This package contains architectural drawings for a federal construction project to upgrade the saltwater system at Dry Dock 8 for CVN-78 at the Norfolk Naval Shipyard in Portsmouth, Virginia. The drawings depict demolition plans, new construction plans, schedules and details for Pumpwell 8 including demolition of existing structures and materials, plans for a new control room, reflected ceiling plans, door and window details, and notes addressing construction requirements. Specifications for the project are available in separate documents. The solicitation number for this opportunity is N40085-22-R-2598, issued by the Naval Facilities Engineering Command.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DOOR NUMBER
DOOR TAG
ARCHITECTURAL SYMBOLS
WINDOW TYPE LETTER
WINDOW TYPE TAG
PARTITION TYPE DESIGNATION
(REFER TO PARTITION SCHEDULE)
PARTITION TYPE TAG
S3.1
PARTITION IN PLAN
B
1. WORK MUST COMPLY WITH APPLICABLE CODES AND STANDARDS AS LISTED
OR REFERENCED ON LIFE SAFETY PLAN AND LIFE SAFETY CRITERIA BY THE
AUTHORITY HAVING JURISDICTION.
2. DIMENSIONS GOVERN. DETAILS GOVERN OVER PLANS AND ELEVATIONS.
LARGE SCALE DETAILS OR PLANS GOVERN OVER SMALL SCALE DETAILS OR
PLANS. DO NOT SCALE DRAWINGS.
3. MANUFACTURER'S OR BRAND NAME PRODUCTS INDICATED OR SPECIFIED
ARE DONE SO TO ESTABLISH A MINIMUM LEVEL OF QUALITY.
4. THE LETTERS I, O, AND Q ARE NOT USED TO INDICATE DETAILS, SECTIONS
OR ELEVATIONS.
5. PAINT, STAIN, OR COAT EXPOSED SURFACES OF CONSTRUCTION UNLESS
NOTED OTHERWISE OR IF SURFACES ARE PRE-FINISHED.
6. OPENING DIMENSIONS ARE NOMINAL. FIELD MEASURE OPENINGS AND
COORDINATE WITH THE SUPPLIER FOR DOORS AND WINDOWS.
7. PROVIDE GALVANIC PROTECTION BETWEEN DISSIMILAR MATERIALS,
WHERE REQUIRED.
8. SEAL AROUND DOOR AND WINDOW FRAMES, WALL-MOUNTED FIXTURES
AND EQUIPMENT TO ADJACENT WALL SURFACES.
9. PROVIDE HVAC, PLUMBING, GAS OR ELECTRIC SERVICE CONNECTIONS TO
CASEWORK, FIXTURES, SIGNAGE, OR EQUIPMENT INDICATED (WHETHER
UNITS ARE INSTALLED BY CONTRACTOR OR BY OTHERS).
10. BRACE PARTITIONS, SUSPENDED CEILINGS, SOFFITS, SUSPENDED ITEMS,
ETC. ONLY TO STRUCTURAL ELEMENTS ABOVE. DO NOT ANCHOR TO ROOF
DECK, PLUMBING / SPRINKLER PIPES, DUCTWORK OR ELECTRICAL CONDUIT.
11. DO NOT REPRODUCE DRAWINGS CONTAINED IN THIS SET FOR SHOP
DRAWINGS. COPIES OF THESE DRAWINGS SUBMITTED AS SHOP DRAWINGS
WILL BE REJECTED AND RETURNED TO THE CONTRACTOR.
12. BECOME ACQUAINTED WITH CONDITIONS RELATED TO THE WORK. REPORT
DISCREPANCIES BETWEEN THE DRAWINGS AND THE CONDITIONS TO THE
CONTRACTING OFFICER FOR RESOLUTION PRIOR TO PROCEEDING WITH
THE WORK.
13. EACH INSTALLER MUST EXAMINE SUBSTRATE AND/OR CONDITIONS UNDER
WHICH THE WORK WILL BE INSTALLED AND REPORT TO THE CONTRACTOR
IN WRITING FOR CONDITIONS DETRIMENTAL TO THE EXECUTION OF THE
INSTALLERS WORK. DO NOT PROCEED UNTIL UNSATISFACTORY
CONDITIONS ARE CORRECTED. INSTALLATION CONSTITUTES ACCEPTANCE
OF THE SUBSTRATE AND/OR CONDITIONS.
14. "TYPICAL" (TYP) AS USED IN THESE DOCUMENTS MEANS THAT THE
CONDITIONS OR DIMENSION IS THE SAME OR REPRESENTATIVE OF
CONDITIONS THROUGHOUT.
15. IN THE CASE OF DISCREPANCIES BETWEEN THE DRAWINGS AND
SPECIFICATIONS, THE SPECIFICATIONS TAKE PRECEDENCE.
DISCREPANCIES MUST BE IDENTIFIED AND/OR CLARIFIED PRIOR TO THE
SPECIFICATION TAKING PRECEDENCE
ROOM NAME
A1 A-101
ROOM TAG
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL TAG
ROOM NAME
ROOM NUMBER
DETAIL NUMBER
SCALE
EXTERIOR ELEVATION
TAG
ELEVATION NUMBER
DIRECTION OF VIEW
SHEET WHERE DRAWN
A1 A-101
WALL / PARTIAL
BUILDING SECTION
TAG
SECTION NUMBER
SHEET WHERE DRAWN
GENERAL PROJECT SYMBOLS
A1 A-101
BUILDING SECTION
TAG
SECTION NUMBER
SHEET WHERE DRAWN
A1 A-101
BUILDING
KEYNOTE TAG
KEYNOTE NUMBER
PLAN
NORTH
SCALE
TRUE NORTH
3-AD101
A1 OH
A1 DETAIL TITLE
1/8" = 1'-0"
A1 DETAIL TITLE
1/8" = 1'-0"
MATERIALS LEGEND
CAST-IN-PLACE CONCRETE
STEEL
EARTH/COMPACT FILL
BATT/LOOSE FILL INSULATION
RIGID INSULATION
GYPSUM BOARD
DIMENSIONAL LUMBER
WOOD BLOCKING
SE
CT
IO
N
VI
EW
EL
EV
AT
IO
N/
PL
AN
V
IE
W
ALUMINUM
GLASS
PLYWOOD
SAND/MORTAR/PLASTER
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N
AV
AL
S
TA
TI
O N
N
O R
FO
LK
, V A
AS NOTED
FI
LE
N
AM
E:
PL
OT
TE
D:
C
:\R ev it_ Pr oj ec ts \D
R
YD
P6
-1
-A -D
R
YD
_p gr eg or y@ bu rn sm cd .c om .rv t 2/
/2
:5
8:
A M
1-A-001
P
D
R Y
D O
C K
S
A
LT
W A
TE
R
S Y
S
TE
M
FO
R C
V N
-7
AR
CH
IT
EC
TU
RA
L
SY
M
BO
LS
, L
EG
EN
DS
, A
BB
RE
VI
AT
IO
NS
A
ND
N O
TE
S
LES
12857649
BSG BSG
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
PO
RT
SM
OU
TH
, V
IR
GI
NI
A
NO
RF
OL
K
NA
VA
L S
HI
PY
AR
D
EJA
CGM
DSN
ARCHITECTURAL ABBREVIATIONS ARCHITECTURAL GENERAL NOTES
STC SOUND TRANSMISSION COEFFICIENT
STD STANDARD
STOR STORAGE
STRUCT STRUCTURAL
SUPP SUPPORT
SUSP SUSPENDED
SYS SYSTEM
-T-
THRU THROUGH
TO TOP OF, AS IN "TO STEEL"
TYP TYPICAL
-U-
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
-V-
VENT VENTILATE, VENTILATOR
VERT VERTICAL
VOL VOLUME
-W-
W WIDTH
W/ WITH
W/O WITHOUT
WD WOOD
WT WEIGHT
-H-
H / HT HEIGHT
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HVAC HEATING, VENTILATION & AIR
CONDITIONING
-I-
IN INCH
INSUL INSULATION
INT INTERIOR
-J-
-L-
L LEFT, LONG, LENGTH
LVL LEVEL
-M-
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR /
MNFR
MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
-N-
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
-O-
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
-P-
PERIM PERIMETER
PKG PACKAGE
PLMB PLUMBING
PLYWD PLYWOOD
PROJ PROJECT
-R-
R RADIUS
RCP REFLECTIVE CEILING PLAN
RD ROOF DRAIN
RECP RECEPTACLE (ASK INT)
REFER REFERENCE
REINF REINFORCED
REQ'D REQUIRED
REV REVISION
RO ROUGH OPENING
-S-
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SIM SIMILAR
SPEC SPECIFICATION
SQ SQUARE, AS IN "SQ FT"
-A-
ADJ ADJACENT, ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
APPROX APPROXIMATE
-B-
BD BOARD
BLDG BUILDING
BO BOTTOM OF, AS IN "BO STEEL"
-C-
CJ CONTROL JOINT, CONSTRUCTION
JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
CORR CORRUGATED OR CORRIDOR
-D-
DBL DOUBLE
DEMO DEMOLITION
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DN DOWN
DR DOOR
DS DOWNSPOUT
DWG DRAWING
-E-
EA EACH
EJ EXPANSION JOINT
EL ELEVATION, AS IN HEIGHT
ELEC /
ELECT
ELECTRIC / ELECTRICAL
ELEV ELEVATOR, OR ELEVATION AS IN
NORTH ELEV
EQ EQUAL
EQUIP EQUIPMENT
ETC AND SO FORTH (ETCETERA)
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
-F-
FD FLOOR DRAIN
FE FIRE EXTINGUISHER WITH WALL
BRACKET
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF&E FURNITURE, FIXTURES & EQUIPMENT
FHC FIRE HOSE CABINET (WITH
EXTINGUISHER & BRACKET)
FHR FIRE HOSE REEL (WITH EXTINGUISHER
& BRACKET)
FIN FINISHED, FINISH
FLR FLOOR
FP FIRE PROTECTION
FT FEET / FOOT
-G-
GA GAUGE
GL GIRT LINE
GYP GYPSUM
GYP BD /
GWB
GYPSUM BOARD
SY
M
DE
S C
RI
PT
I O N
DA
TE
AP
PR
IS
SU
ED
F
OR
C
ON
ST
RU
C T
IO
N
/25 /20
IS
SU
ED
F
OR
B
ID
/28
/20
M
D3
D1
D2
D6
D4 D5
1. REMOVE EXISTING CONSTRUCTION TO THE EXTENT INDICATED ON THE
DRAWINGS. PROTECT OTHER EXISTING STRUCTURES ON ADJACENT
PROPERTIES FROM DAMAGE THROUGHOUT CONSTRUCTION. SHOULD
DAMAGE OCCUR TO EXISTING CONSTRUCTION ON ADJACENT PROPERTIES
OR EXISTING CONSTRUCTION TO REMAIN ON SITE, REPAIR THE DAMAGE TO
THE SATISFACTION OF THE CONTRACTING OFFICER. REMOVE DEBRIS
REGULARLY TO ELIMINATE INTERFERENCE.
2. EXCEPT FOR ITEMS OR MATERIALS INDICATED TO BE REUSED, SALVAGED,
REINSTALLED, OR OTHERWISE INDICATED TO REMAIN THE OWNER’S
PROPERTY, DEMOLISHED MATERIALS BECOME THE CONTRACTOR’S
PROPERTY AND MUST BE REMOVED FROM THE SITE WITH FURTHER
DISPOSITION AT THE CONTRACTOR’S OPTION.DEMOLISHED MATERIALS
MUST BE LEGALLY DISPOSED OF PROMPTLY. DO NOT ALLOW DEMOLISHED
MATERIALS TO ACCUMULATE ON SITE. NO BURNING IS ALLOWED.
3. IF MECHANICAL, ELECTRICAL, OR STRUCTURAL ELEMENTS THAT CONFLICT
WITH THE INTENDED FUNCTION OR DESIGN ARE ENCOUNTERED,
DETERMINE THE NATURE AND EXTENT OF THE CONFLICT AND NOTIFY THE
CONTRACTING OFFICER IMMEDIATELY FOR RESOLUTION.
4. THIS DEMOLITION PLAN OUTLINES THE SCOPE OF THE WORK INVOLVED
FOR THE DEMOLITION PHASE OF THIS PROJECT. REFER TO THE DRAWINGS
FOR THE CONSTRUCTION OF THE NEW ADDITION FOR ADDITIONAL
INFORMATION.
5. WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER WITH
REGARD TO SCHEDULE AND DISRUPTION OF BUSINESS OPERATIONS.
6. ALL FURNITURE & LOOSE EQUIPMENT WILL BE REMOVED OR RELOCATED
BY THE CONTRACTING OFFICER PRIOR TO THE DEMOLITION WORK OF THIS
PROJECT.
7. MEANS OF EGRESS MUST BE MAINTAINED DURING DEMOLITION AND
CONSTRUCTION WORK AS PER CODE AND LIFE SAFETY REQUIREMENTS.
CONTRACTOR MUST MAINTAIN A MINIMUM OF TWO MEANS OF EGRESS OR
OTHER TEMPORARY EGRESS SYSTEM MUST BE PROVIDED.
8. REFER TO STRUCTURAL, MECHANICAL, PLUMBING & ELECTRICAL
DEMOLITION DRAWINGS FOR DEMOLITION EXTENTS OF CONCRETE, PIPING,
FLOOR DRAIN, EQUIPMENT & OTHER ASSOCIATED COMPONENTS
9. CARE SHOULD BE MADE TO KEEP DUST AND NOISE FROM DEMOLITION
ACTIVITIES FROM THE OTHER PORTIONS AND FLOORS OF THE BUILDING.
ERECT AND MAINTAIN DUSTPROOF PARTITIONS. COVER AND PROTECT
FURNITURE, FURNISHINGS AND EQUIPMENT THAT HAVE NOT BEEN
REMOVED.
10. PROVIDE TEMPORARY BARRICADES AND OTHER PROTECTION REQUIRED
TO PREVENT INJURY TO PEOPLE AND DAMAGE TO ADJACENT BUILDING
AREAS TO REMAIN.
11. FALL PROTECTION AND ALL GOVERNMENT SAFETY REQUIREMENTS MUST
BE MAINTAINED DURING DEMOLITION AND CONSTRUCTION PER
SPECIFICATIONS.
12. HAZARDOUS MATERIALS: SEE SPECIFICATIONS APPENDIX, "HAZMAT
INSPECTION DRAWINGS AND LABORATORY REPORTS," FOR TYPICAL
LOCATIONS AND TYPES OF HAZARDOUS MATERIALS THAT MAY BE
ENCOUNTERED. SEE DIVISION 2 SPECIFICATIONS FOR REMEDIATION AND
HANDLING OF HAZARDOUS MATERIALS. PRIOR TO BEGINNING WORK,
NOTIFY THE CONTRACTING OFFICER OF ANY ADDITIONAL MATERIALS
OBSERVED THAT MAY POTENTIALLY CONTAIN HAZARDOUS MATERIALS.
SHEET NOTES
BUILDING SECTION KEY
MOTOR
83'-0"
INTERMED.
68'-0"
MAIN PUMP
46'-0"
DRAINAGE
28'-3 1/4"
COPING
103'-0"
SUC. CHAM.
32'-3"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N
AV
AL
S
TA
TI
O N
N
O R
FO
LK
, V A
AS NOTED
FI
LE
N
AM
E:
PL
OT
TE
D:
C
:\R ev it_ Pr oj ec ts \D
R
YD
P6
-1
-A -D
R
YD
_p gr eg or y@ bu rn sm cd .c om .rv t 2/
/2
:5
8:
A M
1-AD102
P
D
R Y
D O
C K
S
A
LT
W A
TE
R
S Y
S
TE
M
FO
R C
V N
-7
PU
M
PW
EL
L
DE
M O
LI
TI
O N
PL
AN
-M O
TO
R
LES
12857650
BSG BSG
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
PO
RT
SM
OU
TH
, V
IR
GI
NI
A
NO
RF
OL
K
NA
VA
L S
HI
PY
AR
D
EJA
CGM
DSN
SHEET KEYNOTES
D1 REMOVE GYP. BD. STUD WALL PARTITION AT FULL HEIGHT
D2 REMOVE DOOR AND FRAME
D3 REMOVE WINDOW AND FRAME
D4 PREPARE FLOOR SURFACES FOR NEW CONSTRUCTION
D5 REMOVE CEILING FINISHES, METAL DECK ABOVE CAP, ASSOCIATED FRAMING
AND CEILING FIXTURES. RE: MECH. & ELEC.
D6 REMOVE WORK BENCH & ASSOCIATED FIXED FURNISHINGS
PLAN
NORTH
0' 4' 8' 12'3/16" = 1'-0"C1 PUMPWELL 8 - DEMOLITION PLAN - MOTOR LEVEL
SY
M
DE
S C
RI
PT
I O N
DA
TE
AP
PR
IS
SU
ED
F
OR
C
ON
ST
RU
C T
IO
N
/25 /20
/28 /20
/28 /20
IS
SU
ED
F
OR
B
ID
M M M
M
M
M M
M
EQ EQ
1-A-102 A4
CONTROL RM.
MIN.3' -
0"
EQ EQ
10' - 6"
MIN.
3' - 0"
3' - 0"
9'
- 1
1"
SHEET NOTES
1. FOR ARCHITECTURAL GENERAL NOTES, MATERIAL LEGEND, AND
ABBREVIATIONS REFER TO SHEET 1-A-001.
2. FOR PARTITION TYPES CONSTRUCTION AND DESCRIPTION, REFER TO
PARTITION TYPES SHEET.
3. DIMENSIONS ARE FROM: FACE OF CONCRETE WALL, FACE OF METAL
STUD AND CENTERLINE OF EQUIPMENT, UNLESS NOTED OTHERWISE.
4. FURNITURE LAYOUT PROVIDED FOR COORDINATION WITH BUILDING
SYSTEMS ONLY. FURNITURE TO BE GOVERNMENT FURNISHED,
GOVERNMENT INSTALLED (GFGI).
CONTROL RM.
2'
- 2
7'
- 9 " W2
W2
S2AA
S2AA
S2AA
S2AA
A2 1-A-600
9'
- 1
1"
10' - 6"
1' - 0"
W2
EQ
EQ
CL
E A
R 3'
- 0
3' - 2"
CONTROL RM.
A2 1-A-600
FINISH INDEX
MATERIALS DESCRIPTION
FLOORING
ACRYLIC/LATEX, EGGSHELL/SATIN FINISH, FIELD
PAINT
PA-1
EPOXYPE-1
RT INDUSTRIAL VINYL COMPOSITE TILE
MOISTURE-RESISTANT GYPSUM WALL BOARD
WALL & CEILING
MRG
MFR/PRODUCT COLOR/REMARKS
USG
JOHNSONITE OR EQUIVALENT
SHERWIN WILLIAMS
SHERWIN WILLIAMS
COLOR TO BE SELECTED
SW7004 SNOWBOUND
SW7004 SNOWBOUND
RUBBER
BASE
RB-1 TARKETT TRADITIONAL W/ TOE, PEPPERCORN
ACRYLIC/LATEX, SEMI GLOSS - DOOR FRAMESPA-2 SHERWIN WILLIAMS SW9163 TIN LIZZIE
BUILDING SECTION KEY
MOTOR
83'-0"
INTERMED.
68'-0"
MAIN PUMP
46'-0"
DRAINAGE
28'-3 1/4"
COPING
103'-0"
SUC. CHAM.
32'-3"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N
AV
AL
S
TA
TI
O N
N
O R
FO
LK
, V A
AS NOTED
FI
LE
N
AM
E:
PL
OT
TE
D:
C
:\R ev it_ Pr oj ec ts \D
R
YD
P6
-1
-A -D
R
YD
_p gr eg or y@ bu rn sm cd .c om .rv t 2/
/2
:5
8:
A M
1-A-102
P
D
R Y
D O
C K
S
A
LT
W A
TE
R
S Y
S
TE
M
FO
R C
V N
-7
PU
M
PW
EL
L
PL
AN
, R
EF
LE
CT
ED
C
EI
IN
G
P
LA
N
SC
HE
DU
LE
S -M
O
TO
R
LES
12857651
BSG BSG
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
PO
RT
SM
OU
TH
, V
IR
GI
NI
A
NO
RF
OL
K
NA
VA
L S
HI
PY
AR
D
EJA
CGM
DSN
SHEET KEYNOTES
1 CONTROL CONSOLE, RE: MECH
2 SURFACE MOUNTED MECH UNIT & ELEC LIGHT FIXTURE, RE: MECH & ELEC
16 MOISTURE RESISTANT GYP. BD. CEILING
31 WORKBENCH WITH SHELVING AND DRAWERS, GFGI
32 WORKBENCH, GFGI
PLAN
NORTH
0' 4' 8' 12'3/16" = 1'-0"C1 PUMPWELL 8 - PLAN - MOTOR LEVEL
1/4" = 1'-0"A4 CONTROL RM - ENLARGED PLAN
1/4" = 1'-0"B4 CONTROL RM - REFL. CLG PLN
FINISH SCHEDULE
ROOM
FLOOR BASE WALL
CEILING
NOTESNO. NAME FINISH HEIGHT
101 CONTROL RM. RT RB-1 MRG / PA-1 MRG / PE-1 8'-0" BASE AND WALL FINISHES APPLY TO INSIDE AND
OUTSIDE PERIMETER OF CONTROL ROOM
PARTITIONS
2' 4' 8'0'
2' 4' 8'0'
SY
M
DE
S C
RI
PT
I O N
DA
TE
AP
PR
IS
SU
ED
F
OR
C
ON
ST
RU
C T
IO
N
/25 /20
/28 /20
/28 /20
IS
SU
ED
F
OR
F FLUSH DOOR WITH INSULATION
DOOR WIDTH
RE: SCHEDULE
DOOR TYPES
RE
: S
CH
ED
UL
E
DO
OR
H
EI
GH
T
0'
- 2
0' - 5 3/4"
DOUBLE 3 5/8" MTL
STUDS
3 5/8" MTL RUNNER
HM FRAME
BATT INSULATION
SEALANT TYP. AT FULL
PERIMETER ON BOTH
SIDES
5/8" GWB
3 5/8" MTL STUDS @
16" O.C.
BATT INSULATION
0' - 2"
0'
- 5
3/ 4"
DOUBLE 3 5/8" MTL
STUDS
SEALANT TYP. AT FULL
PERIMETER ON BOTH SIDES
HM FRAME
JAMB ANCHORS
(3 PER JAMB)
5/8" GWB BOTH SIDES
INSULATION
BATT INSULATION
WINDOW TYPES
W2
B4 A-600
B5 A-600
A5 A-600
VE
RI
FY
3'
- 4
CLEAR, INSULATED,
TEMPERED GLASS
3'
- 8
3' - 0"
SEE ROOM FINISH
SCHEDULE FOR FINISH
MATERIALS OVER
GYPSUM BOARD
PLAN
BASE
1 LAYER OF 5/8" MOISTURE-
RESISTANT GYPSUM BOARD
EACH SIDE OF METAL
STUDS @ 16" O.C.
PARTITION TYPE S2
INSULATION. SEE
SCHEDULE BELOW
BASE AS SCHEDULED
3 5/8" METAL STUDS @
16"OC
S1AA
INDICATES TYPE OF
PARTITION STRUCTURE:
F = FURRING METAL STUD
S = METAL STUD
H = C-H METAL STUD
M = MASONRY
C = CONCRETE
INDICATES NUMBER OF
LAYERS OF GYPSUM BOARD
OR TYPE OF CMU FINISH
INDICATES THICKNESS OF
PARTITION STRUCTURE
INDICATES VARIATION OF
PARTITION WITH THE SAME
STRUCTURE, FINISH, AND
STRUCTURE THICKNESS
1. METAL STUDS AND BRACING ARE 20 GAUGE UNLESS NOTED OTHERWISE.
REFERENCE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. REFERENCE DRAWINGS 1-A-102 FOR PARTITION TYPE LOCATIONS.
PARTITION TYPES GENERAL NOTES
PARTITION TYPE SYMBOL LEGEND
0'
- 2
DOUBLE 3 5/8" MTL STUDS
3 5/8" MTL RUNNER
HM FRAME
SEALANT TYP. AT FULL
PERIMETER ON BOTH
SIDES
5/8" GWB
3 5/8" MTL STUDS @
16" O.C.
GLAZING
INSULATION
CONTROL RM. SIDE
BATT INSULATION
0' - 2"
DOUBLE 3 5/8"
MTL STUDS
SEALANT TYP. AT
FULL PERIMETER
ON BOTH SIDES
HM FRAME
5/8" GWB
BOTH SIDES
GLAZING
INSULATION
CONTROL RM. SIDE
BATT
INSULATION
MINERAL WOOL
BLANKET INSULATION
WITH VAPOR RETARDER
FACING INTERIOR SIDE
MINERAL WOOL
BLANKET
INSULATION WITH
VAPOR RETARDER
FACING INTERIOR
SIDE 9'
- 6
8'
- 0
CONSOLE
5/8" MOISTURE-
RESISTANT GWB
CEILING
3/4" FIRE RETARDANT
PLYWOOD
3 5/8" STUDS @ 16" OC TO
SUPPORT CAP CEILING
3 5/8" METAL
STUDS @ 16" OC
W2
5/8" MOISTURE-RESISTANT
GWB COVER, PAINT TO MATCH
ADJACENT GWB COLOR, TYP.
0'
- 2
DOUBLE 3 5/8" MTL
STUDS
3 5/8" MTL RUNNER
HM FRAME
SEALANT TYP. AT
FULL PERIMETER
ON BOTH SIDES
5/8" GWB
3 5/8" MTL STUDS
@ 16" O.C.
GLAZING
INSULATION
CONTROL RM. SIDE
BATT INSULATION
EXISTING STUCCO/
EXTERIOR INSULATION
FINISH SYSTEM (EIFS)
REMOVE PORTION OF EIFS.
REFER TO HAZMAT
ABATEMENT SPECIFICATIONS
FOR HAZMAT REMOVAL
OF
C
OR
E
DR
ILL
O
PE
NI
NG
VE
RI
FY
E
XT
EN
TS
CORE DRILL OPENING IN
SQUARE OR RECTANGULAR
(NON-CIRCULAR) PROFILE AS
REQUIRED TO ACCOMODATE
CONDUIT PENETRATION.
PROVIDE NON-SHRINK GROUT
PERIMETER METAL
COUNTER FLASHING
EXISTING CONC. WALL
TO REMAIN
PIPE SLEEVE,
SCHEDULE 40 BLACK
EXTEND CONDUIT
6" BEYOND WALL
SEALANT AT PERIMETER
SEALANT AT PERIMETER
PROVIDE PERIMETER
ENCAPSULANT COATING (DASHED
LINES) AT EXPOSED/AFFECTED
STUCCO/ EIFS FINISHES DURING
ABATEMENT PRIOR TO DEMOLITION
& NEW CONSTRUCTION
FIRESTOPPING WITH 3M
FIRE DAM 150, 3 HOUR
RATED, 1" DEEP MIN.
1/2
PACK WITH OAKUM
SEALANT
NOTES:
1. REFER TO SPECIFICATIONS DIVISION 2, SECTION 02 82 00.00 22 FOR LOCATIONS OF
ASBESTOS CONTAINING MATERIALS AND FOR ABATEMENT REQUIREMENTS.
2. REFER TO ELECTRICAL DRAWINGS FOR BLDG. 272 PIPE PENETRATION LOCATIONS
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N
AV
AL
S
TA
TI
O N
N
O R
FO
LK
, V A
AS NOTED
FI
LE
N
AM
E:
PL
OT
TE
D:
C
:\R ev it_ Pr oj ec ts \D
R
YD
P6
-1
-A -D
R
YD
_p gr eg or y@ bu rn sm cd .c om .rv t 2/
/2
:5
8:
A M
1-A-600
P
D
R Y
D O
C K
S
A
LT
W A
TE
R
S Y
S
TE
M
FO
R C
V N
-7
PU
M
PW
EL
L
-D O
O R
SC
HE
DU
LE
, P
AR
TI
TI
O N
TY
PE
S
M
IS
C
DE
TA
IL
S
LES
12857652
BSG BSG
02/02/2022
DEVIN POULIN,
C984 FACILITIES PLANNER, NNSY
JTL/TLH
1364315
N40085-22-R-2598
PO
RT
SM
OU
TH
, V
IR
GI
NI
A
NO
RF
OL
K
NA
VA
L S
HI
PY
AR
D
EJA
CGM
DSN
DOOR SCHEDULE
DOOR
NO.
DOOR FRAME
STC
DETAIL
HDWR SET REMARKS
SIZE
TYPE MAT'L FINISH MAT'L FINISH HEAD JAMB SILLWIDTH HEIGHT
101 3' - 0" 7' - 0" F HM PA-2 HM PA-2 49 D5/1-A-600 C5/1-A-600 - HW-2
1 1/2" = 1'-0"D5 DOOR HEAD DETAIL
1 1/2" = 1'-0"C5 DOOR JAMB DETAIL
1 1/2" = 1'-0"B5 WINDOW HEAD DETAIL
1 1/2" = 1'-0"B4 WINDOW JAMB DETAIL
3/4" = 1'-0"A2 DETAIL SECTION - CONTROL ROOM
1 1/2" = 1'-0"A5 WINDOW SILL DETAIL
0' 1' 2' 3'
4"0' 8" 1'-4"
4"0' 8" 1'-4"
4"0' 8" 1'-4"
4"0' 8" 1'-4"
4"0' 8" 1'-4"
WALL SCHEDULE - S2
TYPE TYPE COMMENTS
S2AA 3 5/8" METAL STUDS WITH MINERAL WOOL BLANKET
INSULATION & VAPOR RETARDER FACING INTERIOR
SIDE. PROVIDE ASSEMBLY TYPE GA FILE NO. WP 1081
TO ACHIEVE STC 49
1 1/2" = 1'-0"C2 PIPE SLEEVE PENETRATION - BLDG 272
0' 1' 2' 3'
SY
M
DE
S C
RI
PT
I O N
DA
TE
AP
PR
IS
SU
ED
F
OR
C
ON
ST
RU
C T
IO
N
/25 /20
/28 /20
/28 /20
IS
SU
ED
F
OR
| 1-A-001 - ARCHITECTURAL SYMBOLS, LEGENDS, ABBREVIATIONS AND NOTES |
| 1-AD102 - PUMPWELL 8 – DEMOLITION PLAN -MOTOR |
| 1-A-102 - PUMPWELL 8 – PLAN, REFLECTED CEIING PLAN & SCHEDULES - MOTOR |
| 1-A-600 - PUMPWELL 8 - DOOR SCHEDULE, PARTITION TYPES & MISC DETAILS |
2022-02-25T08:03:34-0500
2022-02-25T08:03:43-0500
2022-02-25T08:03:43-0500
2022-02-25T08:03:43-0500
2022-02-25T08:03:55-0500
2022-02-25T08:04:06-0500
2022-02-25T08:04:06-0500
2022-02-25T08:04:06-0500
| 2022-03-15T21:10:23-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-03-15T21:10:58-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-03-15T21:10:58-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-03-15T21:11:01-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-03-15T21:11:13-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-03-15T21:11:30-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-03-15T21:11:31-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2022-03-15T21:11:31-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
File details come from the government source that posted it. Updated .