03.7 Drawing Fire Alarm Ph3.pdf

PDF 3 MB Posted

Attached to
Repair Operations & Training Facility Federal contract opportunity
Solicitation number
W50S8H23B0001
Issued by
Department of the Army New York Army National Guard

About this file

This solicitation is for a construction contract to renovate a two-story, 43,029 square foot Operations and Training Facility at Niagara Falls International Airport in New York. The project magnitude is estimated between $10 million and $25 million. This competitive 8(a) small business set-aside solicitation is seeking bids for repair and construction work in accordance with the provided specifications. The North American Industry Classification code is 236220 and the size standard for small businesses is average annual revenue of $45 million for the past three years. Bids are due by the date specified in the solicitation, with award to be made to the responsible bidder offering the most advantageous price. Funding is not currently available but is expected to be appropriated by 30 September 2023. The soliciting agency is the Department of the Army New York Army National Guard.

View the file

Other files for this federal contract opportunity

Other files attached to Repair Operations & Training Facility, newest first.
File Type Posted
C4 Abstract OF1419.pdf PDF
C4 Bid Opening Sign-In.pdf PDF
Consolidated RFI List.xlsx XLSX spreadsheet
B6 Hazardous Material Report.pdf PDF
B8 W50S8H-23-B-0001 IFB-P00001.pdf PDF
B8 W50S8H-23-B-0001 IFB-P00001 Amend.pdf PDF
B7 Site Visit Sign-In.pdf PDF
B7 Pre-Bid Conference Slides Final.pptx PPTX presentation
01.3 Drawing Mechanical Ph1.pdf PDF
03.1 Drawing Civil Storm Ph3.pdf PDF
03.3 Drawing Structural Ph3.pdf PDF
03.10 Drawing Electrical Ph3.pdf PDF
H8 Specs.pdf PDF
01.1 Drawing Architectural Ph1.pdf PDF
01.4 Drawing Electrical Ph1.pdf PDF
02.2 Drawing Architectural Ph2.pdf PDF
03.08 Drawing Plumbing Ph3.pdf PDF
01.2 Drawing Plumbing Ph1.pdf PDF
02.1 Drawing Architectural Demo Ph2.pdf PDF
03.2 Drawing Civil Utility Ph3.pdf PDF
03.4 Drawing Architectural Demo Ph3.pdf PDF
03.6 Drawing Fire Protection Ph3.pdf PDF
03.11 Drawing Telecom Ph3.pdf PDF
03.12 Drawing Reference Drawings Ph3.pdf PDF
A2 JA FAR Part 6 Advantor SAM Post.pdf PDF
B8 W50S8H-23-B-0001 IFB.pdf PDF
01.0 Drawing General.pdf PDF
03.5 Drawing Architectural Ph3.pdf PDF
03.09 Drawing Mechanical Ph3.pdf PDF
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH UFC 1-200-01, "GENERAL BUILDING REQUIREMENTS", NOVEMBER 2018 CHANGE 2; UFC 3-600-01, "FIRE PROTECTION ENGINEERING FOR FACILITIES", MAY 2019 CHANGE 3; UFC 4-021-01 "DESIGN AND O&M: MASS NOTIFICATION SYSTEMS", JANUARY 2010 CHANGE 1; ECB 2018-17 "NEW REQUIREMENTS FOR VISUAL NOTIFICATION FOR MASS NOTIFICATION SYSTEMS", OCTOBER 2018; UFC 4-010-01, "DOD MINIMUM ANTITERRORISM STANDARD FOR BUILDINGS"; DECEMBER 2018; INTERNATIONAL BUILDING CODE (IBC) 2018 EDITION; NFPA 1, "FIRE CODE", 2018 EDITION;

NFPA 70, "NATIONAL ELECTRICAL CODE", 2017 EDITION; NFPA 72, "NATIONAL FIRE ALARM AND SIGNALING CODE", 2019 EDITION;

NFPA 101, "LIFE SAFETY CODE" 2018 EDITION; NFPA 241, "SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS" 2019 EDITION; NFPA 2001, "STANDARD ON CLEAN AGENT FIRE EXTINGUISHING SYSTEMS" 2018 EDITION. UFC SHALL

TAKE PRECEDENCE OVER NFPA REQUIREMENTS.

FIRE ALARM & MASS NOTIFICATION, AND CLEAN AGENT FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, NFPA 2001, AND SYSTEM MANUFACTURER

REQUIREMENTS AND RECOMMENDATIONS.

CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID WITH THE PROJECT DOCUMENTS AND SPECIFICATIONS TO BECOME FAMILIAR WITH THE SITE AND SCOPE OF WORK. NOTIFY ENGINEER OF RECORD WITH ANY DISCREPANCIES OUTSIDE THIS DESIGN INTENT. ANY CHANGE ORDER REQUEST AS A RESULT OF LACK OF COORDINATION BETWEEN TRADES SHALL BE DENIED.

ADHERE TO AND OBTAIN ALL PERMITS, LICENSES, AND ALL FEDERAL GOVERNMENT REQUIREMENTS.

DO NOT SCALE PLANS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS. FIELD DIMENSIONS GOVERN.

FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE PARTITIONS. FIRE STOPPING SHALL BE OF UL LISTED ASSEMBLY.

1.

2.

3.

4.

5.

6.

GENERAL NOTES

ADDRESSABLE MANUAL PULL STATION

VALVE SUPERVISORY SWITCH

WATER FLOW DETECTOR/SWITCH

MONITOR MODULE

FIRE ALARM AND MASS NOTIFICATION

CONTROL PANEL - SEMI-RECESSED

CONTROL MODULE

FMCP

F

MM

CM

FIRE ALARM BATTERY

CABINET - SEMI-RECESSED

BATT

CONTRACTOR SHALL SUBMIT COMPLETE BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS, MATERIAL DATA SHEETS, AND SHOP DRAWINGS TO OWNER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING FABRICATION AND INSTALLATION. FAILURE TO COMPLY IS AT THE RISK OF THE CONTRACTOR.

ALL AREAS OF THE BUILDING MUST ACHIEVE A CIS SCORE OF 0.8. BUILDING OCCUPANTS MUST BE ABLE TO WALK NOT MORE THAN 33 FEET TO FIND A LOCATION WITH A CIS SCORE OF 0.8. AREAS WITH HARD WALL, FLOOR, AND CEILING

SURFACES ARE PERMITTED TO HAVE CIS SCORE LESS THAN 0.8.

FIRE ALARM SIGNALS AND EMERGENCY COMMUNICATIONS SHALL TAKE PRECEDENCE OVER ALL OTHER SIGNALS, SUCH AS

BUT NOT LIMITED TO PUBLIC ADDRESS SYSTEMS.

ALL NOTIFICATION APPLIANCES CIRCUITS (NAC) SHALL PERFORM TO CLASS "B" AS DEFINED BY NFPA 72.

ALL SIGNALING LINE CIRCUITS (SLC) SHALL PERFORM TO CLASS "B" AS DEFINED BY NFPA 72.

ALL INDICATING DEVICE CIRCUITS SHALL PERFORM TO CLASS "B" AS DEFINED BY NFPA 72.

THE INSTALLATION OF WIRING BETWEEN THE FMCP AND RELAY MODULES OR APPLIANCES SHALL PERFORM TO CLASS "B"

AS DEFINED BY NFPA 72.

CONDUCTORS FOR THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70. THE CONDUCTORS SHALL NOT BE INSTALLED WITH CONDUCTORS OF LIGHTING OR POWER SYSTEMS. THE SUM OF THE CROSS-AREA OF INDIVIDUAL CONDUCTORS SHALL NOT EXCEED 40% OF THE INTERIOR CROSS SECTION OF THE CONDUIT. NEW FIRE ALARM SYSTEM CONDUIT SHALL BE INSTALLED IN SEPARATE CONDUIT AND SHALL BE A MINIMUM 3/4".

WALL MOUNTED FIRE ALARM DEVICES IN UNFINISHED AREAS MAY BE SURFACED MOUNTED, THE CONDUIT MAY BE

INSTALLED EXPOSED ON WALLS AND ON CEILINGS.

IN FINISHED AREAS, WALL MOUNTED DEVICES SHALL BE FLUSH MOUNTED. THE CONDUIT SHALL BE INSTALLED CONCEALED

IN THE WALLS AND CEILINGS UNLESS REFERENCED AS CEILING MOUNTED.

FIRE ALARM CONTRACTOR SHALL COORDINATE WITH FIRE ALARM VENDOR FOR SYSTEM OPERATING INSTRUCTIONS AND

WIRING DIAGRAMS.

FIRE ALARM MANUAL PULL STATIONS AT DOOR OPENINGS SHALL BE WITHIN 5' - 0" HORIZONTALLY OF THE DOOR OPENING.

PROVIDE SYNCHRONIZATION FOR ALL NEW VISIBLE (STROBE) NOTIFICATION APPLIANCES WHERE THERE ARE MORE THAN TWO DEVICES IN THE SAME ROOM OR IN AN ADJACENT SPACE WITHIN THE FIELD OF VIEW TO COMPLY WITH THE

REQUIREMENTS OF NFPA 72.

PROVIDE SYNCHRONIZATION FOR ALL NEW AUDIBLE (SPEAKER) NOTIFICATION APPLIANCES WITHIN A NOTIFICATION ZONE

TO COMPLY WITH THE REQUIREMENTS OF NFPA 72.

PROVIDE TRANSIENT VOLT SURGE SUPPRESSION DEVICE WHERE CIRCUITS PENETRATE THE BUILDING ENVELOPE AND, FIRE ALARM EQUIPMENT SUPPLIED FROM THE BUILDING ELECTRICAL SYSTEM, (I.E DOOR HOLDERS, NAC BOOSTER PANELS, ETC), IN ACCORDANCE WITH NFPA 70 AND NFPA 72 REQUIREMENTS.

STROBE FOR VISUAL FIRE ALARM/MASS NOTIFICATION APPLIANCES SHALL HAVE WHITE/ CLEAR LENS AND BE LABELED

"ALERT" .

INSTALL SMOKE DETECTORS NO CLOSER THAN 3' - 0" TO HVAC AIR SUPPLY DIFFUSERS.

ALL FIRE ALARM PANELS AND EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH NFPA 70 ARTICLE 250 AND 800 WITH

A MAXIMUM OF 25 OHMS RESISTANCE.

CONTRACTOR SHALL PROVIDE A DOCUMENTATION CABINET AT THE SYSTEM CONTROL UNIT IN THE BUILDING WITH ALL REQUIRED DOCUMENTATION AND SOFTWARE REQUIRED BY NFPA 72 SECTIONS 7.7.2 AND 23.2.2.

CONTRACTOR SHALL PROVIDE PATHWAY SURVIVABILITY OF LEVEL 1 IN ACCORDANCE WITH NFPA 72.

DEMOLISH EXISTING FIRE ALARM AND OCCUPANT NOTIFICATION SYSTEM IN ITS ENTIRETY. REFERENCE FD DRAWINGS.

REFER TO FIRE ALARM SYSTEM SPECIFICATION 28 31 76 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

FIRE ALARM/MASS NOTIFICATION CLEAR

VISUAL STROBE. WALL MOUNTED.

FIRE ALARM/MASS NOTIFICATION CLEAR

VISUAL STROBE AND SPEAKER.

C = CEILING MOUNTED DEVICE

WP = WEATHER PROOF

P = PRE -DISCHARGE ALARM

D = DISCHARGE ALARM

SURGE SUPPRESSOR

FIRE ALARM & MASS NOTIFICATION NOTES

RELAY MODULERM

VS

WF

SS

C

WP

LED TEXT SIGN

FIRE ALARM & MASS NOTIFICATION LEGEND

LED

M

MASS NOTIFICATION SPEAKER.

WP=WEATHER PROOF

WP

FIRE ALARM DUCT MOUNTED

PHOTOELECTRIC SMOKE DETECTOR

R = RETURN

S= SUPPLY

SMOKE DETECTOR-PHOTOELECTRIC

ER=ELEVATOR RECALL

US=ULTRA SENSITIVE SMOKE DETECTOR

S

S

REMOTE ALARM INDICATION

AND TESTING SWITCH

R/S

RTS

NAC EXTENDER PANEL - SEMI-RECESSEDNAC

CLEAN AGENT FIRE SUPPRESSION

STORAGE TANK

LOCAL OPERATING CONSOLE -

SEMI-RECESSED

LOC

CARBON MONOXIDE DETECTOR

DACT DIGITAL ALARM COMMUNICATOR

TRANSMITTER CARD

CO

CA

CACP CLEAN AGENT RELEASING PANEL

SOV

SOLENOID VALVE

PRESSURE SWITCHPS

CLEAN AGENT MANUAL PULL STATION

MOUNT 42" - 48" AFF

CA

CLEAN AGENT ABORT SWITCH

MOUNT 42" - 48" AFF

CA

1. CONTRACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS WITH DESIGN CALCULATIONS AND PRODUCT DATA FOR EACH TYPE OF PRODUCT, TO OWNER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING FABRICATION AND

INSTALLATION. FAILURE TO COMPLY IS AT THE RISK OF THE CONTRACTOR.

2. PROVIDE CLEAN AGENT NOTIFICATION APPLIANCES WITH SIGNAGE LABELING APPLIANCES FOR PRE-DISCHARGE AND

DISCHARGE AS INDICATED IN SECTION 3.1.1 OF THE CLEAN AGENT SPECIFICATION.

3. CLEAN AGENT SYSTEM LAYOUT AND DESIGN SHALL BE PERFORMED AND CALCULATED IN ACCORDANCE WITH NFPA 2001, AND MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS. VOLUME OF DISCHARGE SHALL INCLUDE THE AREA

UNDER THE RAISED FLOOR (DATA CENTER-128).

4. SEE PLAN DRAWINGS FOR DEVICE QUANTITIES. CLEAN AGENT RISER DIAGRAM IS DIAGRAMMATIC AND NOT INTENDED TO

SHOW EACH COMPONENT, DEVICE, APPLIANCE, ETC.

5. LOCATE CONTROL/ RELAY MODULE WITHIN 3'-0" OF CONTROL DEVICE.

6. CONTRACTOR SHALL PROVIDE ALL NECESSARY AND REQUIRED SYSTEM PROGRAMMING TO MEET THE DESIGN INTENT AND

CODE COMPLIANCE.

7. BREAKER SERVING THE CLEAN AGENT RELEASING PANEL SHALL BE PAINTED RED AND PROVIDED WITH A NON-SWEEP

DEVICE (LOCK).

8. THE CLEAN AGENT PANEL SHALL IDENTIFY THE ELECTRICAL PANEL WHERE THE CLEAN AGENT CIRCUIT BREAKER IS

LOCATED.

9. REFER TO CLEAN AGENT SYSTEM SPECIFICATIONS 21 22 00.00 40 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.

CLEAN AGENT NOTES

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u it e

P

O B o x

S y ra c u s e

N Y

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:2

:0

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a c ili ty /1

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v

.r v t

FA001

100% B3 SUBMITTAL

F

IR

E A

L A

R M

M

A S

S N

O T

IF

IC

A T

IO

N

L E

G E

N D

A N

D G

E N

E R

A L N

O T

E S

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

A p p ro v e r

N D

S

N D

S

B T

H

M

A R

C H

1 2 4 6 7 8 9 16

12' 13'10' 15'

A

B

D

C

E

L'

K'

J'

H'

G'

F'

F

G

H

9' 16'

E'

PPE TRAINING BAG

STORAGE

COMMANDER

146 OPERATIONS CHIEF

MECHANICAL

RECORDS STAGING/

STORAGE

CEM

SECOND OFFICER

STAN/EVAL

PLANS &

RESOURCES CHIEF

SECURE STORAGE

(CRYPTO)

ITE

STAGING/STORAGE

COMM OPEN OFFICE

MEN

MEN

WEST STAIR

COMM OPEN OFFICE

UTC PREVENTIVE

MAINTENANCE

SF/ COMM

CORRIDOR

SF COMMANDER

SF FIRST

SERGEANT

LAW

ENFORCEMENT

DESK

INFORMATION

PROTECTION CHIEF

CHIEF OF SECURITY

ELEV MACHINE RM

LOWER LANDING

HOTEL W/S

FLIGHT CHIEFS

FSS C/S

BUDGET OFFICE

W/C 1

SF/ CATM

CORRIDOR

CATM ADMIN

CATM NCOIC

021A

SF/ CATM

CORRIDOR

MECHANICAL

TRAINING ROOM

WEAPONS

MAINTENANCE

PPE TRAINING BAG

STORAGE

EQUIPMENT

LOCKERS

WEAPONS

CLEARING

S

WP

WP

WP

SEE B4/FA102 SEE B4/FA102

SF XO/NCO

SF OPEN OFFICE

152 PROGRAM

MANAGEMENT

COMM C/S

DATA CENTER

SHARED WAITING

ROOM

VEST

101A

VAULT

016A

W/C 2

SUPPLY MOBILITY

MANAGEMENT

WS

LED

ER

ER

N A

C

N A

C

S

WP

WP

COMM CORRIDOR

SF/ COMM

CORRIDOR

COMM OPEN OFFICE

ELEC WEST 1

129A

5 ER

OPERATIONS

SUPER

WS

SF W/S

M A

T C

H L

IN

E S

E E

A /F

A

M A

T C

H L

IN

E S

E E

A /F

A

USUS

SOV

CACA

P

D P

D

SEE SHEET FA001 FOR GENERAL NOTES AND

LEGEND.

FIRE ALARM/MASS NOTIFICATION SYSTEM SHALL BE

DESIGNED IN ACCORDANCE WITH UFC 3-600-01, UFC

4-021-01, AND NFPA 72. THE ORDER OF PREFERENCE

OF CODE SHALL BE:

A. UFC 3-600-01

B. UFC 4-021-01

C. NFPA 72

ALL FIRE ALARM/MASS NOTIFICATION STROBES ARE

15 CANDELA UNLESS OTHERWISE NOTED.

GENERAL NOTES:

1.

2.

3.

KEYNOTES:

KEY PLAN

SCALE: = 1'-0"

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

PLAN NORTH

0 8 168

1/8"

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u it e

B o x

S y ra c u s e

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:2

:0

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a c ili ty /1

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v

.r v t

FA101

100% B3 SUBMITTAL

F

IR

E A

L A

R M

M

A S

S N

O T

IF

IC

A T

IO

N

P L A

N

F

IR

S T

F L O

O R

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

A p p ro v e r

N D

S

N D

S

B T

H

M

A R

C H

SCALE: 1/8" = 1'-0"A1

FIRE ALARM & MASS NOTIFICATION PLAN - PARTIAL FIRST FLOOR / BASEMENT

KEY # KEYNOTE DESCRIPTION

COORDINATE EXACT LOCATION OF DEVICE

MOUNTING WITH MECHANICAL UNIT

INSTALLATION LOCATIONS. REFERENCE M

DRAWINGS FOR LOCATIONS.

FLOW SWITCH SHALL HAVE NO TIME DELAY

FUNCTION.

COORDINATE LOCATION, MOUNTING,

CONDUCTOR ROUTING WITH STOREFRONT

FRAMING SYSTEM.

COORDINATE LOCATION OF FIRE ALARM

EQUIPMENT WITH A/V DISPLAY. EQUIPMENT

CAN BE STACKED VERTICALLY WHILE

MAINTAINING REQUIRED MINIMUM AND

MAXIMUM ELEVATIONS OF EQUIPMENT. SHOWN

HORIZONTALLY FOR CLARITY.

PROVIDE CONTROL MODULE TO INTERFACE

WITH ACCESS CONTROL PANEL. FIRE ALARM

CONDITION SHALL UNLOCK ALL LOCKED

DOORS. COORDINATE WITH SECURITY

VENDOR.

COORDINATE CLEAN AGENT TANK LOCATION

WITH THE EXISTING EQUIPMENT IN THE ROOM.

PROVIDE REQUIRED CLEARANCE AROUND

TANK. INSTALL PER NFPA 2001. REFERENCE

FA501, FA502, AND THE SPECIFICATIONS FOR

FURTHER INFORMATION.

16 17 18 19 21 23 24

20 22

A

B

D

C

E

F

G

H

16'

FSS C/S

FIN/ REC CORRIDOR

FINANCE OPEN

OFFICE

FINANCIAL

MANAGEMENT

OFFICER

WOMEN

FINANCE OPEN

OFFICE

ID CARDS

RETENTION

102A

RECRUITING OPEN

OFFICE

RECRUITING

CONSULT

FIN/ REC CORRIDOR

EAST STAIR

STORAGE

JAN

PERSONNEL SUPER

FSS HUDDLE

110A

FSS CORRIDOR

CEM

EAST VEST

102B

WOMEN

FSS OPEN OFFICE

COMMANDER

OPERATIONS

OFFICERS

PPE TRAINING BAG

STORAGE

MECHANICAL

FSS CORRIDOR

HUDDLE / STORAGE

FSS OPEN OFFICE

FSS CORRIDOR

WP

WP

S

FINANCE C/S OFC

103A

RECRUITING

SUPERVISOR

RECRUITING

STORAGE

107A

SHARED TESTING

EDUCATION &

TRAINING OFFICE

N A

C

WP

WP

M A

T C

H L

IN

E S

E E

A /F

A

M A

T C

H L

IN

E S

E E

A /F

A

LACTATION

120A

ELEC EAST 1

110B

FA102

A4

238 SF

INSTALLATION

PERSONNEL

READINESS

118A

23 2422

A

B

STEAM ROOM

SEE SHEET FA001 FOR GENERAL NOTES AND

LEGEND.

FIRE ALARM/MASS NOTIFICATION SYSTEM SHALL BE

DESIGNED IN ACCORDANCE WITH UFC 3-600-01, UFC

4-021-01, AND NFPA 72. THE ORDER OF PREFERENCE

OF CODE SHALL BE:

A. UFC 3-600-01

B. UFC 4-021-01

C. NFPA 72

ALL FIRE ALARM/MASS NOTIFICATION STROBES ARE

15 CANDELA UNLESS OTHERWISE NOTED.

GENERAL NOTES:

1.

2.

3.

12' 13'10' 15'

L'

9'

ELECTRICAL

SEE A1/FA101 SEE A1/FA101

LED

WP

KEYNOTES:

KEY PLAN

SCALE: = 1'-0"

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

PLAN NORTH

0 8 168

1/8"

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u it e

B o x

S y ra c u s e

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:2

:1

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a c ili ty /1

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v

.r v t

FA102

100% B3 SUBMITTAL

F

IR

E A

L A

R M

M

A S

S N

O T

IF

IC

A T

IO

N

P L A

N

F

IR

S T

F L O

O R

/B A

S E

M E

N T

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

A p p ro v e r

N D

S

N D

S

B T

H

M

A R

C H

SCALE: 1/8" = 1'-0"A1

FIRE ALARM & MASS NOTIFICATION PLAN - PARTIAL FIRST FLOOR SCALE: 1/8" = 1'-0"A4

FIRE ALARM & MASS NOTIFICATION PLAN -

SUB BASEMENT

SCALE: 1/8" = 1'-0"B4

FIRE ALARM & MASS NOTIFICATION PLAN -

BASEMENT ELECTRICAL ROOM

KEY # KEYNOTE DESCRIPTION

COORDINATE EXACT LOCATION OF DEVICE

MOUNTING WITH MECHANICAL UNIT

INSTALLATION LOCATIONS. REFERENCE M

DRAWINGS FOR LOCATIONS.

1 2 4 6 7 8 9 16

12' 13'10' 15'

A

B

D

C

E

L'

K'

J'

H'

G'

F'

F

G

H

9' 16'

E'

CONTRACTING

SUPER

229A

CONTRACTING

OPEN OFFICE

MSG COMMANDER

230B

MSG DEPUTY

COMMANDER

230C

MEN

227 WOMEN

SECOND FLOOR

CONFERENCE

MSG CORRIDOR

MSG FIRST

SERGEANT

230E

MSG CHIEF

230D

MULTIMEDIA

STUDIO/STORAGE

231B

ASSEMBLY

LANDING

WOMEN

MEN

JAG 1

JAG 2

UPPER LANDING

MSG CORRIDOR

PUBLIC AFFAIRS

OIC

231A

IGI 2

IGI 1

IGI STAFF

205W

JAG OPEN OFFICE

SMALL

CONFERENCE

STORAGE

160D

BREAK ROOM

PUBLIC AFFAIRS

ADMIN OPEN

OFFICE

COMMAND

CORRIDOR

MULTI PURPOSE

ROOM A

160A

TELECOM ROOM

COMMAND POST

224BWEST STAIR

ER

ER

NAC

JAN

223A

ROOF BELOW

ROOF BELOW

ELEC WEST 2

223B

ASSEMBLY

CORRIDOR

MULTI PURPOSE

ROOM B

160B

MSG OPEN OFFICE

MSG OPEN OFFICE

AV CLOSET

160C

75 75

M A

T C

H L

IN

E S

E E

A /F

A

M A

T C

H L

IN

E S

E E

A /F

A

US

CONTROL PANEL

224C

CMD POST OFC 1

224DCMD POST OFC 2

224E

TRAP

224A

US

SOV

C A

C A

P

D P

D

SEE SHEET FA001 FOR GENERAL NOTES AND

LEGEND.

FIRE ALARM/MASS NOTIFICATION SYSTEM SHALL BE

DESIGNED IN ACCORDANCE WITH UFC 3-600-01, UFC

4-021-01, AND NFPA 72. THE ORDER OF PREFERENCE

OF CODE SHALL BE:

A. UFC 3-600-01

B. UFC 4-021-01

C. NFPA 72

ALL FIRE ALARM/MASS NOTIFICATION STROBES ARE

15 CANDELA UNLESS OTHERWISE NOTED.

GENERAL NOTES:

1.

2.

3.

KEYNOTES:

KEY PLAN

SCALE: = 1'-0"

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

PLAN NORTH

0 8 168

1/8"

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u it e

B o x

S y ra c u s e

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:2

:2

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a c ili ty /1

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v

.r v t

FA103

100% B3 SUBMITTAL

F

IR

E A

L A

R M

M

A S

S N

O T

IF

IC

A T

IO

N

P L A

N

S E

C O

N D

F L O

O R

/A S

S E

M B

L Y

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

A p p ro v e r

N D

S

N D

S

B T

H

M

A R

C H

SCALE: 1/8" = 1'-0"A1

FIRE ALARM & MASS NOTIFICATION PLAN - PARTIAL SECOND FLOOR / ASSEMBLY

KEY # KEYNOTE DESCRIPTION

PROVIDE CONTROL MODULE TO INTERFACE

WITH ACCESS CONTROL PANEL. FIRE ALARM

CONDITION SHALL UNLOCK ALL LOCKED

DOORS. COORDINATE WITH SECURITY

VENDOR.

COORDINATE CLEAN AGENT TANK LOCATION

WITH THE EXISTING EQUIPMENT IN THE ROOM.

PROVIDE REQUIRED CLEARANCE AROUND

TANK. INSTALL PER NFPA 2001. REFERENCE

FA501, FA502, AND THE SPECIFICATIONS FOR

FURTHER INFORMATION.

16 17 18 19 21 23 24

20 22

A

B

D

C

E

F

G

H

16'

SAFETY OFFICER

WING PLANS

OFFICER

OPEN OFFICE

E/O 2

E/O 1

IGQ STAFF

205E

WOMEN

MEN

EAST STAIR

COMMAND JAG (3)

211F

COMMAND CHIEF

MASTER SERGEANT

211E

IGQ

INSPECTOR

GENERAL

DDR

HRA

SAFETY/ IG OPEN

OFFICE

WS

COMMAND

CONFERENCE

VICE COMMANDER

211A EXECUTIVE

SUPPORT

211B

CLOS

211D

WING COMMANDER

211C

COMMAND SUITE

NAC

ROOF BELOW

ELEC EAST 2

202B

ROOF

BELOW

M A

T C

H L

IN

E S

E E

A /F

A

M A

T C

H L

IN

E S

E E

A /F

A

COMMAND

CORRIDOR

SEE SHEET FA001 FOR GENERAL NOTES AND

LEGEND.

FIRE ALARM/MASS NOTIFICATION SYSTEM SHALL BE

DESIGNED IN ACCORDANCE WITH UFC 3-600-01, UFC

4-021-01, AND NFPA 72. THE ORDER OF PREFERENCE

OF CODE SHALL BE:

A. UFC 3-600-01

B. UFC 4-021-01

C. NFPA 72

ALL FIRE ALARM/MASS NOTIFICATION STROBES ARE

15 CANDELA UNLESS OTHERWISE NOTED.

GENERAL NOTES:

1.

2.

3.

KEY PLAN

SCALE: = 1'-0"

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

PLAN NORTH

0 8 168

1/8"

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u it e

B o x

S y ra c u s e

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:2

:3

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a c ili ty /1

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v

.r v t

FA104

100% B3 SUBMITTAL

F

IR

E A

L A

R M

M

A S

S N

O T

IF

IC

A T

IO

N

P L A

N

S E

C O

N D

F L O

O R

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

A p p ro v e r

N D

S

N D

S

B T

H

M

A R

C H

SCALE: 1/8" = 1'-0"A1

FIRE ALARM & MASS NOTIFICATION PLAN - PARTIAL SECOND FLOOR

FMCP FIRE SAFETY

A C

T U

A T

E A

U D

IO

V

IS

U

L

S U

P E

R V

IS

O

R Y

I N

D

IC

A T

IO

N

D E

V

IC

E

A C

T U

A T

E A

U D

IO

V

IS

U

A L A

L A

R M

IN

D

IC

A T

O R

D E

V

IC

E S

A C

T U

A T

E A

U D

IO

V

IS

U

C

M M

O N

T R

O U

B L E

I N

D

IC

A T

O R

S H

U T

D O

W N

A F

F E

C T

E

H

V A

C U

N

IT

S

A B C D E F G H I J K

F1 MANUAL PULL STATION

SMOKE DETECTOR

SPRINKLER CONTROL VALVE

FIRE ALARMS

SUPERVISORY SIGNALS

TROUBLE CONDITIONS

FIRE ALARM AC POWER FAILURE

FIRE ALARM SYSTEM LOW BATTERY

OPEN CIRCUIT

CLEAN AGENT CONTROL PANEL TROUBLE

X

X

X

SYSTEM INPUTS

GROUND FAULT

SMOKE DETECTOR - FIRST FLOOR ELEVATOR LOBBY

X

L

M1

N O P

R E

C A

L L E

L E

V A

T O

R T

O P

R

IM

A

C A

L L F

L O

O R

R E

C A

L L E

L E

V A

T O

R T

O A

L T

E R

N A

T

C

A L L F

L O

O R

M

WIDE AREA MASS NOTIFICATION -

PRE RECORDED MESSAGE

WIDE AREA MASS NOTIFICATION -

LIVE VOICE MESSAGE

S1

T1

MASS NOTIFICATION

F2

F3

F4

T2

T3

T4

T6

M2

T R

A N

S M

IT

A

L A

R M

S

IG

N A

L

N T

R A

L S

T A

T

IO

N

T R

A N

S M

IT

S

U P

E R

V

IS

O

IG

N A

L T

O C

E N

T R

A L S

T A

T

IO

N

T R

A N

S M

IT

T

R O

U B

L E

S

IG

N A

L

N T

R A

L S

T A

T

IO

N

A L E

R T

S T

R O

B E

T H

R O

U G

H O

E

B U

IL

D

IN

G

C

L E

A R

F

IR

E A

L A

R M

E V

A C

U A

T

IO

S S

A G

E T

H R

O U

G H

O U

T B

U

IL

D

IN

G

P R

E R

E C

O R

D E

D M

E S

S A

G

R

O U

G H

O U

T F

A C

IL

IT

Y

S

IL

E N

C E

F

IR

E A

L A

V A

C U

A T

IO

N

M E

S S

A G

E

CENTRAL

STATION

EVAC

SIGNALS

MASS

NOTIFICATION

SYSTEM OUTPUTS

F5

F6

SMOKE DETECTOR - ELEVATOR MACHINE ROOM

WATER FLOW SWITCH

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X

X

X

X

X

X

X

X

X

X

SMOKE DETECTOR - SECOND FLOOR ELEVATOR LOBBY

F7

X

X

X

X

X

LOC MICROPHONE ACTIVATION

LOC PRE-RECORDED MESSAGE SWITCH

M3

M4

A U

D

IB

L E

C A

R B

O N

M O

N O

X

ID

E M

E S

S A

G

R

O U

G H

O U

T T

H E

B U

IL

D

IN

G

S

IL

E N

C E

L O

C M

IC

R

O P

H O

N E

S

L

IV

E V

O

IC

E T

H R

O U

G H

O

F

C

IL

IT

Y

X

X X

X

X

X

X X

X

X X

X

ELEVATOR WATER FLOW SWITCH X X X

X

X

X

X

IN-DUCT SMOKE DETECTORS2

Q

A C

T

IV

A T

E A

L E

R T

M E

S S

A G

E

D T

E X

T S

IG

N

S

X

X

X

X

S

U N

L O

C K

A L L A

C C

E S

S C

O N

T R

O R

S I

N P

A T

H O

F E

G R

E S

S

X

X

X

F8 DATA CENTER OR TELECOM WATER FLOW SWITCH X X

X X

X X

CLEAN AGENT CONTROL PANEL SUPERVISORYS3 X X

R

X

X

X

X

X

X

X

X

D

IS

P L A

Y E

V A

C U

A T

IO

N

M E

S S

A G

E O

N L

X

T S

IG

N

S T

H R

O U

G H

O U

T T

H E

B U

IL

D

IN

G

F9 CARBON MONOXIDE DETECTION X X

X XX

A C

T

IV

A T

E E

X T

E R

IO

R

E L E

C T

R

IC

B E

L L

X

X

T

A C

T

IV

A T

E E

L E

V A

T O

R P

O W

E R

S H

U N

T

X

U

NOTIFICATION APPLIANCE CIRCUIT SHORTT5 X X

F10 CLEAN AGENT CONTROL PANEL ALARM

X XXX

X X

X

X

A C

T

IV

A T

E E

L E

C T

R O

N

IC

E Q

U

IP

M E

W

E R

S H

U N

T

X

V

FIRE

ALARM/MASS

NOTIFICATION

CONTROL

PANEL (FMCP)

S

BATTERIES

SS

DACT

SIGNALING LINE CIRCUIT (SLC)

NOTIFICATION APPLIANCE

CIRCUIT (NAC)

SPEAKER CIRCUIT

120 VAC

M M

F

LOC

BREAKER

POWER

PANEL

POWER

WP WP

LOC

LOC

CHARGER

S

CM

LOC

FIN/REC

CORRIDOR-102

COMM OPEN

OFFICE-136

SF/CATM

CORRIDOR-011

SHARED

WAITING

ROOM-101

SIGNALING LINE CIRCUIT (SLC)

VS

BACKFLOW TEST

HEADER

CONTROL VALVE

VS VS

BACKFLOW

CONTROL VALVES

LED

NAC

SS120 VAC2

LOC

ASSEMBLY

CORRIDOR-157

LOC

MSG

CORRIDOR-223

LOC

COMMAND

CORRIDOR-202

SIGNALING LINE CIRCUIT (SLC)

VS WF

SECOND FLOOR-

ZONE CONTROL

VS WF

FIRST FLOOR-

ZONE CONTROL

SIGNALING LINE CIRCUIT (SLC)

RM RMRM RM

PRIMARY

ELEVATOR

RECALL

RELAY

SECONDARY

ELEVATOR

RECALL

RELAY

POWER

SHUNT TRIP

FIRE HAT

RELAY

CO

F

SS

TO CLEAN AGENT

RELEASING CONTROL

PANEL

VS WF

TELECOM

ROOM-156

VS WF

DATA

CENTER-128

SIGNALING LINE CIRCUIT (SLC)

S

ER

RTS

SEE SHEET FA001 FOR GENERAL NOTES AND LEGEND.

FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE

DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND

EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT

PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED

BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM

MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.

FIRE ALARM CONTRACTOR SHALL PROVIDE POWER PANEL

INFORMATION, BREAKER LOCKING AND IDENTIFICATION

REQUIREMENTS IN ACCORDANCE WITH NFPA 70 AND 72

REQUIREMENTS. LOCKING BREAKER SHALL BE RED.

CONTRACTOR SHALL PROVIDE THE NECESSARY QUANTITY OF

POWER SUPPLY PANELS FOR CONTROL AND OPERATION OF

ALL NOTIFICATION APPLIANCES. 5 NAC EXTENDER PANELS

HAVE BEEN INCLUDED IN THE POWER REQUIREMENTS OF THE

ELECTRICAL SYSTEM, 3 ON THE 1ST FLOOR, 2 ON THE 2ND. IF

ADDITIONAL PANELS ARE REQUIRED OR IN ALTERNATIVE

LOCATIONS, THE CONTRACTOR SHALL COORDINATE THOSE

REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR.

CONTRACTOR SHALL PROVIDE ALL NECESSARY AND

REQUIRED SYSTEM PROGRAMMING TO MEET THE DESIGN

INTENT AND CODE COMPLIANCE.

GENERAL NOTES:

1.

2.

3.

4.

5.

KEYNOTES:

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u it e

B o x

S y ra c u s e

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:2

:3

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a c ili ty /1

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v

.r v t

FA501

100% B3 SUBMITTAL

F

IR

E A

L A

R M

M

A S

S N

O T

IF

IC

A T

IO

N

D E

T A

IL

S

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

A p p ro v e r

N D

S

N D

S

B T

H

M

A R

C H

SCALE: N.T.S.A3

FIRE ALARM & MASS NOTIFICATION OPERATIONAL MATRIX

SCALE: N.T.S.C1

FIRE ALARM & MASS NOTIFCATION RISER DIAGRAM

KEY # KEYNOTE DESCRIPTION

COORDINATE LOCATION OF EXISTING COPPER

PHONE LINES FOR NEW DACT.

POWER FOR NEW FMCP & NAC SHALL BE

FROM DEDICATED LIFE SAFETY CIRCUIT AND

MEET THE NFPA 72 REQUIREMENTS FOR FIRE

ALARM CONTROL PANEL POWER

REQUIREMENTS.

LED TEXT SIGNS LOCATED IN VARIOUS

LOCATIONS THROUGHOUT THE BUILDING. SEE

FA101 - FA104 FOR LOCATIONS.

TYPICAL OF MULTIPLE LOCATIONS IN THE

BUILDING. SEE FA101 - FA104 FOR LOCATIONS.

PROVIDE SURGE PROTECTION DEVICES (SPD)

PER UFC 3-600-01; 9-18.11.2 ON ALL 120 VAC

CIRCUITS TO CONTROL PANELS, SUBPANELS,

TRANSMITTERS, AMPLIFIER PANELS, AND

BOOSTER PANELS. SPD'S MUST HAVE BOTH A

UL 1449 AND UL 1283 LISTING AND MUST BE

LOCATED IN AN ADJACENT HINGED TERMINAL

BOX.

GENERAL NOTES:

1. CLEAN AGENT SYSTEM LAYOUT AND DESIGN SHALL BE

PERFORMED AND CALCULATED IN ACCORDANCE WITH NFPA

2001, AND MANUFACTURER'S REQUIREMENTS AND

RECOMMENDATIONS. VOLUME OF DISCHARGE SHALL

INCLUDE THE AREA UNDER THE RAISED FLOOR (DATA

CENTER-128).

2. SEE PLAN DRAWINGS FOR DEVICE QUANTITIES. CLEAN

AGENT RISER DIAGRAM IS DIAGRAMMATIC AND NOT

INTENDED TO SHOW EACH COMPONENT, DEVICE, APPLIANCE,

ETC.

3. CONTRACTOR SHALL PROVIDE ALL NECESSARY AND

REQUIRED SYSTEM PROGRAMMING TO MEET THE DESIGN

INTENT AND CODE COMPLIANCE.

4. BREAKER SERVING THE CLEAN AGENT RELEASING PANEL

SHALL BE PAINTED RED AND PROVIDED WITH A NON-SWEEP

DEVICE (LOCK).

5. THE CLEAN AGENT PANEL SHALL IDENTIFY THE ELECTRICAL

PANEL WHERE THE CLEAN AGENT CIRCUIT BREAKER IS

LOCATED.

6. REFER TO CLEAN AGENT SYSTEM SPECIFICATIONS 21 22 00.00

40 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.

BUILDING

FMCP

A B C E F G H I J

TROUBLE CONDITIONS

LOW BATTERY VOLTAGE

CIRCUIT FAULT

SUPERVISED COMPONENT FAILURE

AC POWER FAILURE

SYSTEM INPUTS

T R

A N

S M

IT

T

R O

U B

L E

S

IG

N

B U

IL

D

IN

G

F M

C P

T R

A N

S M

IT

S

U P

E R

V

IS

O

IG

N A

L T

O B

U

IL

D

IN

G F

M C

P

T R

A N

S M

IT

A

L A

R M

S

IG

N

B U

IL

D

IN

G

F M

C P

X

X

X

X

ACTIVATION OF ABORT SWITCH

ACTIVATION OF ALERT THRESHOLD LEVEL OF THE

ULTRA SENSITIVE SMOKE DETECTOR

CLEAN AGENT

ACTIVATION OF ALARM THRESHOLD LEVEL OF

THE ULTRA SENSITIVE SMOKE DETECTOR

C1

ACTIVATION OF CLEAN AGENT MANUAL PULL STATION

E N

E R

G

IZ

E

P R

E -D

IS

C

H A

R G

E

S T

R O

B E

S

IL

L U

M

IN

A T

E

A L A

R M

L A

C

A C

P

IL

L U

M

IN

A T

E

P R

E D

IS

C

H A

R G

E

L A

M P

O N

C A

A R

T T

IM

E

D E

L

Q U

E N

A B

L E

C L E

A N

A G

E

B

O R

T S

E Q

U E

N C

E

X

XX

X

X

IN

IT

IA

T

E C

L E

A N

A G

E

L E

N O

ID

R

E L E

A S

E

X

X X X X

X

CLEAN AGENT

X

SYSTEM OUTPUTS

X

D

E N

E R

G

IZ

E

D

IS

C H

A R

G E

S

T R

O B

E S

X

X

X C2

C3

C4

T1

T2

T3

T4

CLEAN AGENT

RELEASING

CONTROL PANEL

(TYP. OF 2)

SIGNALING LINE CIRCUIT (SLC)

NOTIFICATION APPLIANCE

CIRCUIT (NAC)

CA MM

PS

LOW-PRESSURE

SS120 VAC

CA SOV

SOLENOID

TO FIRE ALARM &

MASS NOTIFICATION

CONTROL PANEL

S

US

1 D DP P

KEYNOTES:

1 2 3 4 5

A

B

C

D

SHEET ID

P a rk w a y L a n e

S u it e

P e a c h tr e e C o rn e rs

G

A

P h o n e

-7

F a x

(6

-7

P O

N D

J O

B

S

IZ

E

A N

S I D

F

IL

E N

A M

E

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

IS

S

U E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

F

IL

E N

U M

B E

R

D A

T E

D E

S C

R

IP

T

IO

N M

A R

K

Q P

K D

E S

IG

N

S o u th

S a lin a S tr e e t

S u it e

B o x

S y ra c u s e

-0

Q P

K J

O B

ORIGINAL SHEET SIZE - ANSI D (22" X 34")

/1

/2

:2

:4

P M

B

IM

/1

N

Y A

N G

N ia g a ra

F a lls R e p a ir O

T

F a c ili ty /1

N

Y A

N G

N

IA

G

A R

A M

E P

F

P v

.r v t

FA502

100% B3 SUBMITTAL

C L E

A N

A G

E N

T F

IR

E

S U

P P

R E

S S

IO

N

D E

T A

IL

S

R E

N O

V A

T E

O P

E R

A T

IO

N

S A

N D

T R

A

IN

IN

G

F A

C

IL

IT

Y

B

U

IL

D

IN

G

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

N

IA

G A

R A

F A

L L S

A

IR

R E

S E

R V

E S

T A

T

IO

N

N E

W Y

O R

K A

IR

N

A T

IO

N

A L G

U A

R D

A p p ro v e r

N D

S

N D

S

B T

H

M

A R

C H

SCALE: N.T.S.A1

CLEAN AGENT OPERATIONAL MATRIX

SCALE: N.T.S.C1

CLEAN AGENT RISER DIAGRAM KEY # KEYNOTE DESCRIPTION

POWER FOR NEW CACP SHALL BE FROM

DEDICATED LIFE SAFETY CIRCUIT AND MEET

THE NFPA 72 REQUIREMENTS FOR FIRE ALARM

CONTROL PANEL POWER REQUIREMENTS.

PROVIDE SURGE PROTECTION DEVICES (SPD)

PER UFC 3-600-01; 9-18.11.2 ON ALL 120 VAC

CIRCUITS TO CONTROL PANELS, SUBPANELS,

TRANSMITTERS, AMPLIFIER PANELS, AND

BOOSTER PANELS. SPD'S MUST HAVE BOTH A

UL 1449 AND UL 1283 LISTING AND MUST BE

LOCATED IN AN ADJACENT HINGED TERMINAL

BOX.

FA001 - FIRE ALARM & MASS NOTIFICATION LEGEND AND GENERAL NOTES
FA101 - FIRE ALARM & MASS NOTIFICATION PLAN -FIRST FLOOR
FA102 - FIRE ALARM & MASS NOTIFICATION PLAN -FIRST FLOOR/BASEMENT
FA103 - FIRE ALARM & MASS NOTIFICATIONPLAN -SECOND FLOOR/ASSEMBLY
FA104 - FIRE ALARM & MASS NOTIFICATION PLAN -SECOND FLOOR
FA501 - FIRE ALARM & MASS NOTIFICATION DETAILS
FA502 - CLEAN AGENT FIRE SUPPRESSION DETAILS