This document provides details for a federal contract opportunity to design and install a saltwater system for Dry Dock 8 at Norfolk Naval Shipyard in Portsmouth, Virginia. The solicitation number is N40085-22-R-2598 and related drawings and specifications can be accessed through Notice IDs N40085-22-R-2598_Drawings and N40085-22-R-2598_Specifications. The opportunity type is a special notice and the Naval Facilities Engineering Command is the contracting agency. Offerors will be required to provide engineering and construction services to design and install a new saltwater system for Dry Dock 8 to support maintenance on the aircraft carrier CVN-78. Response is due by the date specified in the notices.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PANEL LP1A
100A, 208Y/120V-30, 4W
FEEDS FROM PANEL MDP
DEVICE ID
DEVICE RATING
POWER SOURCE
LIGHTING
120/277V TOGGLE SWITCH. SINGLE POLE, SUBSCRIPTS (A - E) WHEN
USED, DENOTES FIXTURES CONTROLLED.
LED LUMINAIRE
LED EMERGENCY LUMINAIRE. EMERGENCY BATTERY DRIVER, 1400
LUMENS MINIMUM FOR 90 MINUTES, UON (NOTE: ALL FIXTURES
NOTED ON PLAN WITH HATCH AND/OR LABELED WITH AN 'E' AFTER
THE FIXTURE TYPE INDICATES EMERGENCY)
'E' DENOTES EMERGENCY F1E
MOUNTING HEIGHT
MUST BE SAME AS CEILING UON.
LOWER CASE LETTER DENOTES SWITCH
'LEG'. THE SWITCH WITH THE SAME
LETTER OPERATES THIS FIXTURE.
LUMINAIRE TYPE
8'-0" a
PA-1,3,5 PANEL - CIRCUIT NUMBER
GROUNDING
GROUND RING COUNTERPOISE.
T
GROUND ROD, SUBSCRIPT INDICATES TYPE.
T: TEST WELL; SEE 1-ES516/C1.
POWER
SURFACE MOUNTED DUPLEX CONVENIENCE RECEPTACLE. 20A,
120V. GFI DENOTES GROUND FAULT INTERRUPTER, WPIU DENOTES
WEATHER PROOF ENCLOSURE AND C DENOTES CEILING MOUNT
(FLUSH).
SURFACE MOUNTED QUAD CONVENIENCE RECEPTACLE. 20A, 120V.
GFI DENOTES GROUND FAULT INTERRUPTER, WPIU DENOTES
WEATHER PROOF ENCLOSURE AND C DENOTES CEILING MOUNT
(FLUSH).
MOTOR RATED SWITCH OR MANUAL MOTOR STARTER WITH
OVERLOADS. M
M MOTOR / EQUIPMENT CONNECTION
HOMERUN TO PANEL. PANEL & CIRCUIT DESIGNATIONS AS
INDICATED.
MOTOR CONTROL / SAFETY SWITCH. 600V, 30A, IN NEMA 1
ENCLOSURE, UON. CROSS INDICATES COMINATION STARTER /
SAFETY SWITCH, SLASH INDICATES COMBINATION VFD / SAFETY
SWITCH.
480Y/277V PANELBOARD.
208Y/120V PANELBOARD.
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. CONDUIT
LARGER THAN 1/2" & WIRE LARGER THAN #12 MUST BE INDICATED.
FUSE SIZE IF INDICATED
DS30/F30
AMPACITY
D = SAFETY SWITCH
DS = COMBINATION STARTER / SAFETY SWITCH
V = VFD
ENCLOSED CIRCUIT BREAKER.
GROUNDING BUS BAR, MOUNT AT 7'-0" AFF UON.
SPD SURGE PROTECTIVE DEVICE
M DIGITAL METER
PLC PROGRAMABLE LOGIC CONTROLLER
MEDIUM VOLTAGE CIRCUIT BREAKER
MEDIUM VOLTAGE DRAW OUT CIRCUIT BREAKER
CURRENT TRANSFORMER
TRANSFORMER
LOW VOLTAGE CIRCUIT BREAKER
XXX - Y
ONE LINE DIAGRAM LOW VOLTAGE WIRE SIZE TAG; SEE 1-EP501/B1
XXX: AMPERAGE RATING OF THE CONDUCTORS
Y: NUMBER OF CONDUCTORS
ABBREVIATIONS
Ø PHASE
1/C ONE CONDUCTOR
A AMPERAGE OR AMPS
AFF ABOVE FINISHED FLOOR
ARF ABOVE RAISED FLOOR
AHU AIR HANDLING UNIT
BKR BREAKER
CONDUIT
CIRCUIT BREAKER
CIRCUIT
DRAWING
EACH
EMPTY CONDUIT
ELECTRICAL
ELECTRICAL METALLIC TUBING
ENCLOSURE
EQUIPMENT
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXISTING TO REMAIN
EXPLOSION PROOF EQUIPMENT
FAN COIL UNIT
FEET
GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GOVERNMENT FURNISHED EQUIPMENT
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GROUND
HEIGHT
HIGH INTENSITY DISCHARGE
HORSEPOWER
COMPUTER DISTRIBUTION HUB
LIGHT EMITTING DIODE
LUMINAIRE
MAIN CIRCUIT BREAKER
MAIN DISTRIBUTION PANEL
MECHANICAL
MAIN LUGS ONLY
MOUNTED
MOUNTING HEIGHT
NATIONAL ELECTRICAL CODE
NON FUSIBLE
NOT IN CONTRACT
NIGHT LIGHT
NOT TO SCALE
OUTLET BASE INFEED
OCCUPANCY SENSOR
PANEL
PANELBOARD
POLYVINYL CHLORIDE CONDUIT
QUANTITY
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL
ROOM
SHEET
SUBSTATION
SWITCHBOARD
TELEPHONE
TYPICAL
UNLESS OTHERWISE NOTED
VOLTAGE OR VOLTS
WIRE
WEATHERPROOF WHILE IN USE
WIREWAY (TROUGH)
IN SCHEDULES, ITEM NOT APPLICABLE
VARIABLE REFRIGERANT FLOW UNIT
BH BASEBOARD HEATER
C
CB
CKT
DWG
EA
EC
ELEC
EMT
ENCL
EQUIP
EWC
EWH
ETR
EXP
FCU
FT
GFCI
GFE
GFGI
GFI
GND
HGT
HID
HP
HUB
LED
LTS
MCB
MDP
MECH
MLO
MTD
MTG HT
NEC
NF
NIC
NL
NTS
OBI
OC
PNL
PNLBD
PVC
QU
REC
REQ'D
RGS
RM
SHT
SUB
SWBD
T
TYP
UON
V
VRF
W
WPIU
WW
X
TRANSFORMERXFMR
VARIABLE FREQUENCY DRIVEVFD
SWITCHGEARSWGR
PROGRAMABLE LOGIC CONTROLLERPLC
NORMALLY OPENN.O.
CONTRACT LINE ITEMCLIN
GENERAL
KEYNOTE TAG - REFER TO SHEET KEYNOTES ON EACH SHEET.?
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:3
P
M
1-E-001
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
LE
G
E N
D , A
B B
R E
V
IA
TI
O
N S
A N
D G
E N
E R
A L
N O
TE
S
RHS
12857703
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
GENERAL NOTES
1. ALL 1-E-001 SYMBOLS, ABBREVIATIONS, AND NOTES APPLY ONLY TO ED, EG,
EL, AND EP SERIES SHEETS. FOR ALL SITE ELECTRICAL SYMBOLS,
ABBREVIATIONS, AND NOTES SEE 1-E-011 AND 1-E-012.
2. PROVIDE EQUIPMENT GROUND WIRE(S) WITH FEEDERS AND BRANCH
CIRCUITS.
3. PROVIDE WIRING PER NATIONAL ELECTRICAL CODE (NEC).
4. LABEL AND IDENTIFY ELECTRICAL EQUIPMENT.
5. IDENTIFY FEEDERS/CIRCUITS AT EACH END OF THE WIRE AND AT EVERY
SPLICE OR JUNCTION/PULL BOX.
6. PROVIDE NAMEPLATES ON THE EXTERIOR OF ELECTRICAL PANELS AND
ENCLOSURES AS FOLLOWS:
FOR SAFETY SWITCHES, MOTOR STARTERS & VFDs, INSCRIBE THE TOP
LINE WITH THE NAME/DESIGNATION OF EQUIPMENT BEING FED BY SAME.
7. PROVIDE TYPED DIRECTORIES FOR PANELS (NEW OR EXISTING).
INCLUDED IN THIS PROJECT.
8. INTERIOR WIRING SYSTEMS MUST BE CONCEALED WITH FLUSH MOUNTED
BOXES/DEVICES, UON.
9. DRAWINGS ARE BASED ON EXISTING BUILDING PLANS AND FIELD
INVESTIGATIONS. VISIT THE EXISTING BUILDING AND ACQUAINT
HIMSELF/HERSELF WITH THE EXISTING CONDITIONS. EXAMINE EXISTING
DRAWINGS TO AVOID CONFLICTS.
10. COORDINATE LOCATION AND POWER REQUIREMENTS OF ELECTRICAL
DEVICES WITH MECHANICAL, PLUMBING, ARCHITECTURAL AND FIRE
PROTECTION DRAWINGS.
11. ELECTRICAL DEVICES SHOWN BUT NOT CIRCUITED MUST REMAIN ON THEIR
EXISTING CIRCUIT.
12. PROVIDE ARC-FLASH LABELS ON ALL SWITCHBOARDS / SWITCHGEAR /
PANELS / SAFETY SWITCHES / MOTOR STARTS / VFDs PER UFC 3-560-01
AND NFPA 70E. SEE DETAIL PLATE ON SHEET 1-EP501.
13. SINGLE PHASE (120/208V) BRANCH CIRCUITS MUST CONSIST OF 2 #12, #12 G
IN 1/2" C, UON. THREE PHASE BRANCH CIRCUITS CONSIST OF 3 #12, #12 G IN
1/2" C, UON.
14. REFER TO PLANS FOR CONDUCTOR SIZING. COMPLY WITH THE
FOLLOWING GUIDELINES FOR CONDUCTOR RUN LENGTHS:
20A,120V CIRCUITS LONGER THAN 100' - USE #10 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 120V CIRCUITS LONGER THAN 150' - USE #8 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 277V CIRCUITS LONGER THAN 150' - USE #10 AWG TO
LIMIT VOLTAGE DROP ON BRANCH CIRCUITS TO 3%
15. COORDINATE ELECTRICAL WORK WITH ARCHITECTURAL, MECHANICAL AND
FIRE PROTECTION WORK PRIOR TO FABRICATION AND INSTALLATION TO
PREVENT CONFLICTS. NOTIFY THE CONTRACTING OFFICER WHERE
CONFLICTS ARE DISCOVERED PRIOR TO CONSTRUCTION AND BEFORE
BEGINNING WORK IN THOSE AREAS. ALL CONFLICTS THAT ARISE DUE TO
LACK OF COORDINATION MUST BE RECTIFIED AT NO COST TO THE
GOVERNMENT
16. SEE SECTION 26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL
EQUIPMENT FOR ALL SYSTEMS REQUIRING SEISMIC BRACING AND
SEISMICALLY RATED EQUIPMENT.
17. CLIN EQUIPMENT IS ONLY INDICATED ON 1-ED1** AND 1-EP1** SERIES
SHEETS.
GENERAL DEMOLITION NOTES
1. ON "ED" SERIES SHEETS ONLY, EQUIPMENT SHOWN WITH DASHED LINE
MUST BE REMOVED, UON.
2. CONDUIT CONCEALED IN WALLS AND SLABS MUST BE BLANKED OFF AND
ABANDONED IN PLACE. PATCH WALLS AND SLABS AFTER DEMOLITION IS
COMPLETE.
3. EXISTING ELECTRICAL EQUIPMENT NOT INDICATED ON DEMOLITION PLAN OR
DEMOLITION ONE LINE MUST REMAIN CONNECTED FOR CONTINUED USE,
UON.
4. RECONNECT EXISTING CIRCUIT(S) (INTERRUPTED BY REMOVAL OF EXISTING
DEVICE) TO THE REMAINING ELECTRICAL EQUIPMENT LOCATED
DOWNSTREAM FROM THE POINT OF INTERRUPTION.
CONSTRUCTION NOTES
1. PROVIDE WRITTEN REQUESTS TO THE CONTRACTING OFFICER A MINIMUM
OF 14 CALENDAR DAYS PRIOR TO ANY POWER OUTAGES.
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
B
ID
D E
P A
R T
M E
N T
O
F
T
H
A V
Y
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
S
Y S
T E
M
C
M
M A
N D
DES DRW
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
DRAWFORM REVISION: 25 AUG 2020
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L
S
T A
T I O
N
N
O R
F O
L K
V
A
N O
R F
O L
K
N
A V
L
I P
Y A
R D
P O
R T
S M
O U
T H
V
I R
G I N
I A
P
D
R Y
D O
C K
S A
LT
W
A
TE
R S
Y S
TE
M
FO
R
C V
N -7
JTL/TLH
EJA
DSN
1364315
N40085-22-R-2598
DLB
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
02/02/2022
I S
S U
R
I D
ELECTRICAL LEGEND-(EXTERIOR UNDERGROUND)
UNDERGROUND DUCTBANK, CONCRETE ENCASED UON. DESCRIPTION AS INDICATED
EXISTING UNDERGROUND DUCTBANK, CONCRETE ENCASED UON. DESCRIPTION AS INDICATED
REMOVE EXISTING UNDERGROUND DUCTBANK, CONCRETE ENCASED UON DESCRIPTION AS INDICATED
UNDERGROUND CONDUIT DESCRIPTION AS INDICATED
EXISTING UNDERGROUND CONDUIT DESCRIPTION AS INDICATED
SYMBOL REFERS TO DEPTH OF DUCTBANK SECTION. SEE DUCTBANK DETAILS
UNDERGROUND ELECTRICAL DISTRIBUTION CONCRETE ENCASED DUCTBANK SECTION LOOKING IN DIRECTION OF
ARROWS
SPARE DUCT (TYPICAL). DESCRIPTION PER CABLE AND CONDUIT SCHEDULES ON SHEET 1-ES603
HEAVY LINE INDICATES BOTTOM OF DUCT
EXISTING CABLE DESIGNATION WITH CIRCLE (TYPICAL) DESCRIPTION PER CABLE AND CONDUIT SCHEDULES
ON SHEET 1-ES603
OCCUPIED CONDUIT, UNIDENTIFIED EXISTING CABLE
CABLE DESIGNATION (TYPICAL)
DESCRIPTION PER CABLE AND CONDUIT SCHEDULES ON SHEET 1-ES603
GROUNDING CONDUCTOR
EXOTHERMIC CONNECTION
GROUND ROD
MANHOLE OR HANDHOLE AS NOTED
EQUIPMENT CODE CLEARANCE
EQUIPMENT MAINTENANCE/VENTILATION CLEARANCE
EQUIPMENT MAINTENANCE/VENTILATION AND EGRESS CLEARANCE
JUNCTION BOX
LIGHT POLE
SPEAKER
EQUIPMENT CONNECTION
MOTOR CONNECTION, HP INDICATED
GENERATOR AS NOTED
DISCONNECT SWITCH, 600V IN NEMA 4X ENCLOSURE UON
3P = NO. OF POLES, 60 = SWITCH RATING, 40 = FUSE RATING
(NF INDICATES NON-FUSIBLE)
MOTOR CONTROLLER BY DIVISION 21 CONTRACTOR
EQUIPMENT AS NOTED
ELECTRICAL PANELBOARD (208Y/120 VOLT)
ELECTRICAL PANELBOARD (480Y/277 VOLT)
REMOVE EXISTING EQUIPMENT INDICATED
LIMIT OF DEMOLITION
NEW TO EXISTING CONNECTION
LIGHTING FIXTURE TYPE
COPING WALL JUNCTION CHAMBER
L - LIGHTING
F
P - PUBLIC ADDRESS
2 S1
X N1
J
M
3P
ELECTRICAL LEGEND (ONE-LINE & RISER DIAGRAMS)
POWER TRANSFORMER
POTENTIAL TRANSFORMER
CONTROL POWER TRANSFORMER
SURGE ARRESTOR
FUSED SWITCH
SWITCH
TRANSFER SWITCH
MOLDED CASE CIRCUIT BREAKER
LOW VOLTAGE DRAW-OUT POWER CIRCUIT BREAKER
MEDIUM VOLTAGE POWER CIRCUIT BREAKER
POWER DRAW OUT CIRCUIT BREAKER
GROUNDED WYE CONNECTION
UNGROUNDED WYE CONNECTION
CURRENT TRANSFORMER - SINGLE RATIO AS SHOWN
SURGE PROTECTIVE DEVICE
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
CONTROL SWITCH
CABLE TERMINATIONS
GROUNDING ELECTRODE CONNECTION
CABLE OR BUS, TYPE AND CHARACTERISTICS AS INDICATED
EXISTING CABLE OR BUS, TYPE AND CHARACTERISTICS AS INDICATED
NEW TO EXISTING CABLE SPLICE OR TAP
HOMERUN TO PANELBOARD. NO. OF ARROWS INDICATE NO. OF CIRCUITS.
TICKMARKS INDICATE NO. OF AWG CONDUCTORS.
REMOVE CABLE OR BUS, TYPE AND CHARACTERISTICS AS INDICATED
RELAY AND ANSI CONTROL FUNCTION SYMBOL.
CONTACTS - NORMALLY OPEN
CONTACTS - NORMALLY CLOSED
FUSE
GROUND
PUSHBUTTON
WHD METER
ASTRONOMICAL TIME CLOCK
ELECTRICAL METERING
PT
CPT
CT
600/S
ABBREVIATIONS
ELECTRICAL LEGEND (MISCELLANEOUS)
KEYNOTE SYMBOL
SPD
PT
CS
1/C SINGLE CONDUCTOR
3/C THREE CONDUCTOR
A AMP/AMPERE
AC ALTERNATING CURRENT
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AIC AMPS INTERRUPTING CAPACITY
AMI ADVANCED METERING INFRASTRUCTURE
AS AIR SWITCH
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAGE
BFG BELOW FINISHED GRADE
BLDG. BUILDING
BOD BASIS OF DESIGN
BRKR BREAKER
C CONDUIT
CAP CAPSTAN
CB CIRCUIT BREAKER
CFM CUBIC FEET/MINUTE
CHP CRANE HOTEL POWER
CKT CIRCUIT
CLR CLEAR
CONT CONTINUOUS
CPT CURRENT POTENTIAL TRANSFORMER
CST COMMUNICATIONS SHORE TIE
CT CURRENT TRANSFORMER
CU COPPER
D DEPTH
DDC DIRECT DIGITAL CONTROL
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
ECB ENCLOSED CIRCUIT BREAKER
EDC ENVIRONMENTAL DISTRIBUTION CENTER
EMH ELECTRIC MANHOLE
EPR ETHYLENE PROPYLENE RUBBER
EQ EQUAL
EQUIP EQUIPMENT
EX,EXIST EXISTING
FA FIRE ALARM
FLA FULL LOAD AMPS
FO FIBER OPTIC CABLE
FPMT FUTURE PAD-MOUNTED TRANSFORMER
GFI/GFCI GROUND FAULT CURRENT INTERRUPTER
GND GROUND
GOVT GOVERNMENT
GS GAS SWITCH
H HEIGHT
HMI HUMAN MACHINE INTERFACE
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPS HIGH PRESSURE SODIUM
JBOX JUNCTION BOX
KAIC THOUSAND AMPERE INTERRUPTING CAPACITY
KCMIL/MCM THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
L LENGTH, ANGLE
LAN LOCAL AREA NETWORK
LTS LIGHTS
LV LOW VOLTAGE
LVCB LOW VOLTAGE CONNECTION BOX
LVST LOW VOLTAGE SHORE TIE STATION
MCB MAIN CIRCUIT BREAKER
MAX MAXIMUM
MESG METAL ENCLOSED INTERRUPTER SWITCHGEAR
MH MANHOLE
MIN MINIMUM
MM MULTIMODE
MT MOUNT
MTG HT MOUNTING HEIGHT
MV MEDIUM VOLTAGE
MVA THOUSAND KILOVOLT VOLT AMPERES
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NESC NATIONAL ELECTRICAL SAFETY CODE
NF NON FUSED
NNSY NORFOLK NAVAL SHIPYARD
N.O. NORMALLY OPEN
NO. NUMBER
NTS NOT TO SCALE
NU NAVFAC UTILITIES
O/C ON CENTER
OSP OUTSIDE PLANT
P POLE
PA PUBLIC ADDRESS
PLC PROGRAMMABLE LOGIC CONTROL
PMS PAD-MOUNTED SWITCH
PMT PAD-MOUNTED TRANSFORMER
PT POTENTIAL TRANSFORMER
PW PUMPWELL
PVC POLYVINYL CHLORIDE
REC RECEPTACLE
REOL REMOVABLE END OF LINE RESISTOR
REQ'D. REQUIRED
RSC RIGID STEEL CONDUIT
RTU REMOTE TERMINAL UNIT (SCADA)
SCADA SUPERVISORY CONTROL AND DATA AQUISITION
SCH SCHEDULE
SE SERVICE ENTRANCE
SER SERVICE ENTRANCE RATED (UL LISTED)
SM SINGLE-MODE
SMFO SINGLE MODE FIBER OPTIC
SPA SPACE, SPACING
SMH SIGNAL MANHOLE
SS STAINLESS STEEL
SUB SUBSTATION
T TRANSFORMER
TB TURTLEBACK
TOD TOP OF DUCTBANK ELEVATION
TOM TOP OF MANHOLE ELEVATION
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UL UNDERWRITERS LABORATORIES
V VOLT, VOLTAGE
VAC VOLTS ALTERNATING CURRENT
VFI VACUUM FAULT INTERRUPTER
W WATT, WIRE, WIDTH
WI WEATHERPROOF IN-USE
WP WEATHERPROOF
XFMR TRANSFORMER
E
G
WHD
ATC
S
A
J
FEEDER DESIGNATION. SEE SCHEDULES
FIRE ALARM PULL BOX, 18" X 12" X 18"
J
GROUND TEST PIT
EM
DZ RAD WAS
12857704
L E
G E
N D
A
B B
R E
V I A
T I O
M
B O
L S
1-E-011
AS NOTED
P A
R T
M E
T
V
Y
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
S
Y S
T E
M
M A
N D
DES DRW
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
DRAWFORM REVISION: 25 AUG 2020
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L
S
T A
T I O
N
N
O R
F O
L K
V
A
N O
R F
O L
K
N
A V
I P
Y A
R D
P O
R T
S M
O U
T H
V
I R
G I N
I A
P
D
R Y
D O
C K
S A
LT
W
A
TE
R S
Y S
TE
M
FO
R
C V
N -7
JTL/TLH
EJA
DSN
1364315
N40085-22-R-2598
DLB
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
02/02/2022
I S
S U
D
1. ALL 1-E-011 AND 1-E-012 SYMBOLS, ABBREVIATIONS AND NOTES APPLY ONLY TO ED AND ES
SERIES SHEETS.
2. CONDUIT AND DUCT ROUTINGS SHALL NOT INTERFERE WITH NEW OR EXISTING EQUIPMENT,
PIPING, OR CONDUIT AND SHALL NOT OBSTRUCT ACCESS TO ANY EQUIPMENT.
3. THE EQUIPMENT GROUND CONDUCTOR SHALL BE CONNECTED TO ALL DEVICES SUCH THAT
REMOVAL OF ANY DEVICE CANNOT INTERRUPT THE CONTINUITY OF THE EQUIPMENT
GROUNDING CONDUCTOR TO AND FROM OTHER DEVICES OR EQUIPMENT.
4. WIRE AND CONDUIT FOR EQUIPMENT AND MOTOR LOADS SHALL BE CONTINUOUS IN SIZE AND
COUNT FROM THE SOURCE TO THE FINAL CONNECTION. SIZE AND COUNT SHALL BE AS
INDICATED ON THE CIRCUIT HOMERUN OR FEEDER SCHEDULE, UNLESS OTHERWISE NOTED.
5. CONTRACTOR SHALL PERFORM A FEEDER, MANHOLE AND DUCT-ROUTE SURVEY PRIOR TO
BEGINNING CONSTRUCTION TO VERIFY THE ROUTING OF THE EXISTING FEEDERS,
AVAILABILITY OF EXISTING MANHOLES AND DUCTS INTENDED TO BE USED. PROVIDE THE
CONTRACTING OFFICER WITH RESULTS OF THIS SURVEY AND SKETCH OF DUCTBANK
SECTIONS SHOWING LOCATIONS OF OCCUPIED DUCTS AND CABLES TO BE INSTALLED.
6. THE CONTRACTOR SHALL DE-WATER MANHOLES AND HANDHOLES BEFORE COMMENCING
WORK. THE CONTRACTORS DE-WATERING PUMPS SHALL BE AVAILABLE IN CASE WATER
SEEPAGE DOES NOT SUBSIDE. UNDER NO CIRCUMSTANCES SHALL OPEN CABLE SPLICES OR
CUT TERMINATIONS EVER COME IN CONTACT WITH WATER.
7. UNLESS SPECIFICALLY NOTED TO BE EXISTING, ALL WORK AND MATERIAL SHALL BE
PROVIDED BY THE CONTRACTOR. WHEREVER AN EXISTING TO PROPOSED CONNECTION IS
REQUIRED, PROVIDE EXTENSION RINGS, SPLICES, WIRE, CONDUIT FITTINGS, AND
ASSOCIATED APPURTENANCES. PERFORM ALL CUTTING AND PATCHING AS REQUIRED TO
MAKE THE CONNECTIONS.
8. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ALL COMMUNICATIONS (NAVFAC
UTILITIES, SCADA, ETC.) CABLES AND EQUIPMENT INTO EXISTING FACILITIES AND BUILDINGS
WITH CONTRACTING OFFICER AND NNSY PRIOR TO COMMENCING THIS WORK.
COORDINATION AND DISCUSSION BETWEEN ALL PARTIES INVOLVED WITH THIS WORK SHALL
TAKE PLACE IN WEEKLY MEETING AND ADDITIONAL MEETINGS AS REQUIRED ESPECIALLY
FOR THIS PURPOSE.
9. THE CONTRACTOR SHALL CLOSELY STUDY THE CONSTRUCTION PLANS AND NOTES AS
OUTLINED. SLIGHT DEVIATIONS FROM CONFINED WORK SPACES MAY BE NECESSARY TO
FULLY COMPLETE A CONSTRUCTION AREA AS OUTLINED ON THOSE SHEETS. THE DEVIATIONS
SHALL BE HELD TO A MINIMUM AND SHALL BE FULLY COORDINATED WITH THE CONTRACTING
OFFICER. ALL SUCH DEVIATIONS SHALL BE MADE WITH NO ADDITIONAL COST TO THE
GOVERNMENT.
10. DURING THE EXECUTION OF THIS WORK, THE GOVERNMENT WILL CONTINUE TO OCCUPY AND
OPERATE ALL ADJACENT FACILITIES, PIERS, BERTHS, WHARFS, BUILDINGS AND UTILITIES,
AND, THEREFORE, WILL REQUIRE CONTINUOUS OPERATION OF ALL EXISTING ELECTRIC AND
TELECOMMUNICATIONS SERVICES. OUTAGES REQUIRED FOR CONSTRUCTION PURPOSES
SHALL BE SCHEDULED FOR THE SHORTEST PRACTICAL PERIODS OF TIME, AND THEN ONLY
BY PRE-ARRANGEMENT WITH THE CONTRACTING OFFICER FOR MUTUALLY AGREEABLE
PERIODS. AFTER EACH OF WHICH THE INTERRUPTION SHALL CEASE AND SERVICE SHALL BE
RESTORED.
11. THE CONTRACTOR SHALL PERFORM WORK ON UNENERGIZED CABLES WITH ENERGIZED
CABLES IN MANHOLE.
12. SPLICING OF FEEDERS WITHIN MANHOLES OR UNDERGROUND IS DISCOURAGED.
13. PLATFORM MOUNTED EQUIPMENT (SUBSTATIONS, MV SWITCVHES, SWITCHGEAR,
GENERATORS, FUEL STORAGE SYSTEMS, ETC.) LAYOUT IS PARTIALLY DIAGRAMMATIC.
CONTRACTOR SHALL VERIFY THE CODE REQUIRED CLEARANCES FOR APPROVED
EQUIPMENT AND ADJUST THE EQUIPMENT LAYOUT, DUCTBANK AND CONDUIT ROUTING, AND
SUPPORTING STRUCTURES AS NECESSARY.
1. COORDINATE ALL DUCTBANK ROUTING WITH EXISTING AND NEW STRUCTURES, INCLUDING
PLATFORM PILES. ROUTE DUCTBANKS TO AVOID CONFLICTS.
2. LOCATIONS AND ROUTING OF CONDUITS, DUCTBANKS AND ELECTRICAL STRUCTURES SHOWN
ON THE DRAWINGS ARE APPROXIMATE. PRIOR TO EXCAVATION AND INSTALLATION, THE
CONTRACTOR SHALL COORDINATE AND VERIFY LOCATIONS, ROUTING AND DEPTHS OF ALL
CONDUITS, DUCTS AND STRUCTURES WITH ALL OTHER TRADES TO AVOID CONFLICTS WITH ALL
NEW AND EXISTING UTILITIES AND STRUCTURAL FEATURES.
3. THE CONTRACTOR SHALL COORDINATE THE ROUTING OF THE DUCTBANKS AND MAKE ANY
ADJUSTMENTS REQUIRED IN HORIZONTAL AND VERTICAL DIRECTIONS OF THE ENTIRE
DUCTBANK RUN TO MISS ANY UTILITIES INCLUDING OTHER DUCTBANKS. THE ADJUSTMENTS
SHALL CONSIDER THE ENTIRE CABLING RUN SHALL NOT EXCEED 360 DEGREES WORTH OF
BENDS BETWEEN PULLING POINTS IN A SINGLE RUN PER THE NEC.
4. PROVIDE 20 MIL PLASTIC SHEETING IN BETWEEN DUCTBANKS WHERE DUCTBANKS COME IN
CONTACT.
5. PROVIDE PULL STRING IN EVERY DUCT WHERE EXISTING CABLING IS REMOVED PER
DEMOLITION DRAWINGS.
GENERAL DEMOLITION NOTES:
1. SEE DEMOLITION ONE-LINE DIAGRAMS AND CABLE SCHEDULES ON ES600 SERIES SHEETS.
2. REMOVE CONDUCTORS FROM CONDUITS AND DUCTS AND DISCONNECT FROM ALL POWER
SOURCES AS REQUIRED TO ACCOMPLISH THE WORK OF THIS CONTRACT. REFER TO SHEETS ED
SERIES DRAWINGS FOR DEMOLITION, INCLUDING UTILITIES, DUCTBANKS AND OTHER
STRUCTURES.
3. DEMOLITION OF DUCTBANKS SHALL INCLUDE REMOVAL OF SECTIONS INDICATED IN ED100
SERIES DRAWINGS. ALL MANHOLES ARE EXISTING TO REMAIN, UON.
4. EXCEPT AS NOTED ELSEWHERE AND AS REQUIRED BY CONSTRUCTION PHASING, ALL EXISTING
SERVICES (ELECTRIC, TELEPHONE, LAN, NAVFAC UTILITIES, CATV, PA, NAVFAC UTILITIES
SECURITY, ETC.) SHALL REMAIN ACTIVE.
5. THE ENTIRE RUN OF ABANDONED CONDUITS WITHIN DUCTBANKS SHALL BE GROUTED
COMPLETE. GROUT ABANDONED CONDUITS WITHIN DUCTBANKS FLUSH WITH THE INTERIOR OF
MANHOLES AND FLUSH WITH THE ENDS OF THE CONDUITS.
6. SEE ELECTRICAL GENERAL NOTES FOR ADDITIONAL DEMOLITION AND REDISTRIBUTION
REQUIREMENTS.
ELECTRICAL GENERAL NOTES (APPLICABLE TO ALL SHEETS)ELECTRICAL GENERAL DUCTBANK NOTES
GENERAL CONSTRUCTION NOTES:
1. THE CONTRACTOR SHALL COORDINATE WITH THE CONTRACTING OFFICER FOR OTHER WORK
AROUND DRY DOCK 8.
2. SCHEDULE WORK AROUND ALL TEMPORARY AND PERMANENT EQUIPMENT ASSOCIATED WITH
THE GOVERNMENT WORK IN DRY DOCK 8.
3. ALL OUTAGES REQUIRED WILL BE SCHEDULED WITH THE GOVERNMENT AT LEAST 30 DAYS
PRIOR. THE CONTRACTOR SHALL WORK AROUND THE SCHEDULE OF THE GOVERNMENT WITHIN
DRY DOCK 8.
DZ RAD WAS
12857705
G E
N E
R A
L
N
O T
E S
1-E-012
(E) 2300V
SWGR
(E) MDP-2
MCC
(E) MDP-3
MCC
(E) MDP-4
MCC
(E) DP-1 MCC
(E) DP-2 MCC
(E) DP-3
MCC(E) 480V
SWITCHBOARD (ETR) PANEL LP-3
(E) MDP-1
MCC
(E) MDP-1 (E) MDP-2 (E) MDP-3 (E) MDP-4
(E) DP-1
(E) DP-2
480V PANEL
222 2
(ETR) PANEL LP-1
(ETR) PANEL LP-2
(E) PULL BOX
12 12 12
13131313
(E) PW8-V-56
(E) PW8-V-29
X1
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:3
P
M
1-ED101
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
P U
M P
W E
LL
E
LE
C
T R
IC
A
L D
E M
O
LI
T
IO
N P
LA
N
RHS
12857706
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
SHEET NOTES
1. BOLD, DASHED LINES INDICATE EQUIPMENT TO BE DEMOLISHED.
2. DE-ENERGIZE, DISCONNECT AND DEMOLISH ALL CONDUIT AND CONDUCTORS
FEEDING EQUIPMENT TO BE DEMOLISHED. INFILL ALL ABANDONED CONDUIT
PENETRATIONS WITH NONSHRINK GROUT.
3/16" = 1'-0" B1
PUMPWELL 8 - ELECTRICAL DEMOLITION PLAN - MOTOR
0' 4' 8' 12'
PLAN
NORTH
KEY PLAN
MOTOR
83'-0"
INTERMED.
68'-0"
MAIN PUMP
46'-0"
DRAINAGE
28'-3 1/4"
COPING
103'-0"
SUC. CHAM.
32'-3"
SHEET KEYNOTES
1. DISCONNECT AND REMOVE EXISTING VALVE'S ELECTRICAL CONDUIT AND
CONDUCTORS BACK TO SOURCE.
2. 30A SAFETY SWITCH FOR MDP. DE-ENERGIZE, DISCONNECT, AND DEMOLISH
CONDUIT AND CONDUCTORS BACK TO SOURCE. FED FROM THE 480V
SWITCHBOARD.
3. DISCONNECT AND REMOVE EXISTING AIR COMPRESSOR'S ELECTRICAL
CONDUIT AND CONDUCTORS BACK TO SOURCE.
4. DISCONNECT AND REMOVE EXISTING BUBBLER PANEL'S ELECTRICAL
CONDUIT AND CONDUCTORS BACK TO SOURCE.
5. DISCONNECT AND REMOVE EXISTING PTU'S ELECTRICAL CONDUIT AND
CONDUCTORS BACK TO SOURCE.
6. EXISTING TO REMAIN TRANSFORMER 1 AND TRANSFORMER 2 ARE CEILING
MOUNTED ABOVE EXISTING PANELS LP-1 AND LP-2.
7. DISCONNECT AND REMOVE MOTOR STARTER PANEL. DEMOLISH ALL LOAD
SIDE CONDUIT AND CONDUCTORS BACK TO THE CONNECTED EQUIPMENT.
DEMOLISH ALL LINE SIDE CONDUIT AND CONDUCTORS BACK TO SOURCE.
8. DISCONNECT AND REMOVE SWITCHGEAR / SWITCHBOARD. DISCONNECT AND
REMOVE LINE SIDE CONDUIT BACK TO THE INCOMING PENETRATION AT THE
EXISTING PULLBOX, SEE SHEET KEYNOTE 9. DISCONNECT AND REMOVE LINE
SIDE CONDUCTORS BACK TO SOURCE.
9. SEAL ALL CONDUIT VOIDS WITH NON-SHRINK GROUT.
10. DISCONNECT AND REMOVE ALL LIGHTING AND POWER CIRCUITS
ASSOCIATED WITH THE CONTROL BOOTH. DISCONNECT AND REMOVEALL
CONDUIT AND CONDUCTORS BACK TO SOURCE.
11. DISCONNECT AND REMOVE CONTROL PANEL'S ELECTRICAL CONDUIT AND
CONDUCTORS BACK TO SOURCE.
12. DISCONNECT AND REMOVE MCC'S LINE SIDE CONDUIT AND CONDUCTORS
BACK TO SOURCE. DISCONNECT AND REMOVE LOAD SIDE CONDUIT AND
CONDUCTORS BACK TO LOAD.
13. DISCONNECT AND REMOVE MDP'S ELECTRICAL CONDUIT AND CONDUCTORS
BACK TO SOURCE.
X1. CLIN 0002.
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
1 1
(E) PW8-ACT-10
(E) PW8-ACT-7
(E) PW8-ACT-53
(E) PW8-ACT-3
X1
(E)SP-1
(E)SP-2
X1
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-ED102
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
P U
M P
W E
LL
E
LE
C
T R
IC
A
L D
E M
O
LI
T
IO
N P
LA
N
RHS
12857707
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
3/16" = 1'-0" C1
PUMPWELL 8 - ELECTRICAL DEMOLITION PLAN - INTERMEDIATE
SHEET KEYNOTES
1. 30A SAFETY SWITCH FOR MDP DISCHARGE VALVE. DE-ENERGIZE,
DISCONNECT, AND DEMOLISH CONDUITS AND CONDUCTORS BACK TO
SOURCE. FED FROM THE 480V SWITCHBOARD.
2. DISCONNECT AND REMOVE EXISTING ACT'S ELECTRICAL CONDUIT AND
CONDUCTORS BACK TO SOURCE.
3. DISCONNECT AND REMOVE EXISTING SUMP PUMP'S ELECTRICAL CONDUIT
AND CONDUCTORS BACK TO SOURCE.
4. DISCONNECT AND REMOVE EXISTING HIGH WATER ALARM'S ELECTRICAL
CONDUIT AND CONDUCTORS BACK TO SOURCE.
X1. CLIN 0002.
0' 4' 8' 12'
PLAN
NORTH
KEY PLAN
MOTOR
83'-0"
INTERMED.
68'-0"
MAIN PUMP
46'-0"
DRAINAGE
28'-3 1/4"
COPING
103'-0"
SUC. CHAM.
32'-3"
SHEET NOTES
1. BOLD, DASHED LINES INDICATE EQUIPMENT TO BE DEMOLISHED.
2. DE-ENERGIZE, DISCONNECT AND DEMOLISH ALL CONDUIT AND CONDUCTORS
FEEDING EQUIPMENT TO BE DEMOLISHED.
3/16" = 1'-0" A1
PUMPWELL 8 - ELECTRICAL DEMOLITION PLAN - MAIN PUMP & DRAINAGE PUMP
0' 4' 8' 12'
PLAN
NORTH
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
EMH-N12
MV SWITCH
DD8-G/S-1N
MV SWITCH
DD8-G/S-2N
06 06
06 06
06 06
06 X
06 06
06 06
06 06
06 X
X
X
X
060606
D E
P A
R T
M E
T
V
Y
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
S
Y S
T E
M
M A
N D
DES DRW
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
DRAWFORM REVISION: 25 AUG 2020
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L
S
T A
T I O
N
N
O R
F O
L K
V
A
N O
R F
O L
K
N
A V
I P
Y A
R D
P O
R T
S M
O U
T H
V
I R
G I N
I A
P
D
R Y
D O
C K
S A
LT
W
A
TE
R S
Y S
TE
M
FO
R
C V
N -7
JTL/TLH
EJA
DSN
1364315
N40085-22-R-2598
DLB
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
02/02/2022
I S
S U
D
SHEET NOTES
NORTH
PLAN
KEY PLAN
4 5
11 12
2 3
13 14
SHEET KEYNOTES
SCALE: 1" = 20'
PHASE I - ELECTRICAL DEMOLITION PLAN - AREA 9
A1
PLAN
NORTH
40'10'0 20'
1. REFER TO SHEET 1-ES603 FOR CABLE AND CONDUIT SCHEDULE.
2. REFER TO SHEET 1-E-011 FOR ELECTRICAL LEGEND AND
ABBREVIATIONS.
1. DISCONNECT MV FEEDER 18 BETWEEN MV SWITCH DD8-G/S-1N
AND MV SWITCH DD8-G/S-2N.
2. DISCONNECT AND REMOVE FEEDER 18 FROM DUCTBANK.
MATCH LINE
A1/1-ED134
DZ RAD WAS
12857708
E L
E C
T R
I C
T
E
D
E M
O L
I T
I O
N
P
L A
N
A
R E
A
1-ED129
EMH-631
EMH-S631
MV SWITCH
DD8-G/S-1S
BUILDING 272
EMH-878
EMH-632
EMH-S632
EMH-881
MV SWITCH G/S-4
MV SWITCH G/S-3
EMH-1490
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XXX
X
X
X
X
X
X
XXX
10X
10X
X06
X X X
X
X
X
X
X
X
X X X
D E
P A
R T
M E
T
V
Y
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
S
Y S
T E
M
M A
N D
DES DRW
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
DRAWFORM REVISION: 25 AUG 2020
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L
S
T A
T I O
N
N
O R
F O
L K
V
A
N O
R F
O L
K
N
A V
I P
Y A
R D
P O
R T
S M
O U
T H
V
I R
G I N
I A
P
D
R Y
D O
C K
S A
LT
W
A
TE
R S
Y S
TE
M
FO
R
C V
N -7
JTL/TLH
EJA
DSN
1364315
N40085-22-R-2598
DLB
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
02/02/2022
I S
S U
D
NORTH
PLAN
KEY PLAN
4 5
11 12
2 3
13 14
M A
T C
H
L I N
E
A E
D
SHEET NOTES
SHEET KEYNOTES
1. DISCONNECT FEEDERS 33 FROM DISTRIBUTION VI 2.3KV BUS
INSIDE BUILDING 272.
2. REMOVE FEEDERS 33 CONDUCTORS FROM DUCTBANK.
3. DISCONNECT FEEDER 10 FROM SWITCH DD8-G/S-1S.
4. REMOVE FEEDER 10 CONDUCTORS FROM DUCTBANK.
SCALE: 1" = 20'
PHASE I - ELECTRICAL DEMOLITION PLAN - AREA 12
A1
PLAN
NORTH
40'10'0 20'
1. REFER TO SHEET 1-ES603 FOR CABLE AND CONDUIT SCHEDULE.
2. REFER TO SHEET 1-E-011 FOR ELECTRICAL LEGEND AND
ABBREVIATIONS.
DZ RAD WAS
12857709
E L
E C
T R
I C
T
E
D
E M
O L
I T
I O
N
P
L A
N
A
R E
A
1-ED132
EMH-S640
BUILDING 274
EMH-885
EMH-888
EMH-640
EMH-1487
UNIT SUBSTATIONS
10X
X06
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XXX
X
X
X
X
X
X
XXX
10X
X06
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
D E
P A
R T
M E
T
V
Y
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
S
Y S
T E
M
M A
N D
DES DRW
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
DRAWFORM REVISION: 25 AUG 2020
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L
S
T A
T I O
N
N
O R
F O
L K
V
A
N O
R F
O L
K
N
A V
I P
Y A
R D
P O
R T
S M
O U
T H
V
I R
G I N
I A
P
D
R Y
D O
C K
S A
LT
W
A
TE
R S
Y S
TE
M
FO
R
C V
N -7
JTL/TLH
EJA
DSN
1364315
N40085-22-R-2598
DLB
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
02/02/2022
I S
S U
D
NORTH
PLAN
KEY PLAN
4 5
11 12
2 3
13 14
M A
T C
H
L I N
E
A E
D
M A
T C
H
L I N
E
A E
D
SHEET NOTES
SHEET KEYNOTES
SCALE: 1" = 20'
PHASE I - ELECTRICAL DEMOLITION PLAN - AREA 13
A1
PLAN
NORTH
40'10'0 20'
1. REMOVE FEEDERS 33 CONDUCTORS FROM DUCTBANK.
2. REMOVE FEEDER 10 CONDUCTORS FROM DUCTBANK.
1. REFER TO SHEET 1-ES603 FOR CABLE AND CONDUIT SCHEDULE.
2. REFER TO SHEET 1-E-011 FOR ELECTRICAL LEGEND AND
ABBREVIATIONS.
DZ RAD WAS
12857710
E L
E C
T R
I C
T
E
D
E M
O L
I T
I O
N
P
L A
N
A
R E
A
1-ED133
EMH-S634
DD8-G/S-2S
SUBSTATION Z4-E
SUBSTATION
Z4-F
BUILDING 274
EMH-S635
EMH-635
EMH-S5EMH-634
PUMPWELL
EMH-891
EMH-892
EMH-893
EMH-890
M14
EMH-895 EMH-896
M14
M14
M14
10987
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
C3
X
X
C2
C4
X
X
X
X
X X
X
X
X
X X
X X
X X
X X
X X
X
X
X
X
X
X
C3
C4
C2
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
10X
X06
10X
X06
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
C3
C2
C4
04 04
C3
C2
C4
04 04
D E
P A
R T
M E
T
V
Y
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
S
Y S
T E
M
M A
N D
DES DRW
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
DRAWFORM REVISION: 25 AUG 2020
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L
S
T A
T I O
N
N
O R
F O
L K
V
A
N O
R F
O L
K
N
A V
I P
Y A
R D
P O
R T
S M
O U
T H
V
I R
G I N
I A
P
D
R Y
D O
C K
S A
LT
W
A
TE
R S
Y S
TE
M
FO
R
C V
N -7
JTL/TLH
EJA
DSN
1364315
N40085-22-R-2598
DLB
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
02/02/2022
I S
S U
D
NORTH
PLAN
KEY PLAN
4 5
11 12
2 3
13 14
MATCH LINE
A1/1-ED129
M A
T C
H
L I N
E
A E
D
M A
T C
H
L I N
E
A E
D
SHEET NOTES
SHEET KEYNOTES
SCALE: 1" = 20'
PHASE I - ELECTRICAL DEMOLITION PLAN - AREA 14
A1
PLAN
NORTH
40'10'0 20'
1. DISCONNECT FEEDERS 34 FROM SUBSTATION Z4-E AND Z4-F.
2. REMOVE FEEDERS 34 CONDUCTORS FROM DUCTBANK.
3. REMOVE FEEDERS 33 CONDUCTORS FROM DUCTBANK.
4. REMOVE FEEDER 10 CONDUCTORS FROM DUCTBANK.
5. DISCONNECT AND REMOVE FEEDERS 33 AND 34
CONDUCTORS INSIDE THE PUMPWELL.
6. DISCONNECT FEEDER 10 FROM SWITCH DD8-G/S-2S.
7. REMOVE POWER FEEDER M14 FROM EMH-897 BACK EMH-896.
PROVIDE PULL WIRE IN VACATED CONDUIT. PROTECT THE
REMAINING FEEDER M14 CONDUCTORS INSIDE EMH-896 FOR
FUTURE RECONNECTION.
8. REMOVE SLUICE GATE CONTROL CABLE C2 BACK TO ITS
SOURCE IN BUILDING 274.
9. REMOVE TIDE WATER LEVEL GAUGE CABLE C4 BACK TO
EMH-896. PROVIDE PULL WIRE IN VACATED CONDUIT.
PROTECT THE REMAINING CABLE C4 INSIDE EMH-896 FOR
FUTURE RECONNECTION.
10. REMOVE DOCK WATER LEVEL GAUGE CABLE C3 BACK TO
EMH-896. PROVIDE PULL WIRE IN VACATED CONDUIT.
PROTECT THE REMAINING CABLE C3 INSIDE EMH-896 FOR
FUTURE RECONNECTION.
X1 CLIN 0002
1. REFER TO SHEET 1-ES603 FOR CABLE AND CONDUIT SCHEDULE.
2. REFER TO SHEET 1-E-011 FOR ELECTRICAL LEGEND AND
ABBREVIATIONS.
DZ RAD WAS
12857711
E L
E C
T R
I C
T
E
D
E M
O L
I T
I O
N
P
L A
N
A
R E
A
1-ED134
AS NOTED
X1
X1
X1
EMH-636
EMH-S636
EMH-913
M14
EMH-897
DOCK WATER
LEVEL GAUGE
CAISSON POWER
PEDESTAL
SLUICE GATE VALVE
2 5
M16
EMH-898
M153
CAPSTAN 42
TIDE WATER
LEVEL GAUGE 6
M15 3
C4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX31
C3
C2
C4
04 04
C3
C2
P2
D E
P A
R T
M E
T
V
Y
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
S
Y S
T E
M
M A
N D
DES DRW
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
DRAWFORM REVISION: 25 AUG 2020
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L
S
T A
T I O
N
N
O R
F O
L K
V
A
N O
R F
O L
K
N
A V
I P
Y A
R D
P O
R T
S M
O U
T H
V
I R
G I N
I A
P
D
R Y
D O
C K
S A
LT
W
A
TE
R S
Y S
TE
M
FO
R
C V
N -7
JTL/TLH
EJA
DSN
1364315
N40085-22-R-2598
DLB
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
02/02/2022
I S
S U
D
SHEET NOTES
NORTH
PLAN
KEY PLAN
M A
T C
H
L I N
E
A E
D
4 5
11 12
2 3
13 14
SCALE: 1" = 20'
PHASE I - ELECTRICAL DEMOLITION PLAN - AREA 15
A1
PLAN
NORTH
40'10'0 20'
1. REFER TO SHEET 1-ES603 FOR CABLE AND CONDUIT SCHEDULE.
2. REFER TO SHEET 1-E-011 FOR ELECTRICAL LEGEND AND
ABBREVIATIONS.
SHEET KEYNOTES
1. DISCONNECT SLUICE GATE VALVE POWER FEEDER M16 AND
CONTROL CABLE C2. REMOVE FEEDER M16 BACK TO A SPLICE
INSIDE EMH-897.
2. DISCONNECT CAISSON POWER PEDESTAL FEEDER P2. REMOVE
CONDUCTORS BACK TO A SPLICE INSIDE EMH-897.
3. REMOVE CAPSTAN 42 FEEDER M15 BETWEEN EMH-798 AND
EMH-898. PROVIDE PULL WIRE IN VACATED CONDUIT. PROTECT
FEEDER M15 BETWEEN EMH-898 AND CAPSTAN 42 FOR FUTURE
RECONNECTION.
4. REMOVE POWER FEEDER M14 FROM EMH-897 BACK EMH-896.
PROVIDE PULL WIRE IN VACATED CONDUIT. PROTECT THE
REMAINING FEEDER M14 CONDUCTORS INSIDE EMH-896 FOR
FUTURE RECONNECTION.
5. REMOVE SLUICE GATE CONTROL CABLE C2 BACK TO ITS
SOURCE IN BUILDING 274.
6. DISCONNECT AND REMOVE TIDE WATER LEVEL GAUGE CABLE
C4 BACK TO EMH-896. PROVIDE PULL WIRE IN VACATED
CONDUIT. PROTECT THE REMAINING CABLE C4 INSIDE
EMH-896 FOR FUTURE RECONNECTION.
7. DISCONNECT AND REMOVE DOCK WATER LEVEL GAUGE CABLE
C3 BACK TO EMH-896. PROVIDE PULL WIRE IN VACATED
CONDUIT. PROTECT THE REMAINING CABLE C3 INSIDE
EMH-896 FOR FUTURE RECONNECTION.
X1 CLIN 0002
DZ RAD WAS
12857712
E L
E C
T R
I C
T
E
D
E M
O L
I T
I O
N
P
L A
N
A
R E
A
1-ED135
AS NOTED
15kVA 2300V to 120/240V
BREAKER
CONTROL
TRANSFORMER
2300V SWITCHBOARD
480V SWITCHBOARD
SIDE A
MCC
MDP-1
MCC
MDP-2
MCC
MDP-3
MCC
MDP-4
2300V FEEDER #1 2300V FEEDER #2 2300V FEEDER #3
480V FEEDER A 480V FEEDER B
DP-1
MCC MCC
DP-2
CKT #1 CKT #2 CKT #3 CKT #4 CKT #5 CKT #6CKT #1 CKT #2 CKT #3 CKT #4 CKT #5 CKT #6
480V SWITCHBOARD
SIDE B
1 1
MCC
DP-3
3 3 3
3 3
XFMR #2
37.5KVA
480V - 240V
1 PHASE1
45KVA
480V - 208Y/120V
3 PHASE
BILGE SUMP
PUMP
MDP DISCH.
VALVE
MDP DISCH.
VALVE
MOTOR
HEATERS
SUCTION
CHAMBER
DEWATERING
PUMP
AHU
XFMR #1
37.5KVA
480V - 240V
1 PHASE
BILGE SUMP
PUMP
MDP DISCH.
VALVE
SEWAGE PUMP
STATION
HOIST
RECEPTACLES
SUCTION
TO
BILDGE
MDP DISCH.
VALVE
MDP DISCH.
VALVE
DP
SUCTION
VALVEMOTOR
HEATERS
MDP 1, 2, 3, 4
DP
SUCTION
VALVE
DP
SUCTION
VALVE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-ED700
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
P U
M P
W E
LL
D
E M
O
LI
T
IO
N O
N E
-L
IN
E D
IA
G
R A
M
RHS
12857713
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
SHEET KEYNOTES
1. DEMOLISH CIRCUIT BREAKER FOR EXISTING LOAD. EXISTING CONDUIT,
CONDUCTORS, AND LOAD TO REMAIN AND ARE TO BE EXTENDED TO THE
PROVIDED 480V PANELBOARD.
2. DEMOLISH EXISTING CIRCUIT BREAKER, CONDUIT, CONDUCTOR, AND ANY
ASSOCIATED SAFETY SWITCHES.
3. SEE 1-ED101 FOR EXTENTS OF PRIMARY FEEDER'S CONDUIT AND CONDUCTOR
DEMOLITION.
NOT TO SCALE
A1
PUMPWELL 8 - ELECTRICAL DEMOLITION ONE LINE DIAGRAM
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
GROUND ROD
GROUND ROD
EXOTHERMIC
WELD
COPPER
GROUND
CABLE
BUTT WELD
TEE WELD
WELD TO ROD
WELD RING TO ROD
EITHER BUTT WELD
CONDUCTOR OR 'THRU WELD'
CONNECTION
JUNCTION WELD
PARALLEL
CABLE TO STRAP
CABLE TO BUSBAR
CABLE TO STRAP
STRAP TO MESH
GROUNDING BUSHING
INCOMING
CONDUIT LOCKNUT
GROUNDING LUG
BONDING JUMPER
GROUNDING
TERMINAL STRIP
PANEL
CABINET
BONDING JUMPER
GROUNDING LUG
NOTES:
CONDUIT
GROUNDING
BUSHING
CONDUIT
LOCKNUTS
EQUIPMENT GROUNDING
CONDUCTOR
NEUTRAL
TERMINAL STRIP
1. ALL WIRES MUST BE NEATLY LACED.
2. AT THE POINT OF ATTACHMENT OF THE GROUNDING TERMINAL STRIP
TO THE CABINET, THE SURFACES MUST BE SCRAPPED FREE OF PAINT
AND THOROUGHLY CLEANED TO INSURE PROPER BONDING.
3. NEUTRAL CONDUCTOR NOT SHOWN FOR CLARITY.
NOTES:
1. THIS DETAIL DOES NOT PRECLUDE THE REQUIREMENTS OF NEC
ART. 250 OR NFPA 780. MUST STRICTLY ADHERE TO NEC ART. 250,
WHICH SUPERCEDES THIS DETAIL.
N
GMAIN GND BUS
(MGB)
PUMPWELL
TYP OF ALL
MAJOR ELEC/MECH
EQUIPMENT
SWGR/PANEL BOARD
TYP.
GRADE LEVEL
GROUNDING
ELECTRODE
CONDUCTOR
COUNTERPOISE
SYSTEM
GENERATOR
EXOTHERMIC WELD
TYP.
BONDING CONDUCTOR
TYP.
PW8-SWGR PW8-LOAD
BANK
3' -0
A B
O V
E F
LO
O
R
GROUND CONDUCTOR
GREEN STRANDED
IRREVERSIBLE CRIMP
COORDINATE MOUNTING HARDWARE
BUILDING WALL
NOTES:
2 HOLE LUG
LOCKWASHER
GROUNDING CONNECTION
EXTERIOR TOOTH
HEX NUT
FLAT WASHER
HEX BOLT DIA AS REQD
TOP VIEW
HEX HEAD BOLT WITH NUT AND
LOCK WASHERS SIZE AS
REQUIRED.
LUGS TO BE 2-HOLE TYPE.
GROUND BAR OR
METAL ENCLOSURE
GREEN STRANDED
GROUND CONDUCTOR
1. PROVIDE NUMBER AND SIZE OF CONNECTORS AND GROUND CONDUCTORS AND LENGTH OF GROUND BAR AS
REQUIRED FOR EACH GROUND BAR LOCATION.
2. PROVIDE GROUND BUS IN ACCORDANCE WITH EIA/TIA-607 GROUNDING STANDARDS.
3. DETAIL IS USED AN EXAMPLE. HOLE SIZE, SPACING AND PATTERN MUST BE IN ACCORDANCE WITH TIA-607.
4. PROVIDE UL LISTED GROUND BUS.
GREEN STRANDED
COPPER WIRE TO GROUND
MAIN GROUND
COUNTERPOISE
GROUND BAR MINIMUM SIZE
2' LONG X 4" WIDE X 1/4" THICK SOLID
COPPER, SEE NOTE 1
HEX HEAD BOLTS LENGTH AND DIA
AS REQUIRED WITH LOCK
WASHERS
INSULATED MOUNT, 2" DEEP
EXOTHERMIC WELD
P W
8- S
W G
R
PW8-FOT-1
PW8-GENERATOR
PW8-LOAD
BANK
T
T
1 1
NOTES:
1. THIS DETAIL DOES NOT PRECLUDE THE
REQUIREMENTS OF NEC ART. 250 OR NFPA 780.
MUST STRICTLY ADHERE TO NEC ART. 250,
WHICH SUPERCEDES THIS DETAIL.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-EG501
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
G R
O U
N D
IN
G
D E
T A
IL
S
RHS
12857714
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
NOT TO SCALE
A1
TYPICAL EXOTHERMIC WELDS
NOT TO SCALE
A2
PANELBOARD BONDING DETAIL
NOT TO SCALE
A3
TYPICAL GROUNDING RISER SCHEMATIC
NOT TO SCALE
B1
MAIN GROUND BUS DETAIL (MGB)
NOT TO SCALE
B3
PUMPWELL 8 SITE EQUIPMENT GROUNDING DETAIL
SHEET NOTES
1. SEE 1-E-001 FOR GROUNDING LINETYPES.
SHEET KEYNOTES
1. PROVIDE GROUND CONNECTION TO PLATFORM REBAR AND FOUNDATION
PILE.
2. PROVIDE GROUND CONNECTION TO EQUIPMENT AND ENCLOSURE.
3. PROVIDE GROUND ROD TEST WELL; SEE1-ES516/C1.
4. PROVIDE GROUND CONNECTION TO PLATFORM HANDRAIL. IF HANDRAIL IS
NOT CONTINUOUS, BOND ALL NONCONTINOUS SECTIONS TOGETHER.
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
REVISED: SEPTEMBER 2020 TYPE: A1LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
HOUSING - LOW PROFILE, ONE-PIECE, FIBERGLASS HOUSING WITH INTEGRAL
PERIMETER CHANNEL.
LENS - INJECTION MOLDED, HIGH IMPACT-RESISTANCE ACRYLIC LENS.
LIGHT SOURCE - HIGH-EFFICIENCY LEDS WITH MINIMUM 50K HOURS RATED LIFE AT L70,
3500K CCT UON, MINIMUM 80 CRI.
MOUNTING - SURFACE, WALL.6.
5.
4.
3.
2.
1.
7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE
THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE
A CERTAIN MANUFACTURER OR PREFERENCE.
CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.
COMPLIES WITH LM79, LM80, AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED
WITH EMERGENCY BATTERY BACK-UP.
DRIVER - INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF, OPERATING
VOLTAGE OF 120-277V, THERMAL MANAGEMENT, <20% TOTAL HARMONIC DISTORTION.
ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.
LED ENCLOSED AND GASKETED
4' NOMINAL
4 0.69
RCR
1.03
0.78 0.89
CU
NOMINAL 25W INPUT/
4000 LUMENS
TYPE A1
LPW - 160
MINIMUM
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-EL501
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
LI
G
H
TI
N G
S C
H E
D U
LE
A
N D
D E
TA
IL
S
RHS
12857715
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
LIGHT FIXTURES SCHEDULE
FIXTURE LAMP INFORMATION FIXTURE INFORMATION
TYPE TYPE COLOR TEMP
FIXTURE
LUMENS VOLTAGE WATTAGE DESCRIPTION MOUNTING
A1 LED 3500 K 4000 lm 277 V 25 W 4' ENCLOSED & GASKETED LED LUMINAIRE WITH SHALLOW ACRYLIC LINEAL
RIBBED FROSTED LENS
CEILING, SURFACE, PENDANT
LIGHTING CONTROL SCHEDULE
NAME CONTROLS
CONTROL BOOTH SW
SHEET NOTES
1. LIGHTING FIXTURE LAYOUT IS SHOWN ON SHEET 1-EP101.
LIGHTING SEQUENCE OF OPERATIONS:
1. SPACES INDICATED WITH "SW" MUST HAVE THE FOLLOWING
FEATURES AND FUNCTIONS:
A. STANDARD LOCAL SNAP SWITCH FOR COMPLETE MANUAL
ON-OFF CONTROLL BY THE USER
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
M M M
M
M
M
M
M
M
M
M
MM M
M M
M
M M M
M
M M
M
MMM
M
MM
M M
M
M
M
MM
M
PW8-DSS-01
FACP
PW8-MDP-2
PW8-MDP-3
PW8-MDP-4
D30
PANEL PW8-1
PANEL PW8-4
PW8-XFMR-3PW8-XFMR-4
A1
PW8-2-1
8' - 0" AFF
RT
PW8-AC-1
LEVEL MONITORING
BUBBLE PANEL
PW8-4-4
PW8-4-6
PW8-MCC-MDP-6
PW8-MCC-MDP-4
1-EP201 1
(E) PANEL LP-2
(E) PANEL LP-1
PW8-MCC-DP
1-EP201
A3
PW8-ACT-56
PW8-ACT-29
PW8-2-8,10,12
PW8-2-9,11,13
D30
D30
12 PW8-1-20,22,24
PW8-1-19,21,2313
PW8-3-11,13,158
PW8-3-6,8,107
C3
PANEL PW8-2
(E)PANEL LP-3
PW8-4-3
PW8-4-25
CONTROL BOOTH
PW8-4-9
CONTROL BOOTH
PW8-MCC-MDP
D30 D30
PW8-4-1
PW8-4-20
PANEL PW8-3
MGB
PW8-4-19,21
PW8-4-17
PW8-MDP-2-HEATER
PW8-4-18
PW8-MDP-3-HEATER
PW8-4-22
PW8-MDP-4-HEATERPW8-3-5,7,915
PW8-1-14,16,18
PW8-1-13,15,17
PW8-3-12,14,16
PW8-1-8,10,12(E) AHU
PW8-1-25,27,29
D200
PW8-MCC-MDP-5
PW8-1-26,28,30
PW8-3-2,4
PW8-3-1,3
GENERATOR
ANNUNCIATOR PANEL
5PW8-2-20,22,24
(E) HOIST RECEPTACLE
PW8-2-20,22,24
(E) HOIST RECEPTACLE
PW8-4-30
MCC HEATER
PW8-4-31
MCC HEATER
X1
X1
PW8-4-19,21
PW8-DSS-CU-01
D30
PW8-SWGR
PW8-4-5
ALTERNATOR HEATER
PW8-2-2,4,6
JACKET WATER HEATER
PW8-4-7
OIL COOLER/HEATER
PW8-4-2
BATTERY BLANKET
PW8-4-27
HEATER
PW8-4-24
CONTROL PANEL
PW8-4-11
BATTERY CHARGER
PW8-FPU-1
PW8-4-12,14
PW8-4-8,10
PW8-FTP-1
PW8-4-13,15
PW8-FTP-2
PW8-4-26
CONTROL PANEL
PW8-FOT-1
D30
D30 D30
2 2
PW8-GENERATOR
D30 2
D602
D302
PW8-LOAD
BANK
D60 D30 D30 D30 D30
18 18 18 18 18
PW8-4-29
COOLANT HEATER
PW8-4-28
CONTROL PANEL
PW8-4-33
SWITCHGEAR HEATER
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-EP101
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
P U
M P
W E
LL
E
LE
C
TR
IC
A L
P O
W E
R P
LA
N
RHS
12857716
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
3/16" = 1'-0" B1
PUMPWELL 8 - ELECTRICAL POWER PLAN - MOTOR
SHEET NOTES
1. SEE SHEET 1-EL501 FOR LIGHTING FIXTURE SCHEDULE AND DETAILS.
2. SEE PHASE 1 ELECTRICAL SITE SHEETS FOR GENERATOR, SWITCHGEAR, AND
ACCESSORY CIRCUIT ROUTING.
3. SEE STRUCTURAL SHEETS FOR EQUIPMENT PAD INFORMATION.
4. ALL ELECTRICAL EQUIPMENT MUST BE PLACED SUCH THAT IT DOES NOT
INTERFERE WITH THE ROOFHATCH ENVELOPE.
5. PROVIDE ALL SAFETY SWITCHES AND MOTOR STARTERS IN NEMA-3R
ENCLOSURES, UON.
0' 4' 8' 12'
PLAN
NORTH
SHEET KEYNOTES
1. SEE STRUCTURAL DRAWINGS FOR PROVIDED FLOOR HATCH.
2. PROVIDE 30A SAFETY SWITCH IN NEMA-4X ENCLOSURE.
3. ELECTRICAL DUCTBANK PENETRATION. SEE SHEETS 1-ES134 AND 1-ES603
FOR CONDUIT AND CONDUCTOR INFORMATION. PROVIDE PULLBOX AND
ROUTE CONDUIT TO PW8-MCC-DP, PW8-MCC-MDP, PANEL PW8-2, AND PANEL
PW8-3.
4. EXISTING TRANSFORMERS ARE CEILING MOUNTED ABOVE EXISTING PANELS
LP-1, LP-2, AND LP-3.
5. PROVIDE ELECTRICAL CONNECTION FROM OUTDOOR UNIT TO INDOOR UNIT
PER MANUFACTURER'S INSTRUCTIONS.
6. 60A SAFETY SWITCH FOR CONNECTION WITH "PW8-MONORAIL" LOCATED IN
THE MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103. SAFETY SWITCH MUST
BE CAPABLE OF BEING LOCKED IN THE OPEN POSITION.
7. 30A SAFETY SWITCH FOR CONNECTION WITH "PW8-ACT-61" LOCATED IN THE
MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103. SAFETY SWITCH MUST BE
CAPABLE OF BEING LOCKED IN THE OPEN POSITION.
8. 30A SAFETY SWITCH FOR CONNECTION WITH "PW8-ACT-63" LOCATED IN THE
MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103. SAFETY SWITCH MUST BE
CAPABLE OF BEING LOCKED IN THE OPEN POSITION.
9. 30A SAFETY SWITCH FOR CONNECTION WITH "PW8-ACT-53" LOCATED IN THE
MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103. SAFETY SWITCH MUST BE
CAPABLE OF BEING LOCKED IN THE OPEN POSITION.
10. 100A SAFETY SWITCH/STARTER COMBINATION FOR CONNECTION WITH "PW8-
SP-1" LOCATED IN THE MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103.
SAFETY SWITCH MUST BE CAPABLE OF BEING LOCKED IN THE OPEN
POSITION.
11. 100A SAFETY SWITCH/STARTER COMBINATION FOR CONNECTION WITH "PW8-
SP-2" LOCATED IN THE MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103.
SAFETY SWITCH MUST BE CAPABLE OF BEING LOCKED IN THE OPEN
POSITION.
12. 100A SAFETY SWITCH/STARTER COMBINATION FOR CONNECTION WITH "PW8-
SP-3" LOCATED IN THE MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103.
SAFETY SWITCH MUST BE CAPABLE OF BEING LOCKED IN THE OPEN
POSITION.
13. 100A SAFETY SWITCH/STARTER COMBINATION FOR CONNECTION WITH "PW8-
SP-4" LOCATED IN THE MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103.
SAFETY SWITCH MUST BE CAPABLE OF BEING LOCKED IN THE OPEN
POSITION.
14. CIRCUIT BREAKERS MUST BE CAPABLE OF BEING LOCKED IN THE OPEN
POSITION.
15. 30A SAFETY SWITCH FOR CONNECTION WITH "PW8-ACT-62" LOCATED IN THE
MAIN PUMP/DRAINAGE PUMP AREA; SEE 1-EP103. SAFETY SWITCH MUST BE
CAPABLE OF BEING LOCKED IN THE OPEN POSITION.
16. SCADA DUCTBANK PENETRATION. SEE SHEETS 1-ES134 AND 1-ES603 FOR
CONDUIT AND CONDUCTOR INFORMATION. PROVIDE PULLBOX AND ROUTE
CONDUIT TO WALL-MOUTNED SCADA CABINET; SEE 1-EP501/A2.
17. DEDICATED RECEPTACLE FOR USE WITH RACK MOUNTED UPS.
18. PROVIDE SAFETY SWITCHES INSIDE OF THE GENERATOR ENCLOSURE.
19. PROVIDE A HEATER FOR EACH CUBICLE. ALL HEATERS ARE POWERED FROM
THE INDICATED CIRCUIT.
X1. CLIN 0002.
KEY PLAN
MOTOR
83'-0"
INTERMED.
68'-0"
MAIN PUMP
46'-0"
DRAINAGE
28'-3 1/4"
COPING
103'-0"
SUC. CHAM.
32'-3"1/16" = 1'-0" A3
PUMPWELL 8 - ELECTRICAL POWER PLAN - COPING
8' 16' 32'0'
PLAN
NORTH
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
M
M
PW8-ACT-10
PW8-ACT-8
D30
D30
PW8-2-14,16,18
PW8-2-3,5,7
D30
PW8-2-15,17,19
PW8-ACT-9
D30
PW8-2-21,23,25
(E) SEWAGE PUMP STATION
X2
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-EP102
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
P U
M P
W E
LL
E
LE
C
TR
IC
A L
P O
W E
R P
LA
N
RHS
12857717
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
3/16" = 1'-0" B1
PUMPWELL 8 - ELECTRICAL POWER PLAN - INTERMEDIATE
0' 4' 8' 12'
PLAN
NORTH
KEY PLAN
MOTOR
83'-0"
INTERMED.
68'-0"
MAIN PUMP
46'-0"
DRAINAGE
28'-3 1/4"
COPING
103'-0"
SUC. CHAM.
32'-3"
SHEET NOTES
1. COORDINATE SAFETY SWITCH LOCATIONS WITH EXISTING WALL MOUNTED
EQUIPMENT.
2. PROVIDE ALL SAFETY SWITCHES AND MOTOR STARTERS IN NEMA-4X
ENCLOSURES, UON.
SHEET KEYNOTES
X2. CLIN 0004.
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
M
M
M M
M M
M
M
M
M
M
M
M
(E) DP-3
PW8-DP-2
PW8-DP-1
PW8-SP-1
PW8-SP-2
PW8-ACT-53
PW8-DP-4
PW8-SP-4
PW8-SP-3
PW8-MONORAIL
TROLLEY
PW8-ACT-63
PW8-MCC-DP-7
PW8-MCC-DP-4
PW8-MCC-DP-5
PW8-MCC-DP-6
PW8-1-13,15,17
PW8-1-14,16,18
PW8-3-12,14,16
PW8-3-11,13,15
PW8-3-6,8,10
PW8-1-19,21,23
PW8-1-20,22,24
PW8-1-8,10,12
PW8-MCC-DP-8
PW8-DP-5
PW8-3-5,7,9
PW8-ACT-62
PW8-ACT-61
PW8-4-23
PW8-HIGH WATER ALARM
X1
X4
X2
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-EP103
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
P U
M P
W E
LL
E
LE
C
TR
IC
A L
P O
W E
R P
LA
N
RHS
12857718
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
0' 4' 8' 12'
PLAN
NORTH
KEY PLAN
MOTOR
83'-0"
INTERMED.
68'-0"
MAIN PUMP
46'-0"
DRAINAGE
28'-3 1/4"
COPING
103'-0"
SUC. CHAM.
32'-3"
3/16" = 1'-0" B1
PUMPWELL 8 - ELECTRICAL POWER PLAN - MAIN PUMP & DRAINAGE PUMP
SHEET NOTES
1. SEE 1-EP101 FOR MEANS OF DISCONNECT FOR ALL ELECTRICAL EQUIPMENT
CONNECTIONS SHOWN ON THIS SHEET.
SHEET KEYNOTES
1. COORDINATE SAFETY SWITCH AND EQUIPMENT CONNECTION WITH THE
MONORAIL EQUIPMENT LAYOUT.
X1. CLIN 0002.
X2. CLIN 0004.
X4. CLIN 0006.
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
IS
S U
E D
F O
R C
O N
S
TR
U C
T
IO
N
/2 8/
IS
SU
ED
F
OR
FPP6
WM1
UPS
BATTERY
SBP
SW1
WM2
PW8-XFMR-3
PW8-XFMR-4
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
AS NOTED
F
IL
E N
A M
E
P
LO
T T
E D
C
R e v it P ro je c ts
\D R
Y D
P -1
-E
-D R
Y D ra k e m p .r v t
/2
/2
:3
:4
P
M
1-EP201
P D
R Y
D O
C K
S
A L T
W A
T E
R S
Y S
T E
M
F O
R C
V N
-7
P U
M P
W E
LL
E
Q U
IP
M
E N
T E
LE
V
A T
IO
N
S
RHS
12857719
JCC RAK
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
P O
R T
S M
O U
T H
, V
IR
G
IN
IA
N
O R
F O
LK
N
A V
A L
S H
IP
Y
A R
D
EJA
JAS
DSN
SHEET KEYNOTES
1. WALL-MOUNTED TRANSFORMER; SEE 1-EP501/A1.
2. MOUNT SCADA CABINET SUCH THAT THE TOP OF THE ENCLOSURE DOES NOT
EXCEED 7'-0". COORDINATE WITH EXISTING TO REMAIN OVERHEAD
DUCTWORK.
3. PROVIDE A MINIMUM OF 54 AMPERE HOURS FOR 60 MINUTES…