This document outlines a construction contract solicitation for renovations to the Operations and Training Facility at Niagara Falls International Airport in New York. The project scope involves renovating the two-story, 43,029 square foot facility and has a budget between $10-25 million. The North American Industry Classification code is 236220 and the size standard for small businesses is $45 million average annual revenue for the past three years. This solicitation is set aside for competitive 8(a) small businesses. Interested parties are encouraged to attend the pre-bid conference and site visit. The award will be made to the responsible bidder submitting the most advantageous price-related proposal. Funding is not currently available but is expected to be secured by September 30, 2023, at which time the contract may be awarded if prices are within a reasonable range.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
E-001-01
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DESCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
2 DIGIT CONSTRUCTION
PHASE DESIGNATOR
(REFER TO A3/G-002
FOR CONSTRUCTION
PHASES)
ELECTRICAL GENERAL NOTES:
1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:
1. NFPA 70-2020 (NATIONAL ELECTRICAL CODE)
2. ANSI C2-2017 (NATIONAL ELECTRICAL SAFETY CODE)
3. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.
2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40%
FULL.
3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LIGHTING
FIXTURES AND CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL
DESCRIPTIONS INDICATED.
5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.
6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.
7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE
RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE
ROUGHING-IN.
9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA
COMPENSATION WILL BE GRANTED.
10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM THE
EXISTING SHALL BE REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.
11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND
SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE
CONTRACTOR'S RESPONSIBILITY.
14. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY
MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/8” IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN
WITH AN INDELIBLE MARKER.
17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.
18. EMT SHALL COMPLY WITH ANSI C80.3 AND UL 797. ALL EMT SHALL BE FACTORY PAINTED. PROVIDE THE FOLLOWING COLORS FOR
EACH SYSTEM:
• TELECOMMUNICATIONS - ORANGE
• 208/120V POWER - BLUE
• GENERATOR POWER - GREEN
• SECURITY - PURPLE
19. DATA CENTER 129, VAULT 016A, AND TELECOM ROOM 157 REMAIN OPERATIONAL DURING CONSTRUCTION.
ELECTRICAL ABBREVIATIONS
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS
THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE
DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT
SYSTEM HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY
SYSTEM
HWRP
HWSP
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NO
NTS
P
PA
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
XFMR
Z
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR
SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
TRANSFORMER
IMPEDANCE
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
P
O B o x
S yr a c u s e
N Y
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:3
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-001
100% B3 SUBMITTAL
E L E
C T
R
IC
A L G
E N
E R
A L N
O T
E S
A N
D A
B B
R E
V
IA
T
IO
N S
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
NOTE:
1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS
PROJECT.
WIRE SIZE FOR ALL 120V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT
AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT
AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT
AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
NOTES:
1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.
ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,
DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT
IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF
EACH:
EXISTING EQUIPMENT
NEW OR RELOCATED EQUIPMENT
HATCH INDICATES EQUIPMENT TO BE DEMOLISHED
1/2
B
W
S B
M
MOD
2/60/40/1
60/40/3/3R
40/3/3R
CB
T
M
EM
J J
J
G
G4
LP
A
AE
M
X X
C
D a b
LUMINAIRES
LUMINAIRE AND OUTLET BOX. LETTER INDICATES
LUMINAIRE TYPE. SEE LIGHTING FIXTURE
SCHEDULE.
LUMINAIRE AND OUTLET BOX WIRED FOR
MULTILEVEL SWITCHING, LOWER CASE LETTER
INDICATES SWITCHLEG DESTINATION.
LUMINAIRE AND OUTLET BOX, WITH PROVISIONS
FOR EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LIGHTING FIXTURE
SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LIGHTING FIXTURE SCHEDULE.
CEILING OR WALL MOUNTED EXIT SIGN AND
OUTLET BOX. PROVIDE NUMBER OF ARROWS
AND FACES INDICATED. LETTER INDICATES
LUMINAIRE TYPE. SEE LIGHTING FIXTURE
SCHEDULE. WALL MT AT 96" AFF.
RECESSED OR PENDANT MOUNTED LUMINAIRE
AND OUTLET BOX. LETTER INDICATES LUMINAIRE
TYPE. SEE LIGHTING FIXTURE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LIGHTING FIXTURE SCHEDULE.
CEILING OR WALL MOUNTED LUMINAIRE AND
OUTLET BOX WITH PROVISIONS FOR
EMERGENCY LIGHTING.
EMERGENCY LIGHT UNIT
REMOTE HEAD OR FLOOD LUMINAIRE
WALL WASH DOWNLIGHT
POLE MOUNTED TYPE
POST-TOP OR BOLLARD TYPE
CEILING FAN
EQUIPMENT
MOTOR, HORSEPOWER AS INDICATED
MOTORIZED DAMPER
3-POLE COMBINATION MAGNETIC MOTOR
STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/
NEMA ENCLOSURE) NF = NONFUSED
DISCONNECT SWITCH, (SWITCH AMPS/ FUSE
SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-
FUSED
INDIVIDUALLY MOUNTED CIRCUIT BREAKER, (CB
SIZE/ POLES/ NEMA ENCLOSURE)
DRY TYPE TRANSFORMER, KVA AS INDICATED
METER
ELECTRONIC METER
PANELBOARD, SEE SCHEDULES
DISTRIBUTION PANELBOARD
EQUIPMENT AS INDICATED
CEILING OR WALL MOUNTED JUNCTION BOX
PULL OR JUNCTION BOX
CEILING MOUNTED BLUE LIGHT SYSTEM
ROTATING BEACON
WHITE NOISE PLENUM SPEAKER; MT ABOVE
DROP CEILING
BLUE LIGHT LOCAL CONTROL SWITCH; MT 48"
AFF, UIO
WHITE NOISE ROTARY VOLUME CONTROL; MT
48" AFF, UIO
FURNITURE FEED
CR
ST
TR
M
R
LA-1,3,5
WIRING
CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5
ADJACENT TO ARROW INDICATES HOMERUN OF
CIRCUITS, 1,3,5 TO PANEL LA. MARKS ACROSS
RACEWAY INDICATE THE NUMBER OF PHASE
CONDUCTORS AND NEUTRAL IN RACEWAY.
GROUND CONDUCTORS ARE INDICATED BY
LONGER HASHMARKS. NO MARKS ACROSS
RACEWAY INDICATES 2#12 CONDUCTORS AND 1
#12 GROUND CONDUCTOR. CONDUCTOR SIZE #
12 UNLESS INDICATED OTHERWISE. MINIMUM
RACEWAY SIZE SHALL BE 3/4"
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR
ABOVE FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
PLUG-IN BUSWAY, UIO
SURFACE METAL RACEWAY OR MULTIOUTLET
ASSEMBLY AS INDICATED
CABLE TRAY (SIZE AS INDICATED ON PLAN)
DUCTBANK, TEXT INDICATES QUANTITY AND
SIZE OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)
LIGHTNING PROTECTION
3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG
GROUND CONNECTION
BARE COPPER GROUND CONDUCTOR, 1/0 UIO.
4/0 BARE COPPER GROUND CONDUCTOR
LIGHTNING PROTECTION SYSTEM AIR TERMINAL
LIGHTNING PROTECTION ROOF CONDUCTOR
ELECTRICAL CONNECTION
SITE
ELECTRICAL MANHOLE
ELECTRICAL HANDHOLE
PAD MOUNTED TRANSFORMER
POWER POLE
DOWN GUY AND ANCHOR (QUANTITY AS
INDICATED)
ONE-LINE
TRANSFORMER
CURRENT TRANSFORMER
FUSE
ELECTRICAL CONNECTION
CIRCUIT BREAKER
SWITCH
SURGE ARRESTORS
SEPARABLE CONNECTION
DRY TYPE TRANSFORMER, K-4 RATED, KVA AS
INDICATED
GROUND ROD
GROUND
2W4"
WIRING DEVICES
SIMPLEX RECEPTACLE NEMA 5-20R, MT 18" AFF,
UIO
DUPLEX RECEPTACLE NEMA 5-20R, MT 18" AFF,
UIO
DUPLEX RECEPTACLE, NEMA 5-20R, MT 48" AFF
OR ABOVE COUNTER TOP/BACKSPLASH
DUPLEX GFI RECEPTACLE NEMA 5-20R, MT 18"
AFF, UIO
DUPLEX GFI RECEPTACLE NEMA 5-20R, MT 48"
AFF OR ABOVE COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R, MT
18" AFF, UIO
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MT 18" AFF, UIO
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MT 48" AFF OR ABOVE COUNTER
TOP/BACKSPLASH
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MT 18" AFF, UIO
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MT 48" AFF OR ABOVE COUNTER
TOP/BACKSPLASH
DOUBLE-DUPLEX GFI RECEPTACLE, NEMA
5-20R, MOUNTED CONCEALED BEHIND ELECTRIC
WATER COOLER
FLOOR BOX WITH DUPLEX RECEPTACLE NEMA
5-20R. PROVIDE FIRE RATED POKE THRU
DEVICES ON ALL FLOORS ABOVE GROUND
LEVEL.
SPECIAL RECEPTACLE, NEMA TYPE AS
INDICATED, MT 18" AFF UIO
CEILING BOX WITH DUPLEX RECEPTACLE, NEMA
5-20R
RECEPTACLE WP = IN-USE WEATHER PROOF
SUBSCRIPTS TR = TAMPER RESISTANT
TV = TELEVISION, MOUNT AT 60" AFF
AFCI = ARC FAULT CIRCUIT INTERRUPTER
FLOOR BOX SUITABLE FOR CONCRETE FLOOR
POUR; TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE
WITH HINGED ACCESS TO RECEPTACLES AND
JACKS RECESSED BELOW COVER IN FLOOR
BOX. PROVIDE 8" FIRE RATED POKE THRU
ABOVE GROUND FLOOR. PROVIDE 4 DUPLEX
RECEPTACLES AND 4 DATA PORTS.
FURNITURE FEED POWER POLE; PROVIDE TWO
COMPARTMENTS WITH GROMMETS- ONE FOR
FURNITURE POWER AND ONE FOR FURNITUTRE
TELECOMMUNICATIONS.
WALL SWITCH, AC TYPE, SPST, MOUNT 48" AFF
WALL SWITCH, AC TYPE, DPDT, MOUNT 48" AFF
3-WAY WALL SWITCH, MOUNT 48" AFF
4-WAY WALL SWITCH, MOUNT 48" AFF
SLIDE DIMMER, MT 48" AFF
MOTOR RATED DISCONNECT SWITCH WITH
THERMAL OVERLOADS, SPST, MT. ON UNIT, UIO.
WALL MOUNTED SPEAKER VOLUME SWITCH, MT.
48" AFF
WALL MOUNTED, VACANCY SWITCH, MT. 48" AFF
LOW VOLTAGE ON/OFF WALL SWITCH, WALL MT.
48" AFF. PROVIDE DIMMER CONTROL WITH
DIMMABLE FIXTURES INTEGRAL WITH SWITCH.
CEILING MOUNTED VACANCY SENSOR
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOELECTRIC CELL
ELECTRICAL LEGEND
D
M
V
VS
LV
VS
DS
PE
5-30R
EWC
SCHEMATIC
PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)
CONTROL RELAY COIL
SHUNT TRIP COIL
TIME DELAY RELAY COIL
MOTOR STARTER COIL
S W
J
PP
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:3
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-002
100% B3 SUBMITTAL
E L E
C T
R
IC
A L L
E G
E N
D
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
NOTE:
1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.
MH
Q
EMH
MH T
HH
EMH
KEYNOTES:
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 16 3216
1/16"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:4
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
ESD101
100% B3 SUBMITTAL
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
S
IT
E P
L A
N
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/16" = 1'-0"A1
ELECTRICAL DEMOTLITION SITE PLAN
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
KEY # DESCRIPTION
1 DEMOILISH EXISTING 150 KVA TRANSFORMER,
UNDERGROUND CONDUCTORS, CONDUITS, AND
EXISTING PAD. CONDUCTORS AND CONDUITS
SHALL BE DEMOLISHED BACK TO PAD-MOUNTED
SWITCH.
2 DEMOLISH EXISTING 150 KW NATURAL GAS
GENERATOR, UNDERGROUND CONDUCTORS,
CONDUITS, AND PAD. DEMOLISH NATURAL GAS
LINE BACK TO NEAREST VALVE BOX AND CAP.
3 DEMOLISH EXISITNG GENERATOR EMERGENCY
SHUT OFF.
4 DEMOLISH ELECTRICAL ENTRANCE PULL BOX.
5 EXISTING TO REMAIN FIBER OPTIC ENTRANCE.
PROTECT DURING CONTRUCTION. SERVICE SHALL
REMAIN OPERATIONAL THROUGHOUT
CONSTRUCTION. ENTRANCE DEPTH IS
APPROXIMATELY 1'-3' BELOW GRADE.
6 EXISTING PAD-MOUNTED SWITCH TO REMAIN.
7 EXISTING TO REMAIN FIBER OPTIC ENTRANCE.
PROTECT DURING CONTRUCTION. SERVICE SHALL
REMAIN OPERATIONAL THROUGHOUT
CONSTRUCTION. ENTRANCE DEPTH IS
APPROXIMATELY 2'-3' BELOW GRADE.
8 EXISTING TO REMAIN FLAG POLE LIGHT AND
CONDUIT. CONDUCTORS SHALL BE DEMOLISHED
BACK TO SOURCE PANEL.
"Speed Limit 25"
JJJJ
KEYNOTES:
B4
E-504
C4
E-504
MH
Q
EMH
MH T
EMH
HH
MP-17
MP-11
MP-8
MP-16
11 10
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 16 3216
1/16"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:3
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
ES101
100% B3 SUBMITTAL
E L E
C T
R
IC
A L S
IT
E
P L A
N
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
SCALE: 1/16" = 1'-0"A1
ELECTRICAL SITE PLAN
KEY # DESCRIPTION
7 PROVIDE NEW UNDERGROUND DUCTBANK TO
TRANSFORMER. REFER TO DETAIL B4/E-504
AND REFER TO A1/E-601 FOR CONDUCTOR
SIZING.
8 EXISTING TO REMAIN FIBER OPTIC
ENTRANCE. PROTECT DURING
CONTRUCTION. SERVICE SHALL REMAIN
OPERATIONAL THROUGHOUT
CONSTRUCTION. ENTRANCE DEPTH IS
APPROXIMATELY 2'-3' BELOW GRADE.
9 PROVIDE 120V POWER FOR BLOCKHEATER.
10 PROVIDE 120V POWER FOR BATTERY
CHARGER.
11 PROVIDE 120V POWER FOR ALTERNATOR
HEATER.
12 PROVIDE 120V POWER FOR SPACE HEATER.
13 EXISTING TO REMAIN FLAG POLE LIGHT AND
CONDUIT. PROVIDE NEW CONDUCTORS TO
LP1-2 TO MATCH EXISTING.
KEY # DESCRIPTION
1 PROVIDE NEW CONTRACTOR PROVIDED AND
INSTALLED 750 KVA TRANSFORMER AND PAD.
REFER TO DETAIL A1/E-503 FOR DETAILS.
2 PROVIDE NEW 200 KW DIESEL GENERATOR
WITH 24-HOUR FUEL TANK AND COLD
WEATHER PACKAGE. BASIS OF DESIGN
CATERPILLAR C9 IN SOUND ATTENUATION L1
ENCLOSURE WITH DIESEL SUB-BASE TANK.
REFER TO B1/E-501 FOR PAD DETAIL.
3 EXISTING HIGH VOLTAGE SWITCH TO REMAIN.
4 EXISTING TO REMAIN FIBER OPTIC
ENTRANCE. PROTECT DURING
CONTRUCTION. SERVICE SHALL REMAIN
OPERATIONAL THROUGHOUT
CONSTRUCTION. ENTRANCE DEPTH IS
APPROXIMATELY 1'-3' BELOW GRADE.
5 PROVIDE 4"C. AND PULLSTRING FOR FUTURE
PROVISION FOR EV CHANGING. STUB
CONDUIT AT PARKING LOT EDGE AND CAP.
6 GENERATOR EPO SWITCH. PROVIDE SIGNAGE
NEXT TO SWITCH.
KEYNOTES:
1 2 4 6 7 8 9 1653
12' 13'10' 15'
A
D
C
E
L'
K'
J'
H'
G'
F'
6a
F
G
H
9'
9' 16'
E'
PP1-3
LP1-5
LP1-2
LP1-1
PP1-1
LP1-6
RP1
TRAINING
MANAGER 3
WS
MATCH LINE
SEE C4/ED102
MATCH LINE
SEE C4/ED102
MATCH LINE
SEE C4/ED102
M A
TC
H
L
IN
E
S E
E A
1/ E
D
M A
TC
H
L
IN
E
S E
E A
1/ E
D
11 14
8 11
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:3
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
ED101
100% B3 SUBMITTAL
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
P L A
N
B A
S E
M E
N T
/F
IR
S T
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
SCALE: 1/8" = 1'-0"A1
ELECTRICAL DEMOLITION PLAN - PARTIAL FIRST/ BASEMENT
KEY # KEY DESCRIPTION
1 AREA OF RENOVATION. DEMOLISH ALL POWER,
LIGHTING, DEVICES AND EQUIPMENT INCLUDING
CONDUITS AND CONDUCTORS BACK TO SOURCE
PANEL, UNLESS INDICATED OTHERWISE.
2 PROVIDE TEMPORARY POWER FOR TELECOMM
SYSTEMS DURING CONSTRUCTION.
3 EXISTING DATA CENTER POWER PANELS TO
REMAIN. SCHEDULE SWITCH-OVER WITH BASE
PRIOR TO DISCONNECTING POWER.
4 EXISTING POWER AND TELECOMM TO REMAIN AND
SHALL BE OPERATIONAL THROUGHOUT
CONSTRUCTION.
5 EXISTING (6) 3" CONDUITS TO REMAIN. PROTECT
DURING CONTRUCTION.
6 EXISTING COUPLING TO REMAIN. PROTECT DURING
CONSTRUCTION.
7 EXISTING CONDUIT TO EXISITNG ANTENNA TO
REMAIN. PROTECT DURING CONSTRUCTION.
8 EXISTING ANTENNA EQUIPMENT WALL CABINET TO
BE RELOCATED TO NEW COMMAND POST. REFER
TO A1/T-103 FOR NEW LOCATION.
9 EXISTING ANTENNA EQUIPMENT RACK TO BE
RELOCATED TO NEW COMMAND POST. REFER TO
A1/T-103 FOR NEW LOCATION
10 EXISTING ENTRANCE TERMINAL TO BE
RELOCATED. REFER TO A1/T-101 FOR NEW
LOCATION.
11 EXISTING 110 BLOCKS TO BE RELOCATED. EXTEND
ALL WRING TO NEW LOCATION. REFER TO A1/T-103
FOR NEW LOCATION.
12 EXISTING ADVANTOR PANEL TO REMAIN. PROTECT
DURING CONSTRUCTION.
13 EXISTING ANTENNA RF CABLING ENTRANCE TO
REMAIN. PROTECT DURING CONSTRUCTION.
16 17 18 19 21 23 2420 22
A
B
D
C
E
F
G
H
19a
PP1-2
LP1-4
LP1-3
M A
TC
H
L
IN
E
S E
E A
1/ E
D
M A
TC
H
L
IN
E
S E
E A
1/ E
D
9 1612' 13'10' 15'
L'
9' 16'
MDP
EMER PANEL
EXISTING 1600A
SERVICE
DISCONNECT1
ATS
MATCH LINE
SEE A1/ED101
MATCH LINE
SEE A1/ED101
11 14
4 5
SLP
KEYNOTES:
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:3
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
ED102
100% B3 SUBMITTAL
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
P L A
N
F
IR
S T
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/8" = 1'-0"A1
ELECTRICAL DEMOLITION PLAN - PARTIAL FIRST FLOOR
SCALE: 1/8" = 1'-0"C4
ELECTRICAL DEMOLITION PLAN - BASEMENT ELECTRICAL ROOM
SCALE: 1/8" = 1'-0"B4
ELECTRICAL DEMOLITION PLAN - SUB BASEMENT LEVEL
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
KEY # KEYNOTE DESCRIPTION
1 AREA OF RENOVATION. DEMOLISH ALL POWER,
LIGHTING, DEVICES AND EQUIPMENT INCLUDING
CONDUITS AND CONDUCTORS BACK TO SOURCE
PANEL, UNLESS INDICATED OTHERWISE.
2 EXISTING 800A ATS TO REMAIN.
3 DEMOLISH GENERATOR JUNCTION BOX INCLUDING
CONDUITS AND CONDUCTORS BACK TO SOURCE
PANEL.
4 EXISTING ANTENNA MOUNTED TO BUILDING
EXTERIOR TO REMAIN.
5 EXISTING WIRELESS BOX TO BE RELOCATED. SEE
C1/E-401 FOR NEW LOCATION.
6 EXISTING FLAG POLE FEED SHALL BE RE-FED TO A
NEW PANEL. EXISTING CONDUIT SHALL BE
REUSED. REFER TO ES101 FOR CIRCUITING.
1 2 4 6 7 8 9 1653
12' 13'10' 15'
A
B
D
C
E
L'
K'
J'
H'
G'
F'
6a
F
G
H
9' 16'
E'
PP2-1
LP2-1
2PP2-3
LP2-3 2
M A
TC
H
L
IN
E
S E
E A
1/ E
D
M A
TC
H
L
IN
E
S E
E A
1/ E
D
11 14
5 5
KEYNOTES:
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:3
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
ED103
100% B3 SUBMITTAL
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
P L A
N
S E
C O
N D
F L O
O R
/A S
S E
M B
L Y
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/8" = 1'-0"A1
ELECTRICAL DEMOLITION PLAN - PARTIAL SECOND FLOOR/ ASSEMBLY
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
Key Name DESCRIPTION
1 AREA OF RENOVATION. DEMOLISH ALL POWER,
LIGHTING, DEVICES AND EQUIPMENT INCLUDING
CONDUITS AND CONDUCTORS BACK TO SOURCE
PANEL, UNLESS INDICATED OTHERWISE.
2 EXISTING TELECOM POWER PANELS TO REMAIN.
SCHEDULE SWITCH-OVER WITH BASE PRIOR TO
DISCONNECTING POWER.
3 PROVIDE TEMPORARY POWER FOR TELECOMM
SYSTEMS DURING CONSTRUCTION.
4 POWER AND TELECOMM TO REMAIN AND SHALL BE
OPERATIONAL THROUGHOUT CONSTRUCTION.
5 WIREWAY TO BE DEMOLISHED. EXISTING CABLING
SHALL BE DEMOLISHED BACK TO SOURCE. IF
EXISTING TO REMAIN POWER CONDUCTORS FOR
COMM ROOM PANELS ARE LOCATED WITHIN
WIREWAY, CONDUCTORS SHALL BE RELOCATED.
16 17 18 19 21 23 24
B
D
C
E
F
G
H
19a
LP2-2
PP2-2
M A
TC
H
L
IN
E
S E
E A
1/ E
D
M A
TC
H
L
IN
E
S E
E A
1/ E
D
KEYNOTES:
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:3
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
ED104
100% B3 SUBMITTAL
E L E
C T
R
IC
A L D
E M
O L
IT
IO
N
P L A
N
S E
C O
N D
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/8" = 1'-0"A1
ELECTRICAL DEMOLITION PLAN - PARTIAL SECOND FLOOR
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
KEY # KEY DESCRIPTION
1 AREA OF RENOVATION. DEMOLISH ALL POWER,
LIGHTING, DEVICES AND EQUIPMENT INCLUDING
CONDUITS AND CONDUCTORS BACK TO SOURCE
PANEL, UNLESS INDICATED OTHERWISE.
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS VS VS VS
VS VS
VS VS
VS
VS
VS
VS VS VS
VS
VS VS
VS
VS VS
VS VS
VS
VS
VS
VS
VS VS
D a D b
VS
VSVS
VS
VS
VS
VS
D a D b
VS
3 3
VS VS
OS
KEYNOTES:
1 2 4 6 7 8 9 16
12' 13'10' 15'
A
B
D
C
E
L'
K'
J'
H'
G'
F'
6a
F
G
H
9' 16'
E'
MECHANICAL
DATA CENTER
W/C 1
MEN
ITE
STAGING/STORAGE
UTC PREVENTIVE
MAINTENANCE
PPE TRAINING BAG
STORAGE
OPERATIONS CHIEF
SECOND OFFICER
COMMANDER
CEM
STAN/EVAL
SECURE STORAGE
(CRYPTO)
RECORDS STAGING/
STORAGE
PLANS &
RESOURCES CHIEF
INFORMATION
PROTECTION CHIEF
BUDGET OFFICE
SHARED WAITING
ROOM
W/C 2
ELEV MACHINE RM
COMM OPEN OFFICE
COMM C/S
COMM OPEN OFFICE
LAW
ENFORCEMENT
DESK
PROGRAM
MANAGEMENT
SF OPEN OFFICE
CHIEF OF SECURITY
LOWER LANDING
SF/ COMM
CORRIDOR
VEST
101A
WEST STAIR
COMM CORRIDOR
SF XO/NCO
SF FIRST
SERGEANT
SF COMMANDER
MECHANICAL
TRAINING ROOM
WEAPONS
MAINTENANCE
CATM NCOIC
021A
FLIGHT CHIEFS
HOTEL W/S
SF/ CATM
CORRIDOR
PPE TRAINING BAG
STORAGE
EQUIPMENT
LOCKERS
WEAPONS
CLEARING
VAULT
016A
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
MATCH LINE
SEE C4/E-102
LIGHTING SHOWN
ON SECOND FLOOR
A2E
A2 b
A2E b
A2 a
A2E a
A2 b
A2 b
C1 C1
C1E C1 C1
C1E
C1
C1
C1
C1
C1E
C1C1E
C1
C1
C1E
C1
C1
C1
C1E
C1
C1E
C1
C1E
C1
C1
C1E
C1
C1E C1
C1 C1
A1
A1
A1
A1 A1E
A1 A1
A1
A1
A1
A1
A1
A1
A1
A1
A1 A1 A1
A1 A1 A1
A1E
A1
A1E
A1
A1
A1E
D
D
A1
A1 A1
A1 A1
A1
A1
A1
A1
A1
A1
A1
A1 A1
A1 A1
A1 A1
A1
A1 A1
A1A1
A1 A1
A1
A1
C1E
C1 C1
C1
C1
C1
C1
C1 C1E C1 C1E C1 C1 C1E C1
C1E
C1
A2E A2 A2
A2
A2 A2E
C2E
C2
C2
C2
C2E C2
X
X
X
W
W
W
W
W
W W
A2E
A2 A2
A2
A2
A2
A2E
X
X
X
A2
A2E A2
A2A2
C1
K1E
K1E
K2E
V V
V
V
D DE
KE
X
W
W
C1
C1E C1
C1 C1E
C1
C1
C1
W W
W
W
M
D
M
ELEC WEST 1
129A
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
MATCH LINE
SEE C4/E-102
C4 C4E
C4 C4
C4E C4
LP1-1-3
LP1-1-2
LP1-1-1
LP1-1-5 LP1-6-21
LP1-2-5
VP-2
LP1-1-7
LP1-2-1
X
4 5
UP
UP
DN
LP1-1-9
S1 S2
LP1-1-11
UP
A1
C1E
C1
C4
C4
D
DE
DED D
D DE
C1E
C1
(VIA LCP)
(VIA LCP)
C1 C1 C1E
MEN
134A
LP1-1-6
LP1-1-4 LP1-2-3
C1
SF W/S
CATM ADMIN
C1
MM
MM
MM
M
MM 1
/8
M
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:4
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-101
100% B3 SUBMITTAL
P A
R T
IA
L L
IG
H
T
IN
G P
L A
N
B A
S E
M E
N T
/F
IR
S T
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR LIGHTING FIXTURE SCHEDULE.
3. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
4. EMERGENCY LIGHTING CONTROLLED VIA
OCCUPANCY/VACANCY SENSORS SHALL BE CONNECTED TO
THE BUILDING FIRE ALARM SUCH THAT ACTIVATION OF THE
BUILDING FIRE ALARM SYSTEM BRINGS LIGHTING ON TO 100%
OUTPUT REGARDLESS OF SWITCH POSITION.
SCALE: 1/8" = 1'-0"A1
ELECTRICAL LIGHTING PLAN - PARTIAL FIRST/ BASEMENT
KEY KEY DESCRIPTION
1 SWITCH SHALL BE SURFACE
MOUNTED.
2 FIXTURES IN THIS ROOM SHALL BE
SURFACE MOUNTED TO CAGE.
3 CIRCUIT CONTINUED TO A1/E-102.
4 CIRCUIT CONTINUED TO C4/E-102.
5 CIRCUIT CONTINUED TO C4/E-104.
6 CIRCUIT UP TO UPPER LOBBY.
7 SURFACE MOUNT FIXTURE TO
UNISTRUT(BASIS OF DESIGN). REFER
TO DETAIL A4/E-502.
SCALE: 1/8" = 1'-0"A5
ELEVATOR SHAFT ELEVATION
D3
VS VS
VS
VS VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
3 3
KEYNOTES:
16 17 18 19 21 23 2420 22
A
B
D
C
E
F
G
H
19a
MECHANICAL
PPE TRAINING BAG
STORAGE
COMMANDER
OPERATIONS
OFFICERS
CEM
PERSONNEL SUPER
WOMEN
HUDDLE / STORAGE
SHARED TESTING
RECRUITING
STORAGE
107A
RECRUITING
SUPERVISOR
FINANCIAL
MANAGEMENT
OFFICER
FINANCE C/S OFC
103A
ID CARDS
RECRUITING
CONSULT
RETENTION
102A
FSS HUDDLE
110A
EDUCATION &
TRAINING OFFICE
STORAGE
FSS OPEN OFFICE
RECRUITING OPEN
OFFICE
FSS C/S
FINANCE OPEN
OFFICE
FIN/ REC CORRIDOR
EAST STAIR
EAST VEST
102B
FSS CORRIDOR
JAN
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
A1
A1
A1
A1
A1E
A1E
A1
A1 A1
A1A1
A1 A1
A1
A1
A2
A2A2
A2
A2E
A2E
A1E
A1
C2E C2
C2
C2
X
A1 A1
A1
A1
A1 A1E
A1
A1E
A1E
A1 A1A1
X
C1E C1
X C1C1E
A1 A1 A1
A1A1A1A1
A1E
A1
A1
A1E
A1E
A1
A1
A1
A1 A1
A1
A2
A2E A2
A2 A2
A2E
W
WW
W
W
W
C2E
D DE
D
D
KE
D
A2
A2 A2E
A2 A2
A2
A1
A2E A2
C1 C1E
C1 C1
V
V
X
X
LP1-2-6
LP1-2-4
W
ELEC EAST 1
110B
UP
C4E
C4E
C4E
C4
C4
C4
C4E
C4
X
X
D
DE
DE D
A1
A1
A1
INSTALLATION
PERSONNEL
READINESS
118A
LP1-2-7
C2
C2 C2E
C2
WE
STEAM ROOM
12' 13'10' 15'
VAULT
016A
ELECTRICAL
MATCH LINE
SEE A1/E-101
C1E C1
WE
WE
MATCH LINE
SEE A1/E-101
C1E
DE
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:5
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-102
100% B3 SUBMITTAL
P A
R T
IA
L L
IG
H
T
IN
G P
L A
N
F
IR
S T
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR LIGHTING FIXTURE SCHEDULE.
3. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
4. EMERGENCY LIGHTING CONTROLLED VIA
OCCUPANCY/VACANCY SENSORS SHALL BE CONNECTED TO
THE BUILDING FIRE ALARM SUCH THAT ACTIVATION OF THE
BUILDING FIRE ALARM SYSTEM BRINGS LIGHTING ON TO 100%
OUTPUT REGARDLESS OF SWITCH POSITION.
SCALE: 1/8" = 1'-0"A1
ELECTRICAL LIGHTING PLAN - PARTIAL FIRST FLOOR
SCALE: 1/8" = 1'-0"B4
ELECTRICAL LIGHTING PLAN - SUB BASEMENT
SCALE: 1/8" = 1'-0"C4
ELECTRICAL LIGHTING PLAN - BASEMENT ELECTRICAL ROOM
KEY # DESCRIPTION
1 CIRCUIT CONTINUED TO A1/E-101.
2 CIRCUIT CONTINUED TO B4/E-102.
3 CIRCUIT CONTINUED TO A1/E-102.
4 SWITCH SHALL BE SURFACED MOUNTED.
5 SURFACE MOUNT FIXTURE TO UNISTRUT(BASIS OF
DESIGN). REFER TO DETAIL A4/E-502.
REFREF
VS
VS
VS
VS
VS
VS
VS VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VS
VSVSVSVS
VS
VS
VS VS
VS
VS
VS VS VS
D a
D V
S
VS
D
D
3D 3D
3 3
3D3D c b a
D b
VS
VS
4a 4b 4c
3 3 3
D a b c
OS
1 2 4 6 7 8 9 16
12' 13'10' 15'
A
B
D
C
E
L'
K'
J'
H'
G'
F'
6a
F
G
H
9' 16'
E'
MSG COMMANDER
230B
MSG DEPUTY
COMMANDER
230C
CONTRACTING
SUPER
229A
MSG FIRST
SERGEANT
230E
MSG CHIEF
230D
TELECOM ROOM
COMMAND POST
224B
MEN
WOMEN
MULTIMEDIA
STUDIO/STORAGE
231B
IGI 2
MULTI PURPOSE
ROOM A
160A
STORAGE
160D
WOMEN
BREAK ROOM
SMALL
CONFERENCE
MEN
IGI 1
JAG 2
JAG 1
PUBLIC AFFAIRS
OIC
231A
SECOND FLOOR
CONFERENCE
CONTRACTING
OPEN OFFICE
MSG OPEN OFFICE
PUBLIC AFFAIRS
ADMIN OPEN
OFFICE
UPPER LANDING
ASSEMBLY
LANDING
156WEST STAIR
MSG CORRIDOR
IGI 2
KE
KE
A1 A1 A2
A2
A2E
A1 A1 A1 A1 A2
A2
A1 A1
A1A1
A2E
C1E C2
A2E
A2 A2
A2
A1 A1
A2E
C1EX
X
A1
A1 A1
A1
A1EA1E
D D
D
C1C1C1E
D
D
D
D
D
A1
C2E
C2
C2E
C2 C2
C2C2E
C2 C2
A1A1
A1 A1
A1A1
A1 A1
A1A1
C1
C1E
C1
A1E
A1
A1E
A1
A1 A1E
A1
A1 A1
A1 A1
A1E
A1A1
A1E
A1E
A1
JAN
223A
A2
C2E C2
C2E C2
C2
C2 C2E
C2EC2C2C2E
C2
V
V V
V
K2E
K2E
K2E
VV
V V
X
XX
H
H
M
X
M M
MATCH LINE
SEE C4/E-104
MATCH LINE
SEE C4/E-104
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
C3 a
C3 a
C3 b
C3 a
C3E a
C3 b
C3 b
C3E b
LP2-2-1
AV CLOSET
160C
LP2-1-1
LP2-1-3
DN
DN
DN
J
A1 A1E A1 A1E A1 A1E
A1A1A1A1EA1A1E
A1 A1 A1 A1 A1E A1
A1E
A1A1A1EA1A1
C2
C1
A1
CP-1
LP2-1-5
C1E
DD
D
D D
D
M
C2
MULTI PURPOSE
ROOM B
160B
KEYNOTES:
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:5
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-103
100% B3 SUBMITTAL
P A
R T
IA
L L
IG
H
T
IN
G P
L A
N
S E
C O
N D
F L O
O R
/A S
S E
M B
L Y
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/8" = 1'-0"A1
ELECTRICAL LIGHTING PLAN - PARTIAL SECOND FLOOR/ ASSEMBLY
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR LIGHTING FIXTURE SCHEDULE.
3. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
4. EMERGENCY LIGHTING CONTROLLED VIA
OCCUPANCY/VACANCY SENSORS SHALL BE CONNECTED TO
THE BUILDING FIRE ALARM SUCH THAT ACTIVATION OF THE
BUILDING FIRE ALARM SYSTEM BRINGS LIGHTING ON TO 100%
OUTPUT REGARDLESS OF SWITCH POSITION.
KEY # DESCRIPTION
1 CIRCUIT CONTINUED TO A1/E-101.
VS VS
VS
VS VS
VS
VSVS
VS
VS
VS VS
VS
D
D
VS
VS
VSVS
VS
3D3D3
16 17 18 19 21 23 2420 22
A
B
D
C
E
F
G
H
19a
WING COMMANDER
211C
COMMAND
CONFERENCE
EXECUTIVE
SUPPORT
211B
VICE COMMANDER
211A
COMMAND JAG (3)
211F
COMMAND CHIEF
MASTER SERGEANT
211EMEN
WOMEN
SAFETY OFFICER
E/O 2
E/O 1
WING PLANS
OFFICER
INSPECTOR
GENERAL
HRA
DDR
OPEN OFFICE
COMMAND SUITE
EAST STAIR
IGQ
CLOS
211D
KE
KE
A1 A1
A1 A1
A1 A1
A1 A1
A1E
A1
A1 A1
A1
A1E
A1 A1 A1 A1
A1
A1
A1E
A1 A1
A1 A1
A1
A1
A1
A1
A1A1 A1
A1 A1 A1 A1
A1A1
C2E C2 C2 C2
C2
C2E
V V
VV
C2E
C1
C1 C1
A2E A2 A2
A2EA2A2
A2E A2
A2A2
A2 A2E
A2
A2E A2
A2
A2E
A2
C1E
C1E
C1
A2
A2
D
D
D
X X
X
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
M A
TC
H
L
IN
E
S E
E A
1/ E
-1
LP2-2-3
LP2-2-5
IGI STAFF
205W
DN
D D
D
D
D
D
D
D
C2E
A1
COMMAND
CORRIDOR
12' 13'10' 15'
L'
9' 16'
WE
MATCH LINE
SEE A1/E-103
MATCH LINE
SEE A1/E-103
KEYNOTES:
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 8 168
1/8"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:0
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-104
100% B3 SUBMITTAL
P A
R T
IA
L L
IG
H
T
IN
G P
L A
N
S E
C O
N D
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/8" = 1'-0"A1
ELECTRICAL LIGHTING PLAN - PARTIAL SECOND FLOOR
SCALE: 1/8" = 1'-0"C4
ELECTRICAL LIGHTING PLAN - ASSEMBLY ENTRY
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR LIGHTING FIXTURE SCHEDULE.
3. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
4. EMERGENCY LIGHTING CONTROLLED VIA
OCCUPANCY/VACANCY SENSORS SHALL BE CONNECTED TO
THE BUILDING FIRE ALARM SUCH THAT ACTIVATION OF THE
BUILDING FIRE ALARM SYSTEM BRINGS LIGHTING ON TO 100%
OUTPUT REGARDLESS OF SWITCH POSITION.
KEY # DESCRIPTION
1 CIRCUIT CONTINUED TO A1/E-101.
1 2 4 6 7 8 9 16 17 18 19 21 23 24
A
B
D
C
E
L'
K'
J'
H'
G'
F'
6a
F
G
H
E'
19a
PPE TRAINING BAG
STORAGE
MECHANICAL
COMMANDER
OPERATIONS CHIEF
RECORDS STAGING/
STORAGE
CEM
SECOND OFFICER
PLANS &
RESOURCES CHIEF
SECURE STORAGE
(CRYPTO)
STAN/EVAL
COMM OPEN OFFICE
ITE
STAGING/STORAGE
MEN
WEST STAIR
SF COMMANDER
SF FIRST
SERGEANT
LAW
ENFORCEMENT
DESK
INFORMATION
PROTECTION CHIEF
DATA CENTER
MECHANICAL
VAULT
016A
MECHANICAL
FLIGHT CHIEFS
HOTEL W/S
TRAINING ROOM
PPE TRAINING BAG
STORAGE
EQUIPMENT
LOCKERS
WEAPONS
CLEARING
WEAPONS
MAINTENANCE
CATM NCOIC
021A
CATM ADMIN
PPE TRAINING BAG
STORAGE
COMMANDER
OPERATIONS
OFFICERS
CEM
PERSONNEL SUPER
HUDDLE / STORAGE
SHARED TESTING
W/C 1
RECRUITING
STORAGE
107A
RECRUITING
SUPERVISOR
BUDGET OFFICE
FINANCIAL
MANAGEMENT
OFFICER
SHARED WAITING
ROOM
W/C 2
FINANCE C/S OFC
103A ID CARDS
RECRUITING
CONSULT
RETENTION
102A
ELEV MACHINE RM
FSS HUDDLE
110A
EDUCATION &
TRAINING OFFICE
STORAGE
FSS OPEN OFFICE
RECRUITING OPEN
OFFICE
FSS C/S
FINANCE OPEN
OFFICE
COMM C/S
COMM OPEN OFFICE
PROGRAM
MANAGEMENT
SF OPEN OFFICE
CHIEF OF SECURITY
LOWER LANDING
SF/ CATM
CORRIDOR
SF W/S
FIN/ REC CORRIDOR
EAST STAIR
EAST VEST
102B
FSS CORRIDOR
SF/ COMM
CORRIDOR
VEST
101A
COMM CORRIDOR
ELECTRICAL
SF XO/NCO
JAN
ELEC EAST 1
110B
ELEC WEST 1
129A
SECOND OFFICER
UTC PREVENTIVE
MAINTENANCE
WOMEN
LACTATION
120A
INSTALLATION
PERSONNEL
READINESS
118A
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 16 3216
1/16"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:1
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-105
100% B3 SUBMITTAL
P H
O T
O M
E T
R
IC
P L A
N
F
IR
S T
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/16" = 1'-0"A1
PHOTOMETRIC PLAN - LEVEL 1
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR LIGHTING FIXTURE SCHEDULE.
3. REFER TO E-107 FOR LIGHTING PHOTOMETRIC SCHEDULE.
4. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
1 2 4 6 7 8 9 16 17 18 19 21 23 24
A
B
D
C
E
L'
K'
J'
H'
G'
F'
6a
F
G
H
E'
19a
CONTRACTING
SUPER
229A
CONTRACTING
OPEN OFFICE
MSG OPEN OFFICE
WEST STAIR
MEN
WOMEN
SECOND FLOOR
CONFERENCE
MSG COMMANDER
230B
MSG DEPUTY
COMMANDER
230C
MULTIMEDIA
STUDIO/STORAGE
231B
PUBLIC AFFAIRS
OIC
231A
PUBLIC AFFAIRS
ADMIN OPEN
OFFICE
COMMAND POST
224B
MSG FIRST
SERGEANT
230E
MSG CHIEF
230D
TELECOM ROOM
WING COMMANDER
211C
COMMAND
CONFERENCE
EXECUTIVE
SUPPORT
211B
VICE COMMANDER
211A
COMMAND JAG (3)
211F
COMMAND CHIEF
MASTER SERGEANT
211E
MEN
WOMEN
SAFETY OFFICER
E/O 2
E/O 1
WING PLANS
OFFICER
INSPECTOR
GENERAL
IGI 2
MULTI PURPOSE
ROOM A
160A
STORAGE
160D
WOMEN
BREAK ROOM
SMALL
CONFERENCE
MEN
HRA
DDR
IGI 1
JAG 2
JAG 1
JAG OPEN OFFICE
OPEN OFFICE
IGI STAFF
205W
COMMAND
CORRIDOR
COMMAND SUITE
EAST STAIR
UPPER LANDING
ASSEMBLY
LANDING
MSG CORRIDOR
IGQ
CLOS
211DELEC WEST 2
223B
JAN
223A
MULTI PURPOSE
ROOM B
160B
STORAGE
160D
KEY PLAN
SCALE: = 1'-0"
1 2 3 4 5
A
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
PLAN NORTH
0 16 3216
1/16"
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:2
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-106
100% B3 SUBMITTAL
P H
O T
O M
E T
R
IC
P L A
N
S E
C O
N D
F L O
O R
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
SCALE: 1/16" = 1'-0"A1
PHOTOMETRIC PLAN - LEVEL 2
GENERAL NOTES:
1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,
ABBREVIATIONS & LEGEND.
2. REFER TO E-611 FOR LIGHTING FIXTURE SCHEDULE.
3. 3. REFER TO E-107 FOR LIGHTING PHOTOMETRIC SCHEDULE.
4. DATA CENTER 128, VAULT 016A, AND TELECOM ROOM 158
SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.
1 2 3 4 5
B
C
D
SHEET ID
P a rk w a y
L a n e
S u ite
P e a c h tr e e C o rn e rs
G
A
P h o n e
-7
F a x
(6
-7
P O
N D
J O
B
S
IZ
E
A N
S I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
F
IL
E N
U M
B E
R
D A
T E
D E
S C
R
IP
T
IO
N M
A R
K
Q P
K D
E S
IG
N
S o u th
S a lin a S tr e e t
S u ite
B o x
S yr a c u s e
-0
Q P
K J
O B
ORIGINAL SHEET SIZE - ANSI D (22" X 34")
/1
/2
:5
:2
P M
B
IM
/1
N
Y A
N G
N ia g a ra
F a lls R e p a ir O
T
F a ci lit y/
N
Y A
N G
N
IA
G
A R
A M
E P
F
P v2 .r vt
E-107
100% B3 SUBMITTAL
P H
O T
O M
E T
R
IC
P L A
N R
E S
U L T
S
R E
N O
V A
T E
O P
E R
A T
IO
N
S A
N D
T R
A
IN
IN
G
F A
C
IL
IT
Y
B
U
IL
D
IN
G
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
N
IA
G A
R A
F A
L L S
A
IR
R E
S E
R V
E S
T A
T
IO
N
N E
W Y
O R
K A
IR
N
A T
IO
N
A L G
U A
R D
G L K
S C
M
S C
M
T E
H
M
A R
C H
LIGHTING PHOTOMETRIC SCHEDULE
Calculation Points Name Average Maximum Minimum Average / Minimum Maximum / Minimum
MULTI PURPOSE ROOM B 160B 29 fc 45 fc 8 fc 3.4 5.3
MULTIMEDIA STUDIO/STORAGE 232B 24 fc 29 fc 13 fc 1.8 2.2
OPERATIONS CHIEF 145 37 fc 53 fc 17 fc 2.2 3.1
OPERATIONS OFFICERS 114 29 fc 47 fc 7 fc 4.3 7.0
PERSONNEL SUPER 112 36 fc 54 fc 20 fc 1.8 2.7
PLANS & RESOURCES CHIEF 140 37 fc 54 fc 17 fc 2.1 3.1
PPE TRAINING BAG STORAGE 014 19 fc 26 fc 11 fc 1.7 2.4
PPE TRAINING BAG STORAGE 115 46 fc 55 fc 25 fc 1.8 2.2
PPE TRAINING BAG STORAGE-1 144-1 28 fc 40 fc 15 fc 1.9 2.6
PROGRAM MANAGEMENT 154 39 fc 59 fc 19 fc 2.0 3.1
PUBLIC AFFAIRS ADMIN OPEN OFFICE 232 18 fc 29 fc 5 fc 3.6 6.0
PUBLIC AFFAIRS OIC 231A 50 fc 66 fc 33 fc 1.5 2.0
RECORDS STAGING/ STORAGE 142 36 fc 45 fc 24 fc 1.5 1.9
RECRUITING CONSULT 107 46 fc 64 fc 30 fc 1.6 2.2
RECRUITING OPEN OFFICE 105 20 fc 30 fc 9 fc 2.3 3.4
RECRUITING STORAGE 107A 36 fc 45 fc 26 fc 1.4 1.7
RECRUITING SUPERVISOR 106 52 fc 68 fc 28 fc 1.9 2.5
RETENTION 102A 62 fc 82 fc 35 fc 1.8 2.3
SAFETY OFFICER 219 39 fc 56 fc 23 fc 1.7 2.5
SAFETY/IG OPEN OFFICE 205 26 fc 63 fc 6 fc 4.2 10.0
SECOND FLOOR CONFERENCE 225 40 fc 94 fc 7 fc 5.9 13.8
SECOND FLOOR CORRIDOR 15 fc 28 fc 6 fc 2.4 4.5
SECOND OFFICER 148 36 fc 55 fc 17 fc 2.1 3.2
SECURE STORAGE (CRYPTO) 141 26 fc 39 fc 5 fc 5.2 7.8
SF COMMANDER 133 36 fc 54 fc 16 fc 2.2 3.3
SF FIRST SERGEANT 132 37 fc 56 fc 17 fc 2.2 3.3
SF OPEN OFFICE 152 19 fc 38 fc 3 fc 6.1 11.7
SF XO/NCO 151 45 fc 62 fc 23 fc 2.0 2.7
SF/ CATM CORRIDOR 011 11 fc 20 fc 2 fc 4.4 8.3
SF/ COMM CORRIDOR 129 12 fc 22 fc 2 fc 5.2 9.5
SHARED TESTING 109 24 fc 42 fc 7 fc 3.4 6.0
SHARED TESTING CORRIDOR 12 fc 23 fc 3 fc 4.3 8.3
SHARED WAITING ROOM 101 36 fc 66 fc 10 fc 3.7 6.9
SMALL CONFERENCE 161 0 fc 0 fc 0 fc 0.0 0.0
STAN/EVAL 138 42 fc 63 fc 19 fc 2.2 3.2
STORAGE 120 44 fc 56 fc 29 fc 1.5 1.9
STORAGE 160D 38 fc 46 fc 25 fc 1.5 1.9
TELECOM ROOM 158 33 fc 55 fc 14 fc 2.3 3.9
TRAINING ROOM 019 17 fc 32 fc 6 fc 2.8 5.2
TRAP 224A 37 fc 49 fc 28 fc 1.3 1.7
UPPER LANDING 201 19 fc 28 fc 13 fc 1.5 2.1
UTC PREVENTIVE MAINTENANCE 149 37 fc 58 fc 18 fc 2.1 3.3
VAULT 016A 27 fc 38 fc 12 fc 2.3 3.3
VEST 101A 23 fc 34 fc 15 fc 1.6 2.3
VICE COMMANDER 211A 44 fc 62 fc 21 fc 2.1 3.0
W/C 1 127 31 fc 37 fc 24 fc 1.3 1.6
W/C 2 126 36 fc 39 fc 33 fc 1.1 1.2
WAITING ROOM COORIDOR 20 fc 36 fc 4 fc 4.9 9.0
WEAPONS CLEARING 016 26 fc 39 fc 11 fc 2.4 3.6
WEAPONS MAINTENANCE 020 26 fc 83 fc 4 fc 6.9 22.2
WEST STAIR 8 fc 11 fc 4 fc 1.8 2.5
WING COMMANDER 211C 37 fc 52 fc 17 fc 2.2 3.1
WING PLANS OFFICER 218 47 fc 65 fc 25 fc 1.9 2.6
WOMEN 122 26 fc 48 fc 13 fc 2.1 3.8
WOMEN 163 34 fc 43 fc 22 fc 1.6 2.0
WOMEN 214 53 fc 69 fc 31 fc 1.7 2.2
WOMEN 226 48 fc 58 fc 32 fc 1.5 1.8
LIGHTING PHOTOMETRIC SCHEDULE
Calculation Points Name Average Maximum Minimum Average / Minimum Maximum / Minimum
ASSEMBLY LANDING 156 21 fc 29 fc 12 fc 1.8 2.5
AV CLOSET 160C 37 fc 43 fc 31 fc 1.2 1.4
BREAKROOM 159 19 fc 29 fc 4 fc 5.0 7.7
BUDGET OFFICE 125 29 fc 51 fc 10 fc 3.0 5.2
CATM ADMIN 021 28 fc 57 fc 8 fc 3.3 6.7
CATM NCOIC 021A 26 fc 40 fc 12 fc 2.2 3.4
CEM 111 42 fc 59 fc 21 fc 2.0 2.8
CEM 147 30 fc 44 fc 17 fc 1.7 2.5
CHIEF OF SECURITY 153 48 fc 66 fc 26 fc 1.8 2.5
CLOS 211D 26 fc 27 fc 26 fc 1.0 1.0
COMM C/S 155 25 fc 37 fc 15 fc 1.7 2.5
COMM CORRIDOR 139 13 fc 32 fc 2 fc 7.9 19.5
COMM OPEN OFFICE 136 22 fc 39 fc 4 fc 6.0 10.9
COMM OPEN OFFICE 150 18 fc 35 fc 4 fc 4.5 8.7
COMMAND CHIEF MASTER SERGEANT 211E 34 fc 51 fc 16 fc 2.2 3.3
COMMAND CONFERENCE 210 51 fc 75 fc 17 fc 3.0 4.4
COMMAND CORRIDOR 202 30 fc 60 fc 8 fc 3.8 7.6
COMMAND JAG (3) 211F 34 fc 50 fc 13 fc 2.6 3.8
COMMAND POST 224B 34 fc 60 fc 9 fc 3.8 6.7
COMMAND SUITE 211 24 fc 67 fc 3 fc 7.8 21.5
COMMANDER 113 30 fc 52 fc 6 fc 5.4 9.3
COMMANDER 146 30 fc 51 fc 13 fc 2.4 4.0
CONTRACTING OPEN OFFICE 229 33 fc 56 fc 14 fc 2.3 3.9
CONTRACTING SUPER 229A 32 fc 49 fc 15 fc 2.1 3.3
CONTROL PANEL 224C 67 fc 90 fc 36 fc 1.9 2.5
DATA CENTER 128 35 fc 48 fc 16 fc 2.2 3.0
DDR-2 208-2 50 fc 68 fc 29 fc 1.7 2.3
E/O 1 215 47 fc 64 fc 26 fc 1.8 2.5
E/O 2 216 39 fc 56 fc 23 fc 1.7 2.5
EAST STAIR 8 fc 11 fc 2 fc 3.5 5.2
EAST VEST 102B 30 fc 40 fc 19 fc 1.5 2.1
EDUCATION & TRAINING OFFICE 108 36 fc 50 fc 16 fc 2.2 3.1
ELECTRICAL 017 36 fc 58 fc 15 fc 2.5 4.0
ELEV MACHINE RM 023 21 fc 26 fc 16 fc 1.4 1.7
EQUIPMENT LOCKERS 015 26 fc 35 fc 11 fc 2.3 3.0
EXECUTIVE SUPPORT 211B 42 fc 58 fc 25 fc 1.7 2.4
FIN/ REC CORRIDOR 102 11 fc 27 fc 3 fc 3.2 8.3
FINANCE C/S OFC 103A 50 fc 67 fc 26 fc 1.9 2.5
FINANCE OPEN OFFICE 123 17 fc 31 fc 4 fc 4.1 7.4
FINANCIAL MANAGEMENT OFFICER 124 35 fc 50 fc 19 fc 1.9 2.7
FLIGHTS CHIEFS 022 16 fc 39 fc 4 fc 4.0 9.7
FSS C/S 103 40 fc 55 fc 15 fc 2.7 3.7
FSS CORRIDOR 110 15 fc 31 fc 2 fc 9.3 19.7
FSS HUDDLE 110A 25 fc 38 fc 13 fc 2.0 3.1
FSS OPEN OFFICE 118 18 fc 51 fc 2 fc 8.9 25.7
HOTEL W/S 012 28 fc 46 fc 10 fc 2.8 4.7
HRA 209 49 fc 64 fc 27 fc 1.8 2.4
HUDDLE / STORAGE 117 18 fc 46 fc 3 fc 5.2 13.7
ID CARDS 104 51 fc 67 fc 30 fc 1.7 2.2
IGI 1 203 60 fc 75 fc 35 fc 1.7 2.2
IGI 2 204 50 fc 66 fc 31 fc 1.6 2.1
IGQ 206 50 fc 64 fc 27 fc 1.9 2.4
INFORMATION PROTECTION CHIEF 130 37 fc 55 fc 17 fc 2.2 3.3
INSPECTOR GENERAL 207 39 fc 56 fc 23 fc 1.7 2.5
INSTALLATION PERSONNEL READINESS 118A 56 fc 71 fc 39 fc 1.4 1.8
ITE STAGING/STORAGE 137 32 fc 44 fc 19 fc 1.7 2.4
JAG 1 222 36 fc 53 fc 19 fc 1.9 2.8
JAG 2 221 45 fc 62 fc 23 fc 1.9 2.7
JAG OPEN OFFICE 220 21 fc 31 fc 11 fc 1.9 2.9
JAN 119 44 fc 60 fc 26 fc 1.7 2.3
JAN 223A 20 fc 21 fc 20 fc 1.0 1.0
LACTATION 120A 48 fc 76 fc 27 fc 1.8 2.8
LAW ENFORCEMENT DESK 131 37 fc 56 fc 17 fc 2.2 3.3
LOWER LANDING 010 27 fc 42 fc 15 fc 1.8 2.8
MECHANICAL 018…