P4_-_PLUMBING_SCHEDULES_06_11_26_0002.pdf

PDF 60 KB Posted

Attached to
Hangars 3&4 Construction NY Floyd BennetField Gat
Solicitation number
140P2026R0060
Issued by

About this file

This document is a Plumbing Schedules sheet for the Hangars 3 & 4 Rehabilitation project at Floyd Bennett Field. The schedule specifies fixture requirements, manufacturers, models, and connection specifications for plumbing installations.

The plumbing fixtures section includes four fixture types: Water Closet (WC-1) specified as American Standard 3641.001 with Sloan Royal 111-1.28 flush valve, 1.28 gallons per flush, floor-mounted siphon jet design with 1-1/2" top spud inlet; Lavatory (L-1) specified as American Standard Decorum 2200-4 with Chicago Faucet 7-225-CK mixing valve and Symmons In-Line Circle Seal check valve, 0.5 GPM minimum flow, 1-1/2" waste and vent connections; Janitor's Sink (JS-1) specified as Fiat TSB-200 with Chicago Faucet 782-E27 and Fiat 832-AA hose bracket, 3" P-trap with 3/4" hose connection and vacuum breaker; and Electric Water Cooler (EWC-1) specified as Elkay LZSTL8WSSP, wall-mounted stainless steel module with vinyl cover. The schedule also includes three Electric Point of Use Water Heaters (rows 1-3) specified as EEMAX ProSeries XTP020480 with 0.5-20 GPM flow range, 38-110°F temperature differential, 2 elements, 20 kW wattage, 480V 3-phase at 65 SCCR minimum. Drains and cleanouts include six items from Zurn: floor drains (FD-1, FD-2), open hub drain (HD-1), floor cleanout (FCO), combination main/overflow drain (RD-1), and downspout nozzle (RD-2). A single Backflow Preventer (RPBP-1) is specified as Watts 994 4" for the main meter room. The document was revised under Addendum 1 on 06/11/2026 and is part of drawing package 190066, sheet P4.

View the file

Other files

File Type Posted
Sol_140P2026R0060_Amd_0004.pdf PDF
28_20_00_Video_Surveillance_-_06_23_26_0003.pdf PDF
A3-0_-_BUILDING_SECTIONS_06_23_26_0003.pdf PDF
Sol_140P2026R0060_Amd_0003.pdf PDF
Sign-in_Sheet_for_06_16_26_Site_Visit_0003.pdf PDF
A5-0-2_-_ROOF___HANGAR_DOOR_DETAILS_06_23_26_0003.pdf PDF
FINAL_BID_QUESTIONS_AND_ANSWERS__UPDATED_06_23_26_0003.pdf PDF
GATE_308504_-_140P2026R0060_Bid_Questions_and_Answers_-_06_11_26_0002.docx DOCX document
B08_Solicitation_P2026R0060_Revisions_to_Section_L_06_11_26_0002.docx DOCX document
S2-6_-_WPA_INFILL_ROOF_FRAMING_PLAN_06_11_26_0002.pdf PDF
012700_DefinitionOfContractLineItems_Revised_06_11_26_0002.pdf PDF
G0_-_COVER_SHEET_06_11_26_0002.pdf PDF
Sol_140P2026R0060_Amd_0002.pdf PDF
B08_Fillable_Past_Performance_Questionnaire_0002.docx DOCX document
A0-4_-_EXTERIOR_ELEVATIONS_-_DEMOLITION_06_11_26_0002.pdf PDF
Solicitation_P2026R0060_GATE_308504_Contract_Price_Schedule_Revised_06_11_26_0002.xlsx XLSX spreadsheet
A0-6_-_EXISTING_CONDITIONS_PHOTOS_-_EXTERIOR_06_11_26_0002.pdf PDF
B08_Fillable_Project_Experience_Questionnaire_0002.docx DOCX document
S6-3_-_MASONRY_REPAIR_AND_LINTEL_REPLACEMENT_DETAILS_06_11_26_0002.pdf PDF
S6-5_-_TYPICAL_CONCRETE_REPAIR_DETAILS_06_11_26_0002.pdf PDF
A4-2-1_-_ENLARGED_ELEVATIONS_-_HANGAR_4_DOORS_06_11_26_0002.pdf PDF
S6-2_-_STEEL_BEAM_REPAIR_DETAILS_06_11_26_0002.pdf PDF
WD_NY20260003_05_26_26_-_Issued_06_11_26_0002.pdf PDF
Sol_140P2026R0060_Amd_0001.pdf PDF
Amendment_0001_P2026R0060_0001.pdf PDF
Sol_140P2026R0060.pdf PDF
1__25-1219_GATE_308504_Final_CD_Project_Specifications.pdf PDF
3_25-1219_GATE_308504_Final_CD_Structural_Design_Calculations.pdf PDF
B08_GATE_308504_Hangars_3_and_4_Solicitation_140P2026R0060.pdf PDF
2_Final_CD_Drawings_-_Condensed.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING FIXTURES

FIXTURE TRIM CONNECTION

TAG WASTE VENT TRAP COLD WATER HOT WATER

TYPE MANUFACTURER AND TYPE MANUFACTURER AND TYPE MANUFACTURER AND TYPE MANUFACTURER AND DESCRIPTION BRANCH STOP BRANCH STOP

MODEL NUMBER MODEL NUMBER MODEL NUMBER MODEL NUMBER SUPPLY INLET SUPPLY INLET

WC-1 WATER CLOSET AMERICAN STANDARD FLUSH VALVE SLOAN ROYAL WHITE VITREOUS CHINA, FLOOR MOUNTED SIPHON JET, ELONGATE BOWL, FLOOR MOUNTED 3641.001 111-1.28 1.28 GALLONS PER FLUSH, 1-1/2" TOP SPUD INLET, BARRIER-FREE HEIGHT 4" 2" INTEGRAL 1-1/2" 1" - -

BARRIER-FREE OR EQUAL OR EQUAL 1.28 GALLONS PER FLUSH, EXPOSED MANUAL DIAPHRAGM FLUSHOMETER, SIDE OSCILLATING HANDLE, 1-1/2" TOP SPUD CONNECTION

L-1 LAVATORY AMERICAN STANDARD FAUCET CHICAGO FAUCET MIXING VALVE SYMMONS IN-LINE CIRCLE SEAL 20" X 18" WHITE VITREOUS CHINA, WALL HUNG, SINGLE FAUCET HOLE, WALL HUNG DECORUM 2200-4 7-225-CK CHECK VALVE 2200 SERIES DRILLED FOR CARRIER SUPPORT, MOUNT 34" AFF TO RIM TO BE BARRIER-FREE

BARRIER-FREE OR EQUAL OR EQUAL SINGLE HANDLE, E12 AERATOR 1-1/2" 1-1/2" 1-1/4" 1/2" 1/2" 1/2" 1/2"

EXPOSED LEAD-FREE MIXING VALVE, CHECK/STRAINERS ON INLETS,

TAMPER RESISTANT CAP, 0.5 GPM MINIMUM FLOW

JS-1 JANITOR'S SINK FIAT FACUET CHICAGO FAUCET HOSE AND FIAT STAIN RESISTANT, WHITE, PRE-CAST TERRAZZO, 24" X 24" X 12", TSB-200 782-E27 BRACKET 832-AA INTEGRAL STAINLESS STEEL GRID STRAINER DRAIN OUTLET, 3"P-TRAP TO

OR EQUAL OR EQUAL MATCH PIPING SYSTEM. TYPE 304 STAINLESS STEEL WALL GAURDS, 20 GA, 12" HEIGHT, LOCATED ON TWO WALLS. CAST OR WROUGHT COPPER

ALLOY, COMBINATION FAUCET MOUNTED 36" ABOVE FINISHED FLOOR. SPOUT

SHALL HAVE PAIL HOOK, 3/4" HOSE CONNECTION, WALL BRACE, CONCEALED 3" 1-1/2" 3" 3/4" 1/2" 3/4" 1/2"

INTEGRAL STOPS, 8" CENTERS. CAST, COPPER ALLOY HANDLES. COPPER ALLOY

OR CRS ESCUTCHEON. IN-LINE ASSE 1001 VACUUM BREAKER. EXPOSED PARTS

SHALL BE CHROME PLATED. 30" LONG, 5/8" RUBBER HOSE AND STAINLESS STEEL

HOSE BRACKET. MOUNT BRACKET MINIMUM 18" ABOVE FINISHED FLOOR AND

6" LEFT OF FAUCET CENTER

DELETED

EWC-1 ELECTRIC WATER ELKAY WALL MOUNTED SELF-CONTAINED MODULE WITH BOTTLE FILLING, STAINLESS STEEL BOWL, DRAIN AND FLOW RESTRICTING

BUBBLER. VINYL COVER SHALL BE DESIGNER COLOR AS SELECTED

BY ARCHITECT. MOUNT UNIT FOR BARRIER-FREE ACCESS.

COOLER LZSTL8WSSP 1-1/2" 1-1/2" 1-1/4" 1/2" 1/2" - -

2 EEMAX PROSERIES XTP020480 0.5 20 38 110 2 20 480 3 65

3 EEMAX PROSERIES XTP020480 0.5 20 38 110 2 20 480 3 65

ELECTRIC POINT OF USE WATER HEATERS

TAG BASIS OF DESIGN WATER SIDE ELECTRICAL REMARKS

WH MANUFACTURER AND MODEL MIN. MAX. EWT LWT NUMBER ELEMENT VOLT PH SCCR

OR EQUAL FLOW FLOW OF WATTAGE (MIN.)

(GPM) (GPM) (°F) (°F) ELEMENTS (kw)

1 EEMAX PROSERIES XTP020480 0.5 20 38 110 2 20 480 3 65

DRAINS AND CLEANOUTS

TAG BASIS OF DESIGN DESCRIPTION

MANUFACTURER AND MODEL

OR EQUAL

FD-1 ZURN ZN415B-P-VP 6" ROUND FLOOR DRAIN W/ NICKLE BRONZE TOP, TRAP-GUARD, CLAMPING COLLAR

FD-2 ZURN Z668-VP 11"x19" RECTANGULAR AREA FLOOR DRAIN W/ CAST IRON VANDEL PROOF TOP, NO HUB CONNECTION

HD-1 ZURN Z1870-ZM 6" TO 4" OPEN HUB DRAIN, 316 STAINLESS STEEL, NO HUB CONNECTION

DELETED

FCO ZURN Z1400-ZN-VP FLOOR CLEANOUT, CAST IRON, EXTRA HEAVY DUTY TOP

RD-1 ZURN Z-Z164-G 12" DIA COMBINATION MAIN & OVERFLOW DRAIN LOW SILHOUETTE DOME, 6" PIPING CONNECTION, NO-HUB CONNECTION, AND UNDERDECK CLAMP.

RD-2 ZURN Z199-DC-CP-VP DOWNSPOUT NOZZLE W/ CHROME PLATED COVER, STAINLESS STEEL HINGED STRAINER

OR EQUAL (IN)

RPBP-1 MAIN METER ROOM WATTS 994 4"

BACKFLOW PREVENTER (RPBP)

TAG SERVICE LOCATION BASIS OF DESIGN REMARKS

MANUFACTURER MODEL SIZE

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

TITLE OF SHEET

OF

190066

GATE 308504

HANGARS 3 & 4 REHABILITATION 153

SEAL

/1

/2

:3

:0

P

M A u to d e s k D o c s /G

A T

E F lo y d B e n n e tt F ie ld

/2

-0

G A

T E

M e c h a n ic a l_

R .r v t

Designer

Author

Checker

12/19/2025

P4

PLUMBING SCHEDULES

NO. REVISION DATE BY

1 ADDENDUM 1 06/11/2026 AEI

Sheets
P4 - PLUMBING SCHEDULES

File details come from the government source that posted it. Updated .