This document contains fire hydrant and pressure test results conducted by an authorized representative of the City of Atlanta's Department of Watershed Management. The tests were requested by Calibre Engineering and performed at three different locations in Atlanta, Georgia on March 24, 2022. The test results provide details on the static pressure, residual pressure, pitot reading, and flow rate for each hydrant. This information appears to be provided as supporting documentation for a federal contract opportunity solicitation number 140P2024R0056 to rehabilitate the Visitor Center and Headquarters at the Martin Luther King Jr. National Historical Park in Atlanta, Georgia. The solicitation is being issued by the Department of the Interior, National Park Service National Office.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CITY OF ATLANTA
ANDRE DICKENS 651 FOURTEENTH STREET DEPARTMENT OF
MAYOR ATLANTA, GEORGIA 30318 WATERSHED MANAGEMENT
OFFICE . 404-982-1487 MIKITA BROWNING
FAX . 404-982-1400 COMMISSIONER
Date: 3/24/22
The following report is on FIRE HYDRANT and PRESSURE TEST results.
Done by an Authorized Representative of The City of Atlanta.
Test location: 90 Boulevard
Plat card # 386
Test Hydrant # 404
Flow Hydrant # 3978
Static: 73
Residual: 70
Pitot: 50
Flow: 1190 gpm
Comments: Flowed 2.5 inch nozzle 6 inch main 11:00 a.m. 1 min.
Requested by: Calibre Engineering
Contact: Jessica Kordziel
Phone: 303-502-7287
City of Atlanta-Watershed Management
Representative:
Emanuel Toles 678-878-5192 etoles@atlantaga.gov
ANDRE DICKENS 651 FOURTEENTH STREET DEPARTMENT OF
MAYOR ATLANTA, GEORGIA 30318 WATERSHED MANAGEMENT
Test location: 101 Jackson Street
Plat card # 413
Test Hydrant # 776
Flow Hydrant # 809
Static: 80
Residual: 40
Pitot: 20
Flow: 750 gpm
Comments: Flowed 2.5 inch nozzle 6 inch main 11:25 a.m. 1 min.
ANDRE DICKENS 651 FOURTEENTH STREET DEPARTMENT OF
MAYOR ATLANTA, GEORGIA 30318 WATERSHED MANAGEMENT
Test location: 460 Auburn Avenue
Plat card # 386
Test Hydrant # 2489
Flow Hydrant # 3978
Static: 71
Residual: 69
Pitot: 50
Flow: 1190 gpm
Comments: Flowed 2.5 inch nozzle 6 inch main 11:35 a.m. 1 min.