190067_ATT11_Revised _Drawings.pdf

PDF 23 MB Posted

Attached to
Tinker AFB MACBOA WWYK190067 Repair Fire Suppression System B2136
Solicitation number
WWYK190067
Issued by

About this file

These are detailed architectural and engineering drawings for a repair project of the fire suppression system at Maintenance Hangar B2136 at Tinker Air Force Base, Oklahoma. The comprehensive set of technical drawings includes multiple sheets covering demolition and new work across first, second, and third floor areas, with specific focus on fire alarm, mass notification, fire suppression, electrical, and mechanical systems. The project involves replacing existing fire protection infrastructure, including sprinkler systems, fire alarm equipment, and associated components across three building areas (Areas A, B, and C), with detailed specifications for wet and dry pipe sprinkler systems, alarm check valves, and system modifications to meet current safety standards and UFC (Unified Facilities Criteria) requirements.

The drawings outline a phased approach to system replacement, with key technical details including hydraulic design requirements, system type specifications (wet and dry), minimum density calculations, and installation guidelines. The project scope encompasses demolition of existing fire suppression elements, installation of new alarm check valves, sprinkler mains, branch lines, and integration with existing building systems. The estimated project value is between $5,000,000 and $10,000,000, set aside for small businesses, with a site visit mandatory for Tinker AFB Multiple Award Construction (MAC) BOA contract holders scheduled for January 23, 2025, and request for information (RFI) due by January 30, 2025.

View the file

Other files

File Type Posted
OK20250049- REV 4-19SEP2025-WD.pdf PDF
SOW Revision 1- 25 Aug.pdf PDF
Solicitation Amendment FA813725R00120003 SF 30.pdf PDF
Solicitation Amendment FA813725R00120002 SF 30.pdf PDF
WWYK190067_GOVT RESPONSE TO RFI 02 COR.pdf PDF
190067_ATT9_SOW-Rev 1.pdf PDF
190067_GOVT RESPONSE TO RFI 1 SECOND VISIT SIGNED COR.pdf PDF
Solicitation Amendment FA813725R00120001 SF 30.pdf PDF
Solicitation Amendment - FA813725R00120001.pdf PDF
OK20250049- REV 1-14MAR2025-WD.pdf PDF
Solicitation - FA813725R0012.pdf PDF
190067_ATT8_Liquidated_Damages_CO Signed.pdf PDF
WWYK190067-Site Visit Sign in Sheet- 17 April.pdf PDF
Revised SOW.pdf PDF
WWYK190067-Sign Visit Sign in Sheet- 23 Jan.pdf PDF
190067_ATT10_Submittal_Register.pdf PDF
190067ATT 12.a.iiiFCSpecs.pdf PDF
00 70 00.pdf PDF
01 50 00.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 42 00.pdf PDF
190067 PREBID RFI GOVERNMENT RESPONSE_7APR COR.pdf PDF
01 32 16.00 20.pdf PDF
01 78 23.pdf PDF
00 72 00.pdf PDF
01 78 00.pdf PDF
00 80 00.pdf PDF
190067_Drawings.zip ZIP file
TinkerGenReqSpecsNov22ChLog.pdf PDF
00 71 00.pdf PDF
01 33 00.pdf PDF
00 80 05.pdf PDF
01 33 16.00 10.pdf PDF
01 45 00.00 10.pdf PDF
190067_ATT10_Submittal Register.pdf PDF
190067_ATT3_Green Statement_Signed.pdf PDF
190067_ATT11_IFC_Drawings.pdf PDF
WWYK190067 SITE VISIT PICTURES.pdf PDF
Wage Determination.pdf PDF
190067_ATT9_SOW.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2135 2123

32101

RU

NW

AY

/36

RUNWAY 13/31

TA

XI

W

AY

G

TAXIW

AY H

TAXIWAY B

TAXIWAY C

TAXIWAY M

TA

XI

W

AY

K

TAXIWAY E

TAXIWAY A

TA

XIW

AY EE

TAXIWAY F

TAXIWAY D

TAXIWAY E

TAXIWAY J

TA

XI

W

AY

G

TAXIWAY A

TAXIW

AY H

TAXIWAY C

TAXIWAY D

TAXIWAY EE

TAXIWAY F

Elm Creek

Crutcho Creek

Kuhlman Creek

Soldier Creek

Kuhlman Creek

Elm Creek

East Crutcho Creek

Elm Creek

El m

Cr ee k

Elm Creek

Elm Creek

Elm Creek

Elm Creek

Ku hlm an Cr ee k

Ea st

Cr utc ho C ree k

Elm Cree k

West Crutcho Creek W es t C ru tch o C re ek

Elm Creek

Soldier Creek

Elm Creek

Soldier CreekSoldier Creek

Ea st

Cr utc ho C re ek

Elm Creek

Ea st

Cr utc ho C re ek

East Crutcho Creek

Soldier Creek

So ldi er Cr ee k

East C rutcho Creek

Soldier Creek

Soldier Creek

So ldi er C re ek

East Crutcho Creek

416506

11401128

59035909

838837

62509

62512

62525

99999

62543

71086

53902

50414

55300

56601

61019

62501

45134

62503

61289

62542

15904

15908

15904

15908

62502

41046

62501

62514

62501

41157

45815

40592

62522

15930

11824

3 10

62540

61089

62528

62523

62501X

43774

62516

3592135916

32101

930G

948-E

911-E

948-W

911-W

33001

35913

65672

930S

43609

42116

62517

62515

62526

62527

62513

62501OK

11289

62501

15930

15908

15904

15908

15904

61018

71089

45134

96022

43120

44045

43610

41163

15930

Ea st

Dr

SE 59th St.

St aff

D r.

5th Ave

W ar eh ou se R d.

7th St.

Mc Na rn ey

A ve

Mitchell Ave

Co ok

A ve

W es t D r.

Extender Dr.

5th Ave.

Globemaster Dr.

Ai r D ep ot

Mercury Rd.

Po nd

R d.

"C " A ve

Hi llto p R d.

"M " A ve

Doolittle Ave

W hit e D r.

Ba ll P ar k R d.

6th St.

Po we rh ou se D r.

Int ru de r D r.

Holden Dr.

Vanaman Rd.

1st St.

Arnold St.

SE 74th St

Ai r D ep ot

Patrol Rd.

Reserve Rd.

"A " A ve

Mu nit ion s R d.

"B " A ve

"H " A ve

Al er t R d.

"E "A ve

Sentry Rd.

34th St.

Twining Dr.

Jo ne s

To we r R d.

Vanaman Rd.

Ind us tria l B lvd

So uth

S t.

1st St.

Do oli ttle A ve

Pi cn ic Rd

Ja me s D r.

W olf e D r.

Ai r D ep ot

"D " A ve

Perimeter Rd.

Rapcon Rd.

Reserve Rd

"L " A ve

"F " A ve

1st St.

Br ow n D r.

Ol d A ir D ep ot

Airey Dr.

General Motors Dr

Bradley Dr.

Entrance Road "C"

Entrance Road "A"

"C " A ve

Vandenberg Dr.

Do rm ito ry

Rd

Dormitory Rd.

Chennault Dr.

Mi tch ell A ve

Spaatz Dr.

En gin e T es t D r.

3rd Ave.

"D " D riv e

Joint STARS Dr.

Ai r D ep ot

Bl vd

Turbine Dr. Turbine Dr.

Central Plant Dr.

6th St.

Falcon Dr.

Blac kbi rd D r.

W ey lan d L oo p

Pegasus Dr.

Thunderbolt D r.

Munitions Rd. Ext.

Codding Rd.

Starlifter Dr.

Chidlaw Ct.

Co rsa ir D r.

Rap tor

Ct.

Ni gh t H aw k C t.

Ph an tom D r.

Fr an kli n

Sk ym as ter

D r.

Spaatz Ct.

La wr en ce

Mu nd ell

Nabors Dr.

Mc Ni ck le

Mi lle r D r.

Ta il F ea the r D r.

Air ey

Ci r.

Smith Ct. Raven Ct.

Air Dep ot Ai r D ep ot

1st St.

TAXIWAY F

Ra w li ng s A ve

Mitc he ll Av e.

Mercury Rd.

Ra ily ar d R d.

He rcu les R d.

TINKER AFB, OK

VICINITY MAP

BASE OPERATIONS B240

CONTRACTING B3

GOTT GATE

TINKER GATE

PASS & ID

B6611

HRUSKOCY GATE

EAKER

GATE

FIRE DEPARTMENT B117

VANCE GATE

LIBERATOR GATE

HOPE

GATE

LEGEND

CONTRACTOR

HAUL ROUTE

LANCER GATE

TRUCK GATE

PIAZZA GATE

BASE CIVIL

ENGINEER

B400

PROJECT

LOCATION

REVIEWED BY:

REVIEWED BY:

USING AGENCY:

ASBESTOS EVALUATION:

SAFETY:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

DATE:

INDUSTRIAL HYGIENE:

DATE:

PROJECT DRAWING INDEX SIGNATURES

CORROSION ENGINEER: (CECE)

CE OPERATIONS: (CECO)

COMMUNICATIONS: (COMM)

CHIEF ENGINEER DIR: (CECE)

CHIEF DESIGN BRANCH: (CECE)

DESIGN MANAGER: (CECE)

ZONE MANAGER:

CONSTRUCTION MANAGEMENT: (CECE)

ENVIRONMENTAL:

BASE CIVIL ENGINEER: (CE)

FIRE DEPARTMENT: (CEFT)

GENERAL

G-001 SHEET INDEX AND VICINITY MAP

SHT. SHEET TITLE

WWYK190067

REPAIR FIRE SUPPRESSION

SYSTEM, MAINT HANGAR

B2136

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EP

AI

R

F

IR

E

SU

PP

R

ES

SI

O N

SY

ST

EM

, M

AI

N

T H

AN

G

ER

B

N

O

VE

M

BE

R

H D

R

F-001 FIRE SUPPRESSION GENERAL NOTES

F-002 FIRE ALARM AND MASS NOTIFICATION GENERAL NOTES

MECHANICAL

M-001 MECHANICAL SYMBOLS, LEGEND, AND ABBREVIATIONS

M-101 MECHANICAL OVERALL FIRST FLOOR PLAN

M-401 MECHANICAL ENLARGED FLOOR PLANS - DEMOLITION AND NEW WORK

M-501 MECHANICAL DETAILS AND SCHEDULES

FIRE PROTECTION

G-002 GENERAL PHASING PLAN

G-100 GENERAL CODE ANALYSIS

G-101 GENERAL LIFE SAFETY PLAN - FIRST FLOOR OVERALL

G101A GENERAL LIFE SAFETY PLAN - FIRST FLOOR AREA A

G101B GENERAL LIFE SAFETY PLAN - FIRST FLOOR AREA B

G101C GENERAL LIFE SAFETY PLAN - FIRST FLOOR AREA C

G-102 GENERAL LIFE SAFETY PLAN - SECOND FLOOR

G-103 GENERAL LIFE SAFETY PLAN - THIRD FLOOR

G-104 GENERAL CODE COMPLIANCE SITE PLAN

ELECTRICAL

E-001 ELECTRICAL SYMBOLS, LEGENDS, AND ABBREVIATIONS

FD101 FIRE ALARM - FIRST FLOOR - AREA A - DEMOLITION

FD102 FIRE ALARM - FIRST FLOOR - AREA B - DEMOLITION

FD103 FIRE ALARM - FIRST FLOOR - AREA C - DEMOLITION

FD104 FIRE ALARM - SECOND FLOOR - DEMOLITION

FD105 FIRE ALARM - THIRD FLOOR - AREA A - DEMOLITION

FD106 FIRE ALARM - THIRD FLOOR - AREA B - DEMOLITION

FD107

FD108

FD109

FD110

FIRE ALARM - THIRD FLOOR - AREA C - DEMOLITION

FIRE SUPPRESSION - FIRST FLOOR - AREA A - DEMOLITION

FIRE SUPPRESSION - FIRST FLOOR - AREA B - DEMOLITION

FIRE SUPPRESSION - FIRST FLOOR - AREA C - DEMOLITION

FA101 FIRE ALARM AND MASS NOTIFICATION FIRST FLOOR AREA A

FA102 FIRE ALARM AND MASS NOTIFICATION FIRST FLOOR AREA B

SHT. SHEET TITLE

FA103 FIRE ALARM AND MASS NOTIFICATION FIRST FLOOR AREA C

FA104 FIRE ALARM AND MASS NOTIFICATION SECOND FLOOR

FA105 FIRE ALARM AND MASS NOTIFICATION THIRD FLOOR AREA C

FA601 FIRE ALARM SEQUENCE OF OPERATION

FX101 FIRE SUPPRESSION - FIRST FLOOR - AREA A - NEW WORK

FX102 FIRE SUPPRESSION - FIRST FLOOR - AREA B - NEW WORK

FX501 FIRE SUPPRESSION DETAILS

E-100 ELECTRICAL OVERALL PLAN - NEW WORK

ED100 ELECTRICAL OVERALL PLAN - DEMOLITION

ED101 ELECTRICAL ENLARGED PLANS - DEMOLITION

E-101 ELECTRICAL ENLARGED PLANS - NEW WORK

E-102 ELECTRICAL SECOND FLOOR - NEW WORK

E-601 ELECTRICAL ONE-LINE DIAGRAM

G

EN

ER

AL

G-001

AS JR

M

BP

SH

EE

T

IN

D

EX

A N

D

VI

C

IN

IT

Y

M

AP

FA502 FIRE ALARM DETAIL - MONACO ANTENNA DETAIL

FA501 FIRE ALARM AND MASS NOTIFICATION DETAILS

FA602 FMCU AND RSFACU RISER DIAGRAM

FX401 FIRE SUPPRESSION ENLARGED FLOOR PLANS - NEW WORK

E-602 ELECTRICAL SCHEDULES

FD501 FIRE PROTECTION DEMOLITION PHOTOS

FD111 FIRE SUPPRESSION - SECOND FLOOR - AREA C - DEMOLITION

FD112 FIRE SUPPRESSION - THIRD FLOOR - AREA A - DEMOLITION

FD113 FIRE SUPPRESSION - THIRD FLOOR - AREA B - DEMOLITION

FD114 FIRE SUPPRESSION - THIRD FLOOR - AREA C - DEMOLITION

FX103 FIRE SUPPRESSION - FIRST FLOOR - AREA C - NEW WORK

FX104 FIRE SUPPRESSION - SECOND FLOOR - AREA C - NEW WORK

FX105 FIRE SUPPRESSION - THIRD FLOOR - AREA C - NEW WORK

CIVIL

C-501 CIVIL DETAILS

ARCHITECTURAL

A-101 FLOOR PLAN FIRST FLOOR AREA A

A-102 FLOOR PLAN FIRST FLOOR AREA B

MEN

WOMEN

CORRIDOR

SECURITY

VAULT

BACKSHOP

SUPPORT CELLS

GENERATOR

SHEDGENERATOR

SHED

TEXAS TOWER

POCKET

PROD FOREMAN

OFFICE

EAST

MECH RM

EAST

ELEC RM

MEN

WOMEN

E-3 GEAR

SHOP

ELEV CTL

SCHEDULING

OPEN OFFICE

AISLE

BREAK RM

121A

AIRCRAFT

RECORDS

COMPUTER

WORK RM

AVIONICS

SHOP AREA

AVIONICS / ELEC

BACK SHOP

KITTING

AISLE

AISLE

E-3

TOOL CRIB

ELEC

BREAKER RM

KIT BREAKOUT

SHOP

ELEC /

COMM

GENERATOR

SHED

UP

F

RO

M

FI

RS

T

FIRST

LANDING

SECOND

LANDING

UP FROM

FIRST

FI

RS

T

LA

ND

IN

G

SE

CO

ND

LA

ND

IN

G

UP

UP

UP

UP

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

ELEV

UP

F

RO

M

FI

RS

T

UP

UP

FIRST

LANDING

SECOND

LANDING

UP

F

RO

M

FI

RS

T

FIRST

LANDING

SECOND

LANDING

E- 3 S

ER

VI

CE

S

SC

HE

DU

LIN

G

SE

CT

IO

N

OU

TD

OO

R

ST

OR

AG

E

RA

MP UP

A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

E

B

C

D

D.5

FIRE DEPARTMENT

STORAGE

AISLE

OFFICE

DLA

STAGING

WEST

MECH RM

AI

SL

E

AI

SL

E

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

A

E

B

C

D

D.5

M

ATC

H

LIN

E AR

EA B

M

ATC

H

LIN

E AR

EA A

MATCHLINE AREA A

MATCHLINE AREA C

MATCHLINE AREA B

MATCHLINE AREA C

M

AT

C H

LI

N

E

AR

EA

B

MATCHLINE AREA C

M

AT

C H

LI

N

E

AR

EA

A

G

EN

ER

AL

G-002

D .E

R .D

J.

M

PH

AS

IN

G

P

LA

N

GENERAL PHASING PLAN

SCALE: 1/32"=1'-0"

G-002

GENERAL PHASING NOTES:

1. THE PHASING PLAN PRESENTED IS A SUGGESTED PHASING PLAN ONLY.

THE CONTRACTOR SHALL DEVELOP A FINAL PHASING PLAN THAT

INCORPORATES THE USER REQUIREMENTS AND SHALL BE COORDINATED

WITH AND APPROVED BY THE USER AND GOVERNMENT PRIOR TO

IMPLEMENTATION.

2. NOT ALL ASPECTS OF THE SCOPE OF WORK ARE EXPLICITLY DESCRIBED

IN THIS PLAN. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO

INCLUDE ALL WORK THAT IS REQUIRED IN THE FINAL PHASING PLAN.

3. DEMOLITION AND CONSTRUCTION ACTIVITIES WILL GENERALLY TAKE

PLACE WHILE THE MAJORITY OF THE FACILITY IS OCCUPIED AND

OPERATIONAL. SYSTEM OUTAGES AND CHANGEOVERS SHALL TAKE

PLACE OVERNIGHT OR OVER THE WEEKEND WHEN UNOCCUPIED.

4. COORDINATE ALL SYSTEM OUTAGES AND DOWNTIME WITH GOVERNMENT

A MINIMUM OF 3 WEEKS IN ADVANCE.

5. CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL EXISTING

FURNITURE AND EQUIPMENT THAT IS TO REMAIN WITHIN EACH PHASE.

ALL FURNITURE OR EQUIPMENT THAT NEEDS TO BE MOVED TO

ACCOMMODATE THE WORK OCCURRING IN EACH PHASE SHALL BE DONE

BY THE GOVERNMENT. ANY FURNITURE OR EQUIPMENT DAMAGED

DURING CONSTRUCTION SHALL BE REPLACED BY THE CONTRACTOR.

6. THE MAXIMUM ALLOWABLE DOWNTIME FOR EACH PHASE IS SIX WEEKS.

CONTRACTOR SHALL UTILIZE AFTER-HOURS AND WEEKEND LABOR AS

NEEDED TO MEET THESE MAXIMUM DOWNTIME REQUIREMENTS.

7. PHASES 1, 2, 3, AND 4 MAY BE ACCOMPLISHED CONCURRENTLY TO

REDUCE OVERALL CONSTRUCTION TIME IF ALLOWED BY THE THE

GOVERNMENT.

8. AFFF FOAM TANKS AND ASSOCIATED PIPING UP TO THE PROPORTIONING

VALVE WILL BE DEMOLISHED UNDER SEPARATE AFCEC CONTRACT.

PHASE 1 DESCRIPTION:

1. CONSISTS GENERALLY OF THE REMOVAL OF THE UNDER WING MONITORS,

ASSOCIATED ABOVE GROUND PIPING TO FLOOR FLANGES, DELUGE

VALVE, RELEASING STATION AND ASSOCIATED TRIM.

2. OSCILLATING MONITOR FLOOR FLANGE AND UNDERGROUND PIPING AND

RELEASING STATION CONDUIT SHALL BE REMOVED TEN INCHES BELOW

FINISH FLOOR. EXISTING UNDERGROUND AFFF MAIN TO BE FILLED WITH

GROUT AND ABANDONED IN PLACE. GROUT SHALL BE TIED INTO EXISTING

CONCRETE SLAB. REMOVE BOLLARDS AROUND THE OSCILLATING

MONITORS.

3. REMOVE UNDER WING MONITORS AFFF FOAM TANKS ASSOCIATED TRIM.

4. REMOVE EXISTING UNDER WING MONITORS DELUGE VALVES.

PHASE 2 DESCRIPTION:

1. CONSISTS GENERALLY OF THE REMOVAL OVERHEAD FOAM WATER SPRINKLER

SYSTEM, DELUGE VALVE WITHIN DOCK ONE.

2. DEMOLISH EXISTING DET-TRONICS RELEASING PANEL SERVING DOCK ONE.

3. DEMOLISH EXISTING FLAME DETECTOR AND ASSOCIATED CONDUIT WITHIN DOCK

ONE.

4. DEMOLISH EXISTING DRY-RISER VALVE, ASSOCIATED PIPING AND SPRINKLER HEADS

WITHIN GENERATOR SHED.

5. INSTALL NEW RISER MANIFOLD WITHIN THE WEST MECHANICAL ROOM FOR THE

THREE OVERHEAD WET SPRINKLER SYSTEMS WITHIN THE HANGER AND

ADMINISTRATION WET SPRINKLER SYSTEM.

6. INSTALL NEW WET SPRINKLER SYSTEM WITHIN DOCK ONE.

7. INSTALL NEW DRY PIPE SPRINKLER SYSTEM WITHIN THE GENERATOR SHED.

8. FOLLOWING THE SUCCESSFUL FINAL INSPECTION OF THE OVERHEAD WET

SPRINKLER SYSTEM WITH THE BASE FIRE PROTECTION ENGINEER, BASE FIRE

DEPARTMENT, AND PROJECT COR CONTRACTOR MAY PROCEEDS TO PHASE 3.

PHASE 1

PHASE 1

PHASE 1

PHASE 1PHASE 1PHASE 1PHASE 1

PHASE 2

PHASE 1

PHASE 2

PHASE 1

PHASE 3 PHASE 4

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EP

AI

R

F

IR

E

SU

PP

R

ES

SI

O N

SY

ST

EM

, M

AI

N

T H

AN

G

ER

B

N

O

VE

M

BE

R

H D

R

KEYPLAN

PLAN NORTH

AP

RI

L

TI

N

KE

R P

O

LI

C Y

C H

AN

G

E

PHASE 1 PHASE 1 PHASE 1 PHASE 1

PHASE 1

PHASE 1 PHASE 3

PHASE 3 DESCRIPTION: PHASE 4 DESCRIPTION:

1. CONSISTS GENERALLY OF THE REMOVAL OVERHEAD FOAM WATER SPRINKLER

SYSTEM, DELUGE VALVE WITHIN DOCK TWO.

2. DEMOLISH EXISTING DET-TRONICS RELEASING PANEL SERVING DOCK TWO.

3. DEMOLISH EXISTING FLAME DETECTOR AND ASSOCIATED CONDUIT WITHIN DOCK

TWO.

4. DEMOLISH EXISTING DRY-RISER VALVE, ASSOCIATED PIPING AND SPRINKLER HEADS

WITHIN GENERATOR SHED.

5. INSTALL NEW DRY PIPE SPRINKLER SYSTEM WITHIN THE GENERATOR SHED.

6. INSTALL NEW WET SPRINKLER SYSTEM WITHIN DOCK TWO.

7. FOLLOWING THE SUCCESSFUL FINAL INSPECTION OF THE OVERHEAD WET

SPRINKLER SYSTEM WITH THE BASE FIRE PROTECTION ENGINEER, BASE FIRE

DEPARTMENT, AND PROJECT COR CONTRACTOR MAY PROCEEDS TO PHASE 4 MAY

BEGIN.

1. CONSISTS GENERALLY OF THE REMOVAL OVERHEAD FOAM WATER SPRINKLER

SYSTEM, AND DELUGE VALVE WITHIN DOCK THREE.

2. DEMOLISH EXISTING DET-TRONICS RELEASING PANEL SERVING DOCK THREE.

3. DEMOLISH EXISTING FLAME DETECTOR AND ASSOCIATED CONDUIT WITHIN

DOCK THREE.

4. DEMOLISH EXISTING DRY-RISER VALVE, ASSOCIATED PIPING AND SPRINKLER

HEADS WITHIN GENERATOR SHED.

5. DEMOLISH EXISTING SUPPORT AREA ALARM CHECK VALVE TO FLOOR FLANGE.

AND CAP THE FLOOR FLANGE.

6. INSTALL NEW WET SPRINKLER SYSTEM WITHIN DOCK THREE AND TEXAS

TOWER.

7. INSTALL NEW ALARM CHECK VALVE AND EXTEND TO EXISTING SUPPORT AREA

SPRINKLER MAIN.

8. INSTALL NEW DRY PIPE SPRINKLER SYSTEM WITHIN THE GENERATOR SHED.

PHASE 4

AREA C

AREA A AREA B

04/02/2025

KHENDERSON

Rectangle

KHENDERSON

Snapshot

G

EN

ER

AL

C

O D

E

AN

AL

YS

IS

G-100

D .E

R .D

. J.

M

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EP

AI

R

F

IR

E

SU

PP

R

ES

SI

O N

SY

ST

EM

, M

AI

N

T H

AN

G

ER

B

N

O

VE

M

BE

R

H D

R

AP

RI

L

TI

N

KE

R P

O

LI

C Y

C H

AN

G

E

• ROOF CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS) 1 HOUR

• FLOOR CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS)

• NONBEARING WALLS & PARTITIONS - INTERIOR

• NONBEARING WALLS - EXTERIOR SEPARATION DISTANCE 10'<X<30'

• BEARING WALLS - INTERIOR

• BEARING WALLS - EXTERIOR SEPARATION DISTANCE 10'<X<30'

• STRUCTURAL FRAME (INCLUDING COLUMNS, GIRDERS, AND TRUSSES) 2 HOUR

IBC TABLES 601 & 705.5

ALL ALLOWABLE COMBUSTIBLE MATERIALS

AS DEFINED IN SECTION 603

IBC STRUCTURAL ELEMENTS:

FIRE RESISTANCE REQUIREMENTS

• ALLOWABLE BUILDING HEIGHT AND STORIES: 180 FT; 12 STORIES

• ACTUAL BUILDING HEIGHT AND STORIES: 75 FT; THREE (3) STORY

UFC 4-211-01 § 3-3.1.6 BUILDING

HEIGHT AND NUMBER OF STORIES

• ALLOWABLE BUILDING AREA: UNLIMITED AREA

• ACTUAL BUILDING AREA: 171,080 SQ. FT

ALLOWABLE IBC BUILDING HEIGHT AND FLOOR AREA:

NOTES: • REPAIRS AND STORAGE OCCUR AT THE HANGAR

• FUELING AND DEFUELING PROCESSES ARE COMPLETED OUTSIDE OF THE HANGAR

• JET A FUEL IS USED FOR AIRCRAFT FUELING; CLASS II COMBUSTIBLE LIQUID

SPECIAL-PURPOSE INDUSTRIAL, STORAGE (AIRCRAFT SERVICING/STORAGE HANGAR) NFPA 101 CHAP. 40/42 PER CHAP. 43

EXISTING BUSINESS NFPA 101 CHAP. 39 PER CHAP. 43

• NFPA OCCUPANCY CLASSIFICATIONS - MULTIPLE OCCUPANCY, NONSEPARATED OCCUPANCIES NFPA 101 § 6.1.14

GROUP S-1 (AIRCRAFT HANGAR) IBC § 311.2 (STORAGE AND REPAIR)

GROUP B/S-1 (SUPPORT SPACES) IBC § 304 (BUSINESS)

• IBC OCCUPANCY CLASSIFICATIONS - MIXED USE, NONSEPARATED OCCUPANCIES IBC § 508.3

BUILDING OCCUPANCY CLASSIFICATION

• HANGAR BAYS ARE RECEIVING A RENOVATION AND ONLY NEED TO MEET EXISTING REQUIREMENTS PER NFPA 101 § 43.4.1.3.

• IN ACCORDANCE WITH UFC 3-600-01, CHAPTER 34, WHERE WORK IS PERFORMED IN EXISTING BUILDINGS IT SHALL BE

EVALUATED IN ACCORDANCE WITH CHAPTER 43 OF NFPA 101.

• BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IBC § 903.3.1.1

• BUILDING IS CONSTRUCTED USING TYPE IB CONSTRUCTION PER IBC § 602 & TABLE 601; TYPE II (222) PER NFPA 220

BUILDING DESCRIPTION (EXISTING BUILDING GENERAL INFORMATION)

ARCHITECTURAL BARRIERS ACT (ABA), N/A (WAIVER).

ASME/ANSI A13.1- SCHEME FOR THE IDENTIFICATION OF PIPING SYSTEMS.

ETL 98-8, CHANGE 1, JUNE 25, 1998

DOD SUNDOWN POLICY FOR FOAM FIRE SUPPRESSION SYSTEMS, CHANGE 2, 2022 DEC 29.

INTERNATIONAL CODE COUNCIL, INTERNATIONAL BUILDING CODE (IBC), 2024 EDITION. (AS AMENDED BY UFC 1-200-01).

INTERNATIONAL CODE COUNCIL, INTERNATIONAL EXISTING BUILDING CODE (IEBC), 2024 EDITION. (AS AMENDED BY UFC 1-200-01).

US ARMY CORPS OF ENGINEERS 2018-17 ECB (25, OCT 18; WITH REV 2, 20 JAN 22. NEW REQUIREMENTS FOR VISUAL NOTIFICATION FOR MASS

NOTIFICATION SYSTEMS

OTHER REFERENCES

NFPA 1, FIRE CODE, 2024 EDITION.

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2025 EDITION.

NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2025 EDITION.

NFPA 70, NATIONAL ELECTRIC CODE (NEC), 2023 EDITION.

NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2025 EDITION.

NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2024 EDITION.

NFPA 101, LIFE SAFETY CODE, 2024 EDITION.

NFPA 170, STANDARD FOR FIRE SAFETY AND EMERGENCY SYMBOLS, 2024 EDITION.

NFPA 220, STANDARD ON TYPES OF BUILDING CONSTRUCTION, 2024 EDITION.

NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, 2022 EDITION.

NFPA 291, RECOMMENDED PRACTICE FOR WATER FLOW TESTING AND MARKING OF HYDRANT2025 EDITION.

NFPA 409, STANDARD ON AIRCRAFT HANGARS 2022 EDITION.

NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, 2019 EDITION.

NFPA 5000, BUILDING CONSTRUCTION AND SAFETY CODE, 2024 EDITION.

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) - LATEST EDITIONS

UFC 1-200-01, DOD BUILDING CODE, CHANGE 4, 17 DECEMBER 2024.

UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES, CHANGE 6, 06 MAY 2021.

UFC 3-601-02, FIRE PROTECTION SYSTEMS INSPECTION, TESTING, AND MAINTENANCE, 07 OCTOBER 2021.

UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, CHANGE 3, 24 MAY 2024.

UFC 4-010-05, SENSITIVE COMPARTMENTED INFORMATION FACILITIES PLANNING, DESIGN, AND CONSTRUCTION, CHANGE 2, 26 MAY 2023.

UFC 4-021-01, DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, CHANGE 1, 01 JANUARY 2010.

UFC 4-211-01, AIRCRAFT MAINTENANCE HANGARS, CHANGE 3, 20 APRIL 2021.

UNIFIED FACILITIES CRITERIA (UFC)

REFERENCED CODES AND STANDARDS:

CODE ANALYSIS

• DOORS FROM HANGAR BAYS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL. UFC 4-211-01 § 3-3.1.9

• DOORS SHALL SWING IN THE DIRECTION OF TRAVEL WHERE SERVING MORE THAN 50 PERSONS. NFPA 101 § 7.2.1.4.2

• NOT LESS THAN 28" FOR DOOR CLEAR WIDTH IN EXISTING BUILDINGS NFPA 101 § 7.2.1.2.3.2(4)

• NOT LESS THAN 28" FOR ANY MEANS OF EGRESS IN EXISTING BUILDINGS NFPA 101 § 7.3.4.1.2

MINIMUM WIDTH:

• IN EXISTING BUILDINGS, EXITS AND EXIT ACCESS DOORS SHALL BE REMOTELY LOCATED

FROM EACH OTHER AND BE ARRANGED TO MINIMIZE THE POSSIBILITY OF BLOCKING OF

MORE THAN ONE EXIT DURING A FIRE OR OTHER EMERGENCY.

NFPA 101 § 7.5.1.3.1 &

§ 7.5.1.3.5

REMOTENESS OF EXITS:

• INDUSTRIAL SPECIAL PURPOSE, SPRINKLERED: 50 FEET NFPA 101 TABLE 40.2.5.1

• STORAGE: 50 FEET NFPA 101 § 42.6.3

• BUSINESS: 50 FEET NFPA 101 § 39.2.5.2

DEAD-END LIMITS

• EXISTING MECHANICAL EQUIPMENT ROOMS: 150 FEET NFPA 101 § 7.13.1(2)

• INDUSTRIAL SPECIAL PURPOSE, SPRINKLERED: 100 FEET NFPA 101 TABLE 40.2.5.1

• STORAGE, SPRINKLERED: 100 FEET NFPA 101 TABLE 42.2.5

• BUSINESS, SPRINKLERED: 100 FEET NFPA 101 § 39.2.5.3.1

COMMON PATH OF TRAVEL

NOTE 1 - TRAVEL DISTANCE DOES NOT APPLY WITHIN HANGAR BAYS. TRAVEL DISTANCE STARTS AT HANGAR BAY EXIT ACCESS;

DESIGN TEAM INTERPRETATION ASSUMES TRAVEL DISTANCE LIMIT THROUGH ADJACENT BAYS DOES NOT EXCEED 400FT IN TOTAL FOR STORAGE OCCUPANCIES; THE DESIGN TEAM HAS LIMITED THE TRAVEL DISTANCE STARTING UPON LEAVING THE HANGAR BAY OF ORIGIN TO NOT EXCEED 250FT SUCH THAT THE MAX TRAVEL DISTANCE DOES NOT EXCEED 400FT. AN UNOBSTRUCTED PATH WILL BE

PROVIDED TO REACH THE NEAREST EXTERIOR EXIT DISCHARGE DOOR.

• STORAGE (HANGAR BAY): NOTE 1 UFC 4-211-01 § 3-3.1.9

• BUSINESS, SPRINKLERED: 300 FEET NFPA 101 § 39.2.6.3

TRAVEL DISTANCE TO AN EXIT

• EXISTING MEANS OF EGRESS MEET UFC AND NFPA 101 REQUIREMENTS

MEANS OF EGRESS ARE EXISTING

STORAGE A OR B A, B, OR C A, B, OR C CLASS I OR II

INDUSTRIAL A OR B A, B, OR C A, B, OR C CLASS I OR II

BUSINESS A OR B A OR B A, B, OR C CLASS I OR II

EXITS EXIT ACCESS

CORRIDORS

ROOMS AND

ENCLOSED SPACES

INTERIOR FINISH

FLOOR

GROUP

WITH SPRINKLER SYSTEM

INTERIOR WALL, CEILING, AND FLOOR FINISHES: NFPA 101 CHAPTER 10 TABLE A.10.2.2

• FIRE DAMPERS ARE REQUIRED FOR ALL HVAC PENETRATIONS OF 2-HOUR FIRE RATED BARRIERS.

FIRE DAMPERS NOT REQUIRED FOR FULLY DUCTED HVAC IN 1-HOUR FIRE RATED BARRIERS.

FIRE DAMPERS ARE REQUIRED FOR AIR TRANSFER GRILLES.

IBC § 717.5.2

REQUIRED FIRE DAMPERS IN FIRE RATED BARRIERS

• SHAFT AND STAIR ENCLOSURES SHALL HAVE NOT LESS THAN 1-HOUR FIRE RESISTANCE RATING

WHEN CONNECTING LESS THAN FOUR STORIES.

IBC § 713.4

• PENETRATIONS INTO, AND OPENINGS THROUGH AN EXIT ENCLOSURE, ARE LIMITED

PER NFPA 101 SECTION 7.1.3.2.1 (9) TO UTILITIES SERVING THE STAIRWELL.

NFPA 101 § 7.1.3.2 (9)

SHAFTS AND EXIT ENCLOSURES

• DOORS IN FIRE BARRIERS SHALL BE RATED PER NFPA 101 TABLE 8.3.3.2.2 AND SELF-CLOSING OR

AUTOMATIC-CLOSING

NFPA 101 § 8.3.3

DOORS

• 2 HR FIRE BARRIER SEPARATING DISSIMILAR HANGAR BAY OPERATIONS UFC 4-211-01 § 5-3.1

• 2 HR FIRE BARRIER SEPARATING FIRE AREAS WITHIN THE HANGAR BAY UFC 4-211-01 § 3-3.1.3

• 1 HR FIRE BARRIER SEPARATING FIRE PROTECTION EQUIPMENT ROOMS UFC 4-211-01 § 3-6.7

• 1 HR FIRE BARRIER SEPARATING HANGAR BAY FROM SUPPORT AREAS UFC 4-211-01 § 3-3.1.3

INTERIOR RATED SEPARATIONS

• CORRIDORS PROVIDING ACCESS TO AN EXIT: NO RATING REQUIRED NFPA 101 § 39.3.6,

§ 40.3.6, & § 42.3.6

NFPA 101 EXIT ACCESS CORRIDORS:

• PORTABLE FIRE EXTINGUISHERS ARE EXISTING AND SHALL REMAIN AS CURRENTLY INSTALLED

FIRE EXTINGUISHERS

• WATER IS SUPPLIED FROM TWO REMOTE FIRE PUMPS LOCATED IN BUILDING 2119. FIRE PUMPS ARE ARRANGED IN

PARALLEL, PUMP 1 RATED AT 1500 GPM @ 125 PSI, PUMP 2 RATED AT 1500 GPM @ 100 PSI

• SYSTEM DEMAND INCLUDES SPRINKLER SYSTEM DEMAND

• WET SPRINKLER SYSTEMS SHALL BE PROVIDED FOR THE HANGAR BAY IN ACCORDANCE WITH DOD SUNDOWN POLICY

• STANDPIPE SYSTEMS NOT REQUIRED

FIRE SUPPRESSION SYSTEMS AND WATER SUPPLY

GENERAL FIRE ALARM SYSTEM REQUIREMENTS (UFC-3-600-01, UFC 4-211-01, NFPA 70, NFPA 72, ABA, UFC 4-010-01 & UFC 4-021-01)

• MONACO D-21 REPORTING TO RECEIVING DISPATCH WITH RF TRANSCEIVER

• MANUAL PULL STATION AT ALL EXIT DOORS

• A MASS NOTIFICATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH UFC 4-021-01.

• THE FIRE ALARM EVACUATION SIGNAL SHALL BROADCAST OVER THE MNS SYSTEM.

FIRE ALARM AND MASS NOTIFICATION SYSTEM (MNS)

ACTIVE FIRE PROTECTION SYSTEMS (SHALL COMPLY WITH UFC 3-600-01 CH. 9 AND UFC 4-211-01):

NOTES: THE BUILDING ENEVOLOPE AND FIRE HYDRANTS LOCATIONS ARE EXISTING.

SEE CODE COMPLIANCE SITE PLAN FOR ACTUAL DISTANCES.

PER GOVERNMENT'S DIRECTION, UPGRADES TO NON-CONFORMING CONDITIONS IN REGARDS TO EXISTING FIRE

HYDRANT LOCATIONS ARE NOT WITHIN SCOPE OF WORK.

• ONE MEANS OF PAVED ALL-WEATHER GROUND ACCESS NO FARTHER THAN 33 FEET FROM AN EXTERIOR DOOR ACCESSIBLE FOR FIRE DEPARTMENT INGRESS AND WITHIN 150 FEET OF FIRE DEPARTMENT CONNECTIONS.

• KNOX VAULT 4500 OR SIMILAR AT NOSE ENDS OF EACH HANGAR BAY FOR EMERGENCY ACCESS.

• DIMENSIONS OF FIRE LANES AND TURNAROUNDS COMPLY WITH NFPA 1.

FIRE DEPARTMENT VEHICLE ACCESS (UFC 3-600-01 § 9-1 AND UFC 4-211-01)

NOTE: SEE LIFE SAFETY DRAWINGS FOR BUILDING OCCUPANCY LOADS

• INDUSTRIAL SPECIAL PURPOSE USE; NA

• AIRCRAFT HANGARS; 500 SQ.FT./PERSON GROSS FLOOR AREA

• MECH/ELEC/UTILITIES; 500 SQ.FT./PERSON GROSS FLOOR AREA

• BUSINESS USE; 150 SQ.FT./PERSON GROSS FLOOR AREA

• STORAGE USE; 500 SQ.FT./PERSON GROSS FLOOR AREA

• ASSEMBLY USE; CONFERENCE ROOMS WITH TABLES AND CHAIRS

15 SQ.FT./PERSON NET AREA

UFC 3-600-01 § 10-3.1; NFPA 101

TABLE 7.3.1.2

OCCUPANCY LOAD FACTORS

• STAIRS - 0.3 INCHES PER OCCUPANT FOR STAIRS. NFPA 101 TABLE 7.3.3.1

• LEVEL COMPONENTS (DOORS) - 0.2 INCHES PER OCCUPANT FOR DOORS. NFPA 101 TABLE 7.3.3.1

OCCUPANCY CAPACITY FACTORS:

• EACH REQUIRED ACCESSIBLE MEANS OF EGRESS SHALL BE CONTINUOUS TO A PUBLIC

WAY AND SHALL CONSIST OF ONE OR MORE OF THE FOLLOWING (ONLY THOSE INCLUDED

IN DESIGN ARE LISTED):

1. ACCESSIBLE ROUTES COMPLYING WITH IBC § 1104.

2. INTERIOR EXIT STAIRWAYS COMPLYING WITH IBC § 1009.3 & § 1023.

EXCEPTIONS:

1. THE CLEAR WIDTH OF 48 INCHES BETWEEN HANDRAILS IS NOT REQUIRED

IN BUILDINGS EQUIPPED THROUGHOUT BY AN AUTOMATIC SPRINKLER

SYSTEM IN ACCORDANCE WITH IBC § 903.3.1.1.

2. AREAS OF REFUGE ARE NOT REQUIRED AT STAIRWAYS IN BUILDINGS

EQUIPPED THROUGHOUT BY AN AUTOMATIC SPRINKLER SYSTEM

INSTALLED IN ACCORDANCE WITH IBC § 903.3.1.1.

IBC § 1009.2 & § 1009.3

• ACCESSIBLE SPACES SHALL BE PROVIDED WITH NOT LESS THAN ONE ACCESSIBLE

MEANS OF EGRESS. WHERE MORE THAN ONE MEANS OF EGRESS ARE REQUIRED BY

§ 1006.21 OR § 1006.3 FROM ANY ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION

OF THE SPACE SHALL BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF

EGRESS.

IBC 1009.1

• PER UFC 1-200-01 § 2-10 AND § 2-11, DELETE CHAPTER 10 & 11 OF THE IBC FOR

MEANS OF EGRESS AND ACCESSIBILITY. UTILIZE UFC 3-600-01 AND THE ABA.

WHERE THE ABA REFERENCES THE IBC, THE 2024 EDITION WILL BE USED.

UFC 1-200-01 § 2-10 &

§ 2-11

ACCESSIBLE MEANS OF EGRESS

MEANS OF EGRESS (CONTINUED):

• EXISTING DOORS IN FIRE BARRIERS HAVING A MINIMUM 3/4-HOUR FIRE PROTECTION RATING SHALL BE PERMITTED TO CONTINUE TO BE USED IN EXIT ENCLOSURES IN LIEU OF THE MINIMUM 1-HOUR

FIRE PROTECTION RATING REQUIRED IN NFPA 101 TABLE 8.3.3.2.2.

NFPA 101 § 8.3.3

• NOT LESS THAN 32" FOR DOOR CLEAR WIDTH IN EXISTING BUILDINGS NFPA 101 § 7.2.1.2.3.2

2 HOUR

2 HOUR

1 HOUR

2 HOUR

2 HOUR

GROUP A-3 ASSEMBLY (ACCESSORY USE ONLY , < 10% OF BUILDING AREA) IBC § 303 (ASSEMBLY)

HANGAR CLASSIFICATION: GROUP 1 AIRCRAFT HANGAR NFPA 409 § 6.1.1

EXISTING ASSEMBLY (INCIDENTAL USE) NFPA 101 CHAP. 13 PER CHAP. 43

04/02/2025

AutoCAD SHX Text

KHENDERSON

Rectangle

WOMEN

CORRIDOR

SECURITY

VAULT

BACKSHOP

SUPPORT CELLS

GENERATOR

SHEDGENERATOR

SHED

TEXAS TOWER

POCKET

PROD FOREMAN

OFFICE

EAST

MECH RM

EAST

ELEC RM

MEN

WOMEN

E-3 GEAR

SHOP

ELEV CTL

SCHEDULING

OPEN OFFICE

AISLE

BREAK RM

121A

AIRCRAFT

RECORDS

COMPUTER

WORK RM

AVIONICS

SHOP AREA

AVIONICS / ELEC

BACK SHOP

KITTING

AISLE

AISLE

E-3

TOOL CRIB

ELEC

BREAKER RM

KIT BREAKOUT

SHOP

ELEC /

COMM

GENERATOR

SHED

UP

F

RO

M

FI

RS

T

FIRST

LANDING

SECOND

LANDING

UP FROM

FIRST

FI

RS

T

LA

ND

IN

G

SE

CO

ND

LA

ND

IN

G

UP

UP

UP

UP

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

ELEV

UP

F

RO

M

FI

RS

T

UP

UP

FIRST

LANDING

SECOND

LANDING

UP

F

RO

M

FI

RS

T

FIRST

LANDING

SECOND

LANDING

E- 3 S

ER

VI

CE

S

SC

HE

DU

LIN

G

SE

CT

IO

N

OU

TD

OO

R

ST

OR

AG

E

RA

MP UP

A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

E

B

C

D

D.5

AISLE

OFFICE

DLA

STAGING

WEST

MECH RM

AI

SL

E

AI

SL

E

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

A

E

B

C

D

D.5

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

AIRCRAFT HANGER

103,000 SF/ 500 /

206 PER

AIRCRAFT HANGER

103,000 SF/ 500 /

206 PER

BUSINESS USE

120 SF/ 150 / 1 PER

STORAGE USE

1600 SF/ 500 / 4 PER

STORAGE USE

490 SF/ 500 / 1 PER

BUSINESS USE

595 SF/ 150 / 4 PER

BUSINESS USE

240 SF/ 150 / 2 PER

BUSINESS USE

205 SF/ 150 / 2 PER

M

ATC

H

LIN

E AR

EA B

M

ATC

H

LIN

E AR

EA A

MATCHLINE AREA A

MATCHLINE AREA B

MATCHLINE AREA B

MATCHLINE AREA C

M

AT

C H

LI

N

E

AR

EA

B

MATCHLINE AREA CM

AT

C H

LI

N

E

AR

EA

A

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

INDUSTRIAL USE

678 SF/ 100 / 7PER

STORAGE USE

2060 SF/ 500 / 5 PER

MECH./ELEC. ROOM

680 SF/ 500 / 2 PER

MECH./ELEC. ROOM

125 SF/ 500 / 1 PER

INDUSTRIAL USE

5700 SF/ 500 / 57 PER

INDUSTRIAL USE

3350 SF/ 100 / 34 PER

ASSEMBLY USE

1900 SF/ 15 / 127 PER

INDUSTRIAL USE

1880 SF/ 100 / 19 PER

INDUSTRIAL USE

980 SF/ 100 / 10 PER

BUSINESS USE

815 SF/ 150 / 7 PER

BUSINESS USE

665 SF/ 150 / 5 PER

BUSINESS USE

425 SF/ 150 / 3 PER

BUSINESS USE

380 SF/ 150 / 3 PER

BUSINESS USE

650 SF/ 150 / 5 PER

INDUSTRIAL USE

980 SF/ 100 / 10 PER

BUSINESS USE

200 SF/ 150 / 2 PER

IT EQUIP. ROOM

395 SF/ 500 / 1 PER

BUSINESS USE

130 SF/ 150 / 1 PER

MECH./ELEC. ROOM

480 SF/ 500 / 1 PER

MECH./ELEC. ROOM

2075 SF/ 500 / 5 PER

uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu u u u u uu u u u u uu u u u u uu u u u u uu

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

64 in .20

MATCHLINE AREA C

u u u u u u u u

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 128 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 149 FT EXITS SEPARATION (SHALL LESS THAN 150 FT) - 149 FT

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 109 FT

TRAVEL DISTANCE - 154 FT

TRAVEL DISTANCE - 88 FT

TR

AV

EL

D

IS

TA

N C

E

- 1

F

T

TRAVEL DISTANCE - 170 FT

TRAVEL DISTANCE - 130 FT

TRAVEL DISTANCE - 108 FT

TRAVEL DISTANCE - 84 FT

COMMON PATH - 35 FT

C O

M M

O N

PATH

- 23 FT

C O

M M

O N

P

AT

H

F

T

C O

M M

O N

P

AT

H

F

T

C O

M M

O N

P

AT

H

F

T

COMMON PATH - 84 FT

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 102 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 98 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 128 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 82 FT

EXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 95 FT

EXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 97 FT

EXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 48 FT

EXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 98 FT

STORAGE USE

330 SF/ 500 / 1 PER

STORAGE USE

330 SF/ 500 / 1 PER

STORAGE USE

330 SF/ 500 / 1 PER

STORAGE USE

1330 SF/ 500 / 3 PER

BUSINESS USE

270 SF/ 150 / 2 PER

BUSINESS USE

190 SF/ 150 / 2 PER

u u u u u u u u u u

BUSINESS USE

3500 SF/ 150 / 24 PER

BUSINESS USE

3400 SF/ 150 / 24 PER

BUSINESS USE

970 SF/ 150 / 7 PER

BUSINESS USE

1060 SF/ 150 / 8PER

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 33 FT

H

AN

G

AR

B

AY

D O

O R

FT

H

AN

G

AR

B

AY

D O

O R

FT

D

EAD

EN

D

C O

R R

ID

O

R

- 65 FT

u u u u u u u u u

64 in .20

TRAVEL DISTANCE - 70 FT

COMMON PATH - 70 FT

G

EN

ER

AL

G-101

D .E

R .D

. J.

M

LI

FE

S

AF

ET

Y

PL

AN

FI

R

ST

F

LO

O

R O

VE

R

AL

L

LIFE SAFETY PLAN - FIRST FLOOR OVERALL

SCALE: 1/32" = 1'-0"

G-101

16 32 6432

SCALE: 1/32"=1'-0"

SHEET NOTES:

1. THE INTENT OF THE LIFE SAFETY SHEETS IS TO IDENTIFY

THE EXISTING CONDITIONS ONLY. THE SCOPE OF WORK

DOES NOT INCLUDE UPGRADES TO THE BUILDING RELATED

TO COMPLIANCE WITH THE CURRENT LIFE SAFETY CODE

REQUIREMENTS. IN ACCORDANCE WITH IEBC 804.2, MEANS

OF EGRESS COMPLYING WITH THE REQUIREMENTS OF THE

BUILDING CODE UNDER WHICH THE BUILDING WAS

CONSTRUCTED SHALL BE CONSIDERED TO BE A COMPLIANT

MEANS OF EGRESS SYSTEM IF, IN THE OPINION OF THE

CODE OFFICIAL, THEY DO NOT CONSTITUTE A DISTINCT

HAZARD TO LIFE SAFETY.

2. ALL REQUESTED ROOM NUMBERS HAVE BEEN GIVEN. ALL

AVAILABLE ROOM NUMBERS ARE SHOWN.

3. ALL BUILDING AND LIFE SAFETY FEATURES SHOWN ARE

BASED ON AS-BUILTS AND SITE SURVEYING.

PROJECT EGRESS TRAVEL DISTANCE - FIRST FLOOR

COMMON PATH 100 FEET (WITH SPRINKLERS) TABLE 42.2.5

DEAD-END CORRIDOR

NFPA 101 REF.ALLOWED ACTUAL

400 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

STORAGE OCCUPANCY

COMMON PATH

DEAD-END CORRIDOR

EXISTING BUSINESS OCCUPANCY

TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

50 FEET (WITH SPRINKLERS)

300 FEET (WITH SPRINKLERS)

TABLE 42.2.6

TABLE 42.2.5

COMMON PATH

DEAD-END CORRIDOR

EXISTING ASSEMBLY OCCUPANCY

TRAVEL DISTANCE

75 FEET (WITH SPRINKLERS) 13.2.5.1.2

20 FEET (WITH SPRINKLERS) N/A 13.2.5.1.3

250 FEET (WITH SPRINKLERS) 13.2.6.2(1)170 FT

15 FT

65 FT

134 FT

74 FT

N/A

154 FT

70 FT

39.2.5.2

39.2.5.3

39.2.6.1

COMMON PATH 100 FEET (WITH SPRINKLERS)

DEAD-END CORRIDOR

250 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

50 FEET (WITH SPRINKLERS)

INDUSTRIAL OCCUPANCY - GENERAL

N/A

84 FT

84 FT

BUILDING AREA

EXISTING AREA (GSF)FLOOR

1ST LEVEL HANGAR (GROSS) 103,000

TOTAL 171,080

2ND LEVEL (GROSS)

3RD LEVEL (GROSS)

33,100

1,880

1ST LEVEL SUPPORT AREA (GROSS) 33,100

LIFE SAFETY SYMBOLS:

EGRESS TRAVEL DISTANCEXX'

EXIT DISCHARGE

-CAPACITY FACTOR

-EXIT WIDTH

-EXIT CAPACITY

XXin

XXX

XXX

NFPA 101 OCCUPANCY

ROOM AREA / LOAD FACTOR / OCCUPANT LOAD OCCUPANCY LOAD PER SPACE

u u u u u u 1 HOUR FIRE BARRIER - EXISTING

EXISTING PORTABLE FIRE EXTINGUISHERS

EXISTING EXIT SIGNAGE

uu uu uu uu 2 HOUR FIRE BARRIER - EXISTING uuu uuu uuu 3 HOUR FIRE BARRIER - EXISTING

KEY NOTES:

1 TRAVEL DISTANCES AND COMMON PATHS ORIGINATE FROM UPPER

FLOORS, REFER TO SHEET G-102 AND G-103.

SUPPORT AREAS ARE NOT PERMITTED TO HAVE THEIR REQUIRED EGRESS

THROUGH THE HANGAR BAY WITH THE EXCEPTION OF NORMALLY

UNOCCUPIED ROOMS LESS THAN 100 SQ. FT. THIS REPRESENTS AN

EXISTING NON-COMPLIANT CONDITION PER UFC 4-211-01 § 3-3.1.9. THE

SCOPE OF WORK WILL NOT CORRECT THIS EXISTING NON-COMPLIANT

CONDITION.

THE EXIT EXCEEDS THE 20 FT DISTANCE BETWEEN THE HANGAR BAY

DOOR AND PERSONNEL EXIT AS ALLOWED BY UFC 4-211-01 § 3-3.1.9. THIS

REPRESENTS AN EXISTING NON-COMPLIANT CONDITION. THE

SCOPE OF WORK WILL NOT CORRECT THIS EXISTING NON-COMPLIANT

CONDITION.

DOORS ENCROACH INTO MORE THAN ONE-HALF THE REQUIRED WIDTH OF

THE CORRIDOR IN ACCORDANCE WITH NFPA 101 § 7.2.1.4.3. THE SCOPE OF

WORK WILL NOT CORRECT THIS EXISTING NON-COMPLIANT CONDITION.

DEAD END CORRIDOR GREATER THAN 50 FT IN ACCORDANCE WITH NFPA

101 TABLE 40.2.5.1. THE SCOPE OF WORK WILL NOT CORRECT THIS

EXISTING NON-COMPLIANT CONDITION.

FIRE RATED DOORS PROPPED OPEN WITHOUT THE USE OF A

SELF-CLOSING OR AUTOMATIC CLOSING FEATURES AS PER NFPA 80 §

7.1.4. THE SCOPE OF WORK WILL NOT CORRECT THIS EXISTING

NON-COMPLIANT CONDITION.1

LOADLOAD FACTOR AREA TYPEFLOOR REFERENCE

1ST LEVEL ASSEMBLY USE 15 SF/ OCC. 127

1ST LEVEL STORAGE USE (HANGAR) 500 SF/ OCC. 206

2ND LEVEL

TOTAL

3RD LEVEL 19

OCCUPANT LOAD

1ST LEVEL STORAGE USE 500 SF/ OCC. 20 NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

UFC 3-600-01 TABLE 10-3

1ST LEVEL BUSINESS USE 150 SF/ OCC. 109 NFPA 101 TABLE 7.3.1.2

1ST LEVEL INDUSTRIAL USE 100 SF/ OCC. 130 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 79BUSINESS USE 150 SF/ OCC. NFPA 101 TABLE 7.3.1.2

STORAGE USE 500 SF/ OCC.

INDUSTRIAL USE 100 SF/ OCC.

2ND LEVEL ASSEMBLY USE 15 SF/ OCC. 44 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 110 NFPA 101 TABLE 7.3.1.2INDUSTRIAL USE 100 SF/ OCC.

2 2 2 2 2 2 2

2 2 222

TABLE 40.2.5.1

TABLE 40.2.6.1

TABLE 40.2.5.1

6 6 6 6 6

6 6 6

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EP

AI

R

F

IR

E

SU

PP

R

ES

SI

O N

SY

ST

EM

, M

AI

N

T H

AN

G

ER

B

N

O

VE

M

BE

R

H D

R

KEYPLAN

PLAN NORTH

AP

RI

L

TI

N

KE

R P

O

LI

C Y

C H

AN

G

E

AREA C

AREA A AREA B

04/02/2025

KHENDERSON

Rectangle

WOMEN

GENERATOR

SHEDGENERATOR

SHED

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

B

B

B

B

B

B

B

B

B

B

B

2 3 4 5 6 7 8 9 10 11

A A A A A A A A A A A

1 2 3 4 5 6 7 8 9 10 11

B

C WEST

MECH RM

155 156

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

AIRCRAFT HANGER

103,000 SF/ 500 /

206 PER

STORAGE USE

490 SF/ 500 / 1 PER

BUSINESS USE

240 SF/ 150 / 2 PER

BUSINESS USE

205 SF/ 150 / 2 PER

M

ATC

H

LIN

E AR

EA B

M

ATC

H

LIN

E AR

EA A

MATCHLINE AREA A

MATCHLINE AREA B

M

AT

C H

LI

N

E

AR

EA

B

M

AT

C H

LI

N

E

AR

EA

A uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uu

32in .20

32in .20

MATCHLINE AREA C

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 128 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 149 FT

C O

M M

O N

P

AT

H

F

T

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 102 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 98 FTEXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 48 FT

EXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 98 FT

STORAGE USE

330 SF/ 500 / 1 PER

STORAGE USE

330 SF/ 500 / 1 PER

BUSINESS USE

270 SF/ 150 / 2 PER

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 33 FT

H

AN

G

AR

B

AY

D O

O R

FT

u u u u u u

TRAVEL DISTANCE - 70 FT

COMMON PATH - 70 FT

G

EN

ER

AL

G-101A

D .E

R .D

. J.

M

LI

FE

S

AF

ET

Y

PL

AN

FI

R

ST

F

LO

O

R

AR

EA

A

LIFE SAFETY PLAN - FIRST FLOOR AREA A

SCALE: 1/16" = 1'-0"

G-101A

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EP

AI

R

F

IR

E

SU

PP

R

ES

SI

O N

SY

ST

EM

, M

AI

N

T H

AN

G

ER

B

N

O

VE

M

BE

R

H D

R

KEYPLAN

PLAN NORTH

AP

RI

L

TI

N

KE

R P

O

LI

C Y

C H

AN

G

E

8 16 3216

SCALE: 1/16"=1'-0"

SHEET NOTES:

1. THE INTENT OF THE LIFE SAFETY SHEETS IS TO IDENTIFY

THE EXISTING CONDITIONS ONLY. THE SCOPE OF WORK

DOES NOT INCLUDE UPGRADES TO THE BUILDING RELATED

TO COMPLIANCE WITH THE CURRENT LIFE SAFETY CODE

REQUIREMENTS. IN ACCORDANCE WITH IEBC 804.2, MEANS

OF EGRESS COMPLYING WITH THE REQUIREMENTS OF THE

BUILDING CODE UNDER WHICH THE BUILDING WAS

CONSTRUCTED SHALL BE CONSIDERED TO BE A COMPLIANT

MEANS OF EGRESS SYSTEM IF, IN THE OPINION OF THE

CODE OFFICIAL, THEY DO NOT CONSTITUTE A DISTINCT

HAZARD TO LIFE SAFETY.

2. ALL REQUESTED ROOM NUMBERS HAVE BEEN GIVEN. ALL

AVAILABLE ROOM NUMBERS ARE SHOWN.

3. ALL BUILDING AND LIFE SAFETY FEATURES SHOWN ARE

BASED ON AS-BUILTS AND SITE SURVEYING.

PROJECT EGRESS TRAVEL DISTANCE - FIRST FLOOR

COMMON PATH 100 FEET (WITH SPRINKLERS) TABLE 42.2.5

DEAD-END CORRIDOR

NFPA 101 REF.ALLOWED ACTUAL

400 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

COMMON PATH

DEAD-END CORRIDOR

TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

50 FEET (WITH SPRINKLERS)

300 FEET (WITH SPRINKLERS)

TABLE 42.2.6

TABLE 42.2.5

COMMON PATH

DEAD-END CORRIDOR

TRAVEL DISTANCE

75 FEET (WITH SPRINKLERS) 13.2.5.1.2

20 FEET (WITH SPRINKLERS) N/A 13.2.5.1.3

250 FEET (WITH SPRINKLERS) 13.2.6.2(1)170 FT

15 FT

N/A

134 FT

74 FT

N/A

154 FT

35 FT

39.2.5.2

39.2.5.3

39.2.6.1

COMMON PATH 100 FEET (WITH SPRINKLERS)

DEAD-END CORRIDOR

250 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

50 FEET (WITH SPRINKLERS) N/A

84 FT

84 FT

BUILDING AREA

EXISTING AREA (GSF)FLOOR

1ST LEVEL HANGAR (GROSS) 103,000

TOTAL 171,080

2ND LEVEL (GROSS)

3RD LEVEL (GROSS)

33,100

1,880

1ST LEVEL SUPPORT AREA (GROSS) 33,100

LIFE SAFETY SYMBOLS:

EGRESS TRAVEL DISTANCEXX'

EXIT DISCHARGE

-CAPACITY FACTOR

-EXIT WIDTH

-EXIT CAPACITY

XXin

XXX

XXX

NFPA 101 OCCUPANCY

ROOM AREA / LOAD FACTOR / OCCUPANT LOAD OCCUPANCY LOAD PER SPACE

u u u u u u 1 HOUR FIRE BARRIER - EXISTING uu uu uu uu 2 HOUR FIRE BARRIER - EXISTING uuu uuu uuu 3 HOUR FIRE BARRIER - EXISTING

LOADLOAD FACTOR AREA TYPEFLOOR REFERENCE

1ST LEVEL ASSEMBLY USE 15 SF/ OCC. 127

1ST LEVEL STORAGE USE (HANGAR) 500 SF/ OCC. 206

2ND LEVEL

TOTAL

3RD LEVEL 19

OCCUPANT LOAD

1ST LEVEL STORAGE USE 500 SF/ OCC. 20 NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

1ST LEVEL BUSINESS USE 150 SF/ OCC. 109 NFPA 101 TABLE 7.3.1.2

1ST LEVEL INDUSTRIAL USE 100 SF/ OCC. 130 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 79BUSINESS USE 150 SF/ OCC. NFPA 101 TABLE 7.3.1.2

STORAGE USE 500 SF/ OCC.

INDUSTRIAL USE 100 SF/ OCC.

2ND LEVEL ASSEMBLY USE 15 SF/ OCC. 44 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 110 NFPA 101 TABLE 7.3.1.2INDUSTRIAL USE 100 SF/ OCC.

KEY NOTES:

1 SUPPORT AREAS ARE NOT PERMITTED TO HAVE THEIR REQUIRED

EGRESS THROUGH THE HANGAR BAY WITH THE EXCEPTION OF

NORMALLY UNOCCUPIED ROOMS LESS THAN 100 SQ. FT. THIS

REPRESENTS AN EXISTING NON-COMPLIANT CONDITION PER UFC

4-211-01 § 3-3.1.9. THE SCOPE OF WORK WILL NOT CORRECT THIS

EXISTING NON-COMPLIANT CONDITION.

THE EXIT EXCEEDS THE 20 FT DISTANCE BETWEEN THE HANGAR BAY

DOOR AND PERSONNEL EXIT AS ALLOWED BY UFC 4-211-01 § 3-3.1.9. THIS

REPRESENTS AN EXISTING NON-COMPLIANT CONDITION. THE

SCOPE OF WORK WILL NOT CORRECT THIS EXISTING NON-COMPLIANT

CONDITION.

1 1 1 1

EXISTING PORTABLE FIRE EXTINGUISHERS

EXISTING EXIT SIGNAGE

UFC 3-600-01 TABLE 10-3

STORAGE OCCUPANCY

EXISTING BUSINESS OCCUPANCY

EXISTING ASSEMBLY OCCUPANCY

INDUSTRIAL OCCUPANCY - GENERAL

TABLE 40.2.5.1

TABLE 40.2.6.1

TABLE 40.2.5.1

AREA A

04/02/2025

KHENDERSON

Rectangle

TEXAS TOWER

POCKET

PROD FOREMAN

WOMEN

GENERATOR

SHED

DOCK

OFFICE

DOCK

OFFICE

DOCK

OFFICE

RA

MP UP

B

B

B

B

B

B

B

B

B

B

B

11 12 13 14 15 16 17 18 19 20

A A A A A A A A A A

11 12 13 14 15 16 17 18 19 20 21

120A

A

B

C

BUSINESS USE

120 SF/ 150 / 1 PER

AIRCRAFT HANGER

103,000 SF/ 500 /

206 PER

M

ATC

H

LIN

E AR

EA B

M

ATC

H

LIN

E AR

EA A

MATCHLINE AREA B

MATCHLINE AREA C

M

AT

C H

LI

N

E

AR

EA

B

MATCHLINE AREA CM

AT

C H

LI

N

E

AR

EA

A

BUSINESS USE

120 SF/ 150 / 1 PER

BUSINESS USE

120 SF/ 150 / 1 PER

uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu

32in .20

32in .20

32in .20

MATCHLINE AREA C

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 149 FT EXITS SEPARATION (SHALL LESS THAN 150 FT) - 149 FT

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 109 FT

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 128 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 82 FT

EXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 95 FT

EXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 97 FT

STORAGE USE

330 SF/ 500 / 1 PER

STORAGE USE

1330 SF/ 500 / 3 PER

H

AN

G

AR

B

AY

D O

O R

FT

G

EN

ER

AL

G-101B

D .E

R .D

. J.

M

LI

FE

S

AF

ET

Y

PL

AN

- F

IR

ST

F

LO

O

R A

R

EA

B

LIFE SAFETY PLAN - FIRST FLOOR AREA B

SCALE: 1/16" = 1'-0"

G-101B

8 16 3216

SCALE: 1/16"=1'-0"

PROJECT EGRESS TRAVEL DISTANCE - FIRST FLOOR

COMMON PATH 100 FEET (WITH SPRINKLERS) TABLE 42.2.5

DEAD-END CORRIDOR

NFPA 101 REF.ALLOWED ACTUAL

400 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

COMMON PATH

DEAD-END CORRIDOR

TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

50 FEET (WITH SPRINKLERS)

300 FEET (WITH SPRINKLERS)

TABLE 42.2.6

TABLE 42.2.5

COMMON PATH

DEAD-END CORRIDOR

TRAVEL DISTANCE

75 FEET (WITH SPRINKLERS) 13.2.5.1.2

20 FEET (WITH SPRINKLERS) N/A 13.2.5.1.3

250 FEET (WITH SPRINKLERS) 13.2.6.2(1)170 FT

15 FT

N/A

134 FT

74 FT

N/A

154 FT

35 FT

39.2.5.2

39.2.5.3

39.2.6.1

COMMON PATH 100 FEET (WITH SPRINKLERS)

DEAD-END CORRIDOR

250 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

50 FEET (WITH SPRINKLERS) N/A

84 FT

84 FT

BUILDING AREA

EXISTING AREA (GSF)FLOOR

1ST LEVEL HANGAR (GROSS) 103,000

TOTAL 171,080

2ND LEVEL (GROSS)

3RD LEVEL (GROSS)

33,100

1,880

1ST LEVEL SUPPORT AREA (GROSS) 33,100

LOADLOAD FACTOR AREA TYPEFLOOR REFERENCE

1ST LEVEL ASSEMBLY USE 15 SF/ OCC. 127

1ST LEVEL STORAGE USE (HANGAR) 500 SF/ OCC. 206

2ND LEVEL

TOTAL

3RD LEVEL 19

OCCUPANT LOAD

1ST LEVEL STORAGE USE 500 SF/ OCC. 20 NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

1ST LEVEL BUSINESS USE 150 SF/ OCC. 109 NFPA 101 TABLE 7.3.1.2

1ST LEVEL INDUSTRIAL USE 100 SF/ OCC. 130 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 79BUSINESS USE 150 SF/ OCC. NFPA 101 TABLE 7.3.1.2

STORAGE USE 500 SF/ OCC.

INDUSTRIAL USE 100 SF/ OCC.

2ND LEVEL ASSEMBLY USE 15 SF/ OCC. 44 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 110 NFPA 101 TABLE 7.3.1.2INDUSTRIAL USE 100 SF/ OCC.

SHEET NOTES:

1. THE INTENT OF THE LIFE SAFETY SHEETS IS TO IDENTIFY THE

EXISTING CONDITIONS ONLY. THE SCOPE OF WORK DOES NOT

INCLUDE UPGRADES TO THE BUILDING RELATED TO COMPLIANCE

WITH THE CURRENT LIFE SAFETY CODE REQUIREMENTS. IN

ACCORDANCE WITH IEBC 804.2, MEANS OF EGRESS COMPLYING

WITH THE REQUIREMENTS OF THE BUILDING CODE UNDER

WHICH THE BUILDING WAS CONSTRUCTED SHALL BE

CONSIDERED TO BE A COMPLIANT MEANS OF EGRESS SYSTEM IF,

IN THE OPINION OF THE CODE OFFICIAL, THEY DO NOT

CONSTITUTE A DISTINCT HAZARD TO LIFE SAFETY.

2. ALL REQUESTED ROOM NUMBERS HAVE BEEN GIVEN. ALL

AVAILABLE ROOM NUMBERS ARE SHOWN.

3. ALL BUILDING AND LIFE SAFETY FEATURES SHOWN ARE BASED

ON AS-BUILTS AND SITE SURVEYING.

KEY NOTES:

1 SUPPORT AREAS ARE NOT PERMITTED TO HAVE THEIR REQUIRED

EGRESS THROUGH THE HANGAR BAY WITH THE EXCEPTION OF

NORMALLY UNOCCUPIED ROOMS LESS THAN 100 SQ. FT. THIS

REPRESENTS AN EXISTING NON-COMPLIANT CONDITION PER UFC

4-211-01 § 3-3.1.9. THE SCOPE OF WORK WILL NOT CORRECT THIS

EXISTING NON-COMPLIANT CONDITION.

THE EXIT EXCEEDS THE 20 FT DISTANCE BETWEEN THE HANGAR BAY

DOOR AND PERSONNEL EXIT AS ALLOWED BY UFC 4-211-01 § 3-3.1.9. THIS

REPRESENTS AN EXISTING NON-COMPLIANT CONDITION. THE

SCOPE OF WORK WILL NOT CORRECT THIS EXISTING NON-COMPLIANT

CONDITION.

1 1 1

LIFE SAFETY SYMBOLS:

EGRESS TRAVEL DISTANCEXX'

EXIT DISCHARGE

-CAPACITY FACTOR

-EXIT WIDTH

-EXIT CAPACITY

XXin

XXX

XXX

NFPA 101 OCCUPANCY

ROOM AREA / LOAD FACTOR / OCCUPANT LOAD OCCUPANCY LOAD PER SPACE

u u u u u u 1 HOUR FIRE BARRIER - EXISTING uu uu uu uu 2 HOUR FIRE BARRIER - EXISTING uuu uuu uuu 3 HOUR FIRE BARRIER - EXISTING

EXISTING PORTABLE FIRE EXTINGUISHERS

EXISTING EXIT SIGNAGE

UFC 3-600-01 TABLE 10-3

STORAGE OCCUPANCY

EXISTING BUSINESS OCCUPANCY

EXISTING ASSEMBLY OCCUPANCY

INDUSTRIAL OCCUPANCY - GENERAL

TABLE 40.2.5.1

TABLE 40.2.6.1

TABLE 40.2.5.1

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EP

AI

R

F

IR

E

SU

PP

R

ES

SI

O N

SY

ST

EM

, M

AI

N

T H

AN

G

ER

B

N

O

VE

M

BE

R

H D

R

KEYPLAN

PLAN NORTH

AP

RI

L

TI

N

KE

R P

O

LI

C Y

C H

AN

G

E

AREA B

04/02/2025

KHENDERSON

Rectangle

WOMEN

CORRIDOR

SECURITY

VAULT

BACKSHOP

SUPPORT CELLS

PROD FOREMAN

OFFICE

EAST

MECH RM

EAST

ELEC RM

MEN

WOMEN

E-3 GEAR

SHOP

ELEV CTL

SCHEDULING

OPEN OFFICE

AISLE

BREAK RM

121A

AIRCRAFT

RECORDS

COMPUTER

WORK RM

AVIONICS

SHOP AREA

AVIONICS / ELEC

BACK SHOP

KITTING

AISLE

AISLE

E-3

TOOL CRIB

ELEC

BREAKER RM

KIT BREAKOUT

SHOP

ELEC /

COMM

UP

F

RO

M

FI

RS

T

FIRST

LANDING

SECOND

LANDING

UP FROM

FIRST

FI

RS

T

LA

ND

IN

G

SE

CO

ND

LA

ND

IN

G

UP

UP

UP

UP

ELEV

UP

F

RO

M

FI

RS

T

UP

UP

FIRST

LANDING

SECOND

LANDING

UP

F

RO

M

FI

RS

T

FIRST

LANDING

SECOND

LANDING

E- 3 S

ER

VI

CE

S

SC

HE

DU

LIN

G

SE

CT

IO

N126

121A

OU

TD

OO

R

ST

OR

AG

E

133 138 141

D

D

D.5

B

B

E

E

E

E

E

E

E

E

E

B

B

B

B

B

B

B

B

B

B

B

B

B

B

E

B

C

D

D.5

AISLE

OFFICE

DLA

STAGING

WEST

MECH RM

AI

SL

E

AI

SL

E

155 156

121A

120A

130 154A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

BUSINESS USE

120 SF/ 150 / 1 PER

STORAGE USE

1600 SF/ 500 / 4 PER

STORAGE USE

490 SF/ 500 / 1 PER

BUSINESS USE

595 SF/ 150 / 4 PER

BUSINESS USE

240 SF/ 150 / 2 PER

BUSINESS USE

205 SF/ 150 / 2 PER

MATCHLINE AREA A

MATCHLINE AREA B

MATCHLINE AREA B

MATCHLINE AREA C

M

AT

C H

LI

N

E

AR

EA

B

MATCHLINE AREA CM

AT

C H

LI

N

E

AR

EA

A

INDUSTRIAL USE

678 SF/ 100 / 7PER

STORAGE USE

2060 SF/ 500 / 5 PER

MECH./ELEC. ROOM

680 SF/ 500 / 2 PER

MECH./ELEC. ROOM

125 SF/ 500 / 1 PER

INDUSTRIAL USE

5700 SF/ 500 / 57 PER

INDUSTRIAL USE

3350 SF/ 100 / 34 PER

ASSEMBLY USE

1900 SF/ 15 / 127 PER

INDUSTRIAL USE

1880 SF/ 100 / 19 PER

INDUSTRIAL USE

980 SF/ 100 / 10 PER

BUSINESS USE

815 SF/ 150 / 7 PER

BUSINESS USE

665 SF/ 150 / 5 PER

BUSINESS USE

425 SF/ 150 / 3 PER

BUSINESS USE

380 SF/ 150 / 3 PER

BUSINESS USE

650 SF/ 150 / 5 PER

INDUSTRIAL USE

980 SF/ 100 / 10 PER

BUSINESS USE

200 SF/ 150 / 2 PER

IT EQUIP. ROOM

395 SF/ 500 / 1 PER

BUSINESS USE

130 SF/ 150 / 1 PER

MECH./ELEC. ROOM

480 SF/ 500 / 1 PER

MECH./ELEC. ROOM

2075 SF/ 500 / 5 PER

uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu uuu u u u u u u u u u u uuuu u u u u u u u u u u uu uu u u u u u u u u u u uuuu u u u u u u u u u u uu uu

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

32in .20

64 in .20

MATCHLINE AREA C

u u u u u u u uuu u u u u u u u u u u

TRAVEL DISTANCE - 154 FT

TRAVEL DISTANCE - 88 FT

TR

AV

EL

D

IS

TA

N C

E

- 1

F

T

TRAVEL DISTANCE - 170 FT

TRAVEL DISTANCE - 130 FT

TRAVEL DISTANCE - 108 FT

TRAVEL DISTANCE - 84 FT

COMMON PATH - 35 FT

C O

M M

O N

PATH

- 23 FT

C O

M M

O N

P

AT

H

F

T

C O

M M

O N

P

AT

H

F

T

C O

M M

O N

P

AT

H

F

T

COMMON PATH - 84 FT

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 102 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 98 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 128 FT EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 82 FTEXIT DISTANCE TO HANGAR BAY DOOR (SHALL BE LESS THAN 20 FT) - 48 FT

BUSINESS USE

270 SF/ 150 / 2 PER

BUSINESS USE

190 SF/ 150 / 2 PER

uuu u u u u u u u u u u u u u u u u u u u u u u u u u u

BUSINESS USE

3500 SF/ 150 / 24 PER

BUSINESS USE

3400 SF/ 150 / 24 PER

BUSINESS USE

970 SF/ 150 / 7 PER

BUSINESS USE

1060 SF/ 150 / 8PER

EXITS SEPARATION (SHALL BE LESS THAN 150 FT) - 33 FT

D

EAD

EN

D

C O

R R

ID

O

R

- 65 FT

u u u u u u u u u u u u u u u u u u u

64 in .20

TRAVEL DISTANCE - 70 FT

COMMON PATH - 70 FT

G

EN

ER

AL

G-101C

D .E

R .D

. J.

M

LI

FE

S

AF

ET

Y

PL

AN

FI

R

ST

F

LO

O

R

AR

EA

C

AIR FORCE MATERIEL COMMAND

72 ABW CIVIL ENGINEER DIRECTORATE

TINKER AFB, OK

TI

N

KE

R

A

IR

F O

R C

E

BA

SE

, O

KL

AH

O M

A

PR

O

JE

C

T

IN

FO

R

M

AT

IO

N

R

EV

IS

IO

N S

M

AR

K

D

ES

IG

N

G R

O U

P:

D R

AW

N

B Y:

C H

EC

KE

D B

Y:

D

ES

IG

N

ED

B

Y:

D

AT

E D

ES

C

R

IP

TI

O

N

1 2 3 4 5

E

D

C

B

A

M

AN

AG

EM

EN

T

IN

FO

R M

AT

IO

N

1 2 3 4 5

E

D

C

B

A

IS

SU

E D

AT

E:

SHEET NUMBER

SH

EE

T

TI

TL

E

D

ES

IG

N

F

IL

E

LO

C

AT

IO

N

W W

YK

R

EP

AI

R

F

IR

E

SU

PP

R

ES

SI

O N

SY

ST

EM

, M

AI

N

T H

AN

G

ER

B

N

O

VE

M

BE

R

H D

R

KEYPLAN

PLAN NORTH

AP

RI

L

TI

N

KE

R P

O

LI

C Y

C H

AN

G

E

LIFE SAFETY PLAN - FIRST FLOOR AREA C

SCALE: 1/16" = 1'-0"

G-101C

8 16 3216

SCALE: 1/16"=1'-0"

PROJECT EGRESS TRAVEL DISTANCE - FIRST FLOOR

COMMON PATH 100 FEET (WITH SPRINKLERS) TABLE 42.2.5

DEAD-END CORRIDOR

NFPA 101 REF.ALLOWED ACTUAL

400 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

COMMON PATH

DEAD-END CORRIDOR

TRAVEL DISTANCE

100 FEET (WITH SPRINKLERS)

50 FEET (WITH SPRINKLERS)

300 FEET (WITH SPRINKLERS)

TABLE 42.2.6

TABLE 42.2.5

COMMON PATH

DEAD-END CORRIDOR

TRAVEL DISTANCE

75 FEET (WITH SPRINKLERS) 13.2.5.1.2

20 FEET (WITH SPRINKLERS) N/A 13.2.5.1.3

250 FEET (WITH SPRINKLERS) 13.2.6.2(1)170 FT

15 FT

65 FT

134 FT

74 FT

N/A

154 FT

70 FT

39.2.5.2

39.2.5.3

39.2.6.1

COMMON PATH 100 FEET (WITH SPRINKLERS) TABLE 40.2.5.1

DEAD-END CORRIDOR

250 FEET (WITH SPRINKLERS) TRAVEL DISTANCE

50 FEET (WITH SPRINKLERS)

TABLE 40.2.6.1

TABLE 40.2.5.1N/A

84 FT

84 FT

BUILDING AREA

EXISTING AREA (GSF)FLOOR

1ST LEVEL HANGAR (GROSS) 103,000

TOTAL 171,080

2ND LEVEL (GROSS)

3RD LEVEL (GROSS)

33,100

1,880

1ST LEVEL SUPPORT AREA (GROSS) 33,100

SHEET NOTES:

1. THE INTENT OF THE LIFE SAFETY SHEETS IS TO IDENTIFY THE EXISTING

CONDITIONS ONLY. THE SCOPE OF WORK DOES NOT INCLUDE UPGRADES

TO THE BUILDING RELATED TO COMPLIANCE WITH THE CURRENT LIFE

SAFETY CODE REQUIREMENTS. IN ACCORDANCE WITH IEBC 804.2, MEANS

OF EGRESS COMPLYING WITH THE REQUIREMENTS OF THE BUILDING CODE

UNDER WHICH THE BUILDING WAS CONSTRUCTED SHALL BE CONSIDERED

TO BE A COMPLIANT MEANS OF EGRESS SYSTEM IF, IN THE OPINION OF THE

CODE OFFICIAL, THEY DO NOT CONSTITUTE A DISTINCT HAZARD TO LIFE

SAFETY.

2. ALL REQUESTED ROOM NUMBERS HAVE BEEN GIVEN. ALL AVAILABLE ROOM

NUMBERS ARE SHOWN.

3. ALL BUILDING AND LIFE SAFETY FEATURES SHOWN ARE BASED ON

AS-BUILTS AND SITE SURVEYING.

LOADLOAD FACTOR AREA TYPEFLOOR REFERENCE

1ST LEVEL ASSEMBLY USE 15 SF/ OCC. 127

1ST LEVEL STORAGE USE (HANGAR) 500 SF/ OCC. 206

2ND LEVEL

TOTAL

3RD LEVEL 19

OCCUPANT LOAD

1ST LEVEL STORAGE USE 500 SF/ OCC. 20 NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

NFPA 101 TABLE 7.3.1.2

1ST LEVEL BUSINESS USE 150 SF/ OCC. 109 NFPA 101 TABLE 7.3.1.2

1ST LEVEL INDUSTRIAL USE 100 SF/ OCC. 130 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 79BUSINESS USE 150 SF/ OCC. NFPA 101 TABLE 7.3.1.2

STORAGE USE 500 SF/ OCC.

INDUSTRIAL USE 100 SF/ OCC.

2ND LEVEL ASSEMBLY USE 15 SF/ OCC. 44 NFPA 101 TABLE 7.3.1.2

2ND LEVEL 110 NFPA 101 TABLE 7.3.1.2INDUSTRIAL USE 100 SF/ OCC.

KEY NOTES:

1 TRAVEL DISTANCES AND COMMON PATHS ORIGINATE FROM UPPER FLOORS,

REFER TO SHEET G-102.

SUPPORT AREAS ARE NOT PERMITTED TO HAVE THEIR REQUIRED EGRESS

THROUGH THE HANGAR BAY WITH THE EXCEPTION OF NORMALLY

UNOCCUPIED ROOMS LESS THAN 100 SQ. FT. THIS REPRESENTS AN EXISTING

NON-COMPLIANT CONDITION PER UFC 4-211-01 § 3-3.1.9. THE SCOPE OF

WORK WILL NOT CORRECT THIS EXISTING NON-COMPLIANT CONDITION.

DOORS ENCROACH INTO MORE THAN ONE-HALF THE REQUIRED WIDTH OF

THE CORRIDOR IN ACCORDANCE WITH NFPA 101 § 7.2.1.4.3. THE SCOPE OF

WORK WILL NOT CORRECT THIS EXISTING NON-COMPLIANT CONDITION.

DEAD END CORRIDOR GREATER THAN 50 FT IN ACCORDANCE WITH NFPA 101

TABLE 40.2.5.1. THE SCOPE OF WORK WILL NOT CORRECT THIS EXISTING

NON-COMPLIANT CONDITION.

2 2

LIFE SAFETY SYMBOLS:

EGRESS TRAVEL DISTANCEXX'

EXIT…