B08_Attachment_18_Q_A_4_25R0002_0007.pdf

PDF 247 KB Posted

Attached to
Shoshone Wildland Fire Operations and Field Office
Solicitation number
140L0625R0002
Issued by

About this file

This document is a Questions and Answers (#4) document for the GAOA Shoshone Field Office Replacement project by the Bureau of Land Management (BLM) located in Denver, Colorado. The Q&A addresses multiple technical specifications and clarifications, including: 1) document control requirements (architects and engineers will maintain an online document control system), 2) fire alarm system installation (no specific manufacturer required, must meet NFPA 72), 3) window specifications (laminated windows accepted, but adding tint film is not allowed), 4) exterior concrete work scope (detectable warning panels and trench drains included), and 5) pump and control system details (updated specifications for pump requirements and SCADA signals). The document provides contractors with specific guidance on technical requirements and clarifies ambiguities in the original solicitation documents, helping potential bidders understand the precise expectations for the project.

View the file

Other files

File Type Posted
Sol_140L0625R0002_Amd_0008.pdf PDF
B08_Attachment_19_Revised_Final_Specifications_8-7-25_0007.pdf PDF
B08_Attachment_20C_Revised_Final_Drawings_20250804_Part3_0007.pdf PDF
B08_Attachment_20D_Revised_Final_Drawings_20250804_Part4_0007.pdf PDF
B08_Attachment_20A_Revised_Final_Drawings_20250804_Part1_0007.pdf PDF
B08_Attachment_20E_Revised_Final_Drawings_20250804_Part5_0007.pdf PDF
B08_Attachment_20B_Revised_Final_Drawings_20250804_Part2_0007.pdf PDF
Sol_140L0625R0002_Amd_0007.pdf PDF
Sol_140L0625R0002_Amd_0006.pdf PDF
B08_Attachment_17_J_A_140L0625R0002_0005.pdf PDF
Sol_140L0625R0002_Amd_0005.pdf PDF
B08_Attachment_16_Q_A_3__25R0002_0004.pdf PDF
Sol_140L0625R0002_Amd_0004.pdf PDF
Sol_140L0625R0002_Amd_0003.pdf PDF
B08_Attachment_15_Past_Perf_Questionnaire_UPDATED_0002.docx DOCX document
B08_Attachment_14_Q_A_2__25R0002_0002.docx DOCX document
Sol_140L0625R0002_Amd_0002.pdf PDF
B08_Attachment_12_Q_A_1_0001.pdf PDF
B08_Attachment_13_Site_Visit_Sign-In_Sheet_0001.pdf PDF
Sol_140L0625R0002_Amd_0001.pdf PDF
B08_Attachment_3_Price_Breakout.xlsx XLSX spreadsheet
B08_Attachment_1B_Shoshone_Drawings_8-14.pdf PDF
B08_Attachment_2B_Revised_Specs_012000_Nov2024.pdf PDF
B08_Attachment_9_Wage_Determination.pdf PDF
B08_Attachment_8_Limitations_on_SubK_Breakout.xlsx XLSX spreadsheet
B08_Attachment_1D_Shoshone_Drawings_59-111.pdf PDF
B08_Attachment_1C_Shoshone_Drawings_15-58.pdf PDF
B08_Attachment_1E_Shoshone_Drawings_112-124.pdf PDF
Sol_140L0625R0002.pdf PDF
B08_Attachment_1A_Shoshone_Drawings_1-7.pdf PDF
B08_Attachment_4_Geotech_Report.pdf PDF
B08_Attachment_7_ACM_Report.pdf PDF
B08_Attachment_5_Clarifications.pdf PDF
B08_Attachment_6_Idaho_Lead-Based_Paint_Debris_Fact_Sheet.pdf PDF
B08_Attachment_11_SF1442_Completion_Instructions.pdf PDF
B08_Attachment_10_Past_Perf_Questionnaire.docx DOCX document
B08_Attachment_2A_Specifications.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

United States Department of the Interior

BUREAU OF LAND MANAGEMENT

National Operations Center

Denver Federal Center, Building 85 P.O. Box 25047

Denver, Colorado 80225-0047 http://www.blm.gov

140L0625R0002

GAOA Shoshone Filed Office Replacement

Questions and Answers #4

General Note: The Government is still reviewing questions in addition to the questions below that are listed as “Pending further review.” At this time, additional Q&A is not planned, however, if questions are opened up again the following conditions will apply:

When submitting questions, cite the drawing number and specification section / part / article / paragraph / subparagraph / etc. Questions that fail to properly cite location of question in plans and specifications may be disregarded at the Government’s discretion.

32) - UPDATED: Q: Will the government accept the use of Procore for contract management and document control during the contract?

The Government will require the architects and engineers that designed the building to maintain an online document control system that will be made available to the construction contractor after award.

75) Q: Please confirm whether the fire alarm system must be furnished and installed by a specific manufacturer-certified contractor, or if any qualified fire alarm vendor may provide the system as long as it meets NFPA 72 and project specifications. Additionally, are there any proprietary requirements, monitoring systems, or existing facility standards (e.g., Simplex, EST, Notifier, etc.) that must be matched or integrated with?

A: Specific manufacturer not required. A qualified vendor meeting requirements of NFPA and project specifications meets the requirements.

105) Q: Section 072500 (Specs) lacks details on field testing for weather barriers. Please confirm testing requirements.

A: Follow specifications, per 3.5 B., the Government may, at its discretion, perform additional testing beyond that required by the contract documents.

126) Q: Section 122413 (Specs) outlines roller window shade types but not control mechanisms.

Please confirm if manual or motorized control is required.

A: Please see updated specification 122413.

136) Q: BID ITEM 6 – SITE ROCK REMOVAL, Specs, Section 012000, 3.2(G): Please define the minimum hardness or classification of material considered “rock” for the purposes of this bid item.

A: Please see updated specification 312000.

141) Q: BID ITEM 11 – EXTERIOR CONCRETE WORK, Specs, Section 012000, 3.2(L): Please confirm if detectable warning panels and trench drains are included in the scope of exterior concrete work.

A: Please see updated drawing C110 and 10/C502.

150) Q: 08 53 13 Certainteed Vinyl windows (now owned by PlyGem) as specified provide grey tint window or laminated windows, but not grey tinted lami.

Can we provide the vinyl windows with factory glazed lami and then add grey tint film on, or can we provide heavier tinted tempered glass ¼ over 3/16 with grey tint & low E?

Please advise what is acceptable for the vinyl windows.

A: Laminated windows meeting or exceeding all described salient characteristics, but that are not factory tinted will be accepted. Adding film to windows to provide tinting will not be allowed.

153) Q: Can you confirm if the duty point will reflect the 3U-32-160B-5 HP pump that was specified with 90 GPM @ 130’ TDH or as specified at 90 GPM @ 70’

A: See updated plans and specifications, pump requirements have been updated.

Also confirm if the skid will include the valving, piping, flexible connectors, or will they be installed in the field and separate from the pump as shown in the drawings.

A: Follow Drawings and Specifications to provide a complete and functional system as described in the solicitation. See also revised specification 221123.13 and P502, P601, etc.

154) Q: Confirm if scada signals for BACnet or Lonworks DDC system are required or if simple auxiliary contacts are expected.

Referenced Section “230923 Direct Digital Control (DDC) System for HVAC” are not included in the specifications.

No P&ID is included to confirm this in the drawings.

A: Please follow specification. Broken reference to “230923 Direct Digital Control (DDC) System for HVAC” has been removed. Please see M701 – 2/M701 and 3/M701 - for additional information.

BUREAU OF LAND MANAGEMENT
National Operations Center
Denver Federal Center, Building 85
P.O. Box 25047
Denver, Colorado 80225-0047
http://www.blm.gov