Replace KC-135 Maintenance Hangar and Shops
McGhee Tyson Air National Guard Base Knoxville, Tennessee
PN PSXE999132
Type B.3 Design Submittal
Specifications Volume 3 of 3
Burns & McDonnell Engineering Co., Inc.
Kansas City, Missouri March 2018
95368
This page was intentionally left blank for duplex printing.
Replace KC-135 Maintenance Hangar and Shops McGhee Tyson Air National Guard Base
Knoxville, Tennessee
PN PSXE999132
Specifications
March 2018 Burns & McDonnell 9400 Ward Parkway
Kansas City, MO 64114
CERTIFICATION PAGE
CERTIFICATION(S)
CIVIL ARCHITECTURAL STRUCTURAL
MECHANICAL ELECTRICAL FIRE PROTECTION
Repl ace KC- 135 Mai nt enance Hangar and Shops 95368 McGhee Tyson Ai r Nat i onal Guar d Base, Knoxvi l l e, TN
PROJECT TABLE OF CONTENTS
DI VI SI ON 00 - PROCUREMENT AND CONTRACTI NG REQUI REMENTS
00 22 13. 00 20 SUPPLEMENTARY I NSTRUCTI ONS TO OFFERORS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 22 00. 00 10 PRI CE AND PAYMENT PROCEDURES
01 30 00 ADMI NI STRATI VE REQUI REMENTS
01 32 01. 00 10 PROJECT SCHEDULE
01 33 00 SUBMI TTAL PROCEDURES
01 33 29 SUSTAI NABI LI TY REPORTI NG
01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS
01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS
01 45 00. 00 10 QUALI TY CONTROL
01 45 35 SPECI AL I NSPECTI ONS
01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS
01 74 19 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT
01 78 00 CLOSEOUT SUBMI TTALS
01 78 23 OPERATI ON AND MAI NTENANCE DATA
01 91 00. 15 TOTAL BUI LDI NG COMMI SSI ONI NG
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 DEMOLITION
02 82 13. 00 10 ASBESTOS ABATEMENT
02 82 33. 13 20 REMOVAL/ CONTROL AND DI SPOSAL OF PAI NT WI TH LEAD
02 83 13. 00 20 LEAD I N CONSTRUCTI ON
DI VI SI ON 03 - CONCRETE
03 11 13. 00 10 STRUCTURAL CAST- I N- PLACE CONCRETE FORMI NG
03 15 00. 00 10 CONCRETE ACCESSORI ES
03 20 00. 00 10 CONCRETE REI NFORCI NG
03 30 00. 00 10 CAST- I N- PLACE CONCRETE
03 30 53 MI SCELLANEOUS CAST- I N- PLACE CONCRETE
03 35 00. 00 10 CONCRETE FI NI SHI NG
03 39 00. 00 10 CONCRETE CURI NG
03 53 14. 00 20 LI GHT REFLECTI VE NONFERROUS METALLI C AGGREGATE FLOOR
SYSTEM
DI VI SI ON 04 - MASONRY
04 20 00 UNI T MASONRY
DI VI SI ON 05 - METALS
05 05 23. 16 STRUCTURAL WELDI NG
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOI ST FRAMI NG
05 30 00 STEEL DECKS
05 40 00 COLD- FORMED METAL FRAMI NG
05 51 33 METAL LADDERS
05 52 00 METAL RAI LI NGS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
PROJECT TABLE OF CONTENTS Page 1
06 10 00 ROUGH CARPENTRY
06 41 16. 00 10 WOOD VENEER ARCHI TECTURAL CABI NETS
06 61 16 SOLI D SURFACI NG FABRI CATI ONS
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 05 23 PRESSURE TESTI NG AND AI R BARRI ER SYSTEM FOR AI R TI GHTNESS
07 11 13 BI TUMI NOUS DAMPPROOFI NG
07 21 13 BOARD AND BLOCK I NSULATI ON
07 21 16 MI NERAL FI BER BLANKET I NSULATI ON
07 21 19 SPRAYED POLYURETHANE FOAM I NSULATI ON
07 22 00 ROOF AND DECK I NSULATI ON
07 27 10. 00 10 BUI LDI NG AI R BARRI ER SYSTEM
07 27 26 FLUI D- APPLI ED MEMBRANE AI R BARRI ER
07 42 13 METAL WALL PANELS
07 42 63 FABRI CATED PANEL ASSEMBLI ES
07 60 00 FLASHI NG AND SHEET METAL
07 61 14. 00 20 STEEL STANDI NG SEAM ROOFI NG
07 72 01 ROOF ACCESSORI ES
07 72 13 PREFABRI CATED ROOF CURBS
07 81 01 I NTUMESCENT PAI NT FI REPROOFI NG
07 84 00 FIRESTOPPING
07 92 00. 00 06 JOI NT SEALANTS
07 95 00 EXPANSI ON CONTROL
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 33 13 COI LI NG COUNTER DOORS
08 34 16. 10 STEEL SLI DI NG HANGAR DOORS
08 34 19. 10 20 ROLLI NG SERVI CE AND FI RE DOORS
08 44 00 CURTAI N WALL AND GLAZED ASSEMBLI ES
08 60 45 TRANSLUCENT PANELS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 81 17 FI RE- RATED GLASS
08 91 00 METAL WALL LOUVERS
DI VI SI ON 09 - FI NI SHES
09 06 90 SCHEDULES FOR PAI NTI NG AND COATI NG
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMI C TI LI NG
09 51 00 ACOUSTI CAL CEI LI NGS
09 65 00 RESI LI ENT FLOORI NG
09 67 23. 13 STANDARD RESI NOUS FLOORI NG
09 67 23. 15 FUEL RESI STI VE RESI NOUS FLOORI NG, 3- COAT SYSTEM
09 90 00 PAI NTS AND COATI NGS
09 96 00 HI GH- PERFORMANCE COATI NGS
DI VI SI ON 10 - SPECI ALTI ES
10 11 00 VI SUAL DI SPLAY UNI TS
10 14 00. 10 EXTERI OR SI GNAGE
10 14 00. 20 I NTERI OR SI GNAGE
10 21 13 TOI LET COMPARTMENTS
10 22 29 ACOUSTI CAL VERTI CAL FOLDI NG PANEL PARTI TI ONS
PROJECT TABLE OF CONTENTS Page 2
10 26 00 WALL AND DOOR PROTECTI ON
10 28 13 TOI LET ACCESSORI ES
10 42 10 DI MENSI ONAL LETTERS
10 51 13 METAL LOCKERS
DI VI SI ON 11 - EQUI PMENT
11 01 50 RI GI D RAI L FALL PROTECTI ON SYSTEMS
DI VI SI ON 12 - FURNI SHI NGS
12 21 00 WI NDOW BLI NDS
12 59 00 SYSTEMS FURNI TURE
DI VI SI ON 13 - SPECI AL CONSTRUCTI ON
13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT
13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT
DI VI SI ON 21 - FI RE SUPPRESSI ON
21 13 13. 00 10 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON
21 13 25. 00 10 HI GH EXPANSI ON FOAM ( HI EX. HEF) FI RE PROTECTI ON SYSTEM
21 30 00 FI RE PUMPS
DI VI SI ON 22 - PLUMBI NG
22 00 00 PLUMBI NG, GENERAL PURPOSE
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS
23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC
23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS
23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC
23 09 13 I NSTRUMENTATI ON AND CONTROL DEVI CES FOR HVAC
23 09 23. 02 BACNET DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER BUI LDI NG
CONTROL SYSTEMS
23 11 25 FACI LI TY GAS PI PI NG
23 35 19. 00 20 I NDUSTRI AL VENTI LATI ON AND EXHAUST
23 52 00 HEATI NG BOI LERS
23 64 10 WATER CHI LLERS, VAPOR COMPRESSI ON TYPE
23 64 26 CHI LLED, CHI LLED- HOT, AND CONDENSER WATER PI PI NG SYSTEMS
23 81 00. 00 20 UNI TARY AI R CONDI TI ONI NG EQUI PMENT
23 82 00. 00 20 TERMI NAL HEATI NG UNI TS
DI VI SI ON 26 - ELECTRI CAL
26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS
26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT
26 12 19. 10 THREE- PHASE PAD- MOUNTED TRANSFORMERS
26 13 01 PAD- MOUNTED DEAD- FRONT AI R I NSULATED SWI TCHGEAR
26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM
26 24 13 SWITCHBOARDS
26 28 01. 00 10 COORDI NATED POWER SYSTEM PROTECTI ON
26 29 23 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS
26 35 43 400- HERTZ ( HZ) SOLI D STATE FREQUENCY CONVERTER
26 36 23. 00 20 MANUAL TRANSFER SWI TCHES
26 41 00 LI GHTNI NG PROTECTI ON SYSTEM
PROJECT TABLE OF CONTENTS Page 3
26 51 00 I NTERI OR LI GHTI NG
26 56 00 EXTERI OR LI GHTI NG
DI VI SI ON 27 - COMMUNI CATI ONS
27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM
27 41 11 AUDI O- VI SUAL SYSTEMS
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEM
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 11 00 CLEARI NG AND GRUBBI NG
31 31 16. 13 CHEMI CAL TERMI TE CONTROL
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D
PAVEMENTS
32 11 23 GRADED- CRUSHED AGGREGATE BASE COURSES
32 11 34 PORTLAND CEMENT- STABI LI ZED BASE OR SUBBASE COURSE
32 12 13 BI TUMI NOUS TACK AND PRI ME COATS
32 12 15. 13 HOT- MI X ASPHALT AI RFI ELD PAVI NG
32 12 16 HOT- MI X ASPHALT ( HMA) FOR ROADS
32 13 11 CONCRETE PAVEMENT FOR AI RFI ELDS AND OTHER HEAVY- DUTY
PAVEMENTS
32 13 13. 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SI TE
FACILITIES
32 13 73 COMPRESSI ON JOI NT SEALS FOR CONCRETE PAVEMENTS
32 15 00 AGGREGATE SURFACI NG
32 16 13 CONCRETE SI DEWALKS AND CURBS AND GUTTERS
32 17 23 PAVEMENT MARKI NGS
32 31 13. 53 HI GH- SECURI TY CHAI N LI NK FENCES AND GATES
32 92 19 SEEDING
32 92 23 SODDING
DI VI SI ON 33 - UTI LI TI ES
33 11 00 WATER UTI LI TY DI STRI BUTI ON PI PI NG
33 30 00 SANI TARY SEWERS
33 32 13. 13 PACKAGED SEWAGE LI FT STATI ONS, WET WELL TYPE
33 34 00 FORCE MAI NS AND I NVERTED SI PHONS; SEWER
33 40 00 STORM DRAI NAGE UTI LI TI ES
33 46 16 SUBDRAI NAGE PI PI NG
33 51 15 NATURAL- GAS / LI QUI D PETROLEUM GAS DI STRI BUTI ON
33 61 13. 13 PREFABRI CATED UNDERGROUND HYDRONI C ENERGY DI STRI BUTI ON
33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON
33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)
DI VI SI ON 41 - MATERI AL PROCESSI NG AND HANDLI NG EQUI PMENT
41 22 23. 19 MONORAI L HOI STS
Appendix A SWPPP
- - End of Pr oj ect Tabl e of Cont ent s - -
PROJECT TABLE OF CONTENTS Page 4
SECTI ON 26 00 00. 00 20
BASI C ELECTRI CAL MATERI ALS AND METHODS
07/06
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s Speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.
ASTM I NTERNATI ONAL ( ASTM)
ASTM D709 ( 2017) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code
I EEE C57. 12. 28 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y
I EEE C57. 12. 29 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y f or Coast al Environments
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3) Nat i onal El ect r i cal Code
1. 2 RELATED REQUI REMENTS
Thi s sect i on appl i es t o cer t ai n sect i ons of DI VI SI ON 02, EXI STI NG CONDI TI ONS, DI VI SI ON 11, EQUI PMENT, DI VI SI ON 14, CONVEYI NG EQUI PMENT and DI VI SI ONS 22 and 23, PLUMBI NG and HEATI NG VENTI LATI NG AND AI R CONDI TI ONI NG. Thi s Sect i on appl i es t o al l Sect i ons of DI VI SI ON 26 and 33, ELECTRI CAL and UTI LI TI ES, of t hi s Pr oj ect Speci f i cat i on unl ess speci f i ed ot her wi se i n t he i ndi v i dual Sect i ons. Thi s Sect i on has been i ncor por at ed i nt o, and t hus, does not appl y t o, and i s not r ef er enced i n t he f ol l owi ng Sect i ons.
a. Sect i on 26 12 19. 10 THREE- PHASE PAD MOUNTED TRANSFORMERS.
b. Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.
c. Sect i on 26 24 13 SWI TCHBOARDS.
SECTI ON 26 00 00. 00 20 Page 1
d. Sect i on 26 51 00 I NTERI OR LI GHTI NG.
e. Sect i on 26 56 00 EXTERI OR LI GHTI NG.
f . Sect i on 27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM.
1. 3 DEFINITIONS
a. Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese Speci f i cat i ons, and on t he Dr awi ngs, shal l be as def i ned i n I EEE 100.
b. The t echni cal sect i ons r ef er r ed t o her ei n ar e t hose Speci f i cat i on Sect i ons t hat descr i be pr oduct s, i nst al l at i on pr ocedur es, and equi pment oper at i ons and t hat r ef er t o t hi s Sect i on f or det ai l ed descr i pt i on of submi t t al t ypes.
c. The t echni cal par agr aphs r ef er r ed t o her ei n ar e t hose par agr aphs i n PART 2 - PRODUCTS and PART 3 - EXECUTI ON of t he t echni cal sect i ons t hat descr i be pr oduct s, syst ems, i nst al l at i on pr ocedur es, equi pment , and t est met hods.
1. 4 ELECTRI CAL CHARACTERI STI CS
El ect r i cal char act er i st i cs f or t hi s Pr oj ect shal l be 12. 47 kV pr i mar y, t hr ee phase, f our wi r e, 60 Hz, and 480Y/ 277 vol t s secondar y, t hr ee phase, f our wi r e. Fi nal connect i ons t o t he power di st r i but i on syst em at t he exi st i ng manhol e shal l be made by t he Cont r act or as di r ect ed by t he Cont r act i ng Of f i cer Gover nment .
1. 5 ADDI TI ONAL SUBMI TTALS I NFORMATI ON
Submi t t al s r equi r ed i n ot her Sect i ons t hat r ef er t o t hi s Sect i on must conf or m t o t he f ol l owi ng addi t i onal r equi r ement s as appl i cabl e.
1. 5. 1 Shop Dr awi ngs ( SD- 02)
I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. Wi r i ng di agr ams shal l i dent i f y c i r cui t t er mi nal s and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . Dr awi ngs shal l i ndi cat e adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces.
1. 5. 2 Pr oduct Dat a ( SD- 03)
Submi t t al shal l i ncl ude per f or mance and char act er i st i c cur ves.
1. 6 QUALI TY ASSURANCE
1. 6. 1 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of
SECTI ON 26 00 00. 00 20 Page 2 si mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p shal l be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 6. 2 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year per i od shal l i nc l ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems shal l be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t he t echni cal sect i on.
1. 6. 2. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 6. 2. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 3 year s pr i or t o dat e of del i ver y t o s i t e shal l not be used, unl ess speci f i ed ot her wi se.
1. 7 WARRANTY
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he Cont r act .
1. 8 POSTED OPERATI NG I NSTRUCTI ONS
Pr ovi de f or each syst em and pr i nc i pal i t em of equi pment as speci f i ed i n t he t echni cal sect i ons f or use by oper at i on and mai nt enance per sonnel . The oper at i ng i nst r uct i ons shal l i ncl ude t he f ol l owi ng:
a. Wi r i ng di agr ams, cont r ol di agr ams, and cont r ol sequence f or each pr i nci pal syst em and i t em of equi pment .
b. St ar t up, pr oper adj ust ment , oper at i ng, l ubr i cat i on, and shut down procedures.
c. Saf et y pr ecaut i ons.
d. The pr ocedur e i n t he event of equi pment f ai l ur e.
e. Ot her i t ems of i nst r uct i on as r ecommended by t he manuf act ur er of each syst em or i t em of equi pment .
Pr i nt or engr ave oper at i ng i nst r uct i ons and f r ame under gl ass or i n appr oved l ami nat ed pl ast i c. Post i nst r uct i ons wher e di r ect ed. For
SECTI ON 26 00 00. 00 20 Page 3 oper at i ng i nst r uct i ons exposed t o t he weat her , pr ovi de weat her - r esi st ant mat er i al s or weat her pr oof encl osur es. Oper at i ng i nst r uct i ons shal l not f ade when exposed t o sunl i ght and shal l be secur ed t o pr event easy r emoval or peel i ng.
1. 9 MANUFACTURER' S NAMEPLATE
Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be acceptable.
1. 10 FI ELD FABRI CATED NAMEPLATES
ASTM D709. Pr ovi de l ami nat ed pl ast i c namepl at es f or each equi pment encl osur e, r el ay, swi t ch, and devi ce; as speci f i ed i n t he t echni cal sect i ons or as i ndi cat ed on t he Dr awi ngs. Each namepl at e i nscr i pt i on shal l i dent i f y t he f unct i on and, when appl i cabl e, t he posi t i on. Namepl at es shal l be mel ami ne pl ast i c, 0. 125 i nch t hi ck, whi t e wi t h bl ack cent er cor e.
Sur f ace shal l be mat t e f i ni sh. Cor ner s shal l be squar e. Accur at el y al i gn l et t er i ng and engr ave i nt o t he cor e. Mi ni mum si ze of namepl at es shal l be 1 by 2- 1/ 2 i nches. Let t er i ng shal l be a mi ni mum of 0. 25 i nch hi gh nor mal bl ock st y l e.
1. 11 WARNI NG SI GNS
Pr ovi de war ni ng s i gns f or t he encl osur es of el ect r i cal equi pment i ncl udi ng subst at i ons, pad- mount ed t r ansf or mer s, pad- mount ed swi t ches, gener at or s, and swi t chgear havi ng a nomi nal r at i ng exceedi ng 600 vol t s.
a. When t he encl osur e i nt egr i t y of such equi pment i s speci f i ed t o be i n accor dance wi t h I EEE C57. 12. 28 or I EEE C57. 12. 29, such as f or pad- mount ed t r ansf or mer s, pr ovi de sel f - adhesi ve war ni ng s i gns on t he out s i de of t he hi gh vol t age compar t ment door ( s) . Si gn shal l be a decal and shal l have nomi nal di mensi ons of 7 by 10 i nches wi t h t he l egend " DANGER HI GH VOLTAGE" pr i nt ed i n t wo l i nes of nomi nal 2 i nch hi gh l et t er s. The wor d " DANGER" shal l be i n whi t e l et t er s on a r ed backgr ound and t he wor ds " HI GH VOLTAGE" shal l be i n bl ack l et t er s on a whi t e backgr ound. Decal shal l be Pandui t No. PPSO710D72 or appr oved equal.
b. When such equi pment i s guar ded by a f ence, mount s i gns on t he f ence.
Pr ovi de met al s i gns havi ng nomi nal di mensi ons of 14 by 10 i nches wi t h t he l egend " DANGER HI GH VOLTAGE KEEP OUT" pr i nt ed i n t hr ee l i nes of nomi nal 3 i nch hi gh whi t e l et t er s on a r ed and bl ack f i el d.
1. 12 ELECTRI CAL REQUI REMENTS
El ect r i cal i nst al l at i ons shal l conf or m t o I EEE C2, NFPA 70, and r equi r ement s speci f i ed her ei n.
1. 13 I NSTRUCTI ON TO GOVERNMENT PERSONNEL
Wher e speci f i ed i n t he t echni cal sect i ons, f ur ni sh t he ser vi ces of compet ent i nst r uct or s t o gi ve f ul l i nst r uct i on t o desi gnat ed Gover nment per sonnel i n t he adj ust ment , oper at i on, and mai nt enance of t he speci f i ed syst ems and equi pment , i ncl udi ng per t i nent saf et y r equi r ement s as r equi r ed.
I nst r uct or s shal l be t hor oughl y f ami l i ar wi t h al l par t s of t he i nst al l at i on and shal l be t r ai ned i n oper at i ng t heor y as wel l as pr act i cal
SECTI ON 26 00 00. 00 20 Page 4 oper at i on and mai nt enance wor k. I nst r uct i on shal l be gi ven dur i ng t he f i r st r egul ar wor k week af t er t he equi pment or syst em has been accept ed and t ur ned over t o t he Gover nment f or r egul ar oper at i on. The number of man- days ( 8 hour s per day) of i nst r uct i on f ur ni shed shal l be as speci f i ed i n t he i ndi v i dual sect i on.
PART 2 PRODUCTS
Not Used.
PART 3 EXECUTI ON
3. 1 FI ELD APPLI ED PAI NTI NG
Pai nt el ect r i cal equi pment as r equi r ed t o mat ch f i ni sh of adj acent sur f aces or t o meet t he i ndi cat ed or speci f i ed saf et y cr i t er i a. Pai nt i ng shal l be as speci f i ed i n t he sect i on speci f y i ng t he associ at ed el ect r i cal equi pment .
3. 2 FI ELD FABRI CATED NAMEPLATE MOUNTI NG
Pr ovi de number , l ocat i on, and l et t er desi gnat i on of namepl at es as i ndi cat ed. Fast en namepl at es t o t he devi ce wi t h a mi ni mum of t wo sheet - met al scr ews or t wo r i vet s.
3. 3 WARNI NG SI GN MOUNTI NG
Pr ovi de t he number of s i gns r equi r ed t o be r eadabl e f r om each accessi bl e s i de, but space t he s i gns a maxi mum of 30 f eet apar t .
- - End of Sect i on - -
SECTI ON 26 00 00. 00 20 Page 5
SECTI ON 26 05 48. 00 10
SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT
10/07
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN I NSTI TUTE OF STEEL CONSTRUCTI ON ( AI SC)
AI SC 325 ( 2011) St eel Const r uct i on Manual
ASTM I NTERNATI ONAL ( ASTM)
ASTM E580/ E580M ( 2014) St andar d Pr act i ce f or I nst al l at i on of Cei l i ng Suspensi on Syst ems f or Acoust i cal Ti l e and Lay- i n Panel s i n Ar eas Subj ect t o Ear t hquake Gr ound Mot i ons
U. S. DEPARTMENT OF DEFENSE ( DOD)
UFC 3- 310- 04 ( 2016) Sei smi c Desi gn f or Bui l di ngs wi t h change 1, 20 June 2016
UFC 4- 010- 01 ( 2013) DoD Mi ni mum Ant i t er r or i sm St andar ds f or Bui l di ngs
UNDERWRI TERS LABORATORI ES ( UL)
UL 1598 ( 2008; Repr i nt Oct 2012) Lumi nai r es
1. 2 SYSTEM DESCRI PTI ON
1. 2. 1 Gener al Requi r ement s
The r equi r ement s f or sei smi c pr ot ect i on measur es descr i bed i n t hi s sect i on shal l be appl i ed t o t he el ect r i cal equi pment and syst ems l i s t ed bel ow.
St r uct ur al r equi r ement s shal l be i n accor dance wi t h Sect i on 13 48 00
SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT.
1. 2. 2 El ect r i cal Equi pment
El ect r i cal equi pment shal l i ncl ude t he f ol l owi ng i t ems t o t he ext ent r equi r ed on t he dr awi ngs or i n ot her sect i ons of t hese speci f i cat i ons:
Pumps wi t h Mot or s
Li ght Fi xt ur es
SECTI ON 26 05 48. 00 10 Page 1
Swi t chboar ds ( Fl oor Mount ed)
Transformers
1. 2. 3 El ect r i cal Syst ems
The f ol l owi ng el ect r i cal syst ems shal l be i nst al l ed as r equi r ed on t he dr awi ngs and ot her sect i ons of t hese speci f i cat i ons and shal l be sei smi cal l y pr ot ect ed i n accor dance wi t h t hi s speci f i cat i on:
1. 2. 4 Cont r act or Desi gned Br aci ng
Submi t copi es of t he Desi gn Cal cul at i ons wi t h t he Dr awi ngs. Cal cul at i ons shal l be appr oved, cer t i f i ed, st amped and si gned by a Regi st er ed Pr of essi onal Engi neer . Cal cul at i ons shal l ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace. Desi gn t he br aci ng i n accor dance wi t h UFC 3- 310- 04 and addi t i onal dat a f ur ni shed by t he Cont r act i ng Of f i cer . Resi st ance t o l at er al f or ces i nduced by ear t hquakes shal l be accompl i shed wi t hout consi der at i on of f r i c t i on r esul t i ng f r om gr avi t y l oads. UFC 3- 310- 04 uses par amet er s f or t he bui l di ng, not f or t he equi pment i n t he bui l di ng;
t her ef or e, cor r espondi ng adj ust ment s t o t he f or mul as shal l be r equi r ed.
Loadi ngs det er mi ned usi ng UFC 3- 310- 04 ar e based on st r engt h desi gn;
therefore, AI SC 325 shal l be used f or t he desi gn. Br aci ng shal l compl y wi t h t he r equi r ement s of UFC 4- 010- 01 wher e r equi r ed f or i nhabi t ed and pr i mar y gat her i ng f aci l i t i es and 13 48 00 SEI SMI C PROTECTI ON FOR
MI SCELLANEOUS EQUI PMENT.
1. 2. 5 Condui t s Requi r i ng No Speci al Sei smi c Rest r ai nt s
Sei smi c r est r ai nt s may be omi t t ed f r om el ect r i cal condui t l ess t han 2- 1/ 2 i nches t r ade si ze. Al l ot her i nt er i or condui t , shal l be sei smi cal l y pr ot ect ed as speci f i ed.
1. 3 EQUI PMENT REQUI REMENTS
Submi t det ai l dr awi ngs al ong wi t h cat al og cut s, t empl at es, and er ect i on and i nst al l at i on det ai l s , as appr opr i at e, f or t he i t ems l i s t ed. Submi t t al s shal l be compl et e i n det ai l , i ndi cat i ng t hi ckness, t ype, gr ade, c l ass of met al , and di mensi ons; and shal l show const r uct i on det ai l s , r ei nf or cement , anchor age, and i nst al l at i on wi t h r el at i on t o t he bui l di ng const r uct i on.
Submi t copi es of t he desi gn cal cul at i ons wi t h t he det ai l dr awi ngs.
Cal cul at i ons shal l be st amped by a r egi st er ed engi neer and shal l ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace.
1. 4 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Li ght i ng Fi xt ur es i n Bui l di ngs
SECTI ON 26 05 48. 00 10 Page 2
Equi pment Requi r ement s
SD- 03 Pr oduct Dat a
Li ght i ng Fi xt ur es i n Bui l di ngs; G
Equi pment Requi r ement s; G
Cont r act or Desi gned Br aci ng; G
PART 2 PRODUCTS
2. 1 LI GHTI NG FI XTURE SUPPORTS
Li ght i ng f i x t ur es and suppor t s shal l conf or m t o UL 1598.
2. 2 SWAY BRACI NG MATERI ALS
Sway br aci ng mat er i al s ( e. g. , r ods, pl at es, r ope, angl es, et c. ) shal l be as speci f i ed i n Sect i on 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS
EQUIPMENT.
PART 3 EXECUTI ON
3. 1 SWAY BRACES FOR CONDUI T
Condui t shal l be br aced as f or an equi val ent wei ght pi pe i n accor dance wi t h Sect i on 13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT.
3. 2 LI GHTI NG FI XTURES I N BUI LDI NGS
Li ght i ng f i x t ur es and suppor t s shal l conf or m t o t he f ol l owi ng:
3. 2. 1 Pendant Fi xt ur es
Pendant f i x t ur es shal l conf or m t o t he r equi r ement s of UFC 3- 310- 04.
3. 2. 2 Assembl y Mount ed on Out l et Box
A suppor t i ng assembl y, t hat i s i nt ended t o be mount ed on an out l et box, shal l be desi gned t o accommodat e mount i ng f eat ur es on 4 i nch boxes, pl ast er r i ngs, and f i x t ur e st uds.
3. 2. 3 Wal l - Mount ed Emer gency Li ght Uni t
At t achment s f or wal l - mount ed emer gency l i ght uni t s shal l be desi gned and secur ed f or t he wor st expect ed sei smi c di st ur bance at t he s i t e.
3. 2. 4 Lat er al For ce
St r uct ur al r equi r ement s f or l i ght f i x t ur e br aci ng shal l be i n accor dance wi t h Sect i on 13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT.
SECTI ON 26 05 48. 00 10 Page 3
SECTI ON 26 12 19. 10
THREE- PHASE PAD- MOUNTED TRANSFORMERS
02/12
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN CONCRETE I NSTI TUTE I NTERNATI ONAL ( ACI )
ACI 318M ( 2014; ERTA 2015) Bui l di ng Code Requi r ement s f or St r uct ur al Concr et e & Commentary
ASTM I NTERNATI ONAL ( ASTM)
ASTM A240/ A240M ( 2016) St andar d Speci f i cat i on f or Chr omi um and Chr omi um- Ni ckel St ai nl ess St eel Pl at e, Sheet , and St r i p f or Pr essur e Vessel s and f or Gener al Appl i cat i ons
ASTM C260/ C260M ( 2010a) St andar d Speci f i cat i on f or Ai r - Ent r ai ni ng Admi xt ur es f or Concr et e
ASTM D117 ( 2010) St andar d Gui de f or Sampl i ng, Test Met hods, Speci f i cat i ons and Gui de f or El ect r i cal I nsul at i ng Oi l s of Pet r ol eum Origin
ASTM D1535 ( 2014) Speci f y i ng Col or by t he Munsel l System
ASTM D3487 ( 2009) St andar d Speci f i cat i on f or Mi ner al I nsul at i ng Oi l Used i n El ect r i cal Appar at us
ASTM D877/ D877M ( 2013) St andar d Test Met hod f or Di el ect r i c Br eakdown Vol t age of I nsul at i ng Li qui ds Usi ng Di sk El ect r odes
ASTM D92 ( 2012b) St andar d Test Met hod f or Fl ash and Fi r e Poi nt s by Cl evel and Open Cup Test er
ASTM D97 ( 2016) Pour Poi nt of Pet r ol eum Pr oduct s
FM GLOBAL ( FM)
FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de http://www.approvalguide.com/
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
SECTI ON 26 12 19. 10 Page 1
I EEE 386 ( 2006; I NT 1 2011) St andar d f or Separ abl e I nsul at ed Connect or Syst ems f or Power Di st r i but i on Syst ems Above 600V
I EEE C2 ( 2012; Er r at a 1 2012; I NT 1- 4 2012; Er r at a
2 2013; I NT 5- 7 2013; I NT 8- 10 2014; I NT
11 2015; I NT 12 2016) Nat i onal El ect r i cal Saf et y Code
I EEE C37. 47 ( 2011) St andar d f or Hi gh Vol t age Cur r ent - Li mi t i ng Type Di st r i but i on Cl ass Fuses and Fuse Di sconnect i ng Swi t ches
I EEE C57. 12. 00 ( 2015) St andar d Gener al Requi r ement s f or Li qui d- I mmer sed Di st r i but i on, Power , and Regul at i ng Tr ansf or mer s
I EEE C57. 12. 28 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y
I EEE C57. 12. 29 ( 2014) St andar d f or Pad- Mount ed Equi pment
- Encl osur e I nt egr i t y f or Coast al Environments
I EEE C57. 12. 34 ( 2009) St andar d f or Requi r ement s f or Pad- Mount ed, Compar t ment al - Type, Sel f - Cool ed, Thr ee- Phase Di st r i but i on Tr ansf or mer s, 5 MVA and Smal l er ; Hi gh Vol t age, 34. 5 kV Nomi nal Syst em Vol t age and Bel ow; Low Vol t age, 15 kV Nomi nal Syst em Vol t age and Bel ow
I EEE C57. 12. 90 ( 2015) St andar d Test Code f or Li qui d- I mmer sed Di st r i but i on, Power , and Regul at i ng Tr ansf or mer s
I EEE C57. 13 ( 2008; I NT 2009) St andar d Requi r ement s f or I nst r ument Tr ansf or mer s
I EEE C57. 98 ( 2011) Gui de f or Tr ansf or mer I mpul se Test s
I EEE C62. 11 ( 2012) St andar d f or Met al - Oxi de Sur ge Ar r est er s f or Al t er nat i ng Cur r ent Power Ci r cui t s ( >1kV)
I NTERNATI ONAL ELECTRI CAL TESTI NG ASSOCI ATI ON ( NETA)
NETA ATS ( 2013) St andar d f or Accept ance Test i ng Speci f i cat i ons f or El ect r i cal Power Equi pment and Syst ems
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
ANSI C12. 1 ( 2008) El ect r i c Met er s Code f or El ect r i c i t y Met er i ng
ANSI C12. 7 ( 2014) Requi r ement s f or Wat t hour Met er Sockets
SECTI ON 26 12 19. 10 Page 2
NEMA LI 1 ( 1998; R 2011) I ndust r i al Lami nat i ng Ther moset t i ng Pr oduct s
NEMA/ ANSI C12. 10 ( 2011) Physi cal Aspect s of Wat t hour Met er s
- Saf et y St andar ds
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2014; AMD 1 2013; Er r at a 1 2013; AMD 2 2013; Er r at a 2 2013; AMD 3 2014; Er r at a 3- 4 2014; AMD 4- 6 2014) Nat i onal El ect r i cal Code
ORGANI SATI ON FOR ECONOMI C CO- OPERATI ON AND DEVELOPMENT ( OECD)
OECD Test 203 ( 1992) Fi sh Acut e Toxi c i t y Test
U. S. ENVI RONMENTAL PROTECTI ON AGENCY ( EPA)
EPA 712- C- 98- 075 ( 1998) Fat e, Tr anspor t and Tr ansf or mat i on Test Gui del i nes - OPPTS 835. 3100- " Aer obi c Aquat i c Bi odegr adat i on"
EPA 821- R- 02- 012 ( 2002) Met hods f or Measur i ng t he Acut e Toxi c i t y of Ef f l uent s and Recei v i ng Wat er s t o Fr eshwat er and Mar i ne Or gani sms
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
10 CFR 431 Ener gy Ef f i c i ency Pr ogr am f or Cer t ai n Commer ci al and I ndust r i al Equi pment
UNDERWRI TERS LABORATORI ES ( UL)
UL 467 ( 2013) Gr oundi ng and Bondi ng Equi pment
1. 2 DEFINITIONS
Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, shal l be as def i ned i n
I EEE 100.
1. 3 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Pad- mount ed t r ansf or mer dr awi ngs; G
SD- 03 Pr oduct Dat a
Pad- mount ed t r ansf or mer s; G
SECTI ON 26 12 19. 10 Page 3
Submi t t al shal l i ncl ude manuf act ur er ' s i nf or mat i on f or each component , devi ce, i nsul at i ng f l ui d, and accessor y pr ovi ded wi t h t he t r ansf or mer .
SD- 06 Test Repor t s
Accept ance checks and t est s; G
Submi t t al shal l i ncl ude accept ance cr i t er i a and l i mi t s f or each t est i n accor dance wi t h NETA ATS " Test Val ues" .
SD- 07 Cer t i f i cat es
Tr ansf or mer Ef f i c i enci es; G
Submi t cer t i f i cat i on, i ncl udi ng suppor t i ng cal cul at i ons, f r om t he manuf act ur er i ndi cat i ng conf or mance wi t h t he par agr aph ent i t l ed " Speci f i ed Tr ansf or mer Ef f i c i enci es. "
SD- 09 Manuf act ur er ' s Fi el d Repor t s
Pad- mount ed t r ansf or mer desi gn t est s; G
Pad- mount ed t r ansf or mer r out i ne and ot her t est s; G
SD- 10 Oper at i on and Mai nt enance Dat a
Tr ansf or mer ( s) , Dat a Package 5; G
Submi t oper at i on and mai nt enance dat a i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA and as speci f i ed her ei n.
SD- 11 Cl oseout Submi t t al s
Tr ansf or mer t est schedul e; G
Submi t r epor t of t est r esul t s as speci f i ed by par agr aph ent i t l ed " Fi el d Qual i t y Cont r ol . "
1. 3. 1 Reduced Submi t t al Requi r ement s
Tr ansf or mer s desi gned and manuf act ur ed by ABB i n Jef f er son Ci t y, MO; by Cooper Power Syst ems i n Waukesha, WI ; by ERMCO i n Dyer sbur g, TN; or by Howar d I ndust r i es i n Laur el , MS need not submi t t he ent i r e submi t t al package r equi r ement s of t hi s cont r act . I nst ead, t he f ol l owi ng i t ems shal l be submi t t ed:
a. A cer t i f i cat i on, s i gned by t he manuf act ur er , s t at i ng t hat t he t echni cal r equi r ement s of t hi s speci f i cat i on shal l be met .
b. An out l i ne dr awi ng of t he t r ansf or mer wi t h devi ces i dent i f i ed ( par agr aph ent i t l ed " Pad- Mount ed Tr ansf or mer Dr awi ngs" , i t em a) .
c. ANSI namepl at e dat a of t he t r ansf or mer ( par agr aph ent i t l ed " Pad- Mount ed Tr ansf or mer Dr awi ngs" , i t em b) .
d. Pr ovi de accept ance t est r epor t s r equi r ed by submi t t al i t em " SD- 06 Test Reports".
SECTI ON 26 12 19. 10 Page 4
e. Pr ovi de oper at i on and mai nt enance manual s r equi r ed by submi t t al i t em " SD- 10 Oper at i on and Mai nt enance Dat a" .
1. 4 QUALI TY ASSURANCE
1. 4. 1 Pad- Mount ed Tr ansf or mer Dr awi ngs
Dr awi ngs shal l i ndi cat e, but not be l i mi t ed t o t he f ol l owi ng:
a. An out l i ne dr awi ng, wi t h f r ont , t op, and si de v i ews.
b. ANSI namepl at e dat a.
c. El ement ar y di agr ams and wi r i ng di agr ams.
d. One- l i ne di agr am, i ncl udi ng swi t ch( es) .
e. Manuf act ur er ' s publ i shed t i me- cur r ent cur ves ( on f ul l s i ze l ogar i t hmi c paper ) of t he t r ansf or mer hi gh s i de f uses.
1. 4. 2 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p shal l be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 4. 3 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year per i od shal l i nc l ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems shal l be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.
1. 4. 3. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 4. 3. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 3 year s pr i or t o dat e of del i ver y t o s i t e shal l not be used, unl ess speci f i ed ot her wi se.
SECTI ON 26 12 19. 10 Page 5
1. 5 MAINTENANCE
1. 5. 1 Addi t i ons t o Oper at i on and Mai nt enance Dat a
I n addi t i on t o r equi r ement s of Dat a Package 5, i nc l ude t he f ol l owi ng on t he act ual t r ansf or mer ( s) pr ovi ded:
a. An i nst r uct i on manual wi t h per t i nent i t ems and i nf or mat i on hi ghl i ght ed.
b. An out l i ne dr awi ng, f r ont , t op, and si de v i ews.
c. Pr i ces f or spar e par t s and suppl y l i s t .
d. Rout i ne and f i el d accept ance t est r epor t s.
e. Fuse cur ves f or pr i mar y f uses.
f . Act ual namepl at e di agr am.
g. Dat e of pur chase.
1. 6 WARRANTY
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
PART 2 PRODUCTS
2. 1 PRODUCT COORDI NATI ON
Pr oduct s and mat er i al s not consi der ed t o be pad- mount ed t r ansf or mer s and r el at ed accessor i es ar e speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON
SYSTEM.
2. 2 THREE- PHASE PAD- MOUNTED TRANSFORMERS
I EEE C57. 12. 34, I EEE C57. 12. 28, and as speci f i ed her ei n.
2. 2. 1 Compartments
The hi gh- and l ow- vol t age compar t ment s shal l be separ at ed by st eel i sol at i ng bar r i er s ext endi ng t he f ul l hei ght and dept h of t he compar t ment s.
Compar t ment door s: hi nged l i f t - of f t ype wi t h st op i n open posi t i on and t hr ee- poi nt l at chi ng.
2. 2. 1. 1 Hi gh Vol t age, Dead- Fr ont
Hi gh- vol t age compar t ment shal l cont ai n t he i ncomi ng l i ne, i nsul at ed hi gh- vol t age dead- br eak connect or s, bushi ng wel l i nser t s, s i x hi gh- vol t age bushi ng wel l s conf i gur ed f or l oop f eed appl i cat i on, l oad- br eak swi t ch handl e( s) , access t o oi l - i mmer sed bayonet f uses, t ap changer handl e, connect or par ki ng st ands, and gr ound pad.
a. I nsul at ed hi gh- vol t age l oad- br eak connect or s: I EEE 386, r at ed 15 kV, 95 kV BI L. Cur r ent r at i ng: 200 amper es r ms cont i nuous. Shor t t i me r at i ng: 10, 000 amper es r ms symmet r i cal f or a t i me dur at i on of 0. 17 seconds. Connect or shal l have a st eel r ei nf or ced hook- st i ck eye, SECTI ON 26 12 19. 10 Page 6 gr oundi ng eye, t est poi nt , and ar c- quenchi ng cont act mat er i al .
b. Pr ovi de bayonet t ype, oi l - i mmer sed, expul s i on f uses i n ser i es wi t h oi l - i mmer sed, par t i al - r ange, cur r ent - l i mi t i ng f uses. Bayonet f use l i nks shal l sense bot h hi gh cur r ent s and hi gh oi l t emper at ur e i n or der t o pr ovi de t her mal pr ot ect i on t o t he t r ansf or mer . Coor di nat e t r ansf or mer pr ot ect i on wi t h expul s i on f use c l ear i ng l ow- cur r ent f aul t s and cur r ent - l i mi t i ng f use c l ear i ng hi gh- cur r ent f aul t s beyond t he i nt er r upt i ng r at i ng of t he expul s i on f use. I n or der t o el i mi nat e or mi ni mi ze oi l spi l l s , t he bayonet f use assembl y shal l i ncl ude an oi l r et ent i on val ve i nsi de t he housi ng whi ch c l oses when t he f use hol der i s r emoved and an ext er nal dr i p shi el d. War ni ng shal l be conspi cuousl y di spl ayed wi t hi n t he hi gh- vol t age compar t ment caut i oni ng agai nst r emovi ng or i nser t i ng f uses unl ess t he l oad- br eak swi t ch i s i n t he open posi t i on and t he t ank pr essur e has been r el eased.
( 1) Bayonet f use assembl y: 150 kV BI L.
( 2) Oi l - i mmer sed cur r ent - l i mi t i ng f uses: I EEE C37. 47; 50, 000 r ms amper es symmet r i cal i nt er r upt i ng r at i ng at t he syst em vol t age speci f i ed. Connect cur r ent - l i mi t i ng f uses ahead of t he r adi al - f eed l oad- br eak swi t ch.
c. Sur ge ar r est er s: I EEE C62. 11, r at ed 15 kV, f ul l y shi el ded, dead- f r ont , met al - oxi de- var i st or , el bow t ype wi t h r esi st ance- gr aded gap. Pr ovi de t hr ee ar r est er s f or r adi al f eed c i r cui t s.
d. Pr ot ect i ve caps: I EEE 386, 200 amper es, 15 kV Cl ass. Pr ovi de i nsul at ed pr ot ect i ve caps ( not shi ppi ng caps) f or i nsul at i ng and seal i ng out moi st ur e f r om unused bushi ngs.
2. 2. 1. 2 Low Vol t age
Low- vol t age compar t ment shal l cont ai n l ow- vol t age bushi ngs wi t h NEMA spade t er mi nal s, accessor i es, st ai nl ess st eel or l aser - et ched anodi zed al umi num di agr ammat i c t r ansf or mer namepl at e, and gr ound pad.
a. Accessor i es shal l i ncl ude dr ai n val ve wi t h sampl er devi ce, f i l l pl ug, pr essur e r el i ef devi ce, l i qui d l evel gage, pr essur e- vacuum gage, and di al t ype t her momet er wi t h maxi mum t emper at ur e i ndi cat or . Pr ovi de a r emovabl e 600V Vol t r at ed secondar y NEMA spade t er mi nal i nsul at i ng syst em t o compl et el y i nsul at e and cover t hese exposed l i ve par t s wi t hi n t he secondar y compar t ment .
2. 2. 2 Transformer
a. Less- f l ammabl e l i qui d- i nsul at ed, t wo wi ndi ng, 60 her t z, 65 degr ees C r i se above a 30 degr ees C aver age ambi ent , sel f - cool ed t ype.
b. Tr ansf or mer shal l be r at ed as i ndi cat ed.
c. Tr ansf or mer vol t age r at i ngs: As i ndi cat ed.
d. Tap changer shal l be ext er nal l y oper at ed, manual t ype f or changi ng t ap set t i ng when t he t r ansf or mer i s de- ener gi zed. Pr ovi de f our 2. 5 per cent f ul l capaci t y t aps, t wo above and t wo bel ow r at ed pr i mar y vol t age. Tap changer s shal l c l ear l y i ndi cat e whi ch t ap set t i ng i s i n use.
e. Mi ni mum t est ed per cent i mpedance at 85 degr ees C shal l not be l ess t han
SECTI ON 26 12 19. 10 Page 7 t he f ol l owi ng val ues:
( 1) 2. 50 f or uni t s r at ed 75kVA and bel ow.
( 2) 2. 87 f or uni t s r at ed 112. 5kVA t o 300kVA.
( 3) 4. 03 f or 500kVA r at ed uni t s.
( 4) 5. 32 f or uni t s r at ed 750kVA and above.
f . Audi bl e sound l evel s shal l compl y wi t h t he f ol l owi ng:
kVA DECIBELS
(MAX
1000 58
1500 60
2000 61
2500 62
g. Tr ansf or mer shal l i ncl ude l i f t i ng l ugs and pr ovi s i ons f or j acki ng under base. The t r ansf or mer base const r uct i on shal l be sui t abl e f or usi ng r ol l er s or ski ddi ng i n any di r ect i on. Pr ovi de t r ansf or mer t op wi t h an access handhol e. Tr ansf or mer shal l have i t s kVA r at i ng conspi cuousl y di spl ayed on i t s encl osur e. The t r ansf or mer shal l have an i nsul at ed l ow- vol t age neut r al bushi ng wi t h NEMA spade t er mi nal , and wi t h r emovabl e gr ound st r ap.
2. 2. 2. 1 Speci f i ed Tr ansf or mer Ef f i c i enci es
Pr ovi de t r ansf or mer ef f i c i ency cal cul at i ons ut i l i z i ng t he act ual no- l oad and l oad l oss val ues obt ai ned dur i ng t he r out i ne t est s per f or med on t he act ual t r ansf or mer ( s) pr epar ed f or t hi s pr oj ect . No- l oad l osses ( NLL) shal l be r ef er enced at 20 degr ees C. Load l osses ( LL) shal l be r ef er enced at 55 degr ees C and at 50 per cent of t he namepl at e l oad. The t r ansf or mer i s not accept abl e i f t he cal cul at ed t r ansf or mer ef f i c i ency i s l ess t han t he ef f i c i ency i ndi cat ed i n t he " KVA / Ef f i c i ency" t abl e bel ow. That t abl e i s based on r equi r ement s cont ai ned wi t hi n 10 CFR 431, Subpar t K.
kVA EFFICIENCY (percent)
1000 99.36
1500 99.42
2000 99.46
2500 99.49 above 2500 99.50
SECTI ON 26 12 19. 10 Page 8
2. 2. 3 I nsul at i ng Li qui d
a. Less- f l ammabl e t r ansf or mer l i qui ds: NFPA 70 and FM APP GUI DE f or l ess- f l ammabl e l i qui ds havi ng a f i r e poi nt not l ess t han 300 degr ees C t est ed per ASTM D92 and a di el ect r i c st r engt h not l ess t han 33 kV t est ed per ASTM D877/ D877M. Pr ovi de i dent i f i cat i on of t r ansf or mer as " non- PCB" and " manuf act ur er ' s name and t ype of f l ui d" on t he namepl at e.
b. The f l ui d shal l be a bi odegr adabl e el ect r i cal i nsul at i ng and cool i ng l i qui d c l assi f i ed by UL and appr oved by FM as " l ess f l ammabl e" f l ui ds.
The f l ui d shal l meet t he f ol l owi ng f l ui d pr oper t i es:
( 1) Pour poi nt : ASTM D97, l ess t han - 15 degr ee C
( 2) Aquat i c bi odegr adat i on: EPA 712- C- 98- 075, 100 per cent
( 3) Tr out t oxi c i t y: OECD Test 203, zer o mor t al i t y of EPA 821- R- 02- 012, pass
2. 2. 3. 1 Li qui d- Fi l l ed Tr ansf or mer Namepl at es
Di st r i but i on t r ansf or mer s shal l be pr ovi ded wi t h namepl at e i nf or mat i on i n accor dance wi t h I EEE C57. 12. 00 and as modi f i ed or suppl ement ed by t hi s section.
2. 2. 4 Cor r osi on Pr ot ect i on
Bases and cabi net s of t r ansf or mer s shal l be cor r osi on r esi st ant and shal l be f abr i cat ed of st ai nl ess st eel conf or mi ng t o ASTM A240/ A240M, Type 304 or 304L. Base shal l i ncl ude any par t of pad- mount ed t r ansf or mer t hat i s wi t hi n 3 i nches of concr et e pad.
Pai nt ent i r e t r ansf or mer assembl y Munsel l 7GY3. 29/ 1. 5 gr een. Pai nt coat i ng syst em shal l compl y wi t h I EEE C57. 12. 28 r egar dl ess of base, cabi net , and t ank mat er i al . The Munsel l col or not at i on i s speci f i ed i n ASTM D1535.
2. 3 WARNI NG SI GNS
Pr ovi de war ni ng s i gns f or t he encl osur es of pad- mount ed t r ansf or mer s havi ng a nomi nal r at i ng exceedi ng 600 vol t s.
a. When t he encl osur e i nt egr i t y of such equi pment i s speci f i ed t o be i n accor dance wi t h I EEE C57. 12. 28, such as f or pad- mount ed t r ansf or mer s, pr ovi de sel f - adhesi ve war ni ng s i gns on t he out s i de of t he hi gh vol t age compar t ment door ( s) . Si gn shal l be a decal and shal l have nomi nal di mensi ons of 7 by 10 i nches wi t h t he l egend " DANGER HI GH VOLTAGE" pr i nt ed i n t wo l i nes of nomi nal 2 i nch hi gh l et t er s. The wor d " DANGER" shal l be i n whi t e l et t er s on a r ed backgr ound and t he wor ds " HI GH VOLTAGE" shal l be i n bl ack l et t er s on a whi t e backgr ound. Decal shal l be Pandui t No. PPSO710D72 or appr oved equal .
2. 4 Ar c Fl ash War ni ng Label
Pr ovi de war ni ng l abel f or t he encl osur e of pad- mount ed t r ansf or mer s.
Locat e t hi s sel f - adhesi ve war ni ng l abel on t he out s i de of t he hi gh vol t age compar t ment door war ni ng of pot ent i al el ect r i cal ar c f l ash hazar ds and appr opr i at e PPE r equi r ed. The l abel f or mat shal l be as i ndi cat ed.
SECTI ON 26 12 19. 10 Page 9
2. 5 GROUNDI NG AND BONDI NG
UL 467. Pr ovi de gr oundi ng and bondi ng as speci f i ed i n Sect i on 26 20 00
I NTERI OR DI STRI BUTI ON SYSTEM.
2. 6 PADLOCKS
Padl ocks shal l be pr ovi ded f or pad- mount ed equi pment and f or each f ence gat e.
Padl ocks shal l be keyed as di r ect ed by t he Cont r act i ng Of f i cer . Padl ocks shal l compl y wi t h Sect i on 08 71 00 DOOR HARDWARE.
2. 7 CAST- I N- PLACE CONCRETE
Shal l be composed of f i ne aggr egat e, coar se aggr egat e, por t l and cement , and wat er so pr opor t i oned and mi xed as t o pr oduce a pl ast i c, wor kabl e mi xt ur e.
Fi ne aggr egat e shal l be of har d, dense, dur abl e, c l ean, and uncoat ed sand.
The coar se aggr egat e shal l be r easonabl y wel l gr aded f r om 3/ 16 i nch t o 1 i nch. The f i ne and coar se aggr egat es shal l be f r ee f r om i nj ur i ous amount s of di r t , veget abl e mat t er , sof t f r agment s or ot her del et er i ous subst ances.
Wat er shal l be f r esh, c l ean, and f r ee f r om sal t s, al kal i , or gani c mat t er , and ot her i mpur i t i es. Concr et e associ at ed wi t h el ect r i cal wor k f or ot her t han encasement of under gr ound duct s shal l be 4000 psi mi ni mum 28- day compr essi ve st r engt h unl ess speci f i ed ot her wi se. Sl ump shal l not exceed 4 i nches. Ret emper i ng of concr et e wi l l not be per mi t t ed. Exposed, unf or med concr et e sur f aces shal l be gi ven a smoot h, wood f l oat f i ni sh.