP, 120V
100A 3P
20A 1P
20A 1P
20A 1P
20A 1P
PB1
208/120 VAC
3Ø, 4W 100A
22KAIC
PB2
208/120 VAC
3Ø, 4W 100A
22KAIC
HYPOCHLORITE ROOM
CITRIC ROOM
TO MCB1TO MCB1
FILTRATE LIFT
STATION
PANEL
4HP
3KW
480V/3PH
20A 3P
INFLUENT LIFT
STATION
PANEL
4HP
3KW
480V/3PH
20A 3P
UH-3
Heater
5KW
480V/3PH
20A 3P
20A
1P PMP-6211
CITRIC ROOM PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
20A 1P
20A 1P
PMP-6112
SODIUM HYPO PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
20A 1P
PMP-6212
CITRIC ROOM PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
EXIT LIGHT: 120V
EXIT LIGHT : 120V
SCREENING CHANNEL PANEL
SCN-1011
2.5KW
480V/3PH
20A 3P
OUTDOOR LIGHT : 120VOUTDOOR LIGHT: 120V
G
G
N
G
N
G
N
N
GG
SURGE
ARRESTER
SURGE
ARRESTER
EMERGENCY LIGHT : 120V
PMP-6113
SODIUM HYPO PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
PMP-6114
SODIUM HYPO PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
G G
G G
20A 1P
20A 1P
20A 1P
20A 2P
CU-2
FAN COIL / CONDENSING UNIT
6000 BTUH : 208-230V/1PH
EMERGENCY LIGHT: 120V
AREA LIGHT: 120V
CAUSTIC
ROOM RECEPTACLES
20AMP, 120V
100A 3P
20A 1P
20A 1P
20A 1P
20A 1P
PB4
208/120 VAC
3Ø, 4W 100A
22KAIC
CAUSTIC STORAGE CONTAINER
EXIT LIGHT: 120V
OUTDOOR LIGHT: 120V
G N
G
TO T2B
TO PB4
PMP-6312
CAUSTIC ROOM PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
PMP-6311
CAUSTIC ROOM PUMP 350 VA, 110V
RECEPTACLE: 20AMP, 120V
TO PB3
20A 1P
20A 1P
20A 1P
20A 2P
CU-3
FAN COIL / CONDENSING UNIT
6000 BTUH : 208-230V/1PH
AREA LIGHT : 120V
MEMBRANE STORAGE
RECEPTACLES
20AMP, 120V
100A 3P
20A 1P
20A 1P
20A 1P
PB3
208/120 VAC
3Ø, 4W 100A
22KAIC
MEMBRANE STORAGE
CONTAINER
35A 2P
EXIT LIGHT : 120V
OUTDOOR LIGHT : 120V
N
EMERGENCY LIGHT : 120V
G G
TO T1B
BOOSTER PUMP 2HP - 1PH - 240V
PNEUMATIC PRESSURE SWITCH: 120V
CABLE ID FROM TO CONDUIT CABLE
N MCB3 T1B 2" PVC CONDUIT 1 SET [3#4, #6 (G)]*
O MCB3 IWH-2 2" PVC CONDUIT 1 SET [3#2, #6 (G)]*
P MCB3 UH-3 3/4" PVC CONDUIT 1 SET [3#12, #12 (G)]*
Q MCB3 UH-4 3/4" PVC CONDUIT 1 SET [3#12, #12 (G)]*
R MCB3 FILTRATE LIFT STATION
CONTROL PANEL 2" PVC CONDUIT 1 SET [3#12, #12 (G)]*
S MCB3 INFLUENT LIFT STATION
CONTROL PANEL 2" PVC CONDUIT 1 SET [3#12, #12 (G)]*
T T1B PB1 2" PVC CONDUIT 1 SET [3#2, #2(N), #6 (G)]*
TT T1B PB3 2" PVC CONDUIT 1 SET [3#2, #2(N), #6 (G)]*
CABLE ID FROM TO CONDUIT CABLE
U MCB4 T2B 2" PVC CONDUIT 1 SET [3#4, #6 (G)]*
V MCB4 IWH-1 2" PVC CONDUIT 1 SET [3#2, #6 (G)]*
W MCB4 UH-1 3/4" PVC CONDUIT 1 SET [3#12, #12 (G)]*
X MCB4 UH-2 3/4" PVC CONDUIT 1 SET [3#12, #12 (G)]*
Y MCB4 SCREEN CHANNEL PANEL 2" PVC CONDUIT 1 SET [3#12, #12 (G)]*
Z T2B PB2 2" PVC CONDUIT 1 SET [3#2, #2(N), #6 (G)]*
ZZ T2B PB4 2" PVC CONDUIT 1 SET [3#2, #2(N), #6 (G)]*
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text P
AutoCAD SHX Text Q
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text Y
AutoCAD SHX Text U
AutoCAD SHX Text X
AutoCAD SHX Text W
AutoCAD SHX Text V
AutoCAD SHX Text Z
AutoCAD SHX Text
ZZ
AutoCAD SHX Text
TT
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
NORTH RIM - GRAND CANYON NATIONAL PARK
AutoCAD SHX Text
A/E FIRM
AutoCAD SHX Text
PRIME:
AutoCAD SHX Text
HDR ENGINEERING, INC.
AutoCAD SHX Text
PM: MATTHEW GOUGH
AutoCAD SHX Text
DENVER, CO
AutoCAD SHX Text
TEMPORARY WWTP
AutoCAD SHX Text
SINGLE LINE DIAGRAM 2
AutoCAD SHX Text
AutoCAD SHX Text 182752A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
T. VANG
AutoCAD SHX Text
T. VANG
AutoCAD SHX Text
T. MOORE
AutoCAD SHX Text
MAY 2026
AutoCAD SHX Text 318719
AutoCAD SHX Text E602
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
MCB3 CABLE/CONDUIT SCHEDULE
AutoCAD SHX Text
MCB4 CABLE/CONDUIT SCHEDULE
AutoCAD SHX Text GENERAL NOTES 1. GROUNDING ELECTRODE SYSTEM GROUNDING ELECTRODE SYSTEM IS REQUIRED AT EVERY STRUCTURE AND BUILDING FED FROM MCBS. NEUTRAL IS NOT TO BE BONDED AT THE BUILDING GROUND.
AutoCAD SHX Text KEYNOTES: 1. ALL GROUNDING JUMPER TO BE ALL GROUNDING JUMPER TO BE #4/0 UNLESS OTHERWISE SHOWN. SEE DETAIL 3 ON SHEET E503 FOR GROUNDING ELECTRODE SYSTEM DETAIL. 2. DO NOT BOND NEUTRAL AND DO NOT BOND NEUTRAL AND GROUND TOGETHER. 3. BOND NEUTRAL (X0) TO BOND NEUTRAL (X0) TO GROUND AT TRANSFORMER T1B AND T2B. TRANSFORMERS COMPRISE SEPARATELY-DERIVED SYSTEMS.
AutoCAD SHX Text X
AutoCAD SHX Text
NOTE: (* COPPER CONDUCTORS WITH XHHW-2 INSULATION)
AutoCAD SHX Text
NOTE: (* COPPER CONDUCTORS WITH XHHW-2 INSULATION)
AutoCAD SHX Text
JUNE 2026
AutoCAD SHX Text 7/20/2026 Vang, Tou C:\Users\TVANG\DC\ACCDocs\HDR\10350545_NPS_GRCA_N_Rim_Utility_2022\Project Files\CAD_HDR\DRAWINGS\TEMPORARY WASTEWATER\ELECTRICAL\E601-E602.dwg Vang, Tou C:\Users\TVANG\DC\ACCDocs\HDR\10350545_NPS_GRCA_N_Rim_Utility_2022\Project Files\CAD_HDR\DRAWINGS\TEMPORARY WASTEWATER\ELECTRICAL\E601-E602.dwgVang, Tou C:\Users\TVANG\DC\ACCDocs\HDR\10350545_NPS_GRCA_N_Rim_Utility_2022\Project Files\CAD_HDR\DRAWINGS\TEMPORARY WASTEWATER\ELECTRICAL\E601-E602.dwg C:\Users\TVANG\DC\ACCDocs\HDR\10350545_NPS_GRCA_N_Rim_Utility_2022\Project Files\CAD_HDR\DRAWINGS\TEMPORARY WASTEWATER\ELECTRICAL\E601-E602.dwgC:\Users\TVANG\DC\ACCDocs\HDR\10350545_NPS_GRCA_N_Rim_Utility_2022\Project Files\CAD_HDR\DRAWINGS\TEMPORARY WASTEWATER\ELECTRICAL\E601-E602.dwg