Appendix_3_to_Specifications_Geothermal_Testing_Data.pdf
PDF 928 KB Posted
- Attached to
- Construct Training Support Center, FTIG Federal contract opportunity
- Solicitation number
- W912KC-16-R-0002
About this file
Appendix 3 to Specifications Geothermal Testing Data
View the file
Other files for this federal contract opportunity
Show all 48
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G E O
T H
E R
M A
L M
E M
OGEOTHERMAL TESTING DATA
WESTERN OFFICE
PO Box 256, Elkton, SD 57026
P: 866-991-4784 F: 605-542-3941
MAIN OFFICE
PO Box 150, Bowie, TX 76230
P: 940-872-2222 F: 940-872-3678
EASTERN OFFICE
PO Box 16143, Asheville, NC 28816
P: 828-225-9166 F: 828-281-4139
Test location Indiantown Gap National Guard
Annville, PA
Test Date August 5-7, 2015
Analysis For Morrison Geothermal
63 Gambers Corner Rd
Duncannon, PA 17020
Phone: (717) 834-5667
Fax: (717) 834-9314
Test Performed By Morrison Geothermal
Geothermal Resource Technologies Inc. WWW.GRTI.COM
August 11, 2015 1 of 7 FTC Test Report
Executive Summary
A formation thermal conductivity test was performed at the Indiantown Gap National Guard site at a GPS location of N 40° 25' 56.38" (latitude), W 76° 33' 48.06" (longitude) in Annville, Pennsylvania. The vertical bore was completed on July 26, 2015 by Morrison Geothermal.
Geothermal Resource Technologies’ (GRTI) test unit was attached to the vertical bore on the afternoon of August 5, 2015.
This report provides an overview of the test procedures and analysis process, along with plots of the loop temperature and input heat rate data. The collected data was analyzed using the “line source” method and the following average formation thermal conductivity was determined.
Formation Thermal Conductivity = 1.29 Btu/hr-ft-°F
Due to the necessity of a thermal diffusivity value in the design calculation process, an estimate of the average thermal diffusivity was made for the encountered formation.
Formation Thermal Diffusivity ≈≈≈≈ 0.87 ft /day
The undisturbed formation temperature for the tested bore was established from the initial loop temperature data collected at startup.
Undisturbed Formation Temperature ≈≈≈≈ 54.7-55.5°F
The formation thermal properties determined by this test do not directly translate into a loop length requirement (i.e. feet of bore per ton). These parameters, along with many others, are inputs to commercially available loop-field design software to determine the required loop length.
Additional questions concerning the use of these results are discussed in the frequently asked question (FAQ) section at www.grti.com.
August 11, 2015 2 of 7 FTC Test Report
Test Procedures
The American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE) has published recommended procedures for performing formation thermal conductivity tests in the
ASHRAE HVAC Applications Handbook, Geothermal Energy Chapter. The International
Ground Source Heat Pump Association (IGSHPA) also lists test procedures in their Design and
Installation Standards. GRTI’s test procedures meet or exceed those recommended by ASHRAE and IGSHPA, with the specific procedures described below:
Grouting Procedure for Test Loops – To ensure against bridging and voids, it is recommended that the bore annulus is uniformly grouted from the bottom to the top via tremie pipe.
Time Between Loop Installation and Testing – A minimum delay of five days between loop installation and test startup is recommended for bores that are air drilled, and a minimum waiting period of two days for mud rotary drilling.
Undisturbed Formation Temperature Measurement – The undisturbed formation temperature should be determined by recording the loop temperature as the water returns from the u-bend at test startup.
Required Test Duration – A minimum test duration of 36 hours is recommended, with a preference toward 48 hours.
Data Acquisition Frequency - Test data is recorded at five minute intervals.
Equipment Calibration/Accuracy – Transducers and datalogger are calibrated per manufacturer recommendations. Manufacturer stated accuracy of power transducers is less than ±2%. Temperature sensor accuracy is periodically checked via ice water bath.
Power Quality – The standard deviation of the power should be less than or equal to
1.5% of the average power, with maximum power variation of less than or equal to 10% of the average power.
Input Heat Rate – The heat flux rate should be 51 Btu/hr (15 W) to 85 Btu/hr (25 W) per foot of installed bore depth to best simulate the expected peak loads on the u-bend.
Insulation – GRTI’s equipment has 1 inch of foam insulation on the FTC unit and 1/2 inch of insulation on the hose kit connection. An additional 2 inches of insulation is provided for both the FTC unit and loop connections by insulating blankets.
Retesting in the Event of Failure – In the event that a test fails prematurely, a retest may not be performed until the bore temperature is within 0.5°F of the original undisturbed formation temperature or until a period of 14 days has elapsed.
August 11, 2015 3 of 7 FTC Test Report
Data Analysis
Geothermal Resource Technologies, Inc. (GRTI) uses the "line source" method of data analysis to determine the thermal conductivity of the formation. The line source method assumes an infinitely thin line source of heat in a continuous medium. A plot of the late-time temperature rise of the line source temperature versus the natural log of elapsed time will follow a linear trend.
The linear slope is inversely proportional to the thermal conductivity of the medium. When a u-bend grouted in a borehole is used to inject heat into the ground at a constant rate in order to determine the average formation thermal conductivity, the test must be run long enough to allow the finite dimensions of the u-bend pipes and the grout to become insignificant. Experience has shown that approximately ten hours is required to allow the error of early test times and the effects of finite borehole dimensions to become insignificant.
In order to analyze real data from a formation thermal conductivity test, the average temperature of the water entering and exiting the u-bend heat exchanger is plotted versus the natural log of elapsed testing time. Using the Method of Least Squares, linear coefficients are then calculated to produce a line that fits the data. This procedure is repeated for various time intervals to ensure that variations in the power or other effects are not producing inaccurate results.
The calculated results are based on test bore information submitted by the driller/testing agency.
GRTI is not responsible for inaccuracies in the results due to erroneous bore information. All data analysis is performed by personnel that have an engineering degree from an accredited university with a background in heat transfer and experience with line source theory. The test results apply specifically to the tested bore. Additional bores at the site may have significantly different results depending upon variations in geology and hydrology.
Through the analysis process, the collected raw data is converted to spreadsheet format
(Microsoft Excel) for final analysis. If desired, please contact GRTI and a copy of the data will be made available in either a hard copy or electronic format.
Contact:Contact:Contact:Contact: Chad Martin
Regional Managing Engineer Asheville, NC
(828) 225-9166 cmartin@grti.com
August 11, 2015 4 of 7 FTC Test Report
Test Bore Details (As Provided by Morrison Geothermal)
Site Name…...………………………………….... Indiantown Gap National Guard
Location………………………………….………. Annville, PA
Driller....……………….………………...…..…… Morrison Geothermal
Installed Date....………………….…..…….….… July 26, 2015
Borehole Diameter....…….….……….…….…… 8 inches, 0-20 ft 6 inches, 20-300 ft
Casing…..……………………………………. Temporary 6 1/4 inch steel casing to 20 ft
U-Bend Size.…………………………………….. 1 1/4 inch DR-11 HDPE
U-Bend Depth Below Grade .…………….……. 300 ft
Grout Type……………………………........….… Baroid Barotherm Gold
Grout Mixture……………………………........… 400 lb sand per 50 lb bentonite
Grouted Portion…………..…………..…….…… Entire bore
Drill Log
Formation DescriptionFormation DescriptionFormation DescriptionFormation Description DepthDepthDepthDepth (FT)(FT)(FT)(FT)
Soil 0'-2'
Clay 2'-9'
Limestone 9'-300'
Note: Bore produced 20 gpm water at 87 ft; 30 gpm at 224 ft.
August 11, 2015 5 of 7 FTC Test Report
Thermal Conductivity Test Data
0 6 12 18 24 30 36 42 48
Time (hours)
T e m p e ra tu re
F
In p u t
H e a t
R a te
B tu /h r-ft
Loop Supply
Temperature
9-30 hr Avg
Loop Temp
Loop Return
Temperature
Input
Heat Rate
Fig. 1: Temperature & Heat Rate Data Vs Time
Figure 1 above shows the loop temperature and heat input rate data versus the elapsed time of the test. The temperature of the fluid supplied to and returning from the U-bend are plotted on the left axis, while the amount of heat supplied to the fluid is plotted on the right axis on a per foot of bore basis. In the test statistics below, calculations on the power data were performed over the analysis time period listed in the Line Source Data Analysis section.
Summary Test Statistics
Test Date August 5-7, 2015
Undisturbed Formation Temperature Approx. 54.7-55.5°F
Duration 44.3 hr
Average Voltage 241.2 V
Average Heat Input Rate 25,481 Btu/hr (7,466 W)
Avg Heat Input Rate per Foot of Bore 84.9 Btu/hr-ft (24.9 W/ft)
Calculated Circulator Flow Rate 11.6 gpm
Standard Deviation of Power 0.97%
Maximum Variation in Power 3.32%
August 11, 2015 6 of 7 FTC Test Report
Line Source Data Analysis
-1 0 1 2 3 4 ln(Time)
T e m p e ra tu re
F
In p u t
H e a t
R a te
B tu /h r-ft
Loop Supply
Temperature
9-30 hr Avg
Loop Temp
Loop Return
Temperature
Input
Heat Rate
Fig. 2: Temperature & Heat Rate Vs Natural Log of Time
The loop temperature and input heat rate data versus the natural log of elapsed time are shown above in Figure 2. The temperature versus time data was analyzed using the line source method
(see page 3) in conformity with ASHRAE and IGSHPA guidelines. A linear curve fit was applied to the average of the supply and return loop temperature data between 9 and 30.0 hr. The slope of the curve fit was found to be 5.22. The resulting thermal conductivity was found to be
1.29 Btu/hr-ft-°F.
August 11, 2015 7 of 7 FTC Test Report
Thermal Diffusivity
The reported drilling log for this test borehole indicated that the formation consisted of clay and limestone. A heat capacity value for limestone was calculated from specific heat and density values listed by Kavanaugh and Rafferty (Ground-Source Heat Pumps - Design of Geothermal
Systems for Commercial and Institutional Buildings, ASHRAE, 1997). A weighted average of heat capacity values based on the indicated formation was used to determine an average heat capacity of 35.9 Btu/ft -°F for the formation. A diffusivity value was then found using the calculated formation thermal conductivity and the estimated heat capacity. The thermal diffusivity for this formation was estimated to be 0.87 ft /day.
WESTERN OFFICE
PO Box 256, Elkton, SD 57026
P: 866-991-4784 F: 605-542-3941
MAIN OFFICE
PO Box 150, Bowie, TX 76230
P: 940-872-2222 F: 940-872-3678
EASTERN OFFICE
PO Box 16143, Asheville, NC 28816
P: 828-225-9166 F: 828-281-4139
CERTIFICATE OF CALIBRATION
GRTI maintains calibration of the datalogger, current transducer and voltage transducer on a biannual schedule per the manufacturers recommendations. The components are calibrated by the manufacturer using recognized national or international measurement standards such as those maintained by the National Institute of Standards and Technology (NIST).
FTC Unit 252
DA Unit 46
Primary Equipment
Component Last Calibration Date Calibration Due Date
Datalogger 5/27/2015 5/27/2017
Current Transducer 5/30/2015 5/30/2017
Voltage Transducer 5/30/2015 5/30/2017
GRTI periodically verifies the combined temperature sensor/datalogger accuracy via an ice water bath. Temperature readings are simultaneously taken with a digital thermometer that has been calibrated using instruments traceable to NIST.
Date 6/8/2015
Thermocouple 1 (°F) 32.1 32.0 31.9
Thermocouple 2 (°F) 31.9 31.8 31.8
Thermocouple 3 (°F) 31.9 31.8 31.8
Thermocouple 4 (°F) 31.9 31.8 31.8
Digital Thermometer (°F) 32.1 32.0 32.0
S U
R V
E Y
I N
F O
REVISED CIVIL DRAWINGS
WITH UPDATED SURVEY INFORMATION
| Supplemental Cover |
| Geotech Memo FINAL 8.7.15 |
| Table 1 |
| PA-Annville-8-7-15 |
| tac2 - existing conditions plan-C100A |
| tac2 - existing conditions plan-C100B |
| tac2 - existing conditions plan-C100C |
File details come from the government source that posted it. Updated .