07_Mechanical.pdf
PDF 3 MB Posted
- Solicitation number
- W912J2-18-R-1001
About this file
07 Mechanical
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PG
PA
PITCH
AV
MV
S
FS
LS
PS
TS
CO
CO2
NO2
RS
SP
H
TS
T
T
PIPE TURNED TOWARD
PIPE TURNED AWAY
PIPE TURNED AWAY
FLEXIBLE CONNECTOR
UNION
FLANGES
REDUCER (CONCENTRIC)
REDUCER (ECCENTRIC)
PIPE CAP
FLUID FLOW DIRECTION
PIPE GUIDE
PIPE ANCHOR
PIPE PITCH DIRECTION
NEW CONNECTION TO EXISTING
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW TO BE INSTALLED
AUTOMATIC CONTROL VALVE (2-WAY)
AUTOMATIC CONTROL VALVE (3-WAY)
BACKFLOW PREVENTION VALVE
THROTTLING VALVE
BALANCING VALVE
FLOW MEASUREMENT STATION
RELIEF VALVE
AIR VENT (AUTO)
AIR VENT (MANUAL)
VACUUM BREAKER
PRESSURE GAUGE
TEMPERATURE GAUGE
WATER HAMMER ARRESTOR
ISOLATION/SHUT-OFF/MANUAL VALVE
GLOBE VALVE
BUTTERFLY VALVE
GATE VALVE
GLOBE ANGLE VALVE
PLUG VALVE
PRESSURE REDUCING VALVE
PRESSURE REGULATING VALVE
SOLENOID VALVE ONE-WAY (ELECTRIC)
STRAINER
PIPE TURNED TOWARD
GAUGE CONNECTION
PIPE PLUG
BALL VALVE
FLOW SENSOR
LEVEL SENSOR
PRESSURE SENSOR
TEMPERATURE SENSOR
FILTER
CHECK VALVE
PIPING SYMBOLS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
REFRIGERANT HOT GAS
NATURAL GAS
RS
RL
G
HG
HOT WATER SUPPLY
HOT WATER RETURN
CONDENSATE DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HWS
HWR
CD
CHWS
CHWR
MECHANICAL PIPING:
CHEMICAL FEEDCF
GLYCOL WATER SUPPLY
GLYCOL WATER RETURN
GWS
GWR
(FIRST FIGURE IS SIDE SHOWN)
TEMPERATURE SENSOR
RECTANGLE DUCT SIZE
SUPPLY DUCT TURNED TOWARD
FIRE DAMPER & ACCESS DOOR
VOLUME DAMPER
CARBON MONOXIDE (CO) SENSOR
STATIC PRESSURE SENSOR
HUMIDISTAT
NITROGEN DIOXIDE (NO2) SENSOR
SMOKE DETECTOR
DUCT (FLEXIBLE ROUND)
ROOM SENSOR
TRANSITION (SQUARE-TO-ROUND)
MOTOR OPERATED DAMPER
AIR OUTLET/INLET TYPE
ROUND DUCT (RIGID)
EXHAUST
PARALLEL BLADE DAMPER
OPPOSED BLADE DAMPER
BACKDRAFT DAMPER
FLEXIBLE CONNECTION
(CFM)
TURNING VANES
SUPPLY DUCT TURNED AWAY
S
AD
MOD
FD
BD
12x12
SUPPLY OR OUTDOOR AIR
AIRFLOW (DOOR GRILLE)
AIRFLOW (SUPPLY)
HVAC SYMBOLS:
RETURN
AIRFLOW (RETURN)
DG
A
CARBON DIOXIDE (CO2) SENSOR
THERMOSTAT
INSULATED BASE THERMOSTAT
3/4" DOOR CUTOFF
DCO
12ø
12/12ø OVAL DUCT
SWITCH
SCIF GENERAL NOTES:
1. THE VAULT AREA IS CONSIDERED A SENSITIVE COMPARTMENTED
INFORMATION FACILITY. ALL NEW CONSTRUCTION AND RENOVATION TO THE
AREA INCLUDING WALL CONSTRUCTION, FIRE PROTECTION/DETECTION,
MECHANICAL/HVAC, ELECTRICAL, AND TECHNOLOGY SYSTEMS MUST
COMPLY WITH THE REQUIREMENTS PROVIDED IN UNIFIED FACILITY CRITERIA
4-010-05 SENSITIVE COMPARTMENTED INFORMATION FACILITY PLANNING,
DESIGN, AND CONSTRUCTION WITH CHANGE 1, 1 OCTOBER 2013, AND
REFERENCED IC TECH SPEC FOR ICD/ICS 705 TECHNICAL SPECIFICATIONS
FOR CONSTRUCTION AND MANAGEMENT OF SENSITIVE COMPARTMENTED
INFORMATION FACILITIES, VERSION 1.2, DATED 23 APRIL 2012.
2. CONSTRUCTION, GENERAL: UFC 4-010-05 REQUIREMENTS HAVE BEEN
INCORPORATED INTO THE DESIGN DRAWINGS AND SPECIFICATIONS.
CHANGES TO THE SCOPE OF WORK PROVIDED IN THE CONTRACT
DOCUMENTS MAY INVALIDATE THE APPROVALS RECEIVED FOR THIS
CONSTRUCTION, AND COULD RESULT IN THE REMOVAL AND
RECONSTRUCTION OF FINISHED WORK. ANY PROPOSED DEVIATIONS FROM
THE CONTRACT DOCUMENTS MUST BE FULLY REVIEWED AND APPROVED BY
THE COR PRIOR TO IMPLEMENTATION.
3. ALL CONSTRUCTION MUST BE DONE IN SUCH A MANNER AS TO PROVIDE
VISUAL EVIDENCE OF UNAUTHORIZED PENETRATION. CONSTRUCTION MUST
BE COMPLETED IN A MANNER TO PROVIDE THE REQUIRED STC RATINGS FOR
SOUND CONTROL AT THE WALLS IDENTIFIED. THROUGH-WALL
PENETRATIONS OF PIPE, CONDUIT, AND DUCTWORK REQUIRE SPECIAL
CONSTRUCTION AND INSPECTION PROVISIONS WHICH HAVE BEEN
INCORPORATED INTO THE CONTRACT DOCUMENTS.
4. THE CONTRACTOR SHALL SUBMIT A LIST OF ALL MATERIALS USED IN THE
CONSTRUCTION OF THE VAULT AREA, INCLUDING DIMENSIONAL EXTENTS OF
THE USE AND LOCATION(S) WHERE USED IN THE VAULT. THIS LIST SHALL BE
KEPT UP TO DATE DURING THE COURSE OF CONSTRUCTION AND SUBMITTED
TO THE COR AS PART OF THE CLOSE-OUT REQUIREMENTS AT THE END OF
CONSTRUCTION.
5. PHOTOGRAPHY REQUIREMENTS: THE CONTRACTOR IS NOT ALLOWED TO
HAVE PHOTOGRAPHIC OR RECORDING DEVICES IN THE VAULT AREA. 115 FW
CCZ PERSONNEL WILL BE TAKING PICTURES OF ON-GOING CONSTRUCTION
IN ORDER TO DOCUMENT THAT ALL SECURITY MEASURES ARE BEING MET.
THE COR SHALL BE NOTIFIED AT LEAST ONE WORKING DAY PRIOR TO KEY
CONSTRUCTION MILESTONES. KEY CONSTRUCTION MILESTONES INCLUDE
BUT ARE NOT LIMITED TO: WALL CONSTRUCTION, INCLUDING EACH OF
MULTIPLE LAYERS OF GYPSUM BOARD, FINISHING OF PENETRATIONS,
NON-CONDUCTIVE BREAKS OF PENETRATIONS, AND SOUND BATT
INSULATION INSTALLATIONS.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:0
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-001
MECHANICAL NOTES
& SYMBOLS
XGFG132020ANG NO.:
3141300-141489.01
RRW/SMG
SNW
May 4, 2017
BGD
IPC INTERNATIONAL PLUMBING CODE
INWC INCHES WATER COLUMN PRESSURE
INHG INCHES MERCURY PRESSURE
IN INCH
IE INVERT ELEVATION
ID INSIDE DIAMETER
IBNLT INCLUDING BUT NOT LIMITED TO
IAW IN ACCORDANCE WITH
HZ HERTZ
HX HEAT EXCHANGER
HP HORSEPOWER
HDB HYDROSTATIC DESIGN BASIS
HC HOSE CONNECTION
H HEIGHT
GS GALVANIZED STEEL
GR GROOVED
GPM GALLONS PER MINUTE
GC GENERAL CONTRACTOR
GBS GASKETED BELL AND SPIGOT
GAL GAUGE
GAL GALLON
FTWC FEET WATER COLUMN PRESSURE
FT FEET
FS FLOOR SINK
FPM FEET PER MINUTE
FLOW FLOW OR FLOWRATE
FD FIRE DAMPER
FCO FLOOR CLEANOUT
FC FAN COIL
F FAHRENHEIT
EWT ENTERING WATER TEMPERATURE
EWC ELECTRIC WATER COOLER
ETR EXISTING TO REMAIN
ET EXPANSION TANK
ESEW EMERGENCY SHOWER AND EYE/FACE WASH
ELEC ELECTRIC
EL ELEVATION
EG EXHAUST GRILLE
EG ETHYLENE GLYCOL
EFT ENTERING FLUID TEMPERATURE
EFF EFFICIENCY
EF EXHAUST FAN
EEW EMERGENCY EYE/FACE WASH
EC ELECTRICAL CONTRACTOR
EAT ENTERING AIR TEMPERATURE
EA EXHAUST AIR
E EXISTING
DWV DRAIN, WASTE, AND VENT
DWG DRAWING
DN DOWN
DISCH DISCHARGE
DIM DIMENSION
DIA DIAMETER
DFD DEPARTMENT OF DEFENSE
DEMO DEMOLISH
DCVA DOUBLE CHECK VALVE ASSEMBLY BPD
DCO DOOR CUT-OFF
DBA DECIBELS, BAND A
CU COPPER
CTW CLOSE TO WALL
CTCLM CLOSE TO COLUMN
CTCLG CLOSE TO CEILING
CRA CONCRETE REACTION ANCHOR
COR CONTRACTING OFFICER'S REPRESENTATIVE
COMP COMPRESSOR
CISPI CAST IRON SOIL PIPE INSTITUTE
CI CAST IRON
CFM CUBIC FEET PER MINUTE
BZ BRONZE
BW BUTTWELD
BTW BOOTWASH
BTU BRITISH THERMAL UNIT
BS BLACK (MILD) STEEL
BRZ BRONZE
BRS BRASS
BR BRAZE
BPVC ASME BOILER & PRESSURE VESSEL CODE
BPD BACKFLOW PREVENTION DEVICE
BO BID OPTION
BHF BUTT HEAT FUSION
AT AIR TERMINAL
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,
AND AIR CONDITIONING ENGINEERS
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
APPROX APPROXIMATELY
ANG AIR NATIONAL GUARD
AHU AIR HANDLING UNIT
AHJ AUTHORITY HAVING JURISDICTION
AFF ABOVE FINISHED FLOOR
AFC ACOUSTICAL FLEXIBLE CONNECTOR
ACFM ACTUAL CFM
ABBREVIATIONS
W WATTS OR WIDTH
VLV VALVE
VFD VARIABLE FREQUENCY DRIVE
V VOLTS
UV ULTRAVIOLET
UTR UP THRU ROOF
UNO UNLESS NOTED OTHERWISE
UGD UNDERGROUND
UFC UNIFIED FACILITIES CRITERIA
TYP TYPICAL
TONR TONS COOLING
TH THREADED
TG TRANSFER GRILLE
TFB TO FLOOR BELOW
TFA TO FLOOR ABOVE
TEMP TEMPERATURE
TDS TOTAL DISSOLVED SOLIDS
TDH TOTAL DEVELOPED HEAD
SW SOCKET WELD
SV SOLVENT WELD
STL STEEL
STD STANDARD
SS STAINLESS STEEL
SRV SAFETY RELIEF VALVE
SQ SQUARE
SPEC SPECIFICATIONS
SP STATIC PRESSURE
SMLS SEAMLESS
SHT SHEET
SD SOLDER
SCH SCHEDULE
SCFM STANDARD CFM
RTD RESISTIVE THERMAL DEVICE
SG SUPPLY GRILLE
SA SUPPLY AIR
RTU ROOF TOP UNIT
RPM REVOLUTIONS PER MINUTE
RA RETURN AIR
QTY QUANTITY
PVC POLYVINYL CHLORIDE
PSIG PSI GAGE
PSID PSI DIFFERENTIAL
PSIA PSI ABSOLUTE
PSI POUNDS PER SQUARE INCH
PROP PROPELLER
PREDV PRESSURE REDUCING VALVE
PPH POUND PER HOUR
PL PLACES
PH PHASE
PG PROPYLENE GLYCOL
PD PRESSURE DROP/DIFFERENTIAL
PC PLUMBING CONTRACTOR
P PRESSURE
OFOI OWNER FURNISHED, OWNER INSTALLED
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OED OPEN-ENDED DUCT
OD OUTSIDE DIAMETER
NPSHR NPSH REQUIRED
NPSHA NPSH AVAILABLE
NPSH NET POSITIVE SUCTION HEAD
NOM NOMINAL
NO NORMALLY OPEN
NIC NOT IN CONTRACT
NH NO-HUB
NG NATURAL GAS
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NEMA NATIONAL ELECTRICAL MANUFACTURER'S...
NC NORMALLY CLOSED
NA NOT APPLICABLE
MTL MATERIAL
MSS MANUFACTURERS STANDARDIZATION SOCIETY
MOD MODULATING
MOCP MINIMUM OVER CURRENT PROTECTION
MMBH MILLION BTU PER HOUR
MIN MINIMUM
MFR MANUFACTURER
MCC MOTOR CONTROL CENTER
MCA MINIMUM CIRCUIT AMPACITY
MC MECHANICAL COUPLING
MBH THOUSAND BTU PER HOUR
MAX MAXIMUM
MAWP MAXIMUM ALLOWABLE WORKING PRESSURE
MADP MAXIMUM ALLOWABLE DIFFERENTIAL PRESSURE
LWT LEAVING WATER TEMPERATURE
LPM LITERS PER MINUTE
LPG LIQUIFIED PETROLEUM GAS
LIN LINEAR
LCO LINE CLEANOUT
LB POUNDS
LAT LEAVING AIR TEMPERATURE
ABBREVIATIONS
9. SEQUENCE OF WORK AND/OR PLACE OF COMMENCEMENT OF WORK SHALL BE APPROVED PRIOR TO WORK BEING STARTED. SCHEDULED SHUTDOWNS SHALL BE CLOSELY COORDINATED WITH EXISTING OPERATIONS.
8. VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH OWNER PRIOR TO INSTALLATION.
7. TEMPORARILY PATCH ALL ROOF OPENINGS WATERTIGHT UNTIL FINAL CLOSURE CAN BE MADE.
6. ALL NEW AND EXISTING ROOFING SYSTEMS SHALL BE PROTECTED FROM DAMAGE DURING CONSTRUCTION
ACTIVITIES.
5. ACCURATE AND LEGIBLE AS-BUILT DRAWING MARKUPS SHALL BE MAINTAINED AT THE JOB SITE, AND BE
SUBMITTED PRIOR TO FINAL PAYMENT FOR THE CREATION OF FINAL RECORD DRAWINGS.
4. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH RESPECT TO EXISTING STRUCTURES, UTILITIES, AND MECHANICAL SYSTEMS, IS AS EXACT AS COULD BE SECURED. THE INFORMATION IS NOT WARRANTED NOR GUARANTEED ACCURATE, FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO PROCEEDING WITH WORK.
3. ELEVATION OF PIPING AND DUCTWORK INDICATED ON THESE DRAWINGS ARE TO BE USED AS GUIDELINES TO ASSIST WITH INSTALLATIONS. MINOR CHANGES TO THESE ELEVATIONS MAY BE NECESSARY TO ELIMINATE UNFORESEEN INTERFERENCES. ANY CHANGE IN ELEVATION SHALL BE APPROVED PRIOR TO CHANGE.
2. THESE DRAWINGS ARE DESIGN DRAWINGS AND ARE DIAGRAMMATIC, THEY MAY NOT SHOW ALL PHYSICAL ARRANGEMENTS, OFFSETS, BENDS, OR ELBOWS WHICH MAY BE REQUIRED FOR PROPER INSTALLATION OF VARIOUS MATERIALS, EQUIPMENT, PIPING AND DUCTWORK SYSTEMS IN ALLOTTED SPACES. EXAMINE THESE AND OTHER AVAILABLE DRAWINGS TO DETERMINE SPACE LIMITATIONS AND INTERFERENCES. MAKE ANY MINOR CHANGES IN LOCATIONS OF EQUIPMENT, PIPING, AND DUCTWORK FROM THAT SHOWN ON DRAWINGS AND FOR ALL PHYSICAL DETAILS REQUIRED FOR INSTALLATION. COST FOR ADAPTING WORK TO JOB SITE CONDITIONS
SHALL NOT BE CONSIDERED AS BASIS OF AN EXTRA COST TO CONTRACT.
1. ABBREVIATIONS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY TO THIS
PROJECT. ADDITIONAL ABBREVIATIONS MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
GENERAL NOTES:
05/04/17 TYPE B3
REF.
REF. REF.
REF.
REF.
A B C D E GH J K LM N P Q R S TF Q.1 S.1
19.5
24.1
A B C D E F GH J K LM N P Q R S T
46x18(E) ø (E ø
(E
12x8(E)
AT(E)
AT(E)
AT(E)
AT(E)AT(E)
x1
(E x6 (E x1
(E ø (E x2
(E
48x24(E)
40x16(E)
AT(E)
AT(E)
24x18(E)
12x10(E)
18x10(E) x8 (E x8 (E x6 (E
12x6(E) x1
(E
14x10(E)
AT(E)
AT(E)
40x18(E) 48x24(E)
24x14(E) x2
(E
) AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
x1
(E x1
(E
AT(E)
AT(E)
18x14(E)
14ø(E)
AT(E)
AT(E)
12x8(E)
10x8(E) x1
(E
30x20(E)
AT(E)
AT(E)
FCU(E)
FCU(E)
x1
(E
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
ø (E
AT(E)
AT(E)
AT(E)
24x10ø(E)
AT(E)
AT(E)
12x10(E)
12x10(E)
10x6(E)
8ø(E) 16ø(E)
60x20(E)
AT(E) 42x10(E)
AT(E)
AT(E)
48x8(E)
48x8(E)
EF(E)
x1
(E x6 (E x6
(E
8x6(E)
12x10(E)
CH(E)
x4 (E x4
(E
24x8(E) ø (E ø (E ø
(E
24x8(E) ø
(E ø
(E
8ø(E) ø
(E x1
(E
12x12(E)
24x6(E) ø
(E ø
(E ø
(E ø
(E
10ø(E)8ø(E)
10ø(E)8ø(E)
8ø(E) ø
(E
8x8(E)
10x6(E)
22x10(E)
6x6(E) ø
(E x1
(E
7ø(E)
22x10(E)
12x8(E)
20x14(E)
AT(E)
36x16(E)
AT(E)
5ø(E) 8x8(E)
8x4(E) 8x4(E) ø (E
22x22(E)AT(E)
6ø(E)
AT(E)
AT(E)
6ø(E)
AT(E)
10x6(E)
12x8(E)
12x12(E) x6 (E
10ø(E) 10ø(E)
22x22(E)
12x10(E) ø (E x8 (E
14x6(E)
10x8(E)
6ø(E)
10x10(E)
22x10(E)
LD(E)
LD(E)
LD(E)LD(E)LD(E)LD(E)
LD(E)
LD(E)
LD(E) LD(E) LD(E)
LD(E)
LD(E)
AT(E)
7.001
7.001
7.001
7.001
7.001
7.001
7.001
7.001
7.001
7.003 7.003
7.003
7.003
7.003
7.003
7.003 7.003
7.003
7.003
7.003
7.003
7.003
7.003
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP) (TYP)
(TYP)
(TYP)
(TYP)
(TYP)
7.002
7.004
7.004
7.004
7.004
7.004
7.004
7.004
7.004
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
7.005 7.005
36ø(E)
ELECTRIC CEILING
HEATING UNIT SERVING
THIS VESTIBULE TO REMAIN
P-4(E)
P-3(E)
UH(E)
CHILLER(E)
P-1(E)
ET-1(E)
GLYCOL
MIXING
TANK(E)
P-5(E)
AS-1(E)
7.005
7.005
7.005 ACCU(E)
C(E)
XFMER(E)
GENERATOR(E)
7.003
DEMOLISH DRYER VENT
EXHAUST
FAN(E)
14x6(E)14x6(E)
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:3
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
MD101
HVAC DEMOLITION
FLOOR PLAN
XGFG132020ANG NO.:
3141300-141489.01
RJH
SNW
May 4, 2017
BGD
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
HVAC DEMOLITION FLOOR PLAN
KEYED NOTES
7.001 DEMOLISH ALL EXISTING AIR TERMINAL BOXES AND ALL ASSOCIATED
THERMOSTATS, ROOM SENSORS, VALVING AND SUPPORT HARDWARE.
UNLESS OTHERWISE INDICATED, DELIVER AIR TERMINAL BOXES,
THERMOSTATS, AND ROOM SENSORS TO BASE COMMANDER DESIGNATED
STORAGE SITE IN REUSABLE CONDITION. VERIFY BASE REQUIREMENTS
FOR EQUIPMENT RETENTION PRIOR TO BEGINNING DEMOLITION.
7.002 DEMOLISH ALL EXISTING FAN COIL UNITS AND ASSOCIATED DUCTS, PIPING,
CONTROLS, AND SUPPORT HARDWARE. UNLESS OTHERWISE INDICATED,
DELIVER UNITS TO BASE COMMANDER DESIGNATED STORAGE SITE IN
REUSABLE CONDITION. VERIFY BASE REQUIREMENTS FOR EQUIPMENT
RETENTION PRIOR TO BEGINNING DEMOLITION.
7.003 DEMOLISH ALL SUPPLY, EXHAUST, AND TRANSFER GRILLES, REGISTERS
AND LOUVERS AND ASSOCIATED SUPPORT AND MOUNTING HARDWARE.
7.004 DEMOLISH ALL SUPPLY, EXHAUST, AND TRANSFER DUCTWORK AND
ASSOCIATED SUPPORT AND MOUNTING HARDWARE.
7.005 DEMOLISH ALL DUCTWORK UP THROUGH ROOF INCLUDING ALL
ASSOCIATED ROOF MOUNTED HVAC EQUIPMENT AND PERMANENTLY
ENCLOSE ANY ROOF OPENINGS. REFER TO ARCHITECTURAL PLANS &
DETAILS. DELIVER EXHAUST FANS TO BASE COMMANDER DESIGNATED
STORAGE SITE IN REUSABLE CONDITION. VERIFY BASE REQUIREMENTS
FOR EQUIPMENT RETENTION PRIOR TO BEGINNING DEMOLITION
6. INSTALL TEMPORARY COVER OVER OPENING CREATED BY REMOVED
EQUIPMENT/PIPING. COVER SHALL BE WATERTIGHT, AND MEET OSHA AND
OWNER REQUIREMENTS. COMPLETELY REMOVE TEMPORARY COVER WHEN
OPENING BEING PATCHED TO FINAL CONDITION. REPAIR ANY DAMAGE TO
EXISTING BUILDING COMPONENTS CAUSED BY TEMPORARY COVER.
5. REINSTALL REMOVED EQUIPMENT, SAME AS NEW WORK, IN NEW LOCATION
INDICATED. COMPLETELY CLEAN AND RESTORE EQUIPMENT TO GOOD
OPERATING CONDITION PER SATISFACTION OF OWNER.
4. DELIVER REMOVED EQUIPMENT TO OWNER'S DESIGNATED STORAGE SPACE ON
SITE, PLUG OR CAP ALL EQUIPMENT OPENINGS TO PREVENT DIRT AND
MOISTURE FROM ENTERING EQUIPMENT PER SATISFACTION OF OWNER.
3. COMPLETELY REMOVE EXISTING DUCTWORK, INCLUDING ALL UNNEEDED
ACCESSORIES, INSULATION, HANGER SUPPORTS, ETC. FOR REMAINING DUCT
SYSTEM PLUG OR CAP ALL OPENINGS CREATED BY DUCT DEMOLITION. TEST
DUCTWORK AS SPECIFIED, AND INSULATE OR PAINT SAME AS NEW WORK. PATCH
EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY DEMOLITION
TO ORIGINAL CONDITION PER SATISFACTION OF OWNER. DUCT DEMOLITION
SHALL INCLUDE ALL BOLDLY DISPLAYED DUCT INDICATED ON DRAWINGS.
2. COMPLETELY REMOVE EXISTING EQUIPMENT, INCLUDING ALL UNNEEDED PIPING,
VALVES, INSULATION, HANGERS, SUPPORTS, BASES, CONTROLS, ETC. PATCH
EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY DEMOLITION
TO ORIGINAL CONDITION PER SATISFACTION OF OWNER.
1. COMPLETELY REMOVE INDICATED EXISTING PIPING, INCLUDING ALL UNNEEDED
PIPING, VALVES, INSULATION, HANGERS, SUPPORTS, ETC. FOR REMAINING
PIPING SYSTEMS PLUG OR CAP ALL OPENINGS CREATED BY PIPING DEMOLITION.
TEST PIPING SYSTEMS AS SPECIFIED, AND INSULATE OR PAINT SAME AS NEW
WORK. PATCH EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY
DEMOLITION TO ORIGINAL CONDITION PER SATISFACTION OF OWNER. PIPING
DEMOLITION SHALL INCLUDE ALL BOLDLY DISPLAYED PIPES INDICATED ON
DRAWINGS.
GENERAL HVAC DEMOLITION NOTES:
A B C D E F GH J K LM N P Q R S T
ACCU(E)
RELIEF
HOOD(E)
RELIEF
HOOD(E)
ACCU(E)
ACCU(E)
ACCU(E)
ROOF
EXHAUSTER(E)
ROOF
EXHAUSTER(E)
RTU(E)
7.006
7.006
7.006
7.006
7.005
7.005
7.005
7.005
7.007
7.007
7.008 7.008
7.009
GOOSENECK
GOOSENECKGOOSENECK
7.005
RELIEF
HOOD(E)
7.005
7.005
7.005 7.005
BOILER STACK(E)
BOILER STACK(E)
WATER HEATER STACK(E)
7.005
DRYER VENT
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:3
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
MD102
HVAC DEMOLITION
ROOF PLAN
XGFG132020ANG NO.:
3141300-141489.01
RRW
SNW
May 4, 2017
BGD
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
HVAC DEMOLITION ROOF PLAN
KEYED NOTES
7.005 DEMOLISH ALL DUCTWORK UP THROUGH ROOF INCLUDING ALL
ASSOCIATED ROOF MOUNTED HVAC EQUIPMENT AND PERMANENTLY
ENCLOSE ANY ROOF OPENINGS. REFER TO ARCHITECTURAL PLANS &
DETAILS. DELIVER EXHAUST FANS TO BASE COMMANDER DESIGNATED
STORAGE SITE IN REUSABLE CONDITION. VERIFY BASE REQUIREMENTS
FOR EQUIPMENT RETENTION PRIOR TO BEGINNING DEMOLITION
7.006 DEMOLISH REMOVE ACCU AND DELIVER TO BASE COMMANDER
DESIGNATED STORAGE SITE IN REUSABLE CONDITION UNLESS OTHERWISE
INSTRUCTED. VERIFY BASE REQUIREMENTS FOR EQUIPMENT RETENTION
PRIOR TO BEGINNING DEMOLITION.
7.007 DEMOLISH ROOF EXHAUSTER AND DELIVER TO BASE COMMANDER
DESIGNATED STORAGE SITE IN REUSABLE CONDITION UNLESS OTHERWISE
INSTRUCTED. VERIFY BASE REQUIREMENTS FOR EQUIPMENT RETENTION
PRIOR TO BEGINNING DEMOLITION.
7.008 REMOVE ALL ROOF MOUNTED DUCTWORK AND ASSOCIATED SUPPORTS
WITH NO DAMAGE TO ROOF.
7.009 DEMOLISH RTU AND PERMANENTLY ENCLOSE ANY ROOF OPENINGS. REFER
TO ARCHITECTURAL PLANS & DETAILS. DELIVER RTU TO COMMANDER
DESIGNATED STORAGE SITE IN REUSABLE CONDITION UNLESS OTHERWISE
INSTRUCTED. VERIFY BASE REQUIREMENTS FOR EQUIPMENT RETENTION
PRIOR TO BEGINNING DEMOLITION.
6. INSTALL TEMPORARY COVER OVER OPENING CREATED BY REMOVED
EQUIPMENT/PIPING. COVER SHALL BE WATERTIGHT, AND MEET OSHA AND
OWNER REQUIREMENTS. COMPLETELY REMOVE TEMPORARY COVER WHEN
OPENING BEING PATCHED TO FINAL CONDITION. REPAIR ANY DAMAGE TO
EXISTING BUILDING COMPONENTS CAUSED BY TEMPORARY COVER.
5. REINSTALL REMOVED EQUIPMENT, SAME AS NEW WORK, IN NEW LOCATION
INDICATED. COMPLETELY CLEAN AND RESTORE EQUIPMENT TO GOOD
OPERATING CONDITION PER SATISFACTION OF OWNER.
4. DELIVER REMOVED EQUIPMENT TO OWNER'S DESIGNATED STORAGE SPACE ON
SITE, PLUG OR CAP ALL EQUIPMENT OPENINGS TO PREVENT DIRT AND
MOISTURE FROM ENTERING EQUIPMENT PER SATISFACTION OF OWNER.
3. COMPLETELY REMOVE EXISTING DUCTWORK, INCLUDING ALL UNNEEDED
ACCESSORIES, INSULATION, HANGER SUPPORTS, ETC. FOR REMAINING DUCT
SYSTEM PLUG OR CAP ALL OPENINGS CREATED BY DUCT DEMOLITION. TEST
DUCTWORK AS SPECIFIED, AND INSULATE OR PAINT SAME AS NEW WORK. PATCH
EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY DEMOLITION
TO ORIGINAL CONDITION PER SATISFACTION OF OWNER. DUCT DEMOLITION
SHALL INCLUDE ALL BOLDLY DISPLAYED DUCT INDICATED ON DRAWINGS.
2. COMPLETELY REMOVE EXISTING EQUIPMENT, INCLUDING ALL UNNEEDED PIPING,
VALVES, INSULATION, HANGERS, SUPPORTS, BASES, CONTROLS, ETC. PATCH
EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY DEMOLITION
TO ORIGINAL CONDITION PER SATISFACTION OF OWNER.
1. COMPLETELY REMOVE INDICATED EXISTING PIPING, INCLUDING ALL UNNEEDED
PIPING, VALVES, INSULATION, HANGERS, SUPPORTS, ETC. FOR REMAINING
PIPING SYSTEMS PLUG OR CAP ALL OPENINGS CREATED BY PIPING DEMOLITION.
TEST PIPING SYSTEMS AS SPECIFIED, AND INSULATE OR PAINT SAME AS NEW
WORK. PATCH EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY
DEMOLITION TO ORIGINAL CONDITION PER SATISFACTION OF OWNER. PIPING
DEMOLITION SHALL INCLUDE ALL BOLDLY DISPLAYED PIPES INDICATED ON
DRAWINGS.
REF.
REF. REF.
REF.
REF.
A B C D E GH J K LM N P Q R S TF Q.1 S.1
19.5
24.1
A B C D E F GH J K LM N P Q R S T
2"(E) 2"(E)
2 1/2"(E) 2 1/2"(E)
1 1/2"(E) 1 1/2"(E)
2 1/2"(E) 2 1/2"(E)
/2
E
/2
E
E
E
1"(E) 1"(E)
1 1/2"(E) 1 1/2"(E)
2 1/2"(E) 2 1/2"(E)
E
E
1 1/2"(E) 1 1/2"(E)
E
E
/4
E
/4
E
1"(E) 1"(E)
/4
E
/4
E
/4
E
) 3 /4
E
/4
E
/4
E
/2
E
/2
E
/4
E
/4
E
1 1/4"(E) 1 1/4"(E)
3/4"(E) 3/4"(E)
/4
E
/4
E
3/4"(E) 3/4"(E)
/4
E
/4
E
3/4"(E) 3/4"(E)
C(E) C(E)
AT(E)
AT(E)
C(E)
AT(E)
CH(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
C(E)
AT(E)
AT(E)
AT(E)
AT(E)
C(E)
FT-1(E)
FT(E) FT-1(E)
AT(E)
FT(E)FT(E)
FT(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
FCU(E)
AT(E)
AT(E)
AT(E)
AT(E)
AT(E)
C(E)
AT(E)
AT(E)
AT(E)
UH(E)
AS-1(E)
ET-1(E)
GLYCOL
MIXING
TANK(E)
P-1(E)
P-4(E)
P-3(E)
1/2"(E)
FT(E)
C(E)
CH(E)
FT(E)
FT(E)
FT(E) FT(E)
CH(E)
AT(E)
C(E)
C(E)
CHILLER(E)
8.001
8.007
8.002
8.001 8.001
8.002
8.002
8.002
8.003
8.003
8.002
8.002
8.002
FT(E) FT(E)
FT(E)
8.002
8.002
8.003
8.003
8.003 8.002
8.002
8.002
8.003
8.004
8.001
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
8.003
8.003
(TYP)
(TYP)
BOILER(E) BOILER(E)
ACCU(E)
NATURAL GAS
METER
(ETR)
8.001
8.0058.005
8.0058.005
E
8.006
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:4
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
MD131
MECHANICAL
DEMOLITION FLOOR
PLAN
XGFG132020ANG NO.:
3141300-141489.01
RRW
SNW
May 4, 2017
BGD
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
MECHANICAL DEMOLITION FLOOR PLAN
KEYED NOTES
8.001 DEMOLISH EXISTING MECHANICAL EQUIPMENT AND ALL ASSOCIATED
VALVING AND SUPPORT HARDWARE. UNLESS OTHERWISE INDICATED,
DELIVER ALL EQUIPMENT TO BASE COMMANDER DESIGNATED STORAGE
SITE IN REUSABLE CONDITION. VERIFY BASE REQUIREMENTS FOR
EQUIPMENT RETENTION PRIOR TO BEGINNING DEMOLITION.
8.002 DEMOLISH ALL EXISTING HEATERS AND CONVECTORS AND ASSOCIATED
THERMOSTATS, PIPING, VALVING AND SUPPORT HARDWARE. UNLESS
OTHERWISE INDICATED, DELIVER HEATERS AND CONVECTORS TO BASE
COMMANDER DESIGNATED STORAGE SITE IN REUSABLE CONDITION.
VERIFY BASE REQUIREMENTS FOR EQUIPMENT RETENTION PRIOR TO
BEGINNING DEMOLITION.
8.003 DEMOLISH ALL HYDRONIC WATER SUPPLY AND RETURN PIPING, AND ALL
ASSOCIATED VALVING, HANGERS AND SUPPORT HARDWARE.
8.004 DEMOLISH ALL CHILLED WATER SUPPLY AND RETURN PIPING, AND ALL
ASSOCIATED VALVING, HANGERS AND SUPPORT HARDWARE.
8.005 EXISTING HYDRONIC PIPING TO REMAIN.
8.006 DEMOLISH EXISTING 1" NATURAL GAS PIPING BACK TO METER.
8.007 DEMOLISH UNDERGROUND CHILLED WATER PIPING. FILL IN TRENCH TO
MATCH SURROUNDING AREA.
6. INSTALL TEMPORARY COVER OVER OPENING CREATED BY REMOVED
EQUIPMENT/PIPING. COVER SHALL BE WATERTIGHT, AND MEET OSHA AND
OWNER REQUIREMENTS. COMPLETELY REMOVE TEMPORARY COVER WHEN
OPENING BEING PATCHED TO FINAL CONDITION. REPAIR ANY DAMAGE TO
EXISTING BUILDING COMPONENTS CAUSED BY TEMPORARY COVER.
5. REINSTALL REMOVED EQUIPMENT, SAME AS NEW WORK, IN NEW LOCATION
INDICATED. COMPLETELY CLEAN AND RESTORE EQUIPMENT TO GOOD
OPERATING CONDITION PER SATISFACTION OF OWNER.
4. DELIVER REMOVED EQUIPMENT TO OWNER'S DESIGNATED STORAGE SPACE ON
SITE, PLUG OR CAP ALL EQUIPMENT OPENINGS TO PREVENT DIRT AND
MOISTURE FROM ENTERING EQUIPMENT PER SATISFACTION OF OWNER.
3. COMPLETELY REMOVE EXISTING DUCTWORK, INCLUDING ALL UNNEEDED
ACCESSORIES, INSULATION, HANGER SUPPORTS, ETC. FOR REMAINING DUCT
SYSTEM PLUG OR CAP ALL OPENINGS CREATED BY DUCT DEMOLITION. TEST
DUCTWORK AS SPECIFIED, AND INSULATE OR PAINT SAME AS NEW WORK. PATCH
EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY DEMOLITION
TO ORIGINAL CONDITION PER SATISFACTION OF OWNER. DUCT DEMOLITION
SHALL INCLUDE ALL BOLDLY DISPLAYED DUCT INDICATED ON DRAWINGS.
2. COMPLETELY REMOVE EXISTING EQUIPMENT, INCLUDING ALL UNNEEDED PIPING,
VALVES, INSULATION, HANGERS, SUPPORTS, BASES, CONTROLS, ETC. PATCH
EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY DEMOLITION
TO ORIGINAL CONDITION PER SATISFACTION OF OWNER.
1. COMPLETELY REMOVE INDICATED EXISTING PIPING, INCLUDING ALL UNNEEDED
PIPING, VALVES, INSULATION, HANGERS, SUPPORTS, ETC. FOR REMAINING
PIPING SYSTEMS PLUG OR CAP ALL OPENINGS CREATED BY PIPING DEMOLITION.
TEST PIPING SYSTEMS AS SPECIFIED, AND INSULATE OR PAINT SAME AS NEW
WORK. PATCH EXISTING WALLS, ROOFS, CEILINGS, AND FLOORS DISTURBED BY
DEMOLITION TO ORIGINAL CONDITION PER SATISFACTION OF OWNER. PIPING
DEMOLITION SHALL INCLUDE ALL BOLDLY DISPLAYED PIPES INDICATED ON
DRAWINGS.
R E
F R
E F
F.E.
F.E.
F.E.
REF.
D W
R E
F
DW
REF.
A B C D E GH J K LM N P Q R S TF Q.1 S.1
19.5
24.1
A B C D E F GH J K LM N P Q R S T
VRF-E119
VRF-E122
VRF-E117
VRF-W107
VRF-W101
VRF-W100
VRF-W103
VRF-W116
VRF-W114
VRF-W113
VRF-W115
VRF-W112
VRF-W102
VRF-E120
VRF-W108 VRF-W105
VRF-W110
VRF-W109
VRF-W111
VRF-W106
VRF-E108
VRF-E107 VRF-E106 VRF-E104 VRF-E103
VRF-E102VRF-E101VRF-E109VRF-E110
VRF-E113
VRF-E112
VRF-E114
VRF-E115
VRF-E116
VRF-E123
VRF-E126
VRF-E124
VRF-E100
VRF-E105
VRF-E127
RG-1RG-1RG-1
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-1RG-1RG-1
RG-1RG-1RG-1
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-1RG-1RG-1
RG-2RG-2RG-2
RG-1RG-1RG-1
RG-2RG-2RG-2
RG-1RG-1RG-1
RG-1RG-1RG-1
CD-3CD-3CD-3
CD-3CD-3CD-3
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-3CD-3CD-3
CD-3CD-3CD-3
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-2CD-2CD-2225
CD-2CD-2CD-2
CD-2CD-2CD-2
ACCU-2
FC-1FC-2
CRAC-2 CRAC-1
ACCU-1A
ACCU-1B
CRAC-3
VRF-E125
MOD-1B
EG-1EG-1EG-1
L-1
L-2
8x88x8
UTR TO EF-1
THRU EXISTING
ROOF OPENING
RG-1RG-1RG-1
CD-4CD-4CD-4 175
CD-4CD-4CD-4
RG-1RG-1RG-1
SG-1SG-1SG-1
CD-1CD-1CD-1
CD-1CD-1CD-1
RG-1RG-1RG-1
RG-1RG-1RG-1
CD-1CD-1CD-1
SG-2SG-2SG-2
RG-2RG-2RG-2
SG-3SG-3SG-3
SG-3SG-3SG-3
SG-3SG-3SG-3
14ø SA DN
TO SIM
(900 CFM)
14ø SA DN
TO SIM
(900 CFM)
16x16 EA
UTR TO
AHU-2
18x24 OA
UTR TO
AHU-2
25x22 OA
UTR TO
AHU-1
32x13 EA
UTR TO
AHU-1
T
T T
T
T
TTT
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
CRAC-4
T
T
T
T
T
TT
TT
T
T
T
T
T
T
T
T
T
T
T
RG-2RG-2RG-2
T
S
S
S
S 7.101
7.102
7.101
S
SIMULATOR
ELEC
CORR
ARMS
VEST
COPY
ROOM
HALLWAY
LOBBY
VEST
VEST
HALLWAY
7.103
RG-2RG-2RG-2
16x616x6
OED 335 CFM
CD-2CD-2CD-2
MOD-1A
EG-2EG-2EG-2
RG-2RG-2RG-2
12ø12ø12ø12ø
36x1236x12
6ø6ø
6x66x612x612x6
XFMER(E)
VRF-W117
VRF-E129
VRF-E128
SG-3SG-3SG-3
SG-3SG-3SG-3
SG-3SG-3SG-3
SG-3SG-3SG-3
SG-3SG-3SG-3
x1 x1 x1 x1
16x1616x16 ø ø x1 x1
8ø8ø
19x1019x10 x1 x1 x1 x1 x2 x2 x2 x2
14ø14ø 14ø14ø
6x86x8
6ø6ø
4ø4ø
4ø4ø x1 x1
8ø8ø ø ø x1 x1 x1 x1
12x812x8
4ø4ø 4ø4ø
4ø4ø
4ø4ø
4ø4ø 4ø4ø
10ø10ø ø ø
4ø4ø ø ø ø ø ø ø
30x1430x14
19x1019x1012x812x8
19x1019x10
12x812x8 x1 x1 x8 x8
VRF-E121
ø ø
12x612x6
VRF-E118
CD-2CD-2CD-2
CD-2CD-2CD-2
RG-1RG-1RG-1
CD-2CD-2CD-2
CD-2CD-2CD-2
CD-1CD-1CD-1
RG-2RG-2RG-2
RG-1RG-1RG-1
CD-2CD-2CD-2
CD-2CD-2CD-2
VRF-E111
19x1019x10
12x812x8
12x612x6
RG-2RG-2RG-2
RG-2RG-2RG-235
RG-2RG-2RG-2
x1 x1 x1 x1 x1 x1
6ø6ø ø ø ø ø ø ø ø ø ø ø ø ø
10x610x6
8x88x8
OED 250 CFM
x6 x6
10x1010x1019x1019x1012x812x8 ø ø
16x1216x12
10ø10ø ø ø ø ø x1 x1 x8 x8
19x1019x10
12x1212x12
10ø10ø x x x x x x
10x1010x10
19x1219x1212x1412x14
CD-1CD-1CD-1
8x68x6
12ø12ø
8x88x8
8x88x8
RG-2RG-2RG-2
ø ø ø ø ø ø ø ø x x
4ø4ø
4ø4ø ø ø
4ø4ø
VRF-W104
RG-1RG-1RG-1
RG-2RG-2RG-2
CD-2CD-2CD-2
CD-2CD-2CD-2
12x612x6
14ø14ø
14x1414x14 x1 x1
RG-1RG-1RG-1
CD-3CD-3CD-3
CCA
OSS
COMMANDER
OPERATIONS
GROUP
COMMANDER
FIGHTER
SQUADRON
COMMANDER
VEST
HALLWAY
DIRECTOR
OF
OPERATIONS
AIRFIELD
MANAGEMENT
AFMT
NCOIC
OPERATIONS
CHIEF
STAN
EVAL
CONFERENCE
ROOM
AFE
NCOIC
MEN'S
TOILET/
LOCKER
ROOM
AIRCREW
FLIGHT
EQUIPMENT
SOF
SIMULATOR
SUPPORT
OFFICE
125 SCHEDULING
STORAGE
FLIGHT
COMMANDERS
ARMS
NCOIC
SECURED
VEST
MX
DEBRIEF
COMM/
COMPUTER
STORAGE
WEAPONS
ACMI
CLASSROOM
INTEL
VAULT
INTEL
INTEL
NCOIC
INTEL OIC
BRIEFING
ROOM 3
BRIEFING
ROOM 1
BRIEFING
ROOM 2
BRIEFING
ROOM 4
LIBRARY
STORAGE
BREAK
ROOM
ISSO &
SSR
MISSION
PLANNING
OPEN
OFFICE
PM/PSM
SECURE
VAULT
MAIN
BRIEFING
ROOM
KITCHEN/
VENDING
BREAK
ROOM
STORAGE
AFE
INSPECTION
ROOM
COMM
ELEC
AFE
STORAGE
MECH
JANITOR
WOMEN'S
TOILET/
LOCKER
ROOM
AFE
SUPERINTENDENT,
FEO
NVG
TRAINING
OFFICER
HALLWAY
VEST
HALLWAY
WOMENS
ENTRY
STORAGE
166A
STORAGE
166B
STORAGE
166C
6ø6ø
CD-4CD-4CD-4
CD-4CD-4CD-4
36x1036x10
VRF-E130
18x1018x10 x8 x8
CD-4CD-4CD-4
CD-4CD-4CD-4
CD-4CD-4CD-4
CD-4CD-4CD-4
CD-4CD-4CD-4
CD-4CD-4CD-4
52x1652x16 x1 x1 x1 x1
10ø10ø
7.104
(2-WAY)50
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
RG-2RG-2RG-2
7.105
S
S
14x6(E)
14x6(E)
14x6(E) x1
(E
20x14(E)
CD-(E)CD-(E)CD-(E)CD-(E)
CD-(E)CD-(E)CD-(E)CD-(E)
CD-(E)CD-(E)CD-(E)CD-(E)
CD-(E)CD-(E)CD-(E)CD-(E)
14x1214x12
10ø10ø x8 x8
RG-3RG-3RG-3
SG-4SG-4SG-4
CUH(E)
7.106
UH-2
UH-3
10ø10ø
S
10x810x8
12x1212x12
10ø10ø
10ø10ø
CUH-3
CUH-2
C-1
C-4
C-3
CUH-6
UH-1
CUH-5
CUH-1
CUH-4
CUH-7
RG-2RG-2RG-2
RG-2RG-2RG-2
T x1 x1
12x812x8
52x1852x18
52x1052x10 ø ø
10ø10ø
7.104
H
HH
H
SG-1SG-1SG-1
MOD-2A
ø ø
7.107
MOD-2B 12x1212x12
OED W/ 1/2" X 1/2"
SCREEN UTR TO
EF-2
7.1087.108
7.108
7.108
7.108
UH-4
x1 x1
14x1014x10
16x1016x10
FIRE
ALARM
20x1420x14
12x1212x12
OED
OED
x1 x1 x8 x8
RG-2RG-2RG-2
ø ø
OED
DCO
DCO
DCO
DCO
DCO
DCO
DCO
19x1019x10
19x1019x10
6ø6ø 12x1012x10
DCO
DCO
TG-1TG-1TG-1
TG-1TG-1TG-1
x8 x8
OED
DCO
4ø4ø
TG-2TG-2TG-2
TG-2TG-2TG-2
16x816x8
12x1212x12 ø ø
7.108
7.1087.108
DCO
x1 x1 x1 x1 x1 x1
10x810x810x810x8
10x810x8
10x810x810x810x8
10x810x810x810x8
10x810x8 10x810x8
10x810x8
16x1016x10
16x1016x10
16x1016x10 16x1016x10
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
10x810x8
OED
x1 x1 x1 x1
16x1616x16 ø ø
4ø4ø
18x618x6
10x810x8
10x810x8
M-301
6ø6ø
AD
AD
BURGLAR
BARS
AFC
BURGLAR
BARS
AFC
RG-4RG-4RG-4
SG-5SG-5SG-5
x1 x1 414x1414x14
S
S
(IN RETURN PLENUM)
(IN RETURN PLENUM)
AD
AD
CUH-1
CUH-2
VRF-E100
T
7.109
T
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:1
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-101
HVAC FLOOR PLAN
XGFG132020ANG NO.:
3141300-141489.01
RRW/SMG
SNW
May 4, 2017
BGD
KEYED NOTES
7.101 MECHANICAL VENTILATION EMERGENCY KILL SWITCH.
7.102 BOILER SHUTDOWN BUTTON PER ASME CSD-1. LOCATE A MANUALLY
OPERATED REMOTE SHUTDOWN SWITCH OR CIRCUIT BREAKER LOCATED
JUST INSIDE THE BOILER ROOM EXTERIOR DOOR AND MARKED FOR EASY
IDENTIFICATION. THE SWITCH MUST SHUT DOWN ALL POWER TO THE
BURNER CONTROLS.
7.103 OA DUCT DOWN THRU VAULT CAP
7.104 PROVIDE BURGLAR BARS AT PENETRATION OF SECURE AREA ROOF.
PROVIDE FLEXIBLE CANVAS DUCT CONNECTOR ON SECURE SIDE OF ROOF
AND DUCT ACCESS DOOR FOR INSPECTION OF BURGLAR BAR INTEGRITY.
7.105 COORDINATE WITH SIMULATOR LAYOUT. ROUTE 14" Ø HARD DUCT TO
WITHIN 6 FEET OF FLOOR AND TERMINATE WITH A SECOND VOLUME
DAMPER ADJUSTABLE WHILE STANDING ON THE FLOOR AND 8 FEET OF
FLEXIBLE DUCT. FINAL CONNECTION TO SIMULATOR BY SIMULATOR
INSTALLER.
7.106 ELECTRIC CEILING MOUNTED CABINET UNIT HEATER (ETR)
7.107 4" Ø ALUMINUM DRYER VENT FROM EXISTING DRYER. TERMINATE WITH 4" Ø
WALL CAP.
7.108 EXHAUST DUCTWORK AND DAMPERS SERVING SHOWER AREAS TO BE
CONSTRUCTED OF ALUMINUM FROM THE SHOWER/LOCKER ROOM AREAS
BACK TO MAIN BRANCH TAPS AND MAIN BRANCH BACK TO MAIN DUCT RUN.
7.109 T-STAT FOR UH-4 TO BE SET FOR MINIMUM 5°F BELOW SETPOINT OF CRAC
UNITS.
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
HVAC FLOOR PLAN
05/04/17 TYPE B3
11. PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCES ON ALL EQUIPMENT.
10. VERIFY FINAL LOCATIONS OF ROOM THERMOSTATS / SENSORS / CONTROLS
WITH OWNER PRIOR TO INSTALLATION.
9. PROVIDE MINIMUM 5 FEET OF STRAIGHT DUCT ON OUTLET OF ALL VRF UNITS
PRIOR TO ANY TRANSITION, ELBOW, OR TAKE-OFF.
8. PROVIDE FLEXIBLE DUCTWORK FOR FINAL CONNECTIONS TO SUPPLY AIR
DIFFUSERS UNLESS NOTED OTHERWISE IN SPECIFICATIONS.
7. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH REFLECTED
CEILING PLAN.
6. PROVIDE MANUAL BALANCING DAMPER AT EACH DIFFUSER/GRILLE BRANCH
TAKE-OFF IN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK. LOCATE
BALANCING DAMPER AS CLOSE TO BRANCH TAKE-OFF AS POSSIBLE.
5. DUCT RUN-OUTS TO EACH DIFFUSER TO BE THE SAME AS DIFFUSER NECK SIZE
UNLESS NOTED OTHERWISE.
4. CONTROL CONTRACTOR IS RESPONSIBLE FOR COORDINATING POWER FOR HIS
EQUIPMENT WITH ELECTRICAL CONTRACTOR AND INSURING ALL COSTS
ASSOCIATED WITH SUCH ARE INCLUDED IN THE PROJECT COST.
3. COORDINATE WITH ELECTRICAL CONTRACTOR FOR EXACT LOCATIONS OF
ELECTRICAL PANELS AND EQUIPMENT. DO NOT RUN PIPING/DUCTWORK OVER
TOP OF OR WITHIN 3'-0" CLEAR HORIZONTALLY IN FRONT OF ALL ELECTRICAL
EQUIPMENT OR PANELS.
2. REFER TO SHEET M-001 FOR LEGENDS, ABBREVIATIONS, AND SYMBOLOGY.
1. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THE ATTENTION
OF THE ARCHITECT/ENGINEER FOR FINAL DECISIONS.
GENERAL HVAC NOTES:
NOTE:
SEE DETAILS 13/M-501 AND 14/M-501 FOR SIZES AND SPECIAL
INFORMATION ON TRANSFER DUCTS ABOVE CELING.
A B C D E GH J K LM N Q R S T
AHU-1
EF-1
EF-2
G
1" G
ACCU-4
RL TFB
1" G DN
ACCU-3
RL TFB
RS TFB
RS TFB
ROOF HATCH
AHU-2
UTILIZE EXISTING
ROOF OPENING
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:1
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-102
HVAC ROOF PLAN
XGFG132020ANG NO.:
3141300-141489.01
RRW/SMG
SNW
May 4, 2017
BGD
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
HVAC ROOF PLAN
R E
F .R
E F
F.E.
F.E.
F.E.
REF.
D W
R E
F
DW
REF.
A B C D E GH J K LM N P Q R S TF Q.1 S.1
19.5
24.1
A B C D E F GH J K LM N P Q R S T
FC-2 FC-1
ACCU-1A
ACCU-1B
CRAC-3
M-401
M-401
M-401
UH-1
CUH-4
CUH-2
CUH-3
CUH-1
C-1
1" HWS
1" HWR
2 1/2" HWRCRAC-4
T
3/4" CD
2 1/2" HWS
3/4"
3/4"
3/4"
1 1/4" HWS
CRAC-1CRAC-2
CUH-6
H W
S
/4
/4
CUH-5
CUH-7
3/4"
VRF-E113
VRF-E119
VRF-E108
VRF-E107 VRF-E106 VRF-E104 VRF-E103
VRF-E102VRF-E101VRF-E109
VRF-E110
VRF-E117
VRF-E122
VRF-W107
VRF-E120
VRF-E105
VRF-E112
VRF-E114
VRF-E116
VRF-E115
VRF-W102
VRF-W116
VRF-W115
VRF-W114 VRF-W113
VRF-W111
VRF-W112
VRF-W109
VRF-W110
VRF-W108
VRF-W105
VRF-W103
VRF-E124
VRF-E100
VRF-E127
VRF-E123
VRF-E126
VRF-E125
VRF-W101
VRF-W100
VRF-W117
VRF-W106
VRF-E128
ACCU-2
C-3
C-4
C-2
/4
/4
/4
/4
3/4"
/4
3/4" HWR
3/4"
1 1/4" HWS
1 1/4" HWR
NATURAL
GAS
METER
BSB-6
BSB-5
BSB-4
BSB-3
BSB-2
BSB-1
FT-1
2 FT 1.0 GPM
FT-1
14 FT 1.0 GPM
FT-1
3 FT 0.6 GPM
FT-1
10 FT 1.2 GPM
FT-1
8 FT 1.2 GPM
FT-1
6 FT 0.6 GPM
FT-1
8 FT 0.5 GPM
FT-1
8 FT 0.5 GPM
FT-1
10 FT 0.7 GPM
FT-1
6 FT 0.5 GPM
FT-1
8 FT 1.2 GPM
FT-1
10 FT 1.2 GPM
FT-1
10 FT 0.7 GPM
FT-1
6 FT 1.8 GPM
FT-1
16 FT 1.8 GPM
FT-1
6 FT 1.8 GPM
FT-1
6 FT 0.5 GPM
FT-1
6 FT 0.5 GPM
FT-1
10 FT 0.7 GPM
FT-1
10 FT 0.7 GPM
FT-1
6 FT 0.5 GPM
FT-1
8 FT 0.9 GPM
FT-1
6 FT 0.9 GPM
FT-1
8 FT 0.5 GPM
FT-1
6 FT 0.8 GPM
FT-1
6 FT 0.8 GPM
/2
H W
S
/2
H
W R
2" HWS
2" HWR
H W
S
H
W R
1 1/4" HWR
1 1/4" HWS
3/4"
3/4"
3/4"
/4
H G
R S
R L
H G
R S
R L
R L
R S
H G
RL
RS
HG
RL
RS
HG
H G
R S
R L
RL /RS
RL /RS
R L
RL /RS
RL /RS
RL /RS
R L R
S
R L R
S
RL /RS
RL /RS
R L R
S R
L R
S R
L R
S R
L R
S R
L R
S
RL /RS
R L R
S
R L R
S
R L R
S R
L R
S
3/4"
3/4"
3/4"
3/4"
3/4"
R L
R L R
S R
L R
S
RL /RS
RL /RS
RL /RS
R L R
S R
L R
S
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
RL /RS
R L R
S
R L R
S
RL /RS
VRF-E118
VRF-E111
VRF-E129
VRF-W104
VRF-E121
LCO
LCO
LCO
LCO
LCO
LCO
LCO
CD
CD
CD
C D
1 1/2" CD
C D
C D
CD
C D
C D
C D
C D
C D
1 1/2" CD
C D
CD
/2
C D
CD
CD
CD
CD
CD
CD
CD
C D
1 1/2" CD
CD
CD
CD
CD
CD
/2
C
DCD
CD
/2
C D
CD
CD
CD
CD
CDCD
CD
CD CD
CD
CD
/2
C D
CD
CD
/4
C
D
/2
C D
1 1/2" CD
DN TO HD
1 1/2" CD
DN TO HD
1 1/2" CD
DN TO HD
1 1/2" CD
1 1/4" HWS
1 1/4" HWR
GWS
GWR
1 1/4" HWR
GWS
GWR
LCO
CD
1 1/2" CD
DN TO HD
LCO
1" CD
C D
CD
LCO
CD
C D
C D C D
LCO
LCO
R L R
S R
L R
S R
L R
S R
L R
S
/2
C D
RL UTR
RS UTR
HG
RS
RL
CCA
OSS
COMMANDER
OPERATIONS
GROUP
COMMANDER
FIGHTER
SQUADRON
COMMANDER
VEST
HALLWAY
DIRECTOR
OF
OPERATIONS
AIRFIELD
MANAGEMENT
AFMT
NCOIC
OPERATIONS
CHIEF
STAN
EVAL
CONFERENCE
ROOM
AFE
NCOIC
MEN'S
TOILET/
LOCKER
ROOM
AIRCREW
FLIGHT
EQUIPMENT
SOF
SIMULATOR
SUPPORT
OFFICE
SCHEDULING
STORAGE
FLIGHT
COMMANDERS
ARMS
ARMS
NCOIC
SECURED
VEST
MX
DEBRIEF
COMM/
COMPUTER
STORAGE
WEAPONS
ACMI
CLASSROOM
INTEL
VAULT
INTEL
INTEL
NCOIC
INTEL OIC
BRIEFING
ROOM 3
BRIEFING
ROOM 1
BRIEFING
ROOM 2
BRIEFING
ROOM 4
LIBRARY
STORAGE
BREAK
ROOM
ISSO &
SSR
MISSION
PLANNING
OPEN
OFFICE
PM/PSM
SECURE
VAULT
VEST
LOBBY
MAIN
BRIEFING
ROOM
KITCHEN/
VENDING
BREAK
ROOM
VEST
169HALLWAY
STORAGE
AFE
INSPECTION
ROOM
COMM
ELEC
AFE
STORAGE
MECH
CORR
JANITOR
WOMEN'S
TOILET/
LOCKER
ROOM
AFE
SUPERINTENDENT,
FEO
NVG
COPY
ROOM
TRAINING
OFFICER
SIMULATOR
HALLWAY
VEST
HALLWAY
VEST
HALLWAY
WOMENS
ENTRY
STORAGE
166A
STORAGE
166B
STORAGE
166C
1" G UTR
8.102
8.102
8.103
8.1038.103
8.103
8.103
8.1038.103
8.103
8.1038.103
8.1038.103
1"1"
3/4"3/4"
8.1018.101
8.1018.101
8.1018.101
8.1018.101
8.1018.101
8.1018.101
1 1/2" CD
8.1018.101
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
8.103
(TYP)
ROUTE NEW PIPING TO
CUH-2 SIMILAR TO EXISTING
CUH(E)
7.106
8.101
UH-2
UH-3
P-7 P-6
M-401
M-401
1" 3/4"
3/4" 3/4"
3/4"
1"1" HWS
1" HWR
1"
/4
/4
/4
2" HWS
2" HWR
/4
H W
R
3/4"
3/4"
/4
H W
R
UH-4
/4
H
W R
/4
H
W S
FT-1
3 FT 1.2 GPM
FT-1
3FT 1.2 GPMFT-1
3 FT 1.2 GPM
FT-1
3 FT 1.2 GPM
FT-1
10 FT 1.2 GPM
3/4" HWR
1" HWS
/2
H W
S
/2
H
W R
H W
S
1 1/4" HWS
H W
R
H
W S
2" HWR
2" HWS
8.103 8.103
8.103 8.1038.103 (TYP)
(TYP)
(TYP)
M-301
M-301
M-301
M-301
3/4"
RL UTR
RS UTR
1 1/2" CD
DN TO HD
VRF-E130
8.101
LCO
LCO
LCO
H
T
H
H
T
H
T
8.103
8.103
8.1038.103
8.1038.103
8.103
1"
3/4"
3/4"
1 1/2" CD
DN TO HD
H W
R
/4
H
W S
/4
H
W R
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:1
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-131
MECHANICAL FLOOR
PLAN
XGFG132020ANG NO.:
3141300-141489.01
RRW/SMG
SNW
May 4, 2017
BGD
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
MECHANICAL FLOOR PLAN
KEYED NOTES
7.106 ELECTRIC CEILING MOUNTED CABINET UNIT HEATER (ETR)
8.101 ALL CONDENSATE DRAIN PIPING FROM VRF UNITS SHALL BE 3/4" AND
PITCHED AT 1/8" PER FOOT TO MAIN RUN WITH TOP CONNECTION. ALL MAIN
RUNS SHALL BE 1 1/2" UNLESS SHOWN OTHERWISE AND PITCHED TO HUB
DRAIN AT 1/8" PER FOOT.
8.102 CONNECT NEW PIPING TO EXISTING AT APPROXIMATELY THIS POINT.
8.103 GROUND PIPE AT PENETRATION OF SECURE WALL.
05/04/17 TYPE B3
7. ALL REFRIGERATION PIPING TO BE HARD RIGID COPPER EXCEPT FOR DUCTLESS
SPLIT UNITS WHERE LINESETS MAY BE USED.
6. PITCH ALL CONDENSATE DRAIN PIPING TOWARDS FLOOR OR HUB DRAIN.
5. COORDINATE ALL PIPING WITH HVAC DUCTWORK ROUTING.
4. CONTROL CONTRACTOR IS RESPONSIBLE FOR COORDINATING POWER FOR HIS
EQUIPMENT WITH ELECTRICAL CONTRACTOR AND INSURING ALL COSTS
ASSOCIATED WITH SUCH ARE INCLUDED IN THE PROJECT COST.
3. COORDINATE WITH ELECTRICAL CONTRACTOR FOR EXACT LOCATIONS OF
ELECTRICAL PANELS AND EQUIPMENT. DO NOT RUN PIPING/DUCTWORK OVER
TOP OF OR WITHIN 3'-0" CLEAR HORIZONTALLY IN FRONT OF ALL ELECTRICAL
EQUIPMENT OR PANELS.
2. REFER TO SHEET M-001 FOR LEGENDS, ABBREVIATIONS, AND SYMBOLOGY.
1. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THE ATTENTION
OF THE ARCHITECT/ENGINEER FOR FINAL DECISIONS.
GENERAL MECHANICAL PIPING NOTES:
G H JG H JG H J
SCHEDULING
HALLWAY
MEN'S
TOILET/
LOCKER
ROOM
VRF-E11810x19 SA
8x10 TA
RL /RS
3/4" CD
12x16 EA
20x14 EA1 1/2" CD
10x8 SA 12x6 RA
12x10 OA
1 1/4" HWR
SA
CD-1CD-1CD-1
3/4" HWR
1/8" / 1'-0"
CDEF
GH
CLASSROOM
INTEL
VAULT
FT-1FT-1
FT-1
FT-1
FT-1
/4
H
W S
3/4" HWR
H W
R
1" HWR
1" HWS
3/4" HWR
3/4" HWR
3/4" HWR
3/4" HWR3/4" HWR
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:1
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-301
MECHANICAL
SECTIONS
XGFG132020ANG NO.:
3141300-141489.01
RRW/SMG
SNW
May 4, 2017
BGD
05/04/17 TYPE B3
1/2" = 1'-0"1
ENLARGED SECTION - HALLWAY 131 - LOOKING NORTH
1/2" = 1'-0"2
ENLARGED SECTION - CLASSROOM 110 - LOOKING SOUTH
F.E.
R S TS T
1111 11
12 12
13 13
R
R
S
S
T
T
M-401
M-401
HWB-3 HWB-2 HWB-1
ET-1
AS-1
P-1P-2P-3
2 1/2" HWS
HWS
HWR
NATURAL GAS
METER
(ETR)
UH-1
MECH
3" EXHAUST
(TYP)
3" INLET (TYP)
1 1/2" G
1" G UTR
P-4
P-5
1" G
/4
G
COMBINATION
CHEMICAL
POT
FEEDER/SIDESTREAM
WATER
FILTER
1 1/2" G
/2
G
1155 MBH
CONNECTED
LOAD AT 2 PSIG
/4
/4
/4
1" G
1" CD
/4
C
D
/2
H W
S
/2
H W
R
1 1/2" HWS
(TYP)
1 1/2" HWR
(TYP)
TCP
DDC
PANEL
M-401
M-401
3/4" HWS
3/4" HWR
8.1048.104
1" HWS
1" HWR
/4
H
W S
/4
H
W R
CRAC-3
3/4" G DN TO
WATER HEATER
1 1/2" CD DN TO HD
3/4" HWS
3/4" HWR
RL UTR
RS UTR
R S T
/2
H W
S
/2
H W
S
/2
H W
S
P-1P-2P-3
HWB-1HWB-2HWB-3
ET-1
AS-1
P-5
P-4
/2
H W
S
IN
L
E T
E X
H A
U S
T
IN
L
E T
E X
H A
U S
T
IN
L
E T
E X
H A
U S
T
/2
H W
R
/2
H W
R
/2
H W
R
2 1/2" HWR
UH-1
/4
G
/4
G
/4
G
/2
G
TCP
2 1/2" HWS
2 1/2" HWR
M-401
MECH
8.1048.104
CRAC-3
ACCU-3
RL
RS
131211
M-401
COMBINATION
CHEMICAL
POT
FEEDER/SIDESTREAM
WATER
FILTER
P-5
P-4
ET-1
/2
H W
S
/2
H W
S
2 1/2" HWS
MECH
8.104
G
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:2
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-401
MECHANICAL ROOM
ENLARGED PLAN
AND SECTIONS
XGFG132020ANG NO.:
3141300-141489.01
RRW/SMG
SNW
May 4, 2017
BGD
PLAN
NORTH
TRUE
NORTH
1/2" = 1'-0"1
ENLARGED MECHANICAL ROOM PLAN
KEYED NOTES
8.104 COORDINATE WITH GENERAL CONTRACTOR, THE EXACT SIZE AND
LOCATION OF HOUSEKEEPING PADS PER FINAL EQUIPMENT SELECTIONS.
05/04/17 TYPE B3
1/2" = 1'-0"2
ENLARGED MECHANICALROOM SECTION - LOOKING NORTH
1/2" = 1'-0"3
ENLARGED MECHANICALROOM SECTION - LOOKING WEST
CAULK ALL AROUND
DUCT WORK
INSULATION
JACKET
BANDING
FULL LENGTH
PIANO HINGE
FRAME - SAME
MATERIAL AS DUCT
GASKET ALL AROUND
PERIMETER
1" MIN. HIGH-DENSITY
FIBERGLASS INSUL.
DOVETAILS
BANDING
SASH CAM AND LATCH
DOOR - SAME MATERIAL
AS DUCT
3/8"3"
MAX
3/8"3"
MAX
RECTANGULAR DUCT
GASKET ALL AROUND
PERIMETER
SASH CAM AND LATCH
RIVET
ACCESS DOOR OF SAME
MATERIAL AS DUCT
FULL LENGTH PIANO HINGE
WALL
PROVIDE ANGLES AT
TOP AND SIDES
DAMPER WHERE SPECIFIED
SEE DRAWINGS FOR DUCT
SIZE, SEE SPECIFICATION
FOR INSUL. REQUIREMENTS
ACCESS DOOR
(MIN 10"x10")
BIRD SCREEN TO
BE REMOVABLE OR HINGED
AT TOP
PROVIDE INSULATED METAL
PANEL OR UNUSED PROTION
OF LOUVER. CAULK EDGE
FOR AIR TIGHTNESS.
WATERPROOF
CAULKING
ALL AROUND
LOUVER AS
SCHEDULED
CONNECTION
TYP FOR TOP
AND SIDES
KEYED NOTES:
USE PVC COATED METALIC DUCT FOR BOTTOM OF OUTSIDE
AIR INTAKE DUCT FROM LOUVER TO THIS POINT.
DEPRESSED TO AVOID
AN OBSTRUCTION
SMOOTH RADIUS ELLS
TO AVOID AN OBSTRUCTION
H1
W1
L
15°
W2
H2
H1 X W1 = H2 X W2
R=1 1/2 W
PERMISSIBLE ELBOWS
AIR FLOW
PERMISSIBLE TRANSITIONS
AIR FLOW
R
AIR FLOW
R
R=1 1/2 W
R
AIR FLOW
R
5/2
5 6"
R 0' - 0 21 5/2 5
6"
R 0' - 0 21 5/2 5
6"
W
W
W
R=1 1/2 W
45° 45°
DUCT INSULATION
24 GAUGE SHEET METAL SLEEVE,
EXTEND 1 1/2" BEYOND EACH
SIDE
SEAL SLEEVE TO WALL OPENING
WITH FIRE RESISTANT SEALANT
TAPE (2" MIN. WIDTH)
DUCTWORK
SAME SIZE AS GRILLE
7" MIN.
HEIGHT
RETURN AIRFLOW
(TYP. OF 2 ENDS)
LINED SHEET
METAL SOUND
BAFFLE
RETURN AIR GRILLE
LOCATE DAMPER AS FAR
FROM GRILLE AS POSSIBLE
SEAL DUCT CONNECTION
AIR TIGHT (CONNECTION MAY
BE ON TOP OF PLENUM)
SHEET METAL PLENUM.
PAINT INTERIOR OF METAL
PLENUM FLAT BLACK
RETURN/EXHAUST
GRILLE
CEILING
LINEAR SUPPLY GRILLE
VOLUME DAMPER
GRILLE NECK
SUPPLY BRANCH
45º BRANCH DUCT
TAKE-OFF
SUPPLY DUCTWORK
DUCT INSULATION
OPEN ENDED DUCT
SEE DRAWINGS FOR
SIZE AND SHAPE
ANGLE IRON REINFORCING
WELD OR BOLT TO DUCT
PROVIDE AS MANY BOLTS
AND NUTS AS NECESSARY
TO INSURE A SNUG FIT
BETWEEN SCREEN AND
DUCTWORK (TYP)
METAL SCREEN FRAME
INSECT OR BIRD SCREEN
AS SPECIFIED
NOTES:
1 MATERIALS OF CONSTRUCTION SHALL BE SIMILAR TO OPEN
ENDED DUCT (IE STAINLESS STEEL COMPONENTS FOR
STAINLESS STEEL DUCT).
BACKDRAFT DAMPER
- WHERE SCHEDULED
OR SPECIFIED
CENTRIFUGAL ROOF
EXHAUST FAN
BIRDSCREEN WITHIN UNIT
PREFABRICATED ROOF CURB
FINISHED ROOF
ROOF OPENING
EXHAUST DUCT
SEE CURB CAP
FASTENING DETAIL
M-501
NAIL
STAINLESS STEEL
TRUSS HEAD SCREW
(#10 x 1 1/2" MIN.)
CURB
90° FLANGE OUT ON
ALL SIDES COMPLETE
WITH FILLED CORNERS
1-1/2"x3/8" CLOSED
CELL NEOPRENE SELF
ADHESIVE GASKET
ALL AROUND
1/2 X
1/2 X
ACCOUSTICCALLY
LINED SHEET METAL
DUCT - SIZE
AS SHOWN ON PLANS
INTERIOR WALL
X
X
2X
2X
1/2 X
1/2 X
ACCOUSTICCALLY
LINED SHEET METAL
DUCT - SIZE
AS SHOWN ON PLANS
INTERIOR WALL
X
X
2X
2X
SECURED AREA NON-SECURED
AREA
AFC
1/2 X
1/2 X
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:2
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-501
MECHANICAL
DETAILS
XGFG132020ANG NO.:
3141300-141489.01
RRW
SNW
May 4, 2017
BGD
NO SCALE1
HINGED ACCESS DOOR
OR INSULATED RECTANGULAR DUCT
NO SCALE2
HINGED ACCESS DOOR
FOR UNINSULATED RECTANGULAR DUCT
NO SCALE4
DUCT CONNECTION TO LOUVER
NO SCALE5
TYPICAL DUCT OFFSET
NO SCALE6
TYPICAL DUCT TRANSITIONS
NO SCALE7
DUCT PENETRATION
THRU INTERIOR WALL
NO SCALE8
PLENUM RETURN GRILLE DUCT CAP
NO SCALE9
RETURN/EXHAUST
GRILLE DUCT CONNECTION
NO SCALE3
RIGID DUCT TO LINEAR WALL GRILLE
NO SCALE12
OPEN ENDED DUCT SCREEN TERMINATION
NO SCALE10
CENTRIFUGAL ROOF EXHAUST FAN
NO SCALE11
CURB CAP FASTENING
05/04/17 TYPE B3
NO SCALE13
NON-SCIF TRANSFER DUCT DETAIL
NO SCALE14
SCIF TRANSFER DUCT DETAIL
A
A
ACCESS
HEAT WHEEL PRE-FILTER 2
HEAT WHEEL3
COOLING COIL5
HOT GAS REHEAT COIL6
GAS FIRED HEAT EXCHANGER
FINAL FILTER
OA
EASA
AIR FLOW
A
A A
A
SUPPLY FAN
HEAT WHEEL EXHAUST AIR FILTER
EXHAUST FAN
3 2
10 10
ELECTRIC PREHEAT
FLEXIBLE DUCT
COLLAR
METAL CLAMP
VOLUME DAMPER
45º BRANCH DUCT TAKE-OFF
SUPPLY DUCTWORK
DUCT INSULATION
/1
MAX. SAG = 1/2" PER
FOOT OF LENGTH
4 19/32"
METAL CLAMP
METAL DUCT ELBOW,
LONG RADIUS, DIE STAMPED
SAME SIZE AS DIFFUSER
INLET CONNECTION
DIFFUSER
CEILING
MAX. LENGTH NOT TO EXCEED 5'-0"
EXTEND AND SPOT WELD
TO STRUCTURE ABOVE (TYP)
SECURE WALL
COMPRESSED 1" WIDE x 1/4"
THICK NEOPRENE GASKET
ALL AROUND BETWEEN
DUCT FLANGE AND WALL
SPACE BARS AT EQUAL SPACES NOTE TO
EXCEED 6" O.C.
FULLY WELD TO FRAME AND EACH OTHER
1/2" Ø SOLID STEEL
SECURITY BARS IN BOTH DIRECTIONS(TYP)
SPOT WELD (TYP)
FLANGE MOUNTED DUCT TO
WALL OPENING WITH
FASTENERS AT 8" O.C. ALL AROUND
ACCESS DOOR
NOTE:
ALL GYPSUM BOARD JOINTS TO
BE PERMANENTLY SEALED AND
PROFESSIONALLY FINISHED IN
ACCORDANCE WITH ACOUSTICAL
GYPSUM WALL BOARD
ASSEMBLIES
SECURED AREA
NON-SECURED
AREA
AFC
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/4
/2
:4
:2
A M
C R e vi t L o c a l\
-1
.0
-M
-C e n tr a l-rr w .r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
M-502
MECHANICAL
DETAILS
XGFG132020ANG NO.:
3141300-141489.01
RRW
SNW
May 4, 2017
BGD
05/04/17 TYPE B3
NO SCALE1
AIR HANDLING UNIT COMPONENT VIEW
NO SCALE2
FLEXIBLE DUCT TO CEILING DIFFUSER
NO SCALE3
SECURITY BARS AT DUCT PENETRATION
ROUTE REGULATOR
VENT TO BUILDING
EXTERIOR. TERMINATE
WITH WEATHERPROOF
VENT CAP
12" APPLIANCE
FLEXIBLE CONNECTOR
WITH THREADED
ENDS
APPLIANCE REGULATOR,
IF NOT PART OF
EQUIPMENT
GAS SUPPLY
HEADER
SIZE AS INDICATED
ON DRAWINGS
SHUTOFF VALVE
(TYP)
UNION
SAME SIZE AS
EQUIPMENT
CONNECTION
PLUG OR CAP
SEDIMENT TRAP
PIPE ANCHOR
EQUIPMENT
6"
3'-0"
MAX.
INTERIOR WALL
WALL SLEEVE, OF
SPECIFIED MATERIAL
ESCUTCHEON
WHERE SPECIFIED
PIPE INSULATION
AND JACKETING
WHERE CALLED FOR
TIGHTLY CAULK WITH
SILICONE SEALANT
FOR MIN. 2" EACH END
PIPE - MUST BE
FREE OF STRAIN
TIGHTLY PACKED
WITH FOAM - IN
PLACE INSULATION
1/2" TO 1"
CLEARANCE
ALL SIDES
EXTERIOR WALL
WALL SLEEVE, OF
SPECIFIED MATERIAL
ESCUTCHEON
- WHERE SPECIFIED
PIPE INSULATION
AND JACKETING
WHERE CALLED FOR
TIGHTLY CAULK WITH
SILICONE SEALANT
FOR MIN. 2" EACH END
PIPE - MUST BE
FREE OF STRAIN
TIGHTLY PACKED
WITH FOAMED - IN
PLACE INSULATION
WATERPROOF MASTIC
360˚ AROUND SLEEVE
COLOR TO MATCH WALL
1/2" TO 1"
CLEARANCE
ALL SIDES
UNION
REDUCER
FIN TUBE CONVECTOR
HWS HWR
BALANCING VALVE
AUTOMATIC
CONTROL VALVE
SHUTOFF VALVE
M
AQUASTAT
ROOM
T-STAT
CONTROL DIAGRAM
120V/1ph
CONNECT
TO MAINS
HWS
HWR
AIR FLOW
SHUTOFF VALVE
BALANCING VALVE
STRAINER
CAPPED
DRAIN VALVE
ACV
UNION (TYP)
STRAP-ON
AQUASTAT
UNIT
HEATER
HANGER RODS
TO
STRUCTURE
SEE DWGS
FOR SIZE
HEATING
COIL
REDUCE (TYP)
AS REQUIRED
UNION (TYP)
FLEXIBLE PIPE
CONNECTION
GAGE CONNECTION
(TYP)
3-WAY MIXING
AUTOMATIC CONTROL
VALVE (ACV)
MANUAL AIR VENT
BALANCING VALVE
(TYP)
WATER RETURN
SIZE AS INDICATED
ON PLANS
THERMOMETER
BYPASS LINE
SAME SIZE AS ACV
SHUTOFF VALVE
WATER SUPPLY
SIZE AS INDICATED
ON PLANS
STRAINER WITH BLOW
OFF VALVE AND NIPPLE
3/4" DRAIN VALVE
N.O.
MAKE-UP VALVES
COLD
WATER
FILL
AIR SEPERATOR
REDUCER
(WHERE REQ'D)
TO
SYSTEM
PUMPS(S)
SEE PLANS
FOR PIPE SIZE
/1
12"
MIN
AV
AV
AIR CHARGED
PORT
VERTICAL BLADDER
TYPE EXPANSION
TANK
SHUT-OFF
VALVE (TYP)
PRESSURE
GAUGE
AUTOMATIC
AIR VENT
SEE PLANS
FOR PIPE SIZE
FROM PRIMARY
HEATING/COOLING
EQUIPMENT
REDUCER
WHERE REQ'D
HIGH CAPACITY AIR VENT
EQUAL TO BELL & GOSSET
MODEL #107a
HANGER ROD
SIZE AS SPECIFIED
ADJUSTABLE
CLEVIS HANGER
JACKETING
WHERE SPECIFIED
RIGID INSULATION
AS SPECIFIED
PIPE
INSULATION PROTECTION
SHIELD MATERIAL
EXPANSION BOLT
ANCHOR 'D'
BASE PLATE SIZE 'C'
3/4" LEVELING GROUT
FINISHED FLOOR
PIPE SUPPORT
SIZE 'B'
PIPE SIZE 'A'
CENTERLINE OF PIPE
36" MAX.
BASE PLATE
1 1/2"
1 1/2"
'C' 'A'…