B08_Attachment_20E_Revised_Final_Drawings_20250804_Part5_0007.pdf
PDF 19 MB Posted
- Solicitation number
- 140L0625R0002
About this file
These documents are detailed mechanical, electrical, and HVAC design plans for a new office building project. The plans include comprehensive technical drawings covering ventilation ductwork, piping layouts, mechanical yard configurations, electrical power distribution, lighting plans, fire alarm systems, data infrastructure, and utility connections. Key technical specifications include a 300 kVA pad-mount transformer, 208/120V electrical service, multiple branch electrical panels, energy recovery ventilation systems, and heat pump terminal units. The design appears to incorporate sophisticated building systems with considerations for energy efficiency, including solar photovoltaic integration, ground source electrical grounding, and zoned mechanical systems with multiple air handling units.
The drawings provide intricate details on equipment mounting, conduit routing, cable management, ground bar configurations, and system interconnections across multiple building zones. Electrical plans show detailed circuit layouts, receptacle placements, lighting fixture specifications, and control systems. The mechanical plans include extensive ductwork routing, equipment placement, and support structure details. The overall design suggests a modern, technologically advanced office facility with integrated mechanical, electrical, and communication infrastructure designed to meet contemporary building performance and sustainability standards.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P L O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:0
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
V E N T
IL
A T
IO
N D U C T W O R K
P L A N
A R E A
D
M102D
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
101 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:06:04 -06'00'
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
H V A C
C O N T R O L S
A N D
P
IP
IN
G
P L A N
M103
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
102 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:07:08
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
E N L A R G E D
M E C H A N
IC
A L
V
IE
W S
M401
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
103 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:08:15
12ga - 80 lbs
10ga - 125 lbs
3/4"- 3000 lbs 5/8"- 2000 lbs 1/2"- 1250 lbs 3/8"- 680 lbs
1/4"- 270 lbs
1"x 16ga 700 lbs
1"x 18ga 420 lbs
1"x 20ga 320 lbs
1"x 22ga 260 lbs
1"x 22ga 260 lbs
11/2x11/2x16ga 11/2x11/2x1/8 11/2x11/2x3/16 2x2x1/811/2x11/2x1/4 2x2x3/16 2x2x1/4 21/2x21/2x3/16 21/2x21/2x1/4
11/2"x 16ga 1100 lbs
P L O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
H V A C
D E T A
IL
S
M501
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
104 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:09:38
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
H V A C
D E T A
IL
S
M502
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
105 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:10:53
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
H V A C
D E T A
IL
S
M503
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
106 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:12:23
DUCT DETECTOR
DUCT DETECTOR
P L O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
H V A C
D E T A
IL
S
M504
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
107 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:13:53
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
H V A C
D E T A
IL
S
M505
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
108 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:15:07
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:4
:2
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O H V A C a lf re d o ri c o .r v t
H V A C
S C H E D U L E S
M601
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
N
F R O N G N E R
J
R O D R
IG
U E Z
N F R O N G N E R
L B Y D
F E D E R A L
ID
A H O
F A L L S
N
F R O N G N E R
B
C A R T E R
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
109 124
P R
O
FE
SSIONA L ENGINEER
NATHA N J. FRONGNER
STATE OF IDAHO
L I C E N S E D
18674
N STSS
186662022.07.11 18:16:34
TRANSFORMER
ELECTRICAL GROUND
-GENERAL-
WALL MOUNTED BATTERY PACK EMERGENCY LIGHT
SHADING INDICATES LUMINAIRE ON LIFE SAFETY
COMBINATION MOTOR STARTER
BRANCH CIRCUIT HOME RUN TO PANELBOARD,
DESIGNATION INDICATES PANEL AND CIRCUIT
NUMBERS.
BARE-LAMP FLUORESCENT STRIP LIGHT
OCCUPANCY SENSOR
WALL MOUNTED LUMINAIRE
CONDUIT STUB DOWN (OUT OF DRAWING LIMITS)
CONDUIT STUB UP (OUT OF DRAWING LIMITS)
-GENERAL-
CONDUIT BREAK SYMBOL
LIGHTING, ONE-LINE, AND POWER CIRCUITING
CONDUIT CAP
CEILING MOUNTED FOURPLEX RECEPTACLE
FLOOR MOUNTED SPECIAL PURPOSE RECEPTACLE
CEILING MOUNTED DUPLEX RECEPTACLE
DISCONNECT SWITCH
MOTOR STARTER
FUSED DISCONNECT SWITCH
SPECIAL PURPOSE RECEPTACLE
FOURPLEX RECEPTACLE
-LIGHTING-
FLOOR MOUNTED DUPLEX RECEPTACLE
FLOOR MOUNTED FOURPLEX RECEPTACLE
FUSED SWITCH
PHOTOCELL FOR DAYLIGHTING
MOTOR
-ONE LINE SYMBOLS-
CIRCUIT BREAKER
CONTROL FUSE
TRANSFORMER
MANUAL TRANSFER SWITCH
PANELBOARD
CONDUIT CHANGE IN ELEVATION
SYMBOL DESCRIPTION
DUPLEX RECEPTACLE
GFI = GROUND FAULT CIRCUIT
INTERRUPTER
D = DEDICATED DUPLEX GROUNDED
RECEPTACLE
IG = ISOLATED GROUND
DESCRIPTIONSYMBOL
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
LIGHTING, ONE-LINE, AND POWER CIRCUITING
(UNDERGROUND)
WALL MOUNTED EXIT LIGHT (WITH FACES &
DIRECTION ARROWS INDICATED IF USED)
NEW PANEL, SURFACE MOUNTED
DISTRIBUTION PANEL
T
BONDING POINT
GROUND BUS
GROUND TEST WELL
GROUNDING CONDUCTOR
CONTROL WIRING
FEEDER DESIGNATION, SEE FEEDER SCHEDULE
SPECIAL SYSTEMS SYMBOLS:
CR = CARD READER
OS = OCCUPANCY SENSOR
R = REMOTE INDICATING LIGHT
TC = TIME CLOCK
TS = TAMPER SWITCH
- ABBREVIATIONS - - ABBREVIATIONS -
(E)
(N)
(PART)
+XX
A
AC
AF
AFC
AFF
AFG
AIC
AS
AT
BFG
C
CAM
CB
CKT
CLG
CSC
ELEC
ELEV
EMERG
FA
FACP
FLR
FLUOR
G
EF
GEN
GFCI
GFI
GND
HP
HV
IC
IG
JB
K
LTG
LTS
LV
MAM
MCB
MCSW
MLO
MTD
N
NC
NEC
NF
NIC
NL
NO
P
PB
PNL
PWR
RCPT(S)
SBC
SP
SW
T
TEL
TTB
TV
TVSS
UF
UG
UNO
V
VFD
WG
WP
WSC
XFMR
EXISTING
NEW
PARTIAL CIRCUIT
MOUNTING HEIGHT IN INCHES. AFF UNO
AMP
ABOVE COUNTER TOP
AMP FRAME
ABOVE FINISHED COUNTER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPS INTERRUPTING CAPACITY
AMPS SENSOR
AMP TRIP
BELOW FINISHED GRADE
CONDUIT
CONTROL ADDRESSABLE MODULE
MOLDED CASE CIRCUIT BREAKER
CIRCUIT
CEILING
CEILING SECURITY CAMERA
ELECTRIC
ELEVATION
EMERGENCY
FIRE ALARM
FIRE ALARM CONTROL PANEL
FLOOR
FLUORESCENT
GROUND (EQUIPMENT)
EXHAUST FAN
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT CIRCUIT INTERRUPTER
GROUND (EQUIPMENT)
HORSEPOWER
HIGH VOLTAGE
INTERRUPTING CAPACITY
ISOLATED GROUND
JUNCTION BOX
THOUSAND
LIGHTING
LIGHTS
LOW VOLTAGE
MONITOR ADDRESSABLE MODULE
MAIN CIRCUIT BREAKER
MOLDED CASE SWITCH
MAIN LUGS ONLY
MOUNTED
NEUTRAL
NORMALLY CLOSED
NATIONAL ELECTRIC CODE
NON FUSED
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
POLE
PULL BOX
PANEL
POWER
RECEPTACLE(S)
STRANDED BARE COPPER
SPARE
SWITCH
TRANSFORMER
TELEPHONE
TELEPHONE TERMINAL BOARD
TELEVISION
TRANSIENT VOLTAGE SURGE SUPPRESSOR
UNDERFLOOR
UNDERGROUND
UNLESS NOTED OTHERWISE
VOLTAGE
VARIABLE FREQUENCY DRIVE
WIRE GUARD
WEATHERPROOF
WALL MOUNT SECURITY CAMERA
TRANSFORMER
EXIT LIGHT (WITH FACES & DIRECTION ARROWS
INDICATED IF USED)
MISC. SYSTEM COMPONENT
PAC - PHYSICAL ACCESS CONTROL
ACC - ACCESS CONTROL CONSOLE
ANN = ANNUNCIATOR
CAM = CONTROL ADDRESSABLE MODULE
FACP = FIRE ALARM CONTROL PANEL
FSD = FIRE SMOKE DAMPER
MAM = MONITOR ADDRESSABLE MODULE
TVSS = TRANSIENT VOLTAGE SURGE
SUPPRESSER
VFD = VARIABLE FREQUENCY DRIVE
LED LUMINARIES
# = BRANCH CIRCUIT NUMBER
x = SWITCH LEG IDENTIFIER
#x
SWITCH
DUAL SWITCH
METER
UPS UNINTERRUPTIBLE POWER SUPPLY
(NOTE: NOT ALL SYMBOLS SHOWN ARE USED ON THESE DRAWINGS)ELECTRICAL LEGEND
AHJ AUTHORITY HAVING JURISDICTION
PANEL
XX
J
XXX
M
-TELECOM DEVICES-
SYMBOL DESCRIPTION
X AVAILABLE FAULT CURRENT
MTS MANUAL TRANSFER SWITCH
MCM THOUSAND CIRCULAR MILS
GROUND ROD
EGB ELECTRICAL GROUND BUSBAR
NORTH ARROW
HATCHING INDICATES ITEM(S) TO BE REMOVED
MECHANICAL EQUIPMENT TAG
KEY NOTE
SHADING INDICATES EQUIPMENT
2 PORT DATA FACEPLATE (TYPICAL)
CEILING MOUNTED SPEAKER ROUTED WITH 1"
CONDUIT. Z# CORRESPONDS TO ZONE CONTROL.
VOLUME CONTROL MOUNTED AT +48 AFF. Z#
CORRESPONDS TO THE ZONE CONTROL.
HDMI CABLE PORT MOUNTED AT +72 AFF.
S
VC Z#
TV
Z#
-FIRE ALARM DEVICES-
STROBE LIGHT
COMBINATION FIRE HORN/STROBE LIGHT
SMOKE DETECTOR
X I = IONIZATION TYPE
P = PHOTOELECTRIC TYPE
T = THERMAL TYPE
DT = DUCT TYPE
FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
SYMBOL DESCRIPTION
-GRAPHIC SYMBOLS-
SYMBOL DESCRIPTION
N
19543
SWITCH SYMBOL
SINGLE POLE (IF BLANK)
2 = DOUBLE POLE
3 = THREE-WAY
4 = FOUR-WAY
D = DIMMER
K = KEY OPERATED
LV = LOW VOLTAGE
TO = THERMAL OVERLOAD
WP = WEATHERPROOF
x = SMALL LETTER INDICATES LUMINARIES
CONTROLLED
x
-POWER-
DESCRIPTIONSYMBOL
-GROUNDING-
DESCRIPTIONSYMBOL
GENERAL NOTES:
1. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH LOCAL
BUILDING CODES AND THE LATEST EDITION OF THE NATIONAL
ELECTRIC CODE (NEC).
2. REFERENCE SPECIFICATIONS FOR CONSTRUCTION MATERIALS AND
INSTALLATION PROCEDURES. SPECIFICATIONS ARE A PART OF THE
CONSTRUCTION DOCUMENTS. SHOULD ANY CONFLICT ARISE
BETWEEN THE DRAWINGS AND SPECIFICATIONS, SUCH CONFLICT
SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER FOR RESOLUTION.
3. THESE DRAWINGS ARE DIAGRAMMATIC IN CHARACTER AND DO NOT
NECESSARILY SHOW MATERIALS FOR A COMPLETE INSTALLATION.
4. ALL PENETRATIONS THROUGH FIRE SEPARATION WALLS ARE TO BE
SEALED TO MAINTAIN SEPARATION RATING.
5. JUNCTION BOXES FOR LUMINARIES ARE NOT INDICATED HERE ON.
PROVIDE THE PROPER NUMBER OF J-BOXES TO MEET LOCAL CODE
AND NATIONAL ELECTRICAL CODE.
6. LEGEND SHOWN ABOVE IS APPLICABLE TO ALL ELECTRICAL
DRAWINGS.
SDBTC SOFT DRAWN BARE TINNED COPPER
WELDER RECEPTACLE
JUNCTION BOX MOUNTED AT 100" AFF. FOR
FUTURE SECURITY SYSTEM. WITH 1" CONDUIT
AND PULL STRING.
03:16:40 PM 07-11-2022 (-04'00' GMT)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
X
X
X X
X X
X
X X X X X X
X
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
ELEVATION
UG
P
U G
P
UGP
UGP
UGP
UGP
UGP
UGP
UGP
U G
P
U G
P
U G
P U
G P
UGP
U G
P U
G P
U G
P
U G
P U
G P
U G
P
G P
P
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UG
P
UG
P
X
X
XXX
XXXXXXXXXXXXXX
X
OHP
OHP
OH
U G
XXXXXXXXXXXXXXXX
XXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXX
XXXXXXXXXXXXXX
XXXXXXXXXXXXX
XXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
X
X
OHPOHP
POHPOHPOHPHPOH
OHPPPOHP
OHPO
OHPOOOOOOOOOOOOO
OHP
OHP
OHP
OHO
ELEVATIONLEVATIO
UGP
UGP GPPUGPUGUGUGUUUUGUGUGUUGUGGPUUUGGGPUGGPUGUGGPPU
GPGGPUGP
TC
TC
TC
TC
TC
TC
TC
UGP
UGP
UGP
UGP
UGP
UGP
U
P U
PGP
U
UGP
UGP
UGPGP
U
UG
P
UG
GPUGUUUU
HP
X
X
X
X
X
XXXXXXXXXXXXXXXXXXXXXXXXX
XXXXX
XXXXXXXXXX
XXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
X
X X
X
XXXX
X
UG
P
UG
P
UG
P
UG
P
UUG
P
UGUUUG
P
UGUG
P
UG
P
UGUUG
P
UUGUGUGGGG
P
G
PPP
UUUUUUUUUUUU
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
UGP
UGP
UGP
UGP
UGP
UGP
UGP
U XX
U G
P
U G
P
U G
P U
G P
PP
UGPGP
TC
TC
TC
TC
TC
XXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXX
U
G P
GG
P
G P
U G
P G
PPPPP
G
P G
P G
PP
G
P G
P G
P G
PPPP
G
P G
PP
G
P G
P G
PPP
G
P
GG
P
GG
P G
P G
P
TC
TC
TC
TC
HPPPOHP
OHP
OHPOHH
OHPOHOHO
U G
PP
G
UU
P
G
UU
P
GG
UU
GG
P
GG
P G
U P
G U
PP
G
U P
G
UU
G
PPPP
G
UUUU
G
PP
UU
G
PP
UU
G
PP
U
GG
P
UU
G P
U
GG
PP
G
UU
P
G
UUU
GG
PP
U
GG
P U
GG
P
U
GG
PP
GG
UU
GG
P U
GG
PP
GG
U
P
GG
UU
P
G
UUU
G P
U G
PPP
G
U G
UUU
PP
G
UUUU
PPP
G
P U
G U
P
GG
U P
GG
UU
GG
U
P
GG
P
UU
GGGG
PP
U
GGGG
PP
U
GG
PP
GG
U
PPPP
GG
UU
PPPP
GGG
U
G
UU
PP
GGGG
UU
PPP
GGGG
UU
P
GGG
U G
U
PP
G
UUUU
G
PP
UU
GG
PPPPPPP
GG
UUUUUUUU
GG
PPPP
UU
G U
P U
P G
PP
UU
G U
P U
P G
PP
UUUU
GG
PPPP
UU
GGGG
PP
UU
G U
G P
U P
GG
PP
UU
G
U P
U P
G
PP
UU
GGGG
PP
UU
G P
U P
G
PP
G
UU
P G
UU
P
GG
UUUU
PP
GG
UUU
G
P U
GG
U
G U
GG
U
G U
GG
P
UU
GGGG
PP
U
G U
GG
P
G
PP
GG
U
P
GG
U P
GG
UU
GG
P
UU
GGGG
PPPP
UU
GGGG
PPP
GG
U
P
GG
U
PP
GGGG
UUUU
PP
GGG
UUUU
U G
P
UU
G
PP
UU
G
PP
UUU
G U
P G
PPP
U
GG
P
U
GG
PP
GG
P U
GG
U
PP
GGGG
UU
PP
GGGG
UU
P
GG
UU
GG
P
UUUU
GG
PP
UUUU
GGGG
PP
UU
GGGG
PP
UU
GGGG
PP
U
G U
GG
P
UU
G
PP
GG
UU
PP
GGG
UUUUU
GG
PPPP
GG
UUUU
PP
G
P U
P U
G
UU
PP
G
P U
P U
G
UU
PP
GG
UUUU
PPPP
GG
UU
PP
G
P U
P U
G
UU
PP
G
P U
P U
G
UU
PPPP
GG
UU
PP
G P
U P
U G
UUUU
G
UU
G
PP
UU
G
PP
UU
GG
PPPP
U
G P
G U
P
GG
U
PP
GGGG
UU
P G
P
GG
U G
UU
GG
P U
GG
P
U G
PP
GG
U
PP
GGGG
UU
P
GGGGG
PP
GGGG
UUU
GG
P U
GG
P
UU
GG
PPPP
UU
GG
PP
U G
PPPP
G
UU
PPPP
GG
UUUU
PPP
G
P U
G
UUU
P
GG
U
GG
UU
GG
U P
GG
P
UU
GGGG
PP
UU
GGGG
PP
U
GG
P U
GG
PP
G P
GG
U
G U
PPPP
GG
UUUU
PPPP
GG
U
G U
G
UU
P
GGG
UU
P
GG
UU
P G
P
GG
U
PPPP
GG
UUUU
G U
P U
P G
PP
U
GG
PPPPPPP
GG
UUUUUU
GG
PPPP
UU
G
U P
U P
G
PP
UU
G
PP
UUUU
GG
PP
UU
GGGG
PP
UU
G U
G P
U P
GG
PP
UU
G
PP
UU
GGGG
P
UU
G
U P
U P
G
PPP
G
UU
PP
GG
UUUU
PP
GG
UUUUU
G P
U
GG
U
GG
P G
P U
GG
PP
U G
U
GGG
P
GG
U P
GG
U
P G
P
GG
U G
UU
G
U
GG
P G
P
UU
GGGG
PP
UU
GGG
PP
GG
U
GG
U P
GG
UUU
PP
GGGG
UUUU
U
G
PPPP
G P
U G
UUU
PPPP
GG
UUUU
PP
G
UUU
PP
GG
U
G U
P
GG
P U
GGG
PP
U
GG
P U
GG
P
U
GG
PP
G
P
GG
U G
U
PP
GG
UUUU
PPP
GG
U G
U
PP
GGGG
UU
PPP
GGGG
UU
P
G P
GG
U
G U
PPPP
GG
UUUUUU
G
U P
U P
G
PP
UU
GG
PPPPPPP
GG
UUUUUUU
GG
PPPP
UU
G
PP
UU
G
U P
U P
G
PP
UUUU
GG
PPPP
U
GGGG
PP
UU
P
GG
PP
UU
G
U P
U P
G
PP
UUU
GGGG
PP
UU
G
PPP
G
UU
P G
UU
PP
GG
UUUU
PP
GG
UUUU
GGGG
UU
GGG
P G
U G
P G
U G
U
GG
P G
P
UU
GGGG
PP
U G
U
GG
P G
PP
GG
U P
GG
U
G P
GG
U
G
UU
G U
GG
P
G P
UU
GGGG
PP
UU
GGGG
PPP
GG
U
P
GG
U
PP
GGGG
UUUU
PP
GGGG
UUUU
U G
P U
PP
UU
P
OHP
OHP
UGP
UGP
UGPGP
U
UGP
U
P U
PGP
UTILITIES LEGEND
EXISTING TELECOM
EXISTING UNDERGROUND ELECTRIC
EXISTING
GYM
EXISTING SOLAR
PHOTOVOLTAIC
INVERTER
ENCLOSURE
EXISTING
WAREHOUSE
EXISTING
SHOP
EXISTING
TRANSFORMER &
CT AND JUNCTION
CABINET ENCLOSURE
DEMOLITION SEQUENCE 1
DEMOLITION NOTES
DEMOLITION SEQUENCE 2
1. DEMOLITION SHALL BE SEQUENCED SUCH THAT EXISTING BUILDING
REMAINS FULLY OPERATIONAL DURING CONSTRUCTION OF NEW
FIELD OFFICE.
2. DEMOLITION MAY CONSIST OF THREE SEPARATE SEQUENCES AS
SHOWN OR AS APPROVED BY THE CO.
3. REMOVABLE ITEMS WITHIN EACH SEQUENCE SHALL BE DETERMINED
BY THE CONTRACTOR AND APPROVED BY GOVERNMENT.
4. COORDINATE NEW UTILITY CONNECTIONS AND ROUTING TO ENSURE
ALL SITE BUILDINGS REMAIN OPERATIONAL DURING CONSTRUCTION.
5. EXISTING UNDERGROUND POWER UTILITIES IMPACTED BY THE
PLACEMENT/CONSTRUCTION OF NEW BUILDING SHALL BE
TEMPORARILY REROUTED TO EXISTING FACILITY TO MAINTAIN
CONTINUOUS OPERATIONS.
6. SEE SHEET C-102, MASTER DEMOLITION PLAN, FOR ADDITIONAL
DEMOLITION NOTES.
1. MAINTAIN THE EXISTING SOUTHEAST ACCESS GATE AS
OPERATIONAL UNTIL DEMOLITION AND CONSTRUCTION WORK ON
SOUTHEAST ROADWAY AREA BEGINS. BEFORE DEMOLITION AND
CONSTRUCTION WORK ON SOUTHEAST ROADWAY BEGINS,
NORTHWEST GATE SHALL BE PROVIDED WITH AN ACCESS GATE
CONTROLLER AND MADE OPERATIONAL WITH TEMPORARY POWER.
AFTER NORTHWEST GATE IS MADE OPERATIONAL, DEMOLISH OR CAP
AND ABANDON IN PLACE UNDERGROUND POWER SERVICE FROM
EXISTING BUILDING TO SOUTHEAST ACCESS GATE CONTROLLER.
RETAIN SOUTHEAST ACCESS GATE CONTROLLER IN PLACE AND
RELOCATE POWER FEED TO NEW BUILDING
2. DEMOLISH EXISTING TELECOM SERVICE TO EXISTING BUILDING
AFTER NEW SERVICE HAS BEEN ESTABLISHED TO NEW BUILDING.
3. REMOVE POWER SERVICE FROM SOLAR PANEL INVERTER
ENCLOSURE TO EXISTING BUILDING AND RELOCATE TO NEW
BUILDING.
4. DEMOLISH EXISTING TRANSFORMER AND CT & JUNCTION CABINET
ENCLOSURE AND DEMOLISH OR CAP AND ABANDON IN PLACE
UNDERGROUND POWER SERVICE TO EXISTING BUILDINGS AFTER
NEW TRANSFORMER AND/OR TEMPORARY SERVICE IS PUT INTO
SERVICE TO NEW AND EXISTING BUILDINGS.
5. DEMOLISH OR CAP AND ABANDON IN PLACE POWER FEED TO
EXISTING WAREHOUSE AND SHOP AFTER NEW POWER FEED FROM
NEW TRANSFORMER HAS BEEN ACCOMPLISHED.
6. DEMOLISH ELECTRICAL EQUIPMENT AND APPARATUS IN EXISTING
BUILDING AFTER NEW BUILDING IS OPERATIONAL.
7. REMOVE EXISTING 12KW GENERATOR AND TRANSFER SWITCH / LOAD
PANEL AND REINSTALL AT NEW BUILDING DURING OFFICE
TRANSFER.
8. DEMOLISH LIGHT POLES AND FIXTURES AND DEMOLISH OR CAP AND
ABANDON IN PLACE POWER FEED TO EXISTING LIGHT POLES
FIXTURES.1
EXISTING ACCESS
GATE (SOUTHEAST)
EXISTING
TELECOMM
SERVICE
ENCLOSURE
EXISTING
BUILDING
TC
UGP
DEMOLITION SEQUENCE 3
EXISTING ACCESS
GATE (NORTHWEST)
1954303:17:06 PM 07-11-2022 (-04'00' GMT)
X X
X X
X X
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
OHP
UG
P
U G
P
G P
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
UG
P
UG
P
U G
P U
G P
U G
P U
G P
UG
P
UGP
UGP
U G
P U
G P
U G
P
UGP
UGP
UGP
UGP
UGP
U G
P U
G P
U G
P U
G P
U G
P
TC TC TC TC TC
LTP
LTP
LTP LTP LTP
LTP
LTP
LTP
LT
P
LTP
LTP
LTP
LTP LTP LTP LTP LTPLTP
LTP
LTP
LTP
LTP
LTP
LTP
LTP
LTP
LTP
LTP
LTP
LT
P
LT
P
LT
P
LT
P
LT
P
LTP
LTP
LTP
LTP
LTP
LTP
LTP
LTP
UGP UGP UGP UGP UGP UGP
TC
TC
TC
TC
TC
TC
TC
TC
TC
TC
U G
P U
G P
UG
P
UGP
LTP
LTP
LTP
LT
P
LT
P
LTP
LT
P
LT
P
LT
P
LTP
LTP
LTP
LTP
LTP
CR
CR
CR
CR
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PACS
PAC
S
PACS
PACS
PACS
PA
C
S
PA
C S
PA
C
S
PA
C S
PA
CS
PA
CS
PACS
COM
C O
M C
O M
C O
M C
O M
UG
P
LTPLTP
LT
P
CR
KEY NOTES
1. PROVIDE NEW SERVICE TO NEW TRANSFORMER.
2. PROVIDE NEW 300KVA TRANSFORMER WITH METERING PACKAGE AND NEW SECONDARY
CONNECTION ENCLOSURE. REROUTE POWER CONDUIT RUNS FROM EXISTING CT & JUNCTION
CABINET TO NEW SECONDARY CONNECTION ENCLOSURE.
3. PROVIDE NEW UNDERGROUND POWER FEED FROM NEW SECONDARY CONNECTION
ENCLOSURE TO NEW 400A NEMA 3R DISCONNECT WITH 400A FUSES, MOUNTED ON SIDE OF
NEW BUILDING. PROVIDE NEW POWER FEEDS FROM NEW DISCONNECT TO PANELBOARDS LP1
& LP2 IN MEP ROOM. SEE SINGLE LINE DIAGRAM ON SHEET E-603.
4. REMOVED NOTE.
5. PROVIDE NEW UNDERGROUND POWER FEED FROM NEW SECONDARY CONNECTION
ENCLOSURE TO EXISTING WAREHOUSE. FIELD LOCATE AND TIE INTO EXISTING POWER FEED,
SEE SINGLE DIAGRAM ON SHEET E-603.
6. PROVIDE NEW UNDERGROUND POWER FEED FROM NEW SECONDARY CONNECTION
ENCLOSURE TO EXISTING SHOP. FIELD LOCATE AND TIE INTO EXISTING POWER FEED, SEE
SINGLE DIAGRAM ON SHEET E-603.
7. PROVIDE NEW UNDERGROUND POWER FEED FROM EXISTING SOLAR POWER CONVERTER
INVERTER ENCLOSURE TO NEW PV SYSTEM DISCONNECT PANEL ON SIDE OF NEW BUILDING.
SEE SINGLE LINE DIAGRAM ON SHEET E-603.
8. PROVIDE #2/0 AWG BARE CU GROUND RING, WITH (4) GROUND RODS LOCATED 5FT FROM
BUILDING FOOTPRINT BURIED MINIMUM 36" BELOW FINISHED GRADE. GROUND RING SHALL
BOND WITH ELECTRICAL GROUND BUS BAR (EGB) LOCATED IN MAIN BUILDING MEP ROOM. SEEN
SINGLE LINE DIAGRAM ON SHEET E-603.
9. PROVIDE NEW UNDERGROUND 3" FEED FROM NEW BUILDING I.T./PACS ROOM TO VEHICLE
ACCESS GATE CONTROLLERS.
10. PROVIDE NEW ELECTRIC VEHICLE ACCESS GATE SYSTEM WITH SLIDE GATE OPERATOR. GATE
CONTROLLER TO HAVE BATTERY BACKUP. EACH VEHICLE GATE REQUIRES ACCESS CARD
READERS ON ENTRY AND EXIT. EACH PEDESTAL TO CONTAIN 2 CARD READERS, ONE LOCATED
LOW FOR CARS AND ONE LOCATED HIGHER FOR LARGER VEHICLES. EACH PEDESTAL TO
CONTAIN AN AUDIO/ VIDEO STATION. CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH
MANUFACTURES RECOMMENDATIONS. CONTRACTOR SHALL PROVIDE A FULLY FUNCTIONAL
GATE OPENING SYSTEM.
11. PROVIDE TWENTY-TWO (22) NEW LED AREA LIGHTS, 25' TALL LIGHT POLE, CONTROLLED WITH
EMBEDDED WIRELESS NETWORKED CONTROLS, WITH PHOTOCELL AND DIMMING CAPABILITY.
PROVIDE UNDERGROUND CONDUIT FROM NEW BUILDING MEP ROOM. INSTALL HANDHOLES AS
NECESSARY. REFER TO DETAIL 22 ON SHEET C-505 AND PANEL SCHEDULE LP2 ON SHEET E-601.
12. PROVIDE NEW COMMUNICATION ENCLOSURE, REROUTE EXISTING COMMUNICATION CONDUIT
RUNS FROM EXISTING CT & JUNCTION CABINET ENCLOSURE TO NEW COMMUNICATION
ENCLOSURE.
13. PROVIDE NEW UNDERGROUND COMM CONDUIT FROM NEW COMMUNICATION ENCLOSURE TO
NEW BUILDING COMM ROOM. (2) 3" PVC.
14. REMOVED NOTE.
15. PROVIDE NEW UNDERGROUND COMM CONDUIT TO EXISTING SHOP. FIELD LOCATE AND TIE
INTO EXISTING COMM CONDUIT FEEDS.
16. PROVIDE NEW UNDERGROUND COMM CONDUIT TO EXISTING WAREHOUSE. FIELD LOCATE AND
TIE INTO EXISTING COMM CONDUIT FEEDS.
17. PROVIDE NEW 3' UNDERGROUND COMM CONDUIT FROM EXISTING TELCOM ENCLOSURE TO
NEW BUILDING I.T./PACS ROOM.
18. PROVIDE AND REPLACE BROKEN SOLAR PANEL. REPAIR INVERTER. PROVIDE LIGHTNING
PROTECTION FOR SOLAR ARRAY AND INVERTER CABINET PER MANUFACTURER'S
RECOMMENDTATIONS.
19. PROVIDE 3" UNDERGROUND CONDUIT AND HANDHOLE FOR FUTURE ELECTRIC VEHICLE
CHARGING AREA.
20. PROVIDE NEW UNDERGROUND FEED FROM MEP ROOM TO RELOCATED GENERATOR. SEE
SINGLE LINE DIAGRAM ON SHEET E-601 AND VIEW 2/E103 ON SHEET E-103.
UTILITIES LEGEND
TC
UGP
EXISTING TELECOM
EXISTING UNDERGROUND ELECTRIC
PROPOSED TELECOM
PROPOSED UNDERGROUND ELECTRIC
TC
UGP
EXISTING ACCESS
VEHICLE GATE
CONTROLLER
NEW
OFFICE
BLDG
NEW ACCESS
VEHICLE GATE 2
EXISTING
GYM
EXISTING SOLAR
PHOTOVOLTAIC INVERTER
ENCLOSURE
EXISTING
WAREHOUSE
EXISTING
SHOP
GENERAL NOTES
1. COORDINATE CONNECTIONS AND ROUTING WITH OTHER SITE UTILITIES.
EXISTING
TRANSFORMER &
CT AND JUNCTION
CABINET ENCLOSURE
EXISTING ACCESS
VEHICLE GATE IN
TEMPORARY USE
DURING
CONSTRUCTION
EXISTING
TELECOMM
SERVICE
ENCLOSURE
CR
PACS PROPOSED ACCESS CONTROL SYSTEM
CARD READER STATION
J HANDHOLE /JUNCTION BOX
LTP PROPOSED UNDERGROUND ELECTRIC
FOR LIGHTING
NEW ACCESS
VEHICLE GATE 1
EXISTING ACCESS
VEHICLE GATE
(CURRENTLY NOT
IN OPERATION)
RELOCATED 12KW
GENERATOR
8EXISTING BUILDING
OUTLINE
FUTURE ELECTRIC
VEHICLE CHARGING
AREA
NEW ACCESS
VEHICLE GATE 1
OPERATOR
STATION
1954303:17:19 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:1
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
P O W E R
P L A N
E103
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
114 124
1954303:17:30 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:2
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
L
IG
H T
IN
G P L A N
E104
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
115 124
1954303:17:30 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:2
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
F
IR
E A L A R M
P L A N
E105
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
116 124
1954303:17:31 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:2
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
D A T A
P L A N
E106
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
117 124
1954303:17:31 PM 07-11-2022 (-04'00' GMT)
LP1-1 LP1-1 LP1-1
L O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:2
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
E L E C T R
IC
A L
D E T A
IL
S
E501
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
118 124
1954303:17:32 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:2
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
E L E C T R
IC
A L
D E T A
IL
S
E502
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
119 124
1954303:17:32 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:3
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
E L E C T R
IC
A L
D E T A
IL
S
E503
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
120 124
1954303:17:33 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:3
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
E L E C T R
IC
A L
D E T A
IL
S
E504
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
121 124
1954303:17:33 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:3
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
E L E C T R
IC
A L
S C H E D U L E S
E601
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
122 124
1954303:17:44 PM 07-11-2022 (-04'00' GMT)
O T
D A T E
P L O T T E D
B Y
C H K 'D
B Y
D E S
IG
N O F F
IC
E
D E S
IG
N E D
B Y
P R O J E C T
N O
D R A W N
B Y
A P P R O V E D
B Y
U N
IT
E D
S T A T E S
D E P A R T M E N T
O F
T H E
IN
T E R
IO
R B U R E A U
O F
L A N D
M A N A G E M E N T
D A T E
D E S C R
IP
T
IO
N M A R K
A P P R O V E D
D A T E
SHEET OF
:0
:3
A M
C
U s e rs a ri c o D o c u m e n ts A u to
C a d R e v it
L o c a l
F il e N W B L M D O E L E C T a lf re d o ri c o .r v t
E L E C T R
IC
A L
S C H E D U L E S
E602
S H O S H O N E
F
IE
L D
O F F
IC
E R E P L A C E M E N T
D D
J R
L B Y D
F E D E R A L
ID
A H O
F A L L S
D D B C
T W
IN
F A L L S
D
IS
T R
IC
T
ID
A H O
123 124
1954303:17:45 PM 07-11-2022 (-04'00' GMT)
SCALE: NTS1 ELECTRICAL SINGLE LINE DIAGRAM
NOTES:
1. NEW PAD MOUNT TRANSFORMER SHALL BE OIL FILLED TYPE KNAN WITH ADVANCED
METERING PACKAGE, WITH SECONDARY GROUNDED SERVICE CONDUCTOR GROUNDED
WITH A GROUNDING ELECTRODE.
2. REFER TO SHEET E601 & E602 FOR PANEL SCHEDULES.
3. ALL CONNECTIONS TO GROUNDING BUS BARS SHALL BE MINIMUM #4 AWG CU
4. VERIFY EXISTING WAREHOUSE & SHOP TERMINATION POINTS AND ROUTING.
5. PROVIDE ADVANCED METERING AS REQUIRED BY ENERGY POLICY ACT 2005 § 103 (42
U.S.C. § 8253(e))
6. EXISTING PV METERING NOT SHOWN
NEW PAD MOUNT
TRANSFORMER
300KVA
4.5% Z
3PH 4W
208/120V12.47KV
PANELBOARD 'LP1', 3PH, 4W
120/208V, 400A BUS, 84CKT,
22KAIC
SERVICE
UTILITY POLE
RISER GN
400A
COLD
WATER
PIPE
BUILDING
STEEL
GROUND
RING/
RODS
CONCRETE
ENCASED
ELECTRODE
COMM RM
GND BAR
'TGB'
MEP ROOM GROUND BAR, 'EGB'
TO FACP
DSW-1
800A, 4W
600A FUSE
1 2
NOTE: FACP ONE-LINE DIAGRAM IS SCHEMATIC ONLY. REFER TO PLANS FOR DEVICE QUANTITIES & LOCATIONS.
ALL DEVICES SHALL COMPLY WITH ADA REQUIREMENTS. DEVICES SHALL BE LOCATED PER NFPA & ADA REQUIREMENTS. HORNS SHALL BE CAPABLE OF BEING SILENCED WHILE MAINTAINING STROBE ACTIVATION.
PHOTO-ELECTRIC
DETECTORS
THERMAL
DETECTORS
FACP
HORNS AND STROBES ON SEPARATE CIRCUITS
120VAC CONTROL
CIRCUIT, LPX-XX
1" CONDUIT TO
ANNUNCIATOR
PANEL
SCALE: NTS
FACP SINGLE LINE DIAGRAM2
E602
NOTE 1
NOTE 2
PANELBOARD 'LP2', 3PH, 4W
120/208V, 400A BUS, 84CKT,
22KAIC
400A
NOTE 2
FEEDER SCHEDULE
NUMBER DESCRIPTION
(3) 3" CONDUIT, EA. W/ (3) 300MCM & #2/0 GND
(2) 3" CONDUIT, EA. W/ (4) 350MCM & #1 GND
2" CONDUIT, W/ (3) #4/0 & #2/0 NEUTRAL
#2/0 GEC
(1) 3" CONDUIT, W/ (4) 250MCM & #4 GND
(2) 3" CONDUIT, EA. W/ (4) #4/0 & #2 GND
1-1/4" CONDUIT, W/ (4) #4 & #8 GND
PV SYSTEM
DISCONNECT
SWITCH
400A, 4W
200A FUSE
NEW 1000A
SECONDARY
CONNECTION
ENCLOSURE
EXISTING WAREHOUSE
EXISTING SHOP
NOTE 3
EXISTING
INVERTER
PANEL
TO SOLAR
ARRAY
70A
RELOCATED
KOHLER
GENERATOR
12RESVL SERIES
12 KVA, 240/120 V,
1 , 3W, 60HZ
70 A
GEN
RELOCATED KOHLER
MODEL RXT AUTOMATIC
TRANSFER SWITCH, ATS1,
2P, 3W, SOLID NEUTRAL,
WITH 12-SPACE LOAD
CENTER
100A
NOTE 2
NOTE 4
M
ADVANCED
METER
SEE NOTE 5
NOTE 1
NOTE 6
1954303:17:45 PM 07-11-2022 (-04'00' GMT)
File details come from the government source that posted it. Updated .