This is a pre-solicitation notice for construction of Phase III of the Interagency Natural Resource Center in Coeur d'Alene, Idaho. The project will include construction of a 29,000 square foot main office building to support 173 employees from the U.S. Fish and Wildlife Service, Bureau of Land Management, and U.S. Forest Service. The magnitude of the project is estimated to be between $5 million and $10 million. The solicitation for proposals is expected to be posted to the website on June 5, 2018, with responses due 30 days after posting. The awarding agency will be the U.S. Department of Agriculture Forest Service, Northern Region.
05 - J-2 Project Manual Part 2
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A&E ARCHITECTS P.C. US DEPARTMENT OF AGRICULTURE
IDAHO PANHANDLE NATIONAL FOREST
INRC OFFICE BUILDING – PHASE 3
COEUR D’ALENE, IDAHO
SUSTAINABLE DESIGN REQUIREMENTS 018113 - 1
SECTION 018113 - SUSTAINABLE DESIGN REQUIREMENTS FOR CONSTRUCTION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Phase 3 – INRC Office Building will comply with Green Globes – Two Globe certification.
B. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes general requirements and procedures for compliance with certain Green Building Initiative – Green GlobesR prerequisites, requirements and credits needed for Project to obtain Green Globes - Two Globe certification based on the Green Globes green building assessment and rating tool, Version v.1.3.
1. Other Green Globes requirements and credits needed to obtain the Two Globe certification depends on material selections and may not be specifically identified as Green Globes requirements. Compliance with requirements needed to obtain Green Globes credits may be used as one criterion to evaluate substitution requests and comparable product requests.
2. Additional Green Globes prerequisites, requirements and credits needed to obtain the indicated Two Globe certification depend on Architect's design and other aspects of Project that are not part of the Work of the Contract.
3. A copy of the Green Globes Pre-Construction Questionnaire is attached at the end of this Section for information only.
4. As requested per this project, the contractor shall have at least one Certified Green Globes Professional GGP on their staff of Project Manager, Superintendent, or Quality Control Manager.
Submit the GGP certification to the contracting officer no later than the pre-work meeting.
B. Related Sections:
1. Divisions 01 through 33 Sections for sustainability requirements specific to the work of each of these Sections. Requirements may or may not include reference to Green Globes.
1.3 DEFINITIONS
A. Chain-of-Custody Certificates: Certificates signed by manufacturers certifying that wood used to make products was obtained from forests third party certified by the Sustainable Forestry initiative (SFI), CSA Sustainable Forest Management (SFM), Forestry stewardship Council (FSC), or other SFB accredited certification body to comply with the respective sustainable forestry practices standard. Certificates shall include evidence that manufacturer is certified for chain of custody by one of the aforementioned certification bodies.
B. GBI: The Green Building Initiative, a not for profit organization which holds the rights to market and manage the Green GlobesR green building rating and assessment tool in the United States.
SUSTAINABLE DESIGN REQUIREMENTS 018113 - 2
C. Rapidly Renewable Materials: Materials made from plants that are typically harvested within a 10-year or shorter cycle. Rapidly renewable materials include products made from bamboo, cotton, flax, jute, straw, sunflower seed hulls, vegetable oils, or wool.
D. Regional Materials: Materials that have been extracted, harvested, or recovered, as well as manufactured, within 500 miles of Project site. If only a fraction of a product or material is extracted/harvested/recovered and manufactured locally, then only that percentage (by weight) shall contribute to the regional value.
E. Recycled Content: The recycled content value of a material assembly shall be determined by weight.
The recycled fraction of the assembly is then multiplied by the cost of assembly to determine the recycled content value.
1. "Post-consumer" material is defined as waste material generated by households or by commercial, industrial, and institutional facilities in their role as end users of the product, which can no longer be used for its intended purpose.
2. "Pre-consumer" material is defined as material diverted from the waste stream during the manufacturing process. Excluded is reutilization of materials such as rework, regrind, or scrap generated in a process and capable of being reclaimed within the same process that generated it.
1.4 SUBMITTALS
A. General: Submit additional, separate submittals to comply with sustainability and Green Globes provisions required by other Specification Sections.
B. Sustainability Requirements submittals are in addition to other submittals. If submitted item is identical to that submitted to comply with other requirements, submit duplicate copies as a separate submittal to verify compliance with indicated Green Globes certification requirements.
C. Project Materials Cost Data: Provide statement indicating total cost for building materials used for Project, excluding mechanical, electrical, and plumbing components, and specialty items such as elevators and equipment. Include statement indicating total cost for wood-based materials used for Project.
D. Sustainability Action Plans: Provide preliminary submittals within 30 days of date established for the Notice to Proceed indicating how the following requirements, by Green Globes Assessment Area, will be met:
1. Site, Ecological Impacts: Erosion and Sedimentation Control Plan.
2. Resources, Building Materials and Solid Waste: Waste Management Plan complying with
Division 01 Section "Construction Waste Management and Disposal."
3. Resources, Building Materials and Solid Waste: List of proposed materials with recycled content. Indicate cost, post-consumer recycled content, and pre-consumer recycled content for each product having recycled content.
4. Resources, Building Materials and Solid Waste: List of proposed regional materials. Identify each regional material, including its source, cost, and the fraction by weight that is considered regional.
5. Indoor Environment: Construction Indoor-Air-Quality Management Plan.
E. Sustainability Progress Reports: Concurrent with each Application for Payment, submit reports comparing actual construction and purchasing activities with environmental action plans for the following:
SUSTAINABLE DESIGN REQUIREMENTS 018113 - 3
1. Resources, Building Materials and Solid Waste: Waste reduction progress reports complying with Division 01 Section "Construction Waste Management and Disposal."
2. Resources, Building Materials and Solid Waste: Recycled content.
3. Resources, Building Materials and Solid Waste: Regional materials.
F. Sustainability Documentation Submittals:
1. Resources, Building Materials and Solid Waste: Comply with Division 01 Section "Construction Waste Management and Disposal."
2. Resources, Building Materials and Solid Waste: Receipts for salvaged and refurbished materials used for Project, indicating sources and costs for salvaged and refurbished materials.
3. Resources, Building Materials and Solid Waste: Product data and certification letter indicating percentages by weight of post-consumer and pre-consumer recycled content for products having recycled content. Include statement indicating costs for each product having recycled content.
4. Resources, Building Materials and Solid Waste: Product data for regional materials indicating location and distance from Project of material manufacturer and point of extraction, harvest, or recovery for each raw material. Include statement indicating cost for each regional material and the fraction by weight that is considered regional.
5. Resources, Building Materials and Solid Waste: Product data and chain-of-custody certificates for products containing certified wood. Include statement indicating cost for each certified wood product.
6. Indoor Environment:
a. Construction indoor-air-quality management plan.
b. Product data for temporary filtration media.
c. Product data for filtration media used during occupancy.
d. Construction Documentation: Six photographs at three different times during the construction period, along with a brief description of the SMACNA approach employed, documenting implementation of the indoor-air-quality management measures, such as protection of ducts and on-site stored or installed absorptive materials.
7. Indoor Environment: Product data for adhesives and sealants used inside the weatherproofing system indicating VOC content of each product used. Indicate VOC content in g/L calculated according to 40 CFR 59, Subpart D (EPA Method 24).
8. Indoor Environment: Product data for paints and coatings used inside the weatherproofing system indicating VOC content of each product used. Indicate VOC content in g/L calculated according to 40 CFR 59, Subpart D (EPA Method 24).
9. Indoor Environment: Product data for products containing composite wood or agrifiber products or wood glues indicating that they do not contain urea-formaldehyde resin.
1.5 GENERAL ENVIRONMENTAL GOALS
The Owner and Construction Manager have established the following environmental goals for the project. These goals are general in nature, provide guidance to all project parties on sustainable construction practices, and support the attainment of the One Green Globe green building rating. In no way are these goals to supersede the specific design, performance and material specifications contained herein. Notify Construction Manager if conflicts arise between performance of the work and environmental goals. This section is not intended to limit alternative means of achieving these goals.
Suggestions from trade sub-contractors for implementing these goals is highly recommended, and an integrated team or partnering approach is encouraged.
1. Use resources efficiently:
SUSTAINABLE DESIGN REQUIREMENTS 018113 - 4
a. Select materials that use resources efficiently.
b. Use construction practices that achieve the most efficient use of resources and materials.
c. Recycle or reuse jobsite waste.
d. Select recycled content materials.
e. Select materials that can be recycled.
2. Avoid scarce, irreplaceable or endangered resources:
a. Select materials from abundant, well-managed resources.
b. Select materials that are replaceable, renewable, or can be replenished.
c. Select materials that minimize damage to natural habitats.
3. Use durable materials:
a. Select materials with the longest useable life.
b. Select materials that can be reused.
c. Select materials with the least burdensome maintenance requirements.
4. Create spaces that are healthy for occupants:
a. Select low toxicity products and materials.
b. Select materials without toxic maintenance requirements.
c. Specify mechanical equipment that will provide fresh air and will not trap water or pollutants.
5. Use energy efficiently:
a. Select materials with low embodied energy.
b. Select materials that save energy during building operations.
c. Select products and equipment that save energy during building operations.
6. Use water efficiently:
a. Use conservation practices that will achieve the most efficient use of water.
b. Select water conserving appliances and equipment.
c. Landscape for water conservation.
7. Use materials that generate the least amount of pollution.
a. Consider pollution and toxins generated during harvesting, mining and manufacturing.
b. Consider pollution and toxins generated or present during transport, installation, use and disposal.
8. Protect and/or restore natural habitats.
1.6 QUALITY ASSURANCE
A. Sustainability Coordinator: Engage an experienced a competent green building or sustainability professional to coordinate green building construction requirements and facilitate the attainment of the project’s environmental goals.
SUSTAINABLE DESIGN REQUIREMENTS 018113 - 5
B. Communication of Environmental Goals: Environmental goals shall be discussed at the Pre-Bid meeting, Pre-construction meeting, and at every regular onsite construction project meeting.
C. Documentation: Construction Manager shall be responsible for custody of all sustainability related documentation, including deficiencies in meeting the overall and specific environmental goals and provisions.
PART 2 - PRODUCTS
2.1 RECYCLED CONTENT OF MATERIALS
A. Resources, Building Materials and Solid Waste: Provide building materials with recycled content such that post-consumer recycled content plus one-half of pre-consumer recycled content constitutes a minimum of 20 percent of cost of materials used for Project.
1. Cost of post-consumer recycled content of an item shall be determined by dividing weight of post-consumer recycled content in the item by total weight of the item and multiplying by cost of the item.
2. Cost of post-consumer recycled content plus one-half of pre-consumer recycled content of an item shall be determined by dividing weight of post-consumer recycled content plus one-half of pre-consumer recycled content in the item by total weight of the item and multiplying by cost of the item.
3. Do not include mechanical and electrical components in the calculation.
2.2 REGIONAL MATERIALS
A. Resources, Building Materials and Solid Waste: Provide 20 percent of building materials (by cost) that are regional materials.
2.3 LOW-EMITTING MATERIALS
A. Resources, Building Materials and Solid Waste: For field applications that are inside the weatherproofing system, use adhesives and sealants that comply with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24):
1. Wood Glues: 30 g/L.
2. Metal to Metal Adhesives: 30 g/L.
3. Adhesives for Porous Materials (Except Wood): 50 g/L.
4. Subfloor Adhesives: 50 g/L.
5. Plastic Foam Adhesives: 50 g/L.
6. Carpet Adhesives: 50 g/L.
7. Carpet Pad Adhesives: 50 g/L.
8. VCT and Asphalt Tile Adhesives: 50 g/L.
9. Cove Base Adhesives: 50 g/L.
10. Gypsum Board and Panel Adhesives: 50 g/L.
11. Rubber Floor Adhesives: 60 g/L.
12. Ceramic Tile Adhesives: 65 g/L.
13. Multipurpose Construction Adhesives: 70 g/L.
SUSTAINABLE DESIGN REQUIREMENTS 018113 - 6
14. Fiberglass Adhesives: 80 g/L.
15. Contact Adhesive: 80 g/L.
16. Structural Glazing Adhesives: 100 g/L.
17. Wood Flooring Adhesive: 100 g/L.
18. Structural Wood Member Adhesive: 140 g/L.
19. Special Purpose Contact Adhesive (contact adhesive that is used to bond melamine covered board, metal, unsupported vinyl, Teflon, ultra-high molecular weight polyethylene, rubber or wood veneer 1/16 inch or less in thickness to any surface): 250 g/L.
20. Top and Trim Adhesive: 250 g/L.
21. Plastic Cement Welding Compounds: 350 g/L.
22. ABS Welding Compounds: 400 g/L.
23. CPVC Welding Compounds: 490 g/L.
24. PVC Welding Compounds: 510 g/L.
25. Adhesive Primer for Plastic: 650 g/L.
26. Sheet Applied Rubber Lining Adhesive: 850 g/L.
27. Aerosol Adhesive, General Purpose Mist Spray: 65 percent by weight.
28. Aerosol Adhesive, General Purpose Web Spray: 55 percent by weight.
29. Special Purpose Aerosol Adhesive (All Types): 70 percent by weight.
30. Other Adhesives: 250 g/L.
31. Architectural Sealants: 250 g/L.
32. Nonmembrane Roof Sealants: 300 g/L.
33. Single-Ply Roof Membrane Sealants: 450 g/L.
34. Other Sealants: 420 g/L.
35. Sealant Primers for Nonporous Substrates: 250 g/L.
36. Sealant Primers for Porous Substrates: 775 g/L.
37. Modified Bituminous Sealant Primers: 500 g/L.
38. Other Sealant Primers: 750 g/L.
B. Indoor Environment: For field applications that are inside the weatherproofing system, use paints and coatings that comply with the following limits for VOC content when calculated according to 40 CFR 59, Subpart D (EPA Method 24):
1. Flat Paints, Coatings, and Primers: VOC not more than 50 g/L.
2. Nonflat Paints, Coatings, and Primers: VOC not more than 150 g/L.
3. Anticorrosive and Antirust Paints Applied to Ferrous Metals: VOC not more than 250 g/L.
4. Clear Wood Finishes, Varnishes: VOC not more than 350 g/L.
5. Clear Wood Finishes, Lacquers: VOC not more than 550 g/L.
6. Floor Coatings: VOC not more than 100 g/L.
7. Shellacs, Clear: VOC not more than 730 g/L.
8. Shellacs, Pigmented: VOC not more than 550 g/L.
9. Stains: VOC not more than 250 g/L.
C. Indoor Environment: Do not use composite wood or agrifiber products or adhesives that contain urea-formaldehyde resin.
PART 3 - EXECUTION
3.1 MEASUREMENT AND VERIFICATION
A. If not already in place, install metering equipment to measure energy usage. Monitor, record, and trend log measurements.
SUSTAINABLE DESIGN REQUIREMENTS 018113 - 7
B. Evaluate energy performance and efficiency by comparing actual to predicted performance.
C. Measurement and verification period shall cover at least one year of post-construction occupancy.
3.2 CONSTRUCTION WASTE MANAGEMENT
A. Resources, Building Materials and Solid Waste: Comply with Division 01 Section "Construction Waste Management and Disposal."
3.3 CONSTRUCTION INDOOR-AIR-QUALITY MANAGEMENT
A. Indoor Environment: Comply with SMACNA's "SMACNA IAQ Guideline for Occupied Buildings under Construction."
1. If Owner authorizes use of permanent heating, cooling, and ventilating systems during construction period as specified in Division 01 Section "Temporary Facilities and Controls," install filter media having a MERV 8 according to ASHRAE 52.2 at each return-air inlet for the air-handling system used during construction.
2. Replace all air filters immediately prior to occupancy.
END OF SECTION 018113
CAST-IN-PLACE CONCRETE 033000 - 1
SECTION 033000 - CAST-IN-PLACE CONCRETE
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes cast-in-place concrete, including formwork, reinforcement, concrete materials, mixture design, placement procedures, and finishes.
B. Related Requirements:
1. Section 312000 "Earth Moving" for drainage fill under slabs-on-grade.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Sustainable Design Submittals:
1. Product Data: For recycled content, indicating postconsumer and preconsumer recycled content and cost.
2. Laboratory Test Reports: For curing and sealing compounds, indicating compliance with requirements for low-emitting materials.
C. Design Mixtures: For each concrete mixture.
1.3 INFORMATIONAL SUBMITTALS
A. Material certificates.
B. Material test reports.
C. Floor surface flatness and levelness measurements indicating compliance with specified tolerances.
1.4 QUALITY ASSURANCE
A. Manufacturer Qualifications: A firm experienced in manufacturing ready-mixed concrete products and that complies with ASTM C 94/C 94M requirements for production facilities and equipment.
1. Manufacturer certified according to NRMCA's "Certification of Ready Mixed Concrete Production Facilities."
B. Testing Agency Qualifications: An independent agency, acceptable to authorities having jurisdiction, qualified according to ASTM C 1077 and ASTM E 329 for testing indicated.
C. ACI Publications: Comply with the following unless modified by requirements in the Contract Documents:
http://www.arcomnet.com/sustainable_design.aspx?topic=7 http://www.arcomnet.com/sustainable_design.aspx?topic=121
CAST-IN-PLACE CONCRETE 033000 - 2
1. ACI 301, "Specifications for Structural Concrete," Sections 1 through 5.
2. ACI 117, "Specifications for Tolerances for Concrete Construction and Materials."
D. Concrete Testing Service: Engage a qualified independent testing agency to perform material evaluation tests and to design concrete mixtures.
1.5 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
PART 2 - PRODUCTS
2.1 FORM-FACING MATERIALS
A. Smooth-Formed Finished Concrete: Form-facing panels that provide continuous, true, and smooth concrete surfaces. Furnish in largest practicable sizes to minimize number of joints.
B. Rough-Formed Finished Concrete: Plywood, lumber, metal, or another approved material. Provide lumber dressed on at least two edges and one side for tight fit.
2.2 STEEL REINFORCEMENT
A. Recycled Content of Steel Products: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent.
B. Reinforcing Bars: ASTM A 615/A 615M, Grade 60, deformed.
A. Plain-Steel Welded Wire Reinforcement: ASTM A 185/A 185M, plain, fabricated from as-drawn steel wire into flat sheets.
B. Bar Supports: Bolsters, chairs, spacers, and other devices for spacing, supporting, and fastening reinforcing bars and welded-wire reinforcement in place. Manufacture bar supports from steel wire, plastic, or precast concrete according to CRSI's "Manual of Standard Practice."
2.3 CONCRETE MATERIALS
A. Cementitious Material: Use the following cementitious materials, of the same type, brand, and source, throughout Project:
1. Portland Cement: ASTM C 150, Type I/II. Supplement with the following:
a. Fly Ash: ASTM C 618, Class F or C.
b. Ground Granulated Blast-Furnace Slag: ASTM C 989, Grade 100 or 120.
B. Normal-Weight Aggregates: ASTM C 33/C 33M, graded.
1. Maximum Coarse-Aggregate Size: 1-1/2 inches nominal.
2. Fine Aggregate: Free of materials with deleterious reactivity to alkali in cement.
http://www.arcomnet.com/sustainable_design.aspx?topic=110
CAST-IN-PLACE CONCRETE 033000 - 3
C. Water: ASTM C 94/C 94M and potable.
2.4 ADMIXTURES
A. Air-Entraining Admixture: ASTM C 260.
B. Chemical Admixtures: Provide admixtures certified by manufacturer to be compatible with other admixtures and that will not contribute water-soluble chloride ions exceeding those permitted in hardened concrete. Do not use calcium chloride or admixtures containing calcium chloride.
1. Water-Reducing Admixture: ASTM C 494/C 494M, Type A.
2. Retarding Admixture: ASTM C 494/C 494M, Type B.
3. Water-Reducing and Retarding Admixture: ASTM C 494/C 494M, Type D.
4. High-Range, Water-Reducing Admixture: ASTM C 494/C 494M, Type F.
5. High-Range, Water-Reducing and Retarding Admixture: ASTM C 494/C 494M, Type G.
6. Plasticizing and Retarding Admixture: ASTM C 1017/C 1017M, Type II.
2.5 FIBER REINFORCEMENT
A. Synthetic Micro-Fiber: Monofilament or fibrillated polypropylene micro-fibers engineered and designed for use in concrete, complying with ASTM C 1116/C 1116M, Type III, 1/2 to 1-1/2 inches long.
2.6 WATERSTOPS
A. Self-Expanding Butyl Strip Waterstops: Manufactured rectangular or trapezoidal strip, butyl rubber with sodium bentonite or other hydrophilic polymers, for adhesive bonding to concrete, 3/4 by 1 inch.
1. Products:
a. Colloid Environmental Technologies Company; Volclay Waterstop-RX
b. Substitutions: See 012500 Substitutions Procedures.
2.7 CURING MATERIALS
A. Evaporation Retarder: Waterborne, monomolecular film forming, manufactured for application to fresh concrete.
B. Absorptive Cover: AASHTO M 182, Class 2, burlap cloth made from jute or kenaf, weighing approximately 9 oz./sq. yd. when dry.
C. Moisture-Retaining Cover: ASTM C 171, polyethylene film or white burlap-polyethylene sheet.
D. Water: Potable.
E. Clear, Waterborne, Membrane-Forming Curing Compound: ASTM C 309, Type 1, Class B, dissipating.
CAST-IN-PLACE CONCRETE 033000 - 4
2.8 RELATED MATERIALS
A. Expansion- and Isolation-Joint-Filler Strips: ASTM D 1751, asphalt-saturated cellulosic fiber or ASTM D 1752, cork or self-expanding cork.
2.9 CONCRETE MIXTURES, GENERAL
A. Prepare design mixtures for each type and strength of concrete, proportioned on the basis of laboratory trial mixture or field test data, or both, according to ACI 301.
B. Cementitious Materials: Use fly ash, pozzolan, slag cement, and silica fume as needed to reduce the total amount of portland cement, which would otherwise be used, by not less than 40 percent.
C. Admixtures: Use admixtures according to manufacturer's written instructions.
1. Use water-reducing, high-range water-reducing or plasticizing admixture in concrete, as required, for placement and workability.
2. Use water-reducing and -retarding admixture when required by high temperatures, low humidity, or other adverse placement conditions.
3. Use water-reducing admixture in pumped concrete, concrete for heavy-use industrial slabs and parking structure slabs, concrete required to be watertight, and concrete with a w/c ratio below 0.50.
D. Proportion normal-weight concrete mixture as follows:
1. Minimum Compressive Strength: 3500 psi at 28 days.
2. Maximum Water-Cementitious Materials Ratio: 0.40.
3. Slump Limit: Per drawings.
4. Air Content: 5.5 percent, plus or minus 1.5 percent at point of delivery.
5. Air Content: Do not allow air content of trowel-finished floors to exceed 3 percent.
2.10 FABRICATING REINFORCEMENT
A. Fabricate steel reinforcement according to CRSI's "Manual of Standard Practice."
2.11 CONCRETE MIXING
A. Ready-Mixed Concrete: Measure, batch, mix, and deliver concrete according to ASTM C 94/C 94M and ASTM C 1116/C 1116M, and furnish batch ticket information.
1. When air temperature is between 85 and 90 deg F (30 and 32 deg C), reduce mixing and delivery time from 1-1/2 hours to 75 minutes; when air temperature is above 90 deg F (32 deg C), reduce mixing and delivery time to 60 minutes.
2.12 HARDENER, DENSIFIER, AND SEALER
A. Basis-of-Design: Prosoco, Inc. Consolideck LS, www.prosoco.com , or approved equal.
http://www.prosoco.com/
CAST-IN-PLACE CONCRETE 033000 - 5
PART 3 - EXECUTION
3.1 FORMWORK INSTALLATION
A. Design, erect, shore, brace, and maintain formwork, according to ACI 301, to support vertical, lateral, static, and dynamic loads, and construction loads that might be applied, until structure can support such loads.
B. Construct formwork so concrete members and structures are of size, shape, alignment, elevation, and position indicated, within tolerance limits of ACI 117.
C. Chamfer exterior corners and edges of permanently exposed concrete.
3.2 EMBEDDED ITEM INSTALLATION
A. Place and secure anchorage devices and other embedded items required for adjoining work that is attached to or supported by cast-in-place concrete. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
3.3 STEEL REINFORCEMENT INSTALLATION
A. General: Comply with CRSI's "Manual of Standard Practice" for fabricating, placing, and supporting reinforcement.
3.4 JOINTS
A. General: Construct joints true to line with faces perpendicular to surface plane of concrete.
B. Construction Joints: Install so strength and appearance of concrete are not impaired, at locations indicated or as approved by Contracting Officer.
C. Contraction Joints in Slabs-on-Grade: Form weakened-plane contraction joints, sectioning concrete into areas as indicated. Construct contraction joints for a depth equal to at least one-fourth of concrete thickness as follows:
1. Sawed Joints: Form contraction joints with power saws equipped with shatterproof abrasive or diamond-rimmed blades. Cut 1/8-inch-wide joints into concrete when cutting action does not tear, abrade, or otherwise damage surface and before concrete develops random contraction cracks.
D. Isolation Joints in Slabs-on-Grade: After removing formwork, install joint-filler strips at slab junctions with vertical surfaces, such as column pedestals, foundation walls, grade beams, and other locations, as indicated.
3.5 WATERSTOP INSTALLATION
A. Waterstops: Install in construction joints and at other locations indicated, according to manufacturer's written instructions.
CAST-IN-PLACE CONCRETE 033000 - 6
3.6 CONCRETE PLACEMENT
A. Before placing concrete, verify that installation of formwork, reinforcement, and embedded items is complete and that required inspections are completed.
B. Deposit concrete continuously in one layer or in horizontal layers of such thickness that no new concrete is placed on concrete that has hardened enough to cause seams or planes of weakness. If a section cannot be placed continuously, provide construction joints as indicated. Deposit concrete to avoid segregation.
1. Consolidate placed concrete with mechanical vibrating equipment according to ACI 301.
C. Cold-Weather Placement: Comply with ACI 306.1.
D. Hot-Weather Placement: Comply with ACI 301.
3.7 FINISHING FORMED SURFACES
A. Smooth-Formed Finish: As-cast concrete texture imparted by form-facing material, arranged in an orderly and symmetrical manner with a minimum of seams. Repair and patch tie holes and defects.
Remove fins and other projections that exceed specified limits on formed-surface irregularities.
1. Apply to concrete surfaces exposed to public view, or to be covered with a coating or covering material applied directly to concrete.
B. Related Unformed Surfaces: At tops of walls, horizontal offsets, and similar unformed surfaces adjacent to formed surfaces, strike off smooth and finish with a texture matching adjacent formed surfaces.
Continue final surface treatment of formed surfaces uniformly across adjacent unformed surfaces unless otherwise indicated.
3.8 FINISHING FLOORS AND SLABS
A. General: Comply with ACI 302.1R recommendations for screeding, restraightening, and finishing operations for concrete surfaces. Do not wet concrete surfaces prior to finishing.
B. Scratch Finish: While still plastic, texture concrete surface that has been screeded and bull-floated or darbied. Use stiff brushes, brooms, or rakes to produce a profile amplitude of 1/4 inch in one direction.
1. Apply scratch finish to surfaces indicated.
C. Float Finish: Consolidate surface with power-driven floats or by hand floating if area is small or inaccessible to power-driven floats. Restraighten, cut down high spots, and fill low spots. Repeat float passes and restraightening until surface is left with a uniform, smooth, granular texture.
1. Apply float finish to surfaces indicated.
D. Trowel Finish: After applying float finish, apply first troweling and consolidate concrete by hand or power-driven trowel. Continue troweling passes and restraighten until surface is free of trowel marks and uniform in texture and appearance. Grind smooth any surface defects that would telegraph through applied coatings or floor coverings.
CAST-IN-PLACE CONCRETE 033000 - 7
1. Apply a trowel finish to surfaces indicated.
2. Finish and measure surface, so gap at any point between concrete surface and an unleveled, freestanding, 10-ft.- long straightedge resting on two high spots and placed anywhere on the surface does not exceed 3/16 inch.
E. Trowel and Fine-Broom Finish: Apply a first trowel finish to surfaces indicated. While concrete is still plastic, slightly scarify surface with a fine broom.
1. Comply with flatness and levelness tolerances for trowel-finished floor surfaces.
F. Broom Finish: Apply a broom finish to exterior concrete platforms, steps, ramps, and elsewhere as indicated.
1. Immediately after float finishing, slightly roughen trafficked surface by brooming with fiber-bristle broom perpendicular to main traffic route. Coordinate required final finish with Contracting Officer before application.
3.9 CONCRETE PROTECTING AND CURING
A. General: Protect freshly placed concrete from premature drying and excessive cold or hot temperatures.
Comply with ACI 306.1 for cold-weather protection and ACI 301 for hot-weather protection during curing.
B. Evaporation Retarder: Apply evaporation retarder to unformed concrete surfaces if hot, dry, or windy conditions cause moisture loss approaching 0.2 lb/sq. ft. x h before and during finishing operations.
Apply according to manufacturer's written instructions after placing, screeding, and bull floating or darbying concrete, but before float finishing.
C. Cure concrete according to ACI 308.1, by one or a combination of the following methods:
1. Moisture Curing: Keep surfaces continuously moist with water spray for not less than seven days.
2. Moisture-Retaining-Cover Curing: Cover concrete surfaces with moisture-retaining cover for curing concrete, placed in widest practicable width, with sides and ends lapped at least 12 inches, and sealed by waterproof tape or adhesive. Cure for not less than seven days. Immediately repair any holes or tears during curing period, using cover material and waterproof tape.
3. Curing Compound: Apply uniformly in continuous operation by power spray or roller according to manufacturer's written instructions. Recoat areas subjected to heavy rainfall within three hours after initial application. Maintain continuity of coating and repair damage during curing period.
a. Removal: After curing period has elapsed, remove curing compound without damaging concrete surfaces by method recommended by curing compound manufacturer.
4. Curing and Sealing Compound: Apply uniformly to floors and slabs indicated in a continuous operation by power spray or roller according to manufacturer's written instructions. Recoat areas subjected to heavy rainfall within three hours after initial application. Repeat process 24 hours later and apply a second coat. Maintain continuity of coating and repair damage during curing period.
CAST-IN-PLACE CONCRETE 033000 - 8
3.10 CONCRETE SURFACE REPAIRS
A. Defective Concrete: Repair and patch defective areas when approved by Contracting Officer. Remove and replace concrete that cannot be repaired and patched to Contracting Officer's approval.
3.11 FIELD QUALITY CONTROL
A. Testing and Inspecting: Contracting Officer will engage a qualified testing and inspecting agency to perform field tests and inspections and prepare test reports. Contractor to notify the Contracting Officer at the appropriate time for all inspections and coordinate the specific testing work with testing personnel.
B. Inspections:
1. Verification of use of required design mixture.
2. Concrete placement, including conveying and depositing.
3. Curing procedures and maintenance of curing temperature.
C. Concrete Tests: Testing of composite samples of fresh concrete obtained according to ASTM C 172 shall be performed according to the following requirements:
1. Testing Frequency: Obtain at least one composite sample for each 100 cu. yd. (76 cu. m) or fraction thereof of each concrete mixture placed each day.
a. When frequency of testing will provide fewer than three compressive-strength tests for each concrete mixture, testing shall be conducted from at least three randomly selected batches or from each batch if fewer than five are used.
2. Slump: ASTM C 143/C 143M; one test at point of placement for each composite sample, but not less than one test for each day's pour of each concrete mixture. Perform additional tests when concrete consistency appears to change.
3. Air Content: ASTM C 231, pressure method, for normal-weight concrete or ASTM C 173/C 173M, volumetric method, for structural lightweight concrete; one test for each composite sample, but not less than one test for each day's pour of each concrete mixture.
4. Concrete Temperature: ASTM C 1064/C 1064M; one test hourly when air temperature is 40 deg F and below and when 80 deg F and above, and one test for each composite sample.
5. Unit Weight: ASTM C 567, fresh unit weight of structural lightweight concrete; one test for each composite sample.
6. Coordinate the number of compression test specimens in subparagraph above with number of compressive-strength tests in first subparagraph below.
7. Compressive-Strength Tests: ASTM C 39/C 39M; test one set of two laboratory-cured specimens at 7 days and one set of two specimens at 28 days.
a. A compressive-strength test shall be the average compressive strength from a set of two specimens obtained from same composite sample and tested at age indicated.
8. When strength of field-cured cylinders is less than 85 percent of companion laboratory-cured cylinders, Contractor shall evaluate operations and provide corrective procedures for protecting and curing in-place concrete.
9. Strength of each concrete mixture will be satisfactory if every average of any three consecutive compressive-strength tests equals or exceeds specified compressive strength and no compressive-strength test value falls below specified compressive strength by more than 500 psi.
CAST-IN-PLACE CONCRETE 033000 - 9
10. Test results shall be reported in writing to Contracting Officer, concrete manufacturer, and Contractor within 48 hours of testing. Reports of compressive-strength tests shall contain Project identification name and number, date of concrete placement, name of concrete testing and inspecting agency, location of concrete batch in Work, design compressive strength at 28 days, concrete mixture proportions and materials, compressive breaking strength, and type of break for both 7- and 28-day tests.
11. Nondestructive Testing: Impact hammer, sonoscope, or other nondestructive device may be permitted by Contracting Officer but will not be used as sole basis for approval or rejection of concrete.
12. Additional Tests: Testing and inspecting agency shall make additional tests of concrete when test results indicate that slump, air entrainment, compressive strengths, or other requirements have not been met, as directed by Contracting Officer. Testing and inspecting agency may conduct tests to determine adequacy of concrete by cored cylinders complying with ASTM C 42/C 42M or by other methods as directed by Contracting Officer.
13. Additional testing and inspecting, at Contractor's expense, will be performed to determine compliance of replaced or additional work with specified requirements.
14. Correct deficiencies in the Work that test reports and inspections indicate do not comply with the Contract Documents.
15. Concrete tests are further defined on Structural Drawing S0.1.
3.12 HARDENER, DENSIFIER, SEALER APPLICATION
A. Pre-test a small area of surface to confirm suitability, coverage rate, and desired results before beginning overall application. Apply a single coat application with a low pressure sprayer or microfiber pad in accordance with manufacturer’s recommendations.
END OF SECTION 033000
INRC OFFICE BUILDING – PHASE 3
COEUR D’ALENE, IDAHO
PRECAST ARCHITECTURAL CONCRETE 034500 - 1
SECTION 034500 - PRECAST ARCHITECTURAL CONCRETE
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes architectural precast concrete veneer banding, exterior bench tops, and miscellaneous trim units.
1.2 DEFINITIONS
A. Design Reference Sample: Sample of approved architectural precast concrete color, finish and texture, preapproved by Architect.
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Sustainable Design Submittals:
1. Product Data: For recycled content, indicating postconsumer and preconsumer recycled content and cost.
C. Design Mixtures: For each precast concrete mixture. Include compressive strength and water-absorption tests.
D. Shop Drawings:
1. Detail fabrication and installation of architectural precast concrete units.
2. Indicate locations, plans, elevations, dimensions, shapes, and cross sections of each unit.
3. Indicate joints, reveals, drips, chamfers, and extent and location of each surface finish.
4. Indicate details at building corners.
E. Samples: Design reference samples for initial verification of design intent, for each type of finish indicated on exposed surfaces of architectural precast concrete units, in sets of three, representative of finish, color, and texture variations expected; approximately 12 by 12 by 2 inches.
F. Delegated-Design Submittal: For architectural precast concrete indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
INRC OFFICE BUILDING – PHASE 3
COEUR D’ALENE, IDAHO
PRECAST ARCHITECTURAL CONCRETE 034500 - 2
1.5 INFORMATIONAL SUBMITTALS
A. Welding certificates.
B. Material certificates.
C. Material Test Reports: For aggregates.
D. Field quality-control reports.
1.6 QUALITY ASSURANCE
A. Quality-Control Standard: For manufacturing procedures and testing requirements, quality-control recommendations, and dimensional tolerances for types of units required, comply with PCI MNL 117, "Manual for Quality Control for Plants and Production of Architectural Precast Concrete Products."
B. Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D.1.1M, "Structural Welding Code - Steel"; and AWS D1.4/D1.4M, "Structural Welding Code - Reinforcing Steel."
C. Sample Unit: After sample approval and before fabricating architectural precast concrete units, produce one sample unit approximately 4 feet long in area for review by Architect. Incorporate full-scale details of architectural features, finishes, textures, and transitions in sample panels.
1.7 COORDINATION
A. Furnish loose connection hardware and anchorage items to be embedded in or attached to other construction without delaying the Work. Provide locations, setting diagrams, templates, instructions, and directions, as required, for installation.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Structural Performance: Provide architectural precast concrete units and connections capable of withstanding design loads indicated within limits and under conditions indicated.
2.2 REINFORCING MATERIALS
A. Recycled Content of Steel Products: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent.
B. Reinforcing Bars: ASTM A 615/A 615M, Grade 60, deformed.
C. Low-Alloy-Steel Reinforcing Bars: ASTM A 706/A 706M, deformed.
D. Plain-Steel Welded Wire Reinforcement: ASTM A 185/A 185M, fabricated from as-drawn steel wire into flat sheets.
http://www.arcomnet.com/sustainable_design.aspx?topic=110
INRC OFFICE BUILDING – PHASE 3
COEUR D’ALENE, IDAHO
PRECAST ARCHITECTURAL CONCRETE 034500 - 3
E. Deformed-Steel Welded Wire Reinforcement: ASTM A 497/A 497M, flat sheet.
F. Supports: Suspend reinforcement from back of mold or use bolsters, chairs, spacers, and other devices for spacing, supporting, and fastening reinforcing bars and welded wire reinforcement in place according to PCI MNL 117.
2.3 CONCRETE MATERIALS
A. Portland Cement: ASTM C 150/C 150M, Type I or Type III, gray, unless otherwise indicated.
1. For surfaces exposed to view in finished structure, use gray or white cement, of same type, brand, and mill source.
B. Supplementary Cementitious Materials:
1. Fly Ash: ASTM C 618, Class C or F, with maximum loss on ignition of 3 percent.
2. Metakaolin: ASTM C 618, Class N.
3. Silica Fume: ASTM C 1240, with optional chemical and physical requirement.
4. Ground Granulated Blast-Furnace Slag: ASTM C 989, Grade 100 or 120.
5. Blended Hydraulic Cement: ASTM C 595, Type IS, portland blast-furnace slag cement.
C. Normal-Weight Aggregates: Except as modified by PCI MNL 117, ASTM C 33/C 33M, with coarse aggregates complying with Class 5S. Stockpile fine and coarse aggregates for each type of exposed finish from a single source (pit or quarry) for Project.
1. Face-Mixture-Coarse Aggregates: Selected, hard, and durable; free of material that reacts with cement or causes staining; to match selected finish sample.
a. Gradation: Uniformly graded.
2. Face-Mixture-Fine Aggregates: Selected, natural or manufactured sand compatible with coarse aggregate; to match approved finish sample.
D. Coloring Admixture: ASTM C 979/C 979M, synthetic or natural mineral-oxide pigments or colored water-reducing admixtures, temperature stable, and nonfading.
E. Water: Potable; free from deleterious material that may affect color stability, setting, or strength of concrete and complying with chemical limits of PCI MNL 117.
F. Air-Entraining Admixture: ASTM C 260, certified by manufacturer to be compatible with other required admixtures.
G. Chemical Admixtures: Certified by manufacturer to be compatible with other admixtures and to not contain calcium chloride, or more than 0.15 percent chloride ions or other salts by weight of admixture.
2.4 STEEL CONNECTION MATERIALS
A. Carbon-Steel Shapes and Plates: ASTM A 36/A 36M.
INRC OFFICE BUILDING – PHASE 3
COEUR D’ALENE, IDAHO
PRECAST ARCHITECTURAL CONCRETE 034500 - 4
B. Carbon-Steel-Headed Studs: ASTM A 108, AISI 1018 through AISI 1020, cold finished, AWS D1.1/D1.1M, Type A or Type B, with arc shields and with minimum mechanical properties of PCI MNL 117, Table 3.2.3.
C. Carbon-Steel Plate: ASTM A 283/A 283M, Grade C.
D. Malleable Iron Castings: ASTM A 47/A 47M, Grade 32510 or Grade 35028.
E. Carbon-Steel Castings: ASTM A 27/A 27M, Grade 60-30.
F. High-Strength, Low-Alloy Structural Steel: ASTM A 572/A 572M.
G. Carbon-Steel Structural Tubing: ASTM A 500/A 500M, Grade B or Grade C.
H. Wrought Carbon-Steel Bars: ASTM A 675/A 675M, Grade 65.
I. Deformed-Steel Wire or Bar Anchors: ASTM A 496/A 496M or ASTM A 706/A 706M.
J. Carbon-Steel Bolts and Studs: ASTM A 307, Grade A or ASTM F 1554, Grade 36; carbon-steel, hex-head bolts and studs; carbon-steel nuts, ASTM A 563; and flat, unhardened steel washers, ASTM F 844.
K. High-Strength Bolts and Nuts: ASTM A 325, Type 1, heavy hex steel structural bolts; heavy hex carbon-steel nuts, ASTM A 563; and hardened carbon-steel washers, ASTM F 436.
L. Zinc-Coated Finish: For exterior steel items, steel in exterior walls, and items indicated for galvanizing, apply zinc coating by hot-dip process according to ASTM A 123/A 123M or ASTM A 153/A 153M.
1. Galvanizing Repair Paint: High-zinc-dust-content paint with dry film containing not less than 94 percent zinc dust by weight, and complying with DOD-P-21035B or SSPC-Paint 20.
M. Shop-Primed Finish: Prepare surfaces of nongalvanized steel items, except those surfaces to be embedded in concrete, according to requirements in SSPC-SP 3 and shop-apply lead- and chromate-free, rust-inhibitive primer, complying with performance requirements in MPI 79 according to SSPC-
PA 1.
2.5 GROUT MATERIALS
A. Sand-Cement Grout: Portland cement, ASTM C 150/C 150M, Type I, and clean, natural sand, ASTM C 144 or ASTM C 404. Mix at ratio of 1 part cement to 2-1/2 to 3 parts sand, by volume, with minimum water required for placement and hydration. Water-soluble chloride ion content less than 0.06 percent by weight of cement when tested according to ASTM C 1218/C 1218M.
2.6 CONCRETE MIXTURES
A. Prepare design mixtures for each type of precast concrete required.
B. Limit use of fly ash and ground granulated blast-furnace slag to 20 percent of portland cement by weight; limit metakaolin and silica fume to 10 percent of portland cement by weight.
INRC OFFICE BUILDING – PHASE 3
COEUR D’ALENE, IDAHO
PRECAST ARCHITECTURAL CONCRETE 034500 - 5
C. Design mixtures may be prepared by a qualified independent testing agency or by qualified precast plant personnel at architectural precast concrete fabricator's option.
D. Limit water-soluble chloride ions to maximum percentage by weight of cement permitted by ACI 318 or PCI MNL 117 when tested according to ASTM C 1218/C 1218M.
E. Normal-Weight Concrete Mixtures: Proportion mixtures by either laboratory trial batch or field test data methods according to ACI 211.1, with materials to be used on Project, to provide normal-weight concrete with the following properties:
1. Compressive Strength (28 Days): 4000 psi minimum.
F. Water Absorption: 6 percent by weight or 14 percent by volume, tested according to ASTM C 642, except for boiling requirement.
G. Add air-entraining admixture at manufacturer's prescribed rate to result in concrete at point of placement having an air content complying with PCI MNL 117.
H. When included in design mixtures, add other admixtures to concrete mixtures according to manufacturer's written instructions.
2.7 FABRICATION
A. Cast-in Anchors, Inserts, Plates, Angles, and Other Anchorage Hardware: Fabricate anchorage hardware with sufficient anchorage and embedment to comply with design requirements. Accurately position for attachment of loose hardware, and secure in place during precasting operations. Locate anchorage hardware where it does not affect position of main reinforcement or concrete placement.
1. Weld-headed studs and deformed bar anchors used for anchorage according to AWS D1.1/D1.1M and AWS C5.4, "Recommended Practices for Stud Welding."
B. Furnish loose hardware items including steel plates, clip angles, seat angles, anchors, dowels, cramps, hangers, and other hardware shapes for securing architectural precast concrete units to supporting and adjacent construction.
C. Cast-in reglets, slots, holes, and other accessories in architectural precast concrete units as indicated on the Contract Drawings.
D. Reinforcement: Comply with recommendations in PCI MNL 117 for fabricating, placing, and supporting reinforcement.
E. Reinforce architectural precast concrete units to resist handling, transportation, and erection stresses and specified in-place loads.
F. Comply with requirements in PCI MNL 117 and requirements in this Section for measuring, mixing, transporting, and placing concrete. After concrete batching, no additional water may be added.
G. Place face mixture to a minimum thickness after consolidation of the greater of 1 inch or 1.5 times the maximum aggregate size, but not less than the minimum reinforcing cover specified.
H. Place concrete in a continuous operation to prevent cold joints or planes of weakness from forming in precast concrete units.
INRC OFFICE BUILDING – PHASE 3
COEUR D’ALENE, IDAHO
PRECAST ARCHITECTURAL CONCRETE 034500 - 6
1. Place backup concrete mixture to ensure bond with face-mixture concrete.
I. Thoroughly consolidate placed concrete by internal and external vibration without dislocating or damaging reinforcement and built-in items, and minimize pour lines, honeycombing, or entrapped air voids on surfaces. Use equipment and procedures complying with PCI MNL 117.
1. Place self-consolidating concrete without vibration according to PCI TR-6, "Interim Guidelines for the Use of Self-Consolidating Concrete in Precast/Prestressed Concrete Institute Member Plants." Ensure adequate bond between face and backup concrete, if used.
J. Comply with PCI MNL 117 for hot- and cold-weather concrete placement.
K. Identify pickup points of architectural precast concrete units and orientation in structure with permanent markings, complying with markings indicated on Shop Drawings. Imprint or permanently mark casting date on each architectural precast concrete unit on a surface that does not show in finished structure.
L. Cure concrete, according to requirements in PCI MNL 117, by moisture retention without heat or by accelerated heat curing using low-pressure live steam or radiant heat and moisture. Cure units until compressive strength is high enough to ensure that stripping does not have an effect on performance or appearance of final product.
M. Discard and replace architectural precast concrete units that do not comply with requirements, including structural,…