Attachment 7 Site Visit Questions 31 MAR (002).pdf
PDF 66 KB Posted
- Attached to
- Cooling Tower Maintance Federal contract opportunity
- Solicitation number
- W91RUS26QA021
About this file
This document is a Site Visit Questions and Answers attachment for federal contract solicitation W91RUS26QA021 for Cooling Tower Maintenance services. It contains a single question-and-answer exchange addressing contractor inquiries during the site visit phase of procurement.
Question 1 requests basic makeup water quality analysis for the cooling tower system. The government provided city water analysis data from two months (February and March 2026) to establish baseline water characteristics. The February 2026 analysis shows conductivity of 314, pH of 7.74, calcium hardness of 100 ppm CaCO3, alkalinity of 120 ppm CaCO3, and chlorides of 30 ppm Cl. The March 2026 analysis reflects minimal variation with conductivity of 316, pH of 7.85, identical calcium hardness and chlorides, and slightly elevated alkalinity of 160 ppm CaCO3. This water quality data is essential for contractors to develop appropriate cooling tower maintenance proposals and treatment chemical requirements. The document does not address pricing, timelines, or other procurement terms, serving solely as a factual reference for technical specifications.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 6 Site Visit Sign in sheet.pdf | ||
| Attachment 1 Page 2 Site Visit Info.pdf | ||
| SF 30 Amendment 2.pdf | ||
| Attachment 1 Page 1 Extension and Site Visit Info.pdf | ||
| SF 30 Amendment 1.pdf | ||
| Attachment 4 Revised SOW 23Mar26.pdf | ||
| Atch 5 Questions and Answers 23 MAR26.pdf | ||
| Amendment 1 Extension and Site Visit Info.pdf | ||
| Attachment 1 Site Visit Info 19Mar.pdf | ||
| SOW Cooling Tower Monthly Service Revised 19 FEB 26.pdf | ||
| Solicitation - W91RUS26QA021 Cooling Tower final.pdf | ||
| Atch 3 FAR 52.204-26 fill in.pdf | ||
| Atch 2 FAR 52.204-24 Need Filled In and Signed-Returned.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment 7 Site Visit Q & A
Site Visit Questions from Contractors
Cooling Tower Maintenance Solicitation: W91RUS26QA021
Question 1:
• Can you supply a basic make up water quality analysis?
Response: City water analysis as follows:
February 2026 City Water Analysis:
- Conductivity: 314
- pH: 7.74
- Hardness, Calcium (as ppm CaCO3): 100
- Alkalinity, M (as ppm CaCO3): 120
- Chlorides (as ppm CI): 30 March 2026 City Water Analysis:
- Conductivity: 316
- pH: 7.85
- Hardness, Calcium (as ppm CaCO3): 100
- Alkalinity, M (as ppm CaCO3): 160
- Chlorides (as ppm CI): 30