This document is a Job Order Contract Unit Pricebook addendum listing items added to the 2026 Unit Price Book (UPB) that did not exist in the 2025 UPB.

The document specifies new contract line item numbers and their associated specifications across multiple product categories. HVAC equipment comprises the majority of new items, including a start-up service (79-0606 600-0101) and 21 split air conditioning units (79-0606 700-0101 through 700-0121) with varying cooling capacities ranging from 22.4 kW to 135 kW and heating capacities from 25 kW to 150 kW. These units support connectable indoor units ranging from 26 to 64 depending on model size. Building infrastructure items include two fire-rated wall penetrations (81-1302 7210702 and 7210703) for fire department supply DN 80 and alarm bell operation DN 20, both with F90 fire ratings and zinc-coated sheet steel sleeves. Electrical equipment additions include one switch and busbar riser unit (82-0602 0101) rated at 630A-12.5 kA with phase protections, four circuit breakers (82-0604 0101-0104) ranging from 630A to 1,250A, five busbar mounting configurations with rear mounting points and sectionable options (82-0605 01010101 through 01010502), two additional circuit breaker options (82-0605 020101-020102) with operational currents up to 250A and 400A respectively, and a communication module (82-0605 020103) for remote monitoring and operation of motorized circuit breakers. One work-at-height item (98-25 0103) covers work performed at heights between 8 meters and 12 meters.

View the file

Other files

File Type Posted
B08_Conformed_Solicitation Amendment - W912PF26RA0020005-20260506.pdf PDF
B08 - Unit Price Book 2026 DPW_Items Deleted-20260501.pdf PDF
B08_Solicitation Amendment W912PF26RA0020005-20260506.pdf PDF
B08_ATTACHMENT 2_Unit Price Book Europe 2026-20260429.pdf PDF
B08_Solicitation Amendment W912PF26RA0020004-20260429.pdf PDF
B08_Comformed_Solicitation Amendment-W912PF26RA0020004-20260429.pdf PDF
B08-Solicitation Amendment Conformed - W912PF26RA0020003-20260422.pdf PDF
B08-ATTACHMENT 3_JOC Pricing Schedule FY26 Italy(Updated) 20260421.xlsx XLSX spreadsheet
B08-Solicitation Amendment W912PF26RA0020003-20260422.pdf PDF
B08-Attachment 8-(JOC) Pre-Proposal Conference Slides-20260417.pptx PPTX presentation
B08-Attachment 7-JOC Pre-Propoaal Conferance Attendance List-20260417.pdf PDF
B08_Conformed_Solicitation Amendment - W912PF26RA0020002 20260416.pdf PDF
B08_Solicitation Amendment W912PF26RA0020002 SF 30 20260416 1.pdf PDF
B08_Confomed _Solicitation Amendment - W912PF26RA0020002 2020416.pdf PDF
B08_Solicitation Amendment W912PF26RA0020002 SF 30 20260416.pdf PDF
Notice for Pre-Proposal Conference alternate method .pdf PDF
B08_Conformed RFP Amendment - W912PF26RA0020001 20260323.pdf PDF
B08_Solicitation Amendment W912PF26RA0020001 SF 30 20260323.pdf PDF
B08-ATTACHMENT 2_Unit Price Book Europe 2025_Excel version_20251112.xlsx XLSX spreadsheet
B08-ATTACHMENT 3_JOC Pricing Schedule FY26 Italy.xlsx XLSX spreadsheet
B08-ATTACHMENT 5 Past Performance Questionnaire (Form PPQ-0)20260115.pdf PDF
B08_W912PF26RA002_Final_20260309.pdf PDF
B08_ATTACHMENT 1 SOW_20260108.pdf PDF
B08-ATTACHMENT 4 Construction Experience Project Data Sheet 20260115.pdf PDF
B08-ATTACHMENT 6 Example Project Statistics for individual task order_20251112.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Job Order Contract Unit Pricebook

Items added to 2026 UPB

• 79-0606 600-0101 Does Not Exist in 2025 UPB -- Start-up consisƟng of: adjustment of the split air condiƟoner and switch and funcƟon check of the enƟre system. InstrucƟons of the operaƟng staff. PreparaƟon of technical documentaƟon in triplicate for the as-built documentaƟon.

• 79-0606 700-0101 Does Not Exist in 2025 UPB -- Cooling capacity 22.4 kW, power consumpƟon 4.56 kW; heaƟng capacity 25 kW, power consumpƟon 4.47 kW; up to 26 indoor units can be connected.

• 79-0606 700-0102 Does Not Exist in 2025 UPB -- Cooling capacity 28 kW, power consumpƟon 6.19 kW; heaƟng capacity 31.5 kW, power consumpƟon 5.47 kW; up to 33 indoor units can be connected.

• 79-0606 700-0103 Does Not Exist in 2025 UPB -- Cooling capacity 33.5 kW, power consumpƟon 8.31 kW; heaƟng capacity 37.5 kW, power consumpƟon 6.83 kW; up to 40 indoor units can be connected.

• 79-0606 700-0104 Does Not Exist in 2025 UPB -- Cooling capacity 40 kW, power consumpƟon 9.61 kW; heaƟng capacity 45 kW, power consumpƟon 9.37 kW; up to 46 indoor units can be connected.

• 79-0606 700-0105 Does Not Exist in 2025 UPB -- Cooling capacity 45 kW, power input

9.88 kW; heaƟng capacity 50 kW, power input 11.9 kW; up to 53 connectable indoor units.

• 79-0606 700-0106 Does Not Exist in 2025 UPB -- Cooling capacity 50.4 kW, power input

15.2 kW; heaƟng capacity 56.5 kW, power input 12.3 kW; up to 60 connectable units.

• 79-0606 700-0107 Does Not Exist in 2025 UPB -- Cooling capacity 56 kW, power input

18.6 kW; heaƟng capacity 63 kW, power input 14.9 kW; up to 64 connectable indoor units.

• 79-0606 700-0108 Does Not Exist in 2025 UPB -- Cooling capacity: 61.5 kW; power input:

16.38 kW; heaƟng capacity: 69 kW; power input: 14.34 kW; up to 64 connectable indoor units.

• 79-0606 700-0109 Does Not Exist in 2025 UPB -- Cooling capacity 67.4 kW, power input

18.11 kW; heaƟng capacity 75 kW, power input 15.95 kW; up to 64 connectable indoor units.

• 79-0606 700-0110 Does Not Exist in 2025 UPB -- Cooling capacity 73.5 kW, power input

19.93 kW; heaƟng capacity 82.5 kW, power input 17.65 kW; up to 64 connectable indoor units.

• 79-0606 700-0111 Does Not Exist in 2025 UPB -- Cooling capacity 78.5 kW, power input

22.03 kW; heaƟng capacity 87.5 kW, power input 19.25 kW; up to 64 connectable indoor units.

• 79-0606 700-0112 Does Not Exist in 2025 UPB -- Cooling capacity 78.5 kW, power input

22.03 kW; heaƟng capacity 87.5 kW, power input 19.25 kW; up to 64 connectable indoor units.

• 79-0606 700-0113 Does Not Exist in 2025 UPB -- Cooling capacity: 90 kW; power input:

25.6 kW; heaƟng capacity: 100 kW; power input: 22.4 kW; up to 64 connectable indoor units.

• 79-0606 700-0114 Does Not Exist in 2025 UPB -- Cooling capacity 95.4 kW, power input 28 kW; heaƟng capacity 106.5 kW, power input 23.5 kW; up to 64 connectable indoor units.

• 79-0606 700-0115 Does Not Exist in 2025 UPB -- Cooling capacity 101 kW, power input

31.4 kW; heaƟng capacity 113 kW, power input 26.1 kW; up to 64 connectable indoor units.

• 79-0606 700-0116 Does Not Exist in 2025 UPB -- Cooling capacity: 106.3 kW, power input: 29.74 kW; heaƟng capacity: 119 kW, power input: 25.1 kW; up to 64 connectable indoor units.

• 79-0606 700-0117 Does Not Exist in 2025 UPB -- Cooling capacity 111.9 kW, power input

31.58 kW; heaƟng capacity 125.5 kW, power input 26.64 kW; up to 64 connectable indoor units.

• 79-0606 700-0118 Does Not Exist in 2025 UPB -- Cooling capacity 118 kW, power input

32.75 kW; heaƟng capacity 131.5 kW, power input 28.69 kW; up to 64 connectable indoor units.

• 79-0606 700-0119 Does Not Exist in 2025 UPB -- Cooling capacity 123.5 kW, power input

34.83 kW; heaƟng capacity 137.5 kW, power input 30.45 kW; up to 64 indoor units connectable.

• 79-0606 700-0120 Does Not Exist in 2025 UPB -- Cooling capacity 130 kW, power input

36.3 kW; heaƟng capacity 145 kW, power input 32 kW; up to 64 connectable indoor units.

• 79-0606 700-0121 Does Not Exist in 2025 UPB -- Cooling capacity 135 kW, power input

38.4 kW; heaƟng capacity 150 kW, power input 33.6 kW; up to 64 connectable indoor units.

• 81-1302 7210702 Does Not Exist in 2025 UPB -- Opening in exterior wall for fire department supply DN 80 shall be fabricated and pipe lead-through sleeve (fire-rated sleeve) of sheet steel furnished, installed to fit and fixed. ConstrucƟon: Opening W x H = approx. 12 x 12 cm Zinc coated sheet steel sleeve for two-part entry sleeve for pipe penetraƟon DN 80. CoaƟng: 2 coats, Fire stop shall be furnished and installed in the interior wall, fire raƟng F90

• 81-1302 7210703 Does Not Exist in 2025 UPB -- Opening in exterior wall for operaƟon of the alarm bell, shall be fabricated and pipe lead-through sleeve (fire-rated sleeve) of sheet steel to match trapezoidal sheet wall shall be furnished, installed to fit and fixed.

ConstrucƟon: Opening W x H = approx. 12 x 12 cm Zinc coated sheet steel sleeve for two-part pipe penetraƟon for pipe penetraƟon DN 20. CoaƟng: 2 coats, Fire stop shall be furnished and installed in the interior wall, fire-raƟng F90.

• 82-0602 0101 Does Not Exist in 2025 UPB -- 630 A - 12.5 kA switch and busbar riser unit and TA-TV with phase protecƟons (50-51-51N-67N)

• 82-0604 0101 Does Not Exist in 2025 UPB -- four-pole, 630 A

• 82-0604 0102 Does Not Exist in 2025 UPB -- four-pole, 800 A

• 82-0604 0103 Does Not Exist in 2025 UPB -- four-pole, 1,000 A

• 82-0604 0104 Does Not Exist in 2025 UPB -- four-pole, 1,250 A

• 82-0605 01010101 Does Not Exist in 2025 UPB -- Rear mounƟng points

• 82-0605 01010102 Does Not Exist in 2025 UPB – SecƟonable

• 82-0605 01010201 Does Not Exist in 2025 UPB -- Rear mounƟng points

• 82-0605 01010202 Does Not Exist in 2025 UPB – SecƟonable

• 82-0605 01010301 Does Not Exist in 2025 UPB -- Rear mounƟng points

• 82-0605 01010302 Does Not Exist in 2025 UPB – SecƟonable

• 82-0605 01010401 Does Not Exist in 2025 UPB -- Rear mounƟng points

• 82-0605 01010402 Does Not Exist in 2025 UPB – SecƟonable

• 82-0605 01010501 Does Not Exist in 2025 UPB -- Rear mounƟng points

• 82-0605 01010502 Does Not Exist in 2025 UPB – SecƟonable

• 82-0605 020101 Does Not Exist in 2025 UPB -- four-pole with rated operaƟonal current up to 250 A

• 82-0605 020102 Does Not Exist in 2025 UPB -- four-pole with rated operaƟonal current up to 400 A

• 82-0605 020103 Does Not Exist in 2025 UPB -- CommunicaƟon module for circuit breakers with electronic trip unit on BUS line, for remote reading of measurements, seƫngs and status of the circuit breaker/electronic trip unit, remote programming of the trip unit, remote operaƟon of motorized circuit breakers

• 98-25 0103 Does Not Exist in 2025 UPB -- at heights => 8M & < 12M