This solicitation is for a design-build elevator modernization project at the Harry S Truman Federal Office Building in Washington, DC. The General Services Administration seeks to renovate 21 elevators and associated machine rooms to extend the building's useful life and comply with operational requirements. The scope of work includes abatement, demolition, HVAC replacement, electrical work, and elevator monitoring/communication upgrades. All noisy construction must occur on weeknights and weekends. Companies must have Secret-level facility clearance and workers must have Final Secret clearance. Small businesses certified in NAICS Code 238290 are encouraged to respond. The estimated design-build cost is over $10 million and period of performance is approximately 1,095 calendar days from notice to proceed.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LERCH BATES INC. Electric Traction Elevator Modernization
Elevator Consulting Groups Division 14 – Conveying Systems
March 17, 2015 ©2011Lerch Bates Inc.
14220 - 1 Phase 2 Upgrade Elevator Upgrade Elevator 14
LB Project No. R0100002829
SECTION 14220
TRACTION ELEVATORS
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY
A. One (1) Service Elevator
B. Unless specifically identified as “retain existing,” provide new equipment.
Existing Equipment Disposition
Number: Car 14 Car 14
Capacity: 8,000 lbs. 8,000 lbs.
Class Loading: Service Class C Retain Existing
Contract Speed: 200 F.P.M. 200 F.P.M.
Roping: 1:1 Retain Existing
Machine: Geared Retain Existing
Machine Location: Overhead Retain Existing
Operational Control: Remove Existing Selective Collective
Provide New Selective Collective Microprocessor-Based System
Motor Control: Remove existing DC Variable Voltage
Provide new AC Variable Voltage Variable Frequency Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz Field Verify
480-3-60 Provided By Others
14220 - 2 Phase 2 Upgrade Elevator Upgrade
Stops: 9 Front; 0 Rear Retain Existing
Openings: 9 Front; 0 Rear Retain Existing
Travel: 96’-0” ± Field Verify Retain Existing
Platform Size: 8’-3” Wide X 11’-7” Deep Field Verify
Retain Existing
Entrance Size: 5’-0” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Two Speed, Center Opening Retain Existing
Door Operation: Remove existing Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
Provide New High Speed, Heavy- Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Infrared Device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Flexible Guide Clamp – Type B, Car
Retain Existing
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Spring Retain Existing
Compensation: Provide new Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
Illuminate Portion of Normal Car Lighting
14220 - 3 Phase 2 Upgrade Elevator Upgrade
Signal Fixtures: Provide new LED Illumination Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Single Hall Pushbutton Riser Single Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Single Digital with Car Direction Arrows
Provide new Security Control Panel
Provide new Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction Vandal Resistant Assembly
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors, Vandal Resistant Assembly
Communication System:
Provide new Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Car 14:
Provide new Car and Counterweight Swivel Slide Type Guides
Provide new Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
14220 - 4 Phase 2 Upgrade Elevator Upgrade
Standby Power Transfer (Automatic to Main Floor) with Manual Override in Firefighters’ Control Panel
Provide new Accessibility and Emergency Medical Services Signage
Stationary Car Return Panel(s) Arranged for Surface Applied Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Platform Isolation
Remove existing governor. Provide new governor.
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
CCTV Provisions, All Cars
Provide new Security Control Panel and Remote Wiring
Provide new Firefighters’ Control Panel and Remote Wiring
Provide new Power Conversion Unit and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance with 24-Hour Call-Back Service
Sill Support Angles
Emergency Paging Speaker Installation
14220 - 5 Phase 2 Upgrade Elevator Upgrade
No Visible Company Name or Logo
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
Monitoring System incorporated into LIFTNET
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches
Locate upper hall pushbuttons maximum of 42 inches to centerline of pushbutton. Locate highest floor pushbutton in car station at maximum of 42 inches above floor
2.02 CAR PERFORMANCE
A. Car Speed: ± 3% of contract speed under any loading condition.
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Car 14: 1.9 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Car 14: 3.1 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-0” typical floor height):
1. Car 14: 11.2 seconds.
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating conditions. Not more than 20 mg peak to peak (adjacent peaks) in the 1 - 10 Hz range.
2. Acceleration and Deceleration: Smooth constant and not less than and not more than 3 feet/second² with an initial ramp between 0.5 and 0.75 second.
3. Sustained Jerk: Not more than 8 feet/second³.
14220 - 6 Phase 2 Upgrade Elevator Upgrade
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO 18738, using low pass cutoff frequency of 10 Hz and A95 peak-to-peak average calculations.
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
3.02 FINAL INSPECTION AND TEST
A. Comply with ASME A17.2-latest edition Inspectors’ Manual.
14220 - 7 Phase 2 Upgrade Elevator Upgrade Elevators 15, 16, 17
LB PROJECT NO. R0100002829
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY – TRACTION ELEVATOR EQUIPMENT
A. Three (3) Passenger Elevators
Number: Cars 15, 16, 17 Cars 15, 16, 17
Capacity: 4,000 lbs. 4,000 lbs.
Class Loading: Passenger Class A Retain Existing
Contract Speed: 500 F.P.M. 500 F.P.M.
Roping: 2:1 Retain Existing
Machine: Remove Existing Gearless Provide new permanent magnet gearless
Machine Location: Overhead Retain Existing location
Supervisory Control: Remove Existing Group Automatic System
Provide New Group Automatic Microprocessor-Based System
Motor Control: Remove existing DC Variable Voltage
Provide new AC Variable Voltage Variable Frequency Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 8 Phase 2 Upgrade Elevator Upgrade
Stops: 8 Front; 0 Rear Retain Existing
Openings: 8 Front; 0 Rear Retain Existing
Travel: 79’-0” ± Field Verify Retain Existing
Platform Size: 8’-0” Wide X 6’-3” Deep Field Verify
Retain Existing
Entrance Size: 4’-0” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Single Speed, Center Opening Retain Existing
Door Operation: Remove Existing Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
Provide New High Speed, Heavy- Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Infrared Device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Remove existing Flexible Guide Clamp – Type B, Car
Provide New Flexible Guide Clamp- Type B, Car
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Remove Existing – Oil Provide New – Oil
Compensation: Remove Existing Provide New Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New As Detailed On Architectural Drawings
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads Cars 15, 16, 17
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
14220 - 9 Phase 2 Upgrade Elevator Upgrade
Signal Fixtures: Provide New LED Illumination Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Dual Hall Pushbutton Riser Dual Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Dual Digital with Car Direction Arrows
Provide New Security Control Panel
Provide New Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors
Communication System:
Provide New Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Cars 15, 16, 17:
Provide New Car and Counterweight Roller Guides
Provide New Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
Standby Power Transfer (Automatic to Main Floor) with Manual Override in Firefighters’ Control Panel
14220 - 10 Phase 2 Upgrade Elevator Upgrade
Provide New Accessibility and Emergency Medical Services Signage
Swing Car Return Panel(s) Arranged for Integral Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Remove Existing car sling and platform. Provide New car sling and platform
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
Remove Existing Governor.
Provide New Governor.
Remove Existing entrances.
Provide New stainless steel entrances.
CCTV Provisions, All Cars
Provide New Security Control Panel and Remote Wiring
Provide New Firefighters’ Control Panel and Remote Wiring
Provide New Machine, Power Conversion Unit, and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance with 24-Hour Call-Back Service
Sill Support Angles
14220 - 11 Phase 2 Upgrade Elevator Upgrade
Installation
No Visible Company Name or Logo
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
Monitoring System incorporated into Liftnet
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches.
Located upper hall pushbutton to maximum 42 inches to carline of pushbutton. Located highest floor push button in car station at maximum of 42 inches above floor.
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Cars 15, 16, 17: 1.6 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Cars 15, 16, 17: 2.5 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-6” typical floor height):
1. Cars 15, 16, 17: 8.5 seconds.
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating conditions. Not more than 20 mg peak to peak (adjacent peaks) in the 1 - 10 Hz range.
14220 - 12 Phase 2 Upgrade Elevator Upgrade
2. Acceleration and Deceleration: Smooth constant and not less than and not more
3. Sustained Jerk: Not more than 8 feet/second³.
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO
18738, using low pass cutoff frequency of 10 Hz and A95 peak-to-peak average calculations.
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
14220 - 13 Phase 2 Upgrade Elevator Upgrade Elevators 18, 19, 20, 21
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY – TRACTION ELEVATOR EQUIPMENT
A. Four (4) Passenger Elevators
Number: Cars 18, 19, 20, 21 Cars 18, 19, 20, 21
Capacity: 4,000 lbs. 4,000 lbs.
Class Loading: Passenger Class A Retain Existing
Contract Speed: 500 F.P.M. 500 F.P.M.
Roping: 2:1 Retain Existing
Machine: Remove Existing Gearless Provide new permanent magnet gearless
Machine Location: Overhead Retain Existing location
Supervisory Control: Remove Existing Group Automatic System
Provide New Group Automatic Microprocessor-Based System
Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 14 Phase 2 Upgrade Elevator Upgrade
Openings: 9 Front; 0 Rear Retain Existing
Travel: 96’-0” ± Field Verify Retain Existing
Platform Size: 8’-0” Wide X 6’-2” Deep Field Verify
Retain Existing
Entrance Size: 4’-0” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Single Speed, Center Opening Retain Existing
Door Operation: Remove Existing Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
Provide New High Speed, Heavy- Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Infrared Device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Remove existing Flexible Guide Clamp – Type B, Car
Provide New Flexible Guide Clamp- Type B, Car
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Remove Existing – Oil Provide New – Oil
Compensation: Remove Existing Provide New Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New As Detailed On Architectural Drawings
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads Cars 18, 19, 20, 21
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
14220 - 15 Phase 2 Upgrade Elevator Upgrade
Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Dual Hall Pushbutton Riser Dual Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Dual Digital with Car Direction Arrows
Provide New Security Control Panel
Provide New Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors
Communication System:
Provide New Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Cars 18, 19, 20, 21
Provide New Car and Counterweight Roller Guides
Provide New Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
Standby Power Transfer (Automatic
14220 - 16 Phase 2 Upgrade Elevator Upgrade
Emergency Medical Services Signage
Swing Car Return Panel(s) Arranged for Integral Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Remove Existing car sling and platform. Provide New car sling and platform
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
Priority Service, Cars 18, 19, 20, 21
Remove Existing Governor.
Provide New Governor.
Remove Existing entrances.
Provide New stainless steel entrances.
CCTV Provisions, All Cars
Provide New Security Control Panel and Remote Wiring
Provide New Firefighters’ Control Panel and Remote Wiring
Provide New Machine, Power Conversion Unit, and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance
14220 - 17 Phase 2 Upgrade Elevator Upgrade
Emergency Paging Speaker Installation
No Visible Company Name or Logo
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
Monitoring System incorporated into Liftnet
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches.
Located upper hall pushbutton to maximum 42 inches to carline of pushbutton. Located highest floor
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Cars 18, 19, 20, 21: 1.7 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Cars 18, 19, 20, 21: 2.7 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-0” typical floor height):
1. Cars 18, 19, 20, 21: 8.5 seconds.
14220 - 18 Phase 2 Upgrade Elevator Upgrade
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating conditions. Not more than 20 mg peak to peak (adjacent peaks) in the 1 - 10 Hz range.
2. Acceleration and Deceleration: Smooth constant and not less than and not more than 3 feet/second² with an initial ramp between 0.5 and 0.75 second.
3. Sustained Jerk: Not more than 8 feet/second³.
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO
18738, using low pass cutoff frequency of 10 Hz and A95 peak-to-peak average calculations.
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
14220 - 19 Phase 2 Upgrade Elevator Upgrade Elevator 22
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY – TRACTION ELEVATOR EQUIPMENT
A. One (1) Passenger Elevator
Number: Car 22 Car 22
Capacity: 2,500 lbs. 2,500 lbs.
Class Loading: Passenger Class A Retain Existing
Contract Speed: 500 F.P.M. 500 F.P.M.
Roping: 2:1 Retain Existing
Machine: Remove Existing Gearless Provide new permanent magnet gearless
Machine Location: Overhead Retain Existing location
Operational Control: Remove Existing Selective Collective
Provide New Selective Collective Microprocessor-Based System
Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 20 Phase 2 Upgrade Elevator Upgrade
Openings: 9 Front; 0 Rear Retain Existing
Travel: 96’-0” ± Field Verify Retain Existing
Platform Size: 6’-6” Wide X 4’-4” Deep Field Verify
Retain Existing
Entrance Size: 3’-6” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Single Speed, Center Opening Single Speed, Center Opening
Door Operation: Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
Provide New High Speed, Heavy- Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Infrared Device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Remove existing Flexible Guide Clamp – Type B, Car
Provide New Flexible Guide Clamp- Type B, Car
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Remove Existing – Oil Provide New – Oil
Compensation: Remove Existing Provide New Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New As Detailed On Architectural Drawings
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
14220 - 21 Phase 2 Upgrade Elevator Upgrade
Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Single Hall Pushbutton Riser Dual Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Dual Digital with Car Direction Arrows
Provide New Security Control Panel
Provide New Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors
Communication System:
Provide New Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Car 22:
Provide New Car and Counterweight Roller Guides
Provide New Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
Standby Power Transfer (Automatic
14220 - 22 Phase 2 Upgrade Elevator Upgrade
Emergency Medical Services Signage
Swing Car Return Panel(s) Arranged for Integral Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Remove Existing car sling and platform. Provide New car sling and platform
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
Remove Existing Governor.
Provide New Governor.
Remove Existing entrances.
Provide New stainless steel entrances.
CCTV Provisions, All Cars
Provide New Security Control Panel and Remote Wiring
Provide New Firefighters’ Control Panel and Remote Wiring
Provide New Machine, Power Conversion Unit, and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance
14220 - 23 Phase 2 Upgrade Elevator Upgrade
Installation
No Visible Company Name or Logo
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
Monitoring System incorporated into Liftnet
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches.
Located upper hall pushbutton to maximum 42 inches to carline of pushbutton. Located highest floor
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Car 22: 1.6 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Car 22: 2.5 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-0” typical floor height):
1. Car 22: 8.0 seconds.
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating
14220 - 24 Phase 2 Upgrade Elevator Upgrade
3. Sustained Jerk: Not more than 8 feet/second³.
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO
18738, using low pass cutoff frequency of 10 Hz and A95 peak-to-peak average calculations.
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
14220 - 25 Phase 2 Upgrade Elevator Upgrade Elevator 23
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY
Number: Car 23 Car 23
Capacity: 8,000 lbs. 8,000 lbs.
Class Loading: Service Class C Retain Existing
Contract Speed: 200 F.P.M. 200 F.P.M.
Roping: 1:1 Retain Existing
Machine: Geared Retain Existing
Machine Location: Overhead Retain Existing
Operational Control: Remove Existing Selective Collective
Provide New Selective Collective Microprocessor-Based System
Motor Control: Remove existing DC Variable Voltage
Provide new AC Variable Voltage Variable Frequency Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 26 Phase 2 Upgrade Elevator Upgrade
Openings: 9 Front; 0 Rear Retain Existing
Travel: 96’-0” ± Field Verify Retain Existing
Platform Size: 8’-3” Wide X 11’-7” Deep Field Verify
Retain Existing
Entrance Size: 5’-0” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Two Speed, Center Opening Retain Existing
Door Operation: Remove existing Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
Provide New High Speed, Heavy- Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Infrared Device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Remove existing Clamp Flexible Guide Clamp – Type B, Car
Provide new Flexible Guide Clamp- Type B, Car
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Oil Retain Existing
Compensation: Provide new Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
14220 - 27 Phase 2 Upgrade Elevator Upgrade
Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Single Hall Pushbutton Riser Single Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Single Digital with Car Direction Arrows
Provide new Security Control Panel
Provide new Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors, Vandal Resistant Assembly
Communication System:
Provide new Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Car 23:
Provide new Car and Counterweight Swivel Slide Type Guides
Provide new Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
Standby Power Transfer (Automatic
14220 - 28 Phase 2 Upgrade Elevator Upgrade
Provide new Accessibility and Emergency Medical Services Signage
Stationary Car Return Panel(s) Arranged for Surface Applied Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Platform Isolation
Remove existing governor. Provide new governor.
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
CCTV Provisions, All Cars
Provide new Security Control Panel and Remote Wiring
Provide new Firefighters’ Control Panel and Remote Wiring
Provide new Power Conversion Unit, and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance with 24-Hour Call-Back Service
Sill Support Angles
Emergency Paging Speaker
14220 - 29 Phase 2 Upgrade Elevator Upgrade
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
Monitoring System incorporated into LIFTNET
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches
Locate upper hall pushbuttons maximum of 42 inches to centerline of pushbutton. Locate highest floor
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Car 23: 1.9 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Car 23: 3.1 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-0” typical floor height):
1. Car 23: 11.2 seconds.
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating conditions. Not more than 20 mg peak to peak (adjacent peaks) in the 1 - 10 Hz range.
2. Acceleration and Deceleration: Smooth constant and not less than and not more
14220 - 30 Phase 2 Upgrade Elevator Upgrade calculations.
H. Noise and Vibration Control
1. Airborne Noise: Measured noise level of elevator equipment and its operation shall not exceed 60 dBA inside car under any condition including door operation and car ventilation exhaust blower on its highest speed. Limit noise level in the machine room relating to elevator equipment and its operation to no more than 80 dBA. All dBA readings to be taken 3'-0" off the floor and 3'-0" from the equipment using the “A” weighted scale.
2. Vibration Control: All elevator equipment provided under this contract, including power unit, controller, oil supply lines, and their support shall be mechanically isolated from the building structure and electrically isolated from the building power supply and to each other to minimize the possibility of objectionable noise and vibrations being transmitted to occupied areas of the building.
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
14220 - 31 Phase 2 Upgrade Elevator Upgrade Elevator 24
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY – TRACTION ELEVATOR EQUIPMENT
Number: Car 24 Car 24
Capacity: 2,500 lbs. 2,500 lbs.
Class Loading: Passenger Class A Retain Existing
Contract Speed: 500 F.P.M. 500 F.P.M.
Roping: 2:1 Retain Existing
Machine: Remove Existing Gearless Provide new permanent magnet gearless
Machine Location: Overhead Retain Existing location
Operational Control: Remove Existing Selective Collective
Provide New Selective Collective Microprocessor-Based System
Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 32 Phase 2 Upgrade Elevator Upgrade
Openings: 9 Front; 0 Rear Retain Existing
Travel: 96’-0” ± Field Verify Retain Existing
Platform Size: 6’-6” Wide X 4’-4” Deep Field Verify
Retain Existing
Entrance Size: 3’-6” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Single Speed, Center Opening Single Speed, Center Opening
Door Operation: Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
Provide New High Speed, Heavy- Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Infrared Device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Remove existing Flexible Guide Clamp – Type B, Car
Provide New Flexible Guide Clamp- Type B, Car
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Remove Existing – Oil Provide New – Oil
Compensation: Remove Existing Provide New Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New As Detailed On Architectural Drawings
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads Car 24
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
14220 - 33 Phase 2 Upgrade Elevator Upgrade
Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Single Hall Pushbutton Riser Dual Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Dual Digital with Car Direction Arrows
Provide New Security Control Panel
Provide New Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors
Communication System:
Provide New Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Car 24:
Provide New Car and Counterweight Roller Guides
Provide New Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
Standby Power Transfer (Automatic
14220 - 34 Phase 2 Upgrade Elevator Upgrade
Emergency Medical Services Signage
Swing Car Return Panel(s) Arranged for Integral Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Remove Existing car sling and platform. Provide New car sling and platform
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
Remove Existing Governor.
Provide New Governor.
Remove Existing entrances.
Provide New stainless steel entrances.
CCTV Provisions, All Cars
Provide New Security Control Panel and Remote Wiring
Provide New Firefighters’ Control Panel and Remote Wiring
Provide New Machine, Power Conversion Unit, and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance
14220 - 35 Phase 2 Upgrade Elevator Upgrade
Installation
No Visible Company Name or Logo
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
Monitoring System incorporated into Liftnet
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches.
Located upper hall pushbutton to maximum 42 inches to carline of pushbutton. Located highest floor
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Car 24: 1.6 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Car 24: 2.5 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-0” typical floor height):
1. Car 24: 8.0 seconds.
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating
14220 - 36 Phase 2 Upgrade Elevator Upgrade
3. Sustained Jerk: Not more than 8 feet/second³.
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO
18738, using low pass cutoff frequency of 10 Hz and A95 peak-to-peak average calculations.
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
14220 - 37 Phase 2 Upgrade Elevator Upgrade Elevators 25, 26, 27, 28
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY – TRACTION ELEVATOR EQUIPMENT
A. Four (4) Passenger Elevators
Number: Cars 25, 26, 27, 28 Cars 25, 26, 27, 28
Capacity: 4,000 lbs. 4,000 lbs.
Class Loading: Passenger Class A Retain Existing
Contract Speed: 500 F.P.M. 500 F.P.M.
Roping: 2:1 Retain Existing
Machine: Remove Existing Gearless Provide new permanent magnet gearless
Machine Location: Overhead Retain Existing location
Supervisory Control: Remove Existing Group Automatic System
Provide New Group Automatic Microprocessor-Based System
Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 38 Phase 2 Upgrade Elevator Upgrade
Openings: 9 Front; 0 Rear Retain Existing
Travel: 96’-0” ± Field Verify Retain Existing
Platform Size: 8’-0” Wide X 6’-2” Deep Field Verify
Retain Existing
Entrance Size: 4’-0” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Single Speed, Center Opening Retain Existing
Door Operation: Remove Existing Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
Provide New High Speed, Heavy- Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Remove Existing infrared device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Remove existing Flexible Guide Clamp – Type B, Car
Provide New Flexible Guide Clamp- Type B, Car
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Remove Existing – Oil Provide New – Oil
Compensation: Remove Existing Provide New Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New As Detailed On Architectural Drawings
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
14220 - 39 Phase 2 Upgrade Elevator Upgrade
Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Dual Hall Pushbutton Riser Dual Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Dual Digital with Car Direction Arrows
Provide New Security Control Panel
Provide New Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors
Communication System:
Provide New Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Cars 25, 26, 27, 28
Provide New Car and Counterweight Roller Guides
Provide New Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
Standby Power Transfer (Automatic
14220 - 40 Phase 2 Upgrade Elevator Upgrade
Emergency Medical Services Signage
Swing Car Return Panel(s) Arranged for Integral Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Remove Existing car sling and platform. Provide New car sling and platform
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
Priority Service, Cars 25, 26, 27, 28
Remove Existing Governor.
Provide New Governor.
Remove Existing entrances.
Provide New stainless steel entrances.
CCTV Provisions, All Cars
Provide New Security Control Panel and Remote Wiring
Provide New Firefighters’ Control Panel and Remote Wiring
Provide New Power Conversion Unit, and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance
14220 - 41 Phase 2 Upgrade Elevator Upgrade
Emergency Paging Speaker Installation
No Visible Company Name or Logo
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
Monitoring System incorporated into Liftnet
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches.
Located upper hall pushbutton to maximum 42 inches to carline of pushbutton. Located highest floor
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Cars 25, 26, 27, 28: 1.7 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Cars 25, 26, 27, 28: 2.7 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-0” typical floor height):
1. Cars 25, 26, 27, 28: 8.5 seconds.
14220 - 42 Phase 2 Upgrade Elevator Upgrade
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating conditions. Not more than 20 mg peak to peak (adjacent peaks) in the 1 - 10 Hz range.
2. Acceleration and Deceleration: Smooth constant and not less than and not more than 3 feet/second² with an initial ramp between 0.5 and 0.75 second.
3. Sustained Jerk: Not more than 8 feet/second³.
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO
18738, using low pass cutoff frequency of 10 Hz and A95 peak-to-peak average calculations.
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
14220 - 43 Phase 2 Upgrade Elevator Upgrade Elevators 29, 30
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY – TRACTION ELEVATOR EQUIPMENT
A. Two (2) Passenger Elevators
Number: Cars 29, 30 Cars 29, 30
Capacity: 3,500 lbs. 3,500 lbs.
Class Loading: Passenger Class A Retain Existing
Contract Speed: 600 F.P.M. 600 F.P.M.
Roping: 2:1 Retain Existing
Machine: Gearless Retain Existing
Machine Location: Overhead Retain Existing
Operational Control: Remove Existing Pushbutton Duplex Selective Collective
Provide New Duplex Selective Collective Microprocessor-Based System
Provide new DC Variable Voltage
Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 44 Phase 2 Upgrade Elevator Upgrade
Openings: 8 Front; 0 Rear Retain Existing
Travel: 79’-0” ± Field Verify Retain Existing
Platform Size: 7’-0” Wide X 6’-3” Deep Field Verify
Retain Existing
Entrance Size: 3’-6” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Single Speed, Center Opening Retain Existing
Door Operation: Medium Speed, Heavy-Duty Door Operator, Minimum Opening Speed 1-1/2 F.P.S.
High Speed, Heavy-Duty, Door Operator, Minimum Opening Speed 2-1/2 F.P.S.
Door Protection: Remove Existing Infrared Device Provide new 3-Dimensional Infrared, Full Screen Device with Differential Timing, Nudging and Interrupted Beam Time
Safety: Flexible Guide Clamp – Type B, Car
Retain Existing
Guide Rails: Planed Steel Tees Retain Existing
Buffers: Oil Oil – Retain Existing
Compensation: Remove Existing Provide New Encapsulated Chain with Pit Guide
Car Enclosure: Remove Existing Provide New As Detailed On Architectural Drawings
Car Interior Finishes Provided Under This Section
Pad Buttons and Vinyl Covered Pads Cars 29, 30
Battery Powered Emergency Car Lighting. Provide Separate Constant Pressure Test Button In Car Service Compartment.
14220 - 45 Phase 2 Upgrade Elevator Upgrade
Contractor’s Custom Design Vandal Resistant Assembly
Hall and Car Pushbutton Stations:
Single Hall Pushbutton Riser Dual Car Operating Panel(s)
Vandal Resistant Car and Hall Pushbuttons
Car Position Indicators:
Dual Digital with Car Direction Arrows
Provide New Security Control Panel
Provide New Firefighters’ Control Panel
Hall Lanterns: At All Floors with Volume Adjustable Electronic Chime or Tone. Sound Twice for Down Direction
Hall Car Position Indicator:
Digital with Car Direction Arrows at All Floors
Communication System:
Provide New Self-Dialing, Vandal Resistant, Push to Call, Two-Way Communication System with Recall, Tracking and Voiceless Communication
Fixture Submittal: Submit Brochure Depicting Contractor’s Proposed Designs with Bid
Additional Features, Cars 29, 30
Provide New Car and Counterweight Roller Guides
Provide New Car Top Inspection Station
Firefighters’ Service, Phase I and II, including Alternate Floor Return
Standby Power Transfer (Automatic
14220 - 46 Phase 2 Upgrade Elevator Upgrade
Emergency Medical Services Signage
Swing Car Return Panel(s) Arranged for Integral Car Operating Panel(s)
Hoistway Access Switches, Top And Bottom Floors
Hoistway Door Unlocking Device, All Floors
Platform Isolation
Load-Weighing Device
Anti-Nuisance Feature
Independent Service Feature
CCTV Provisions, All Cars
Provide New Security Control Panel and Remote Wiring
Provide New Firefighters’ Control Panel and Remote Wiring
Provide New Machine, Power Conversion Unit, and Controller Sound Isolation
Tamper Resistant Fasteners for All Fastenings Exposed to the Public
One Year Warranty Maintenance with 24-Hour Call-Back Service
Sill Support Angles
Emergency Paging Speaker Installation
No Visible Company Name or Logo
Wiring Diagrams, Operating Instructions, and Parts Ordering Information
14220 - 47 Phase 2 Upgrade Elevator Upgrade
Monitoring System incorporated into Liftnet
Non-Proprietary Control System and Diagnostics Provisions
All elevator keyswitches will be keyed similar to the existing elevator in the building. “Northeast” brand keyswitches.
Located upper hall pushbutton to maximum 42 inches to carline of pushbutton. Located highest floor
B. Car Capacity: Safely lower, stop and hold 125% of rated load.
C. Car Stopping Zone: ±1/4" under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully open:
1. Cars 29, 30: 1.6 seconds.
E. Door Closing Time: Seconds from start of closing to fully closed:
1. Cars 29, 30: 2.5 seconds.
F. Car Floor-to-Floor Performance Time: Seconds from start of doors closing until doors are 3/4 open (1/2 open for side opening doors) and car stopped at next successive floor under any loading condition or travel direction (12’-0” typical floor height):
1. Cars 29, 30: 8.0 seconds.
G. Car Ride Quality
1. Horizontal and vertical acceleration within car during all riding and door operating conditions. Not more than 20 mg peak to peak (adjacent peaks) in the 1 - 10 Hz range.
2. Acceleration and Deceleration: Smooth constant and not less than and not more than 3 feet/second² with an initial ramp between 0.5 and 0.75 second.
3. Sustained Jerk: Not more than 8 feet/second³.
4. Measurement Standards: Measure and evaluate ride quality consistent with ISO calculations.
14220 - 48 Phase 2 Upgrade Elevator Upgrade
PART 3 EXECUTION
3.01 INSTALLATION
A. Comply with applicable codes, manufacturer’s instructions, shop drawings, and recommendations. Comply with National Electrical Code (ASME C1 by NFPA) for electrical work required during construction.
14220 - 49 Phase 2 Upgrade Elevator Upgrade Elevator 31
PART 1 GENERAL
1.01 QUALITY ASSURANCE
A. All work shall be performed in accordance with the latest edition of the “American Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks” (ASME A17.1), including published supplements; “National Electrical Code,” “OSHA,” “NFPA,” “UBC,” A.D.A. Handicapped Code, and such state and local codes as may be applicable.
PART 2 PRODUCTS
2.01 SUMMARY
Number: Car 31 Car 31
Capacity: 8,000 lbs. 8,000 lbs.
Class Loading: Service Class C Retain Existing
Contract Speed: 200 F.P.M. 200 F.P.M.
Roping: 1:1 Retain Existing
Machine: Geared Retain Existing
Machine Location: Overhead Retain Existing
Operational Control: Remove Existing Selective Collective
Provide New Selective Collective Microprocessor-Based System
Motor Control: Remove existing DC Variable Voltage
Provide new AC Variable Voltage Variable Frequency Microprocessor Based with Digital Closed-Loop Feedback
Power Characteristics: 480 Volts, 3 Phase, 60 Hertz
14220 - 50 Phase 2 Upgrade Elevator Upgrade
Openings: 9 Front; 0 Rear Retain Existing
Travel: 96’-0” ± Field Verify Retain Existing
Platform Size: 8’-3” Wide X 11’-7” Deep Field Verify
Retain Existing
Entrance Size: 5’-0” Wide X 7’-0” High Field Verify
Retain Existing
Entrance Type: Two Speed, Center Opening Retain Existing
Door Operation: Remove existing Medium Speed, Heavy-Duty Door…