05_Fire_Protection.pdf
PDF 1 MB Posted
- Solicitation number
- W912J2-18-R-1001
About this file
05 Fire Protection
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TS
TS
LOC
1 SUPERVISED INDICATING VALVE (TAMPER SWITCH)
2 MAIN DRAIN SHUT-OFF VALVE
3 ALARM TEST
4 PRESSURE GAUGE
5 FLOW SWITCH
6 CHECK VALVE
7 DOUBLE CHECK DETECTOR ASSEMBLY
8 CONNECTION FLANGE BY FIRE PROTECTION CONSTRACTOR
9 BALL DRIP VALVES-ROUTE TO DRAIN
10 FLOOR OR HUB DRAIN
RISER SCHEMATIC KEYED NOTES:
/3
18"
EXTERIOR
WALL
SPLASH
BLOCK
FS
11 FIRE DEPARTMENT CONNECTION @ 36" AFG
12 2" MAIN DRAIN & TEST OUTLET 18" AFG
13 FORWARD FLOW TEST CONNECTION @ 48" AFG (ABOVE FINISHED
GRADE) (PITCH PIPE TO DRAIN OUTSIDE OF BUILDING)
FINISHED
FLOOR
2"
1"
MINIMUM REQUIRED FEATURES SHOWN. FINAL
PIPING SIZE & DESIGN BY FIRE PROTECTION
CONTRACTOR.
NOTES:
1.
IF ANY SPRINKLER PIPING DOWNSTREAM OF
FLANGED ENTRY TEE IS 6" OR LARGER, USE
WELDED, FLANGED OR THREADED
CONNECTIONS ON ALL PIPING BETWEEN
FLANGED ENTRY TEE AND ALARM VALVES.
2.
FIRE PROTECTION SYMBOLS:
FIRE DEPARTMENT CONNECTION
ORIFICE
FLOW SWITCH
ALARM BELL
ISOLATION VALVE
GATE VALVE
PRESSURE GAUGE
CHECK VALVE
VALVE SUPERVISION/TAMPER
SWITCH
STRAINER
T
PIPE DROP
PIPE RISE
STRAINER
FORWARD FLOW TEST CONNECTION
FIRE PROTECTION HATCH
PATTERN LEGEND:
LIGHT HAZARD (H-1)
EXTRA HAZARD (H-3)
ORDINARY HAZARD (H-2)
1 1/16"
/3
/3
4"MIN.
4"MIN.
4"MIN.
24"MIN.
PLAN VIEW
BPD
BPD
/3
"18"MIN.
/1
"12"-84"
ELEVATION VIEW
FINISHED FLOOR
FLOOR/HUB DRAIN
PITCHED DRAIN
AIR GAP FITTING
LOW POINT
ISOLATION VALVE
HIGH POINT
OBSTRUCTIONS
VALVE HANDLE SIDE
BPD DRAIN
< 2" 2"
2" - 3" 3"
4" 4"
O N
A S
S E
-1
O N
L Y
FLANGE
MAINTAIN 1' ANNULAR GAP
BETWEEN PIPE AND SLAB.
SEAL GAP
EXTERIOR WALL
FINISHED FLOOR LEVEL
GRADE
/3
78" MINIMUM
LOCATE JOINT 24" OUTSIDE OF
FOOTING PRESSURE LINE
45.00°
FOOTING PRESSURE LINE
EXTEND CASING 2" PAST
FOOTING PRESSURE LINE
(TYP)
END SEAL (TYP)
CASING
THRUST
BLOCK
SERVICE
ENTRANCE
PIPE
/3
X
/1
12"
IF DIMENSION "X" IS LESS THAN 12", INSTALL DI OR RCP CASING.
MAINTAIN AT LEAST 2" ANNULAR GAP BETWEEN PIPE AND CASING.
APPLY CASING END SEALS.
FIRE ALARM & MASS NOTIFICATION SYMBOLS
FIRE ALARM PULL STATION
FIRE ALARM ANNUNCIATOR PANEL
SUPERVISED FIRE ALARM HORN LOUDSPEAKER
NEW CONTROL MODULE
FIRE ALARM SPEAKER
FIRE ALARM DUAL WHITE/AMBER MASS NOTIFICATION STROBE, (##) IS
CANDELA RATING
INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR
INTELLIGENT PHOTOELECTRIC DUCT SMOKE DETECTOR
CEILING MOUNTED FIRE ALARM/MASS NOFICATION SPEAKER
NEW SPRINKLER FLOW SWITCH (PROVIDE
ADDRESSIBLE CONTROL MODULE)
NEW MONITOR MODULE
NEW REMOTE TEST SWITCH WITH INDICATOR
NEW SPRINKLER TAMPER SWITCH (PROVIDE
ADDRESSIBLE CONTROL MODULE)
FIRE SUPPRESSION SYSTEM PANEL
S
S
DS
S
MM
CM
FS
TS
RTS/I
FMCP
FAAP
FSS
FIRE & MASS NOTIFICATION CONTROL PANEL
MASS NOTIFICATION SPEAKER VOLUME CONTROLLER.
CONTROLS SPEAKERS WITHIN ROOM INSTALLED.
V
LOCAL OPERATING CONSOLE
FIRE ALARM SPEAKER/DUAL WHITE/AMBER STROBE, (##) IS
CANDELA RATINGS
LINE TYPE KEY
EXISTING TO BE REMOVED BY THIS
CONTRACTOR (DARK DASHED LINE)
EXISTING TO REMAIN WORK
(THIN SOLID LINE)
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
GENERAL SYMBOLS
KEYED NOTE, USED TO DESCRIBE ADDITIONAL
INFORMATION OF WORK REQUIRED, SPECIFIC TO
THE SHEET AND/OR DETAIL IT IS SHOWN WITH.
DETAIL NUMBER / SHEET NUMBER#/E-###
9.###
FIRE ALARM & MASS NOTIFICATION SYSTEM NOTES:
FIRE ALARM CONTROL UNIT AND MASS NOTIFICATION AUTONOMOUS CONTROL UNIT (FMCP) IS A COMBINED UNIT OF THE FIRE ALARM CONTROL PANEL (FACP) AND THE MNS AUTONOMOUS CONTROL UNIT (ACU). THE UNIT COULD USE
ONE OR MORE ENCLOSURES.
MASS NOTIFICATION ACU SHALL BE INTERFACED WITH THE TELEPHONE SYSTEM, SO THAT ANNOUNCEMENTS MAY BE
MADE OVER THE FA / MNS SPEAKERS VIA THE TELEPHONE SYSTEM.
ALL DETECTION AND ALARM CIRCUITS SHALL BE OF THE SUPERVISED CLASS A, STYLE D FOR INITIATING CIRCUITS AND A SUPERVISED CLASS A, STYLE Z FOR NOTIFICATION APPLIANCE CIRCUITS. SIGNALING LINE CIRCUITS (SLC) SHALL BE CLASS A, STYLE 2α.
MONITORED DEVICES INCLUDE FLOW AND TAMPER SWITCHES.
IF NOTIFICATION APPLIANCE CIRCUIT (NAC) POWER SUPPLIES OR AMPLIFIERS ARE REQUIRED, LOCATIONS SHALL BE APPROVED BY THE OWNER AND SHALL BE ACCESSIBLE TO THE FIRE DEPARTMENT. PROVIDE SMOKE DETECTOR (NOT SHOWN ON FLOOR PLANS) AT EACH NAC POWER SUPPLY/AMPLIFIER LOCATION UNLESS THE ROOM IS COVERED BY AREA SMOKE DETECTION. PROVIDE 120V POWER TO EACH LOCATION. NOTE THE SPEAKERS IN THE
SECURE AREA SHALL HAVE THEIR OWN HIGH GAIN POWER AMPLIFIER.
SEE PLANS FOR SPECIFIC CANDELA (CD) RATINGS ON NOTIFICATION APPLIANCES
ALL JUNCTION, TERMINAL, AND PULLING BOXES AND COVERS SHALL BE PAINTED RED AND SHALL BE IDENTIFIED WITH ENGRAVED LABELS BY CIRCUIT THAT IT CONTAINS. ALL CONDULETS AND SIMILAR UNITS SHALL BE PAINTED RED. ALL DETECTION AND TERMINAL DEVICES SHALL HAVE ENGRAVED PLASTIC OR METALLIC ALPHANUMERIC IDENTIFICATION, WHICH SHALL BE KEYED TO THE POSTED AND OPERATIONS AND MAINTENANCE INSTRUCTIONS.
ALL WIRING SHALL BE PER MANUFACTURER'S RECOMMENDATIONS.
WHEN THE MNS IS ANNOUNCING, AUDIBLE AND VISUAL FIRE ALARMS SHALL BE DE-ENERGIZED. CONTRACTOR SHALL
SUPPLY ALL NECESSARY EQUIPMENT TO ACCOMPLISH THIS PROCEDURE.
ALL SPEAKER AND STROBE CIRCUITS SHALL BE SUPERVISED.
STROBES SHALL BE DUAL AMBER/CLEAR TYPE WITH SEPARATE CABLING TO EACH STROBE.
SEE DRAWING FOR EXACT LOCATION OF REMOTE LOCAL OPERATION CONSOLE (LOC).
ALL SPEAKERS IN THE SECURE AREA SHALL BE TIED INTO THEIR OWN HIGH GAIN AMPLIFIER THAT IS LOCATED IN THE
SECURE AREA ROOM 126.
COORDINATE REQUIRED ALARMS MONITORED AT BASE HEAD END SYSTEM WITH OWNER PRIOR TO PROGRAMMING.
RTS/I
DS MM CM
S S S S
CDCD CDCD
24V POWER
SLC CIRCUIT
ANTENNA CABLING IN CONDUIT
FMCP
COMBINED
FIRE ALARM
CONTROL PANEL
(FACP)
MNS
AUTONOMOUS
CONTROL UNIT
(ACU)
ROOM 174
120 VAC
TO OTHER DUAL AMBER/CLEAR STROBES
AND THEN BACK TO FACP/ACU
TO OTHER SPEAKERS
AND THEN BACK TO AMPLIFIER
MONITORED
DEVICE
CONTROLLED
DEVICE
RTS/I
DS MM CM
S S S S
CDCD CDCD
24V POWER
SLC CIRCUIT
TO OTHER DUAL AMBER/CLEAR STROBES
AND THEN BACK TO FACP/ACU
TO OTHER SPEAKERS
AND THEN BACK TO AMPLIFIER
TO OTHER EQUIPMENT
AND THEN BACK TO FACP/ACU
MONITORED
DEVICE
CONTROLLED
DEVICE
S E
C U
R E
A R
E A
S E
C U
R E
A R
E A
FMCP
COMBINED
FIRE ALARM
CONTROL PANEL
(FACP)
MNS
AUTONOMOUS
CONTROL UNIT
(ACU)
ROOM 126
120 VAC
EWS
TO OTHER EQUIPMENT
AND THEN BACK TO FACP/ACU
EWS
LOC
LOC
LOC
MONACO BT-XM
MASS NOTIFICATION
COMMUNICATOR
ROOM 174
120 VAC
(26) #14 IN 1-1/2" C.
OPTICAL FIBER WITH NO METALLIC SHIELDING, CLADDING OR
STRENGTH MEMBERS PER UFC REQUIREMENTS.
AMPLIFIER
ROOM 126
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
LOC
LOC
LOC
LOC
SCIF GENERAL NOTES:
1. THE VAULT AREA IS CONSIDERED A SENSITIVE COMPARTMENTED
INFORMATION FACILITY. ALL NEW CONSTRUCTION AND RENOVATION TO THE
AREA INCLUDING WALL CONSTRUCTION, FIRE PROTECTION/DETECTION,
MECHANICAL/HVAC, ELECTRICAL, AND TECHNOLOGY SYSTEMS MUST
COMPLY WITH THE REQUIREMENTS PROVIDED IN UNIFIED FACILITY CRITERIA
4-010-05 SENSITIVE COMPARTMENTED INFORMATION FACILITY PLANNING,
DESIGN, AND CONSTRUCTION WITH CHANGE 1, 1 OCTOBER 2013, AND
REFERENCED IC TECH SPEC FOR ICD/ICS 705 TECHNICAL SPECIFICATIONS
FOR CONSTRUCTION AND MANAGEMENT OF SENSITIVE COMPARTMENTED
INFORMATION FACILITIES, VERSION 1.2, DATED 23 APRIL 2012.
2. CONSTRUCTION, GENERAL: UFC 4-010-05 REQUIREMENTS HAVE BEEN
INCORPORATED INTO THE DESIGN DRAWINGS AND SPECIFICATIONS.
CHANGES TO THE SCOPE OF WORK PROVIDED IN THE CONTRACT
DOCUMENTS MAY INVALIDATE THE APPROVALS RECEIVED FOR THIS
CONSTRUCTION, AND COULD RESULT IN THE REMOVAL AND
RECONSTRUCTION OF FINISHED WORK. ANY PROPOSED DEVIATIONS FROM
THE CONTRACT DOCUMENTS MUST BE FULLY REVIEWED AND APPROVED BY
THE COR PRIOR TO IMPLEMENTATION.
3. ALL CONSTRUCTION MUST BE DONE IN SUCH A MANNER AS TO PROVIDE
VISUAL EVIDENCE OF UNAUTHORIZED PENETRATION. CONSTRUCTION MUST
BE COMPLETED IN A MANNER TO PROVIDE THE REQUIRED STC RATINGS FOR
SOUND CONTROL AT THE WALLS IDENTIFIED. THROUGH-WALL
PENETRATIONS OF PIPE, CONDUIT, AND DUCTWORK REQUIRE SPECIAL
CONSTRUCTION AND INSPECTION PROVISIONS WHICH HAVE BEEN
INCORPORATED INTO THE CONTRACT DOCUMENTS.
4. THE CONTRACTOR SHALL SUBMIT A LIST OF ALL MATERIALS USED IN THE
CONSTRUCTION OF THE VAULT AREA, INCLUDING DIMENSIONAL EXTENTS OF
THE USE AND LOCATION(S) WHERE USED IN THE VAULT. THIS LIST SHALL BE
KEPT UP TO DATE DURING THE COURSE OF CONSTRUCTION AND SUBMITTED
TO THE COR AS PART OF THE CLOSE-OUT REQUIREMENTS AT THE END OF
CONSTRUCTION.
5. PHOTOGRAPHY REQUIREMENTS: THE CONTRACTOR IS NOT ALLOWED TO
HAVE PHOTOGRAPHIC OR RECORDING DEVICES IN THE VAULT AREA. 115 FW
CCZ PERSONNEL WILL BE TAKING PICTURES OF ON-GOING CONSTRUCTION
IN ORDER TO DOCUMENT THAT ALL SECURITY MEASURES ARE BEING MET.
THE COR SHALL BE NOTIFIED AT LEAST ONE WORKING DAY PRIOR TO KEY
CONSTRUCTION MILESTONES. KEY CONSTRUCTION MILESTONES INCLUDE
BUT ARE NOT LIMITED TO: WALL CONSTRUCTION, INCLUDING EACH OF
MULTIPLE LAYERS OF GYPSUM BOARD, FINISHING OF PENETRATIONS,
NON-CONDUCTIVE BREAKS OF PENETRATIONS, AND SOUND BATT
INSULATION INSTALLATIONS.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-P
-C e n tr a l-jo n .t ie d e m e a d h u n t.
c o m
.r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
F-001
FIRE PROTECTION &
FIRE ALARM NOTES,
SYMBOLS, ABBREV.,
SCHEDULES &
DETAILS
XGFG132020ANG NO.:
3141300-141489.01
JET/MRF
RMM/ARG
May 4, 2017
MFP/MRF
NO SCALE1
WET PIPE SPRINKLER RISER SCHEMATIC
NO SCALE3
ASSE-1013 & ASSE-1015
NO SCALE2
WATER SERVICE ENTRANCE
12. GENERAL NOTES APPLY UNLESS NOTED OTHERWISE
11. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS. CONTRCTOR SHALL VERIFY ALL CONDITIONS
AND DIMENSIONS AT THE PROJECT SITE PRIOR TO THE START OF CONSTRUCTION. WHERE
SPECIFIC DEMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMIND, CONSULT COR
BEFORE PROCEEDING WITH THE WORK.
10. NOMINAL FINISHED FLOOR ELEVATION = 100.0 FT. UNLESS OTHERWISE NOTED
9. SEQUENCE OF WORK AND/OR PLACE OF COMMENCEMENT OF WORK SHALL BE
APPROVED PRIOR TO WORK BEING STARTED.
8. VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH COR PRIOR TO INSTALLATION.
7. TEMPORARILY PATCH ALL ROOF OPENINGS WATERTIGHT UNTIL FINAL CLOSURE CAN BE MADE.
6. ALL EXISTING ROOFING SYSTEMS SHALL BE PROTECTED FROM DAMAGE DURING CONSTRUCTION
ACTIVITIES.
5. ACCURATE AND LEGIBLE RECORD (AS-BUILT) DRAWINGS SHALL BE MAINTAINED AT THE JOB SITE, AND BE SUBMITTED PRIOR TO FINAL PAYMENT.
4. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH RESPECT TO
EXISTING STRUCTURES, UTILITIES, AND MECHANICAL SYSTEMS, IS AS EXACT AS
COULD BE SECURED. THE INFORMATION IS NOT WARRANTED NOR GUARANTEED
ACCURATE, FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO PROCEEDING WITH WORK.
3. ELEVATION OF PIPING INDICATED ON THESE DRAWINGS ARE TO BE USED AS GUIDELINES TO
ASSIST WITH INSTALLATIONS. MINOR CHANGES TO THESE ELEVATIONS MAY BE NECESSARY TO
ELIMINATE UNFORESEEN INTERFERENCES. ANY CHANGE IN ELEVATION SHALL BE APPROVED...
2. THESE DRAWINGS ARE DESIGN DRAWINGS AND ARE DIAGRAMMATIC, THEY MAY NOT
SHOW ALL PHYSICAL ARRANGEMENTS, OFFSETS, BENDS, OR ELBOWS WHICH MAY
BE REQUIRED FOR PROPER INSTALLATION OF VARIOUS MATERIALS, EQUIPMENT, AND PIPING
SYSTEMS IN ALLOTTED SPACES. EXAMINE THESE AND OTHER AVAILABLE DRAWINGS TO DETERMINE
SPACE LIMITATIONS AND INTERFERENCES. MAKE ANY MINOR CHANGES IN LOCATIONS OF
EQUIPMENT, AND PIPING FROM THAT SHOWN ON DRAWINGS AND FOR ALL PHYSICAL DETAILS
REQUIRED FOR INSTALLATION. COST FOR ADAPTING WORK TO JOB SITE CONDITIONS SHALL NOT BE
CONSIDERED AS BASIS OF AN EXTRA COST TO CONTRACT.
1. ABBREVIATIONS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY
TO THIS PROJECT. ADDITIONAL ABBREVIATIONS MAY BE INDICATED IN THE CONTRACT
DOCUMENTS.
GENERAL FIRE PROTECTION NOTES:
INSTALL EXTENDED SLEEVES AT ALL WALL PENETRATIONS.
PROVIDE SPLASH BLOCKS FOR DRAINS.
PAINT EXPOSED PIPE. SHOW FLOW DIREDTION AND PIPE IDENTIFICATION.
PROVIDE IDENTIFICATION TAGS ON SPECIFIC COMPONENTS. SEE SPECIFICATIONS.
VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH COR PRIOR TO INSTALLATION.
PROVIDE SUPERVISORY SWITCHES ON ALL ISOLATION VALVES INSTALLED IN CIRCUITS TO ANY
SPRINKLERS.
PROVIDE VALVED OUTLETS TO DRAIN ALL PIPING. ESTEND DRAIN PIPING TO EXTERIOR.
USE VALUES SHOWN IN TABLE 9-4 UFC 3-600-01 (DOD) IN-LIEU OF EQUIVELENT TABLE IN NFPA 13.
USE AREA / DENSITY METHOD TO DETERMINE WATER DEMAND REQUIREMENTS
2. ANG AND UFC SPECIFIC DESIGN REQUIREMENTS INCLUDE BUT NOT LIMITED TO THE FOLLOWING
A. ANG ETL 15-01-04.
B. UFC 3-600-01 (8 AUGUST 2016)
C. NFPA 13 (LATEST PREVAILING EDITION)
D. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) STANDARDS
1. PROVIDE A HYDRAULICALLY DESIGNED WET PIPE SPRINKLER SYSTEM FOR HAZARD
CLASSIFICATION SHOWN. SYSTEM SHALL BE IN CONFORMANCE WITH THE FOLLOWING CODES
AND STANDARDS:
FIRE PROTECTION NOTES:
FLOW GPM: 1500 GPM
RESIDUAL PRESSURE: 82 PSI
STATC PRESSURE: 90 PSI
HYD. OUTLET ELEV.: 20" OFF FINISHED GRADE
TEST HYDRANTS PRESSURE @ HYD. # 10, FLOW @ HYD. #2, 8" WATER MAIN.
LOCATION: TRUAX FIELD ANGB MADISON AT BUILDING 404
DATE OF TEST: AUG. 23, 2016 @ 11:15 AM
FIRE PROTECTION DESIGN / INSTALLATION CONTRACTOR SHALL CONDUCT SEPARATE WATER
FLOW TEST AND USE RESULTS IN HYDRAULIC CALCULATIONS.
NOTE: INFORMATION SHOW FOR BID ONLY, NOT FOR DESIGN.
WATER SUPPLY FLOW BASES FOR BID:
EXTRA (H-3) 500 (1900) 500 (1900) 90
ORDINARY (H-2) 250 (950) 500 (1900) 60
LIGHT (H-1) 250 (950) 500 (1900) 60
CEILING HEIGHT 60 FT.
OR LESS (18.3m)
CEILING HEIGHT
GREATER THAN 60 FT.
(18.3m)
HAZARD
CLASIFICATION
HOSE DEMAND, gpm (lpm)
DURATION, MIN
Table 9-4 Hose Stream Demand and Duration
K-factor 11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
25.2 (360)
N/A
EXTRA
(H-3)
DESIGN
.3/2500 (12/230)
.3/3500 (12/330)
.3/3600 (12/340)
.3/4600 (12/430)
.5/3000 (20/280)
.5/4000 (20/370)
12.0 @ 7 psi
N/A
K-factor 8.0
(115) 8.0
(115) 11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
25.2 (360)
N/A
ORDINARY
(H-2)
DESIGN
.2/2500 (8/230)
.2/3500 (8/330)
.2/2500 (8/230)
.2/3500 (8/330)
.2/2500 (8/230)
.2/3500 (8/330)
12.0 @ 7 psi
N/A
K-factor 5.6 (80)
5.6 (80)
11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
25.2 (360)
N/A
LIGHT
(H-1)
DESIGN
.1/1500 (4/140)
.1/1500 (4/140)
.2/2500 (8/230)
.2/3500 (8/330)
.2/2500 (8/230)
.2/3500 (8/330)
12.0 @ 7 psi
N/A
WET DRY WET DRY WET DRY WET DRY
HAZARD
CLASIFICATION
CEILING HEIGHT
UP TO 30 FT.
(9.1m)
CEILING HEIGHT
UP TO >30-45FT.
(9.1-13.7m)
CEILING HEIGHT
UP TO 45-60 FT.
(13.7-18.3m)
CEILING
HEIGHT UP TO
60-100 FT.
(18.3m-30.5)
(gpm/ft²)/ft² (mm/min)/m² [minimum K factor]
Table 9-3 Sprinkler Design Demand and Minimum K-Factor
05/04/17 TYPE B3
NO SCALE4
FIRE ALARM & MASS NOTIFICATION RISER DIAGRAM
FS
NF
NF
8"
NF
6"
6"
6"
1/2" 8"
NF
Chimney Pier
FIRE HYDRANT
(PRESSURE READING)
FIRE HYDRANT
(FLOW TEST)
456'-0"
4" FP-W
F P
-W
F P
-W
4" FP-W
PM/PSM
SECURE
VAULT
BREAK
ROOM
VEST
MECH
VEST-1
141-1
VEST
CONFERENCE
STAN
EVAL
Space
HALLWAY
Space
JAN
WOMEN'S
TOILET/
LOCKER
ROOM
STORAGE
AIRCREW
FLIGHT
GROUP
STORAGE
COMM
ELEC
KITCHEN/
VENDING
STOR
BRIEFING/DD
CLASSROOM
SCIF
COPY
ROOM
ARMS
NCOIC
FIRE
ALARM
STORAGE
LIBRARY
BRIEFING
ROOM
INTELLIGENCE
OPEN
OFFICE
INTEL
NCO
INTEL
SUPERVISOR
BRIEFING
ROOM
WEAPONS
HALLWAY
BREAK
ROOM
VEST
AFMT
NCOIC
DO
HALLWAY
OG CHIEF
MISSSION
PLANNING
Space
NVG
AFE
SUPERINTENDENT
AFE
INSPECTION
ROOM
AIRCREW
FLIGHT
GROUP
VEST-2
141-2
LARGE
BRIEFING
STORAGE
Space
Space
FS CC
OG CC
CCA
OSS CC
FLIGHT
COMMANDER
WORK
ROOM
SECURED
VEST
ISSO &
SSR
HALLWAY
MAINT
DEBRIEF
AFE
NCOIC
SIMULATOR
SUPPORT
OFFICE
OPEN
OFFICE
TRAIN
OSF
SCHEDULING
SOF AREA
MEN'S
TOILET/
LOCKER
ROOM
HALLWAY
COMM/
COMPUTER
STORAGE
BREIFING
ROOM
BRIEFING
ROOM
ACMI/CLASSIFIED
WORK
ROOM
AFMT
OPEN
OFFICE
LOBBY
FDC
FORWARD FLOW TEST CONNECTION
MAIN DRAIN AND TEST
F P
-W
F
P -W
4" FP-W
4" FP-W
SCIF BOUNDARY
SCIF BOUNDARY 5.1015.101
5.102
SCIF BOUNDARY
4" FP-W
FIRE ENTRANCE
FIRE RISER
(SEE CIVIL FOR CONTINUATION)
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:5
A
M C
R e v it L o c a l\
-1
.0
-P
-C e n tr a l-jo n .t ie d e m e a d h u n t.
c o m
.r v t
W
IS
C O
N S
IN
A
IR
N
A T
IO
N
A L G
U A
R D
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
A D
A L B
F-101
FIRE PROTECTION -
FIRST FLOOR PLAN
XGFG132020ANG NO.:
3141300-141489.01
JET
RMM
May 4, 2017
MFP
05/04/17 TYPE B3
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1
FIRST FLOOR FIRE PROTECTION PLUMBING PLAN
12" = 1'-0"2
SITE PLAN TEST HYDRANT LOCATIONS
KEYED NOTES
5.101 THERE SHALL BE NO PENETRATIONS THRU PERIMETER OF SCIF BOUNDARY
OTHER THAN SHOWN ON DRAWINGS. (ALL PIPING PENETRATIONS THRU
PERIMETER SCIF-AREA WALLS SHALL BE GROUNDED.)
5.102 METALLIC SPRINKLER (FIRE SUPPRESSION) PIPE: PROVIDE A UL LISTED
DIELECTRIC UNION INSIDE THE SCIF PERIMETER ADJACENT TO THE
PENETRATION, OR GROUND THE CONDUIT WITHIN 6" OF THE PERIMETER
PENETRATION USING A NO. 4 WIRE (0.2043-DIAMETER COPPER WIRE) TO
THE BUILDING GROUND.
H
H
H
H
H
H
H
HH
FA
C
P
H
H
H
H H H
H
HH
H
H
H
H
H
H
H
H
H
H
H H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H H
H
H
H
H
H
H
H
H
H
H
H
HH
H
H
H
H
H
H
H
H
JJ
J
J
J J
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
L
L
M
M
N
N
P
P
Q
Q
R
R
S
S
T
T
24 24
23 23
22 22
21 21
20 20
19 19
18 18
17 17
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9 9
8 8
6 6
5 5
4 4
3 3
2 2
1 1
FIRE ALARM DEMOLITION
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
THE INFORMATION SHOWN IS BASED ON EXISTING DRAWINGS AND SITE
OBSERVATIONS TO ASSIST CONTRACTOR IN BIDDING. THE FIRE ALARM
DRAWINGS INDICATE EXISTING ELECTRICAL ITEMS TO BE REMOVED. THE
DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED
AND DO NOT INDICATE EVERY BOX, CONDUIT, OR WIRE THAT MUST BE
REMOVED. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING
A BID AND VERIFY EXISTING CONDITIONS. REFER TO SPECIFICATION
SECTION 26 05 02 FOR ADDITIONAL REQUIREMENTS.
DASHED WALLS ON THE FLOOR PLANS INDICATE EXISTING WALLS BEING
DEMOLISHED. DO NOT RELY ON ELECTRICAL DRAWINGS TO DETERMINE
EXTENT OF GENERAL CONSTRUCTION DEMOLITION. REFER TO THE
ARCHITECTURAL DEMOLITION PLANS FOR THE EXACT EXTENT OF WORK
REQUIRED BY THIS PROJECT. REMOVE ALL DEVICES ON DASHED WALLS
NOT SHOWN ON THE CONTRACT DRAWINGS. REFER TO DEMOLITION
DRAWINGS OF OTHER TRADES.
FIRE ALARM ITEMS REMOVED AND NOT RELOCATED REMAIN THE PROPERTY
OF THE OWNER AND SHALL BE TURNED OVER TO THE OWNER, IN A
STORAGE AREA TO BE DESIGNATED BY THE OWNER. EQUIPMENT BEING
REMOVED SHALL BE HANDLED SO AS NOT TO FURTHER REDUCE ITS VALUE
TO THE OWNER. THE CONTRACTOR SHALL DISPOSE OF MATERIAL THE
OWNER DOES NOT WANT TO REUSE OR RETAIN FOR MAINTENANCE
PURPOSES.
ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE BEING REMOVED.
WHERE CONDUIT IS IN THE CONCRETE SLAB, CUT OFF FLUSH, PULL OUT
WIRE, AND PLUG. WHERE CONDUIT IS RUN EXPOSED, ALL ASSOCIATED
CLAMPS, SUPPORTS, HANGERS, ETC., SHALL ALSO BE REMOVED. CONDUIT
CONCEALED IN WALL CONSTRUCTION MAY BE ABANDONED IN PLACE IF NOT
AFFECTED BY OTHER CONSTRUCTION.
THIS CONTRACTOR SHALL COORDINATE ALL HIS WORK, INCLUDING
PHASING WITH OTHER CONTRACTORS AT THE JOB SITE BEFORE REMOVING
EXISTING ELECTRICAL AND INSTALLING NEW ITEMS.
EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED IN PLACE.
RELOCATED EXISTING CONDUIT SHALL NOT BE ALLOWED. BONDING
CONDUCTORS SHALL BE INSTALLED IN ALL REUSED CONDUIT TO ASSURE
PROPER GROUND PATH.
CONTRACTOR SHALL REMOVE AND INSTALL ALL CEILING TILES AS
REQUIRED FOR THE EXECUTION OF ELECTRICAL WORK THAT IS OUTSIDE
THE CONTRACT LIMITS OF CONSTRUCTION. CONTRACTOR SHALL REPLACE
CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS
CONTRACTOR.
REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING ABANDONED
CONDUIT ABOVE ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH
WITH WALLS AND FLOORS, PATCH SURFACES TO MATCH EXISTING. REMOVE
ALL ASSOCIATED CLAMPS, HANGERS, SUPPORTS, ETC. ASSOCIATED WITH
RACEWAY REMOVAL.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
5/ 2/
1:
:0
AM
C :\R ev it
Lo ca l\3
-1
9.
-E
-C en tra l-2
7_ m rf.
rv t
W
IS
C O
N
SI
N A
IR
N
AT
IO
N
AL
G U
AR
D
TR
U
AX
F
IE
LD
A N
G B
M
AD
IS
O
N , W
I
AD
AL
B
FD201
FIRST FLOOR
DEMOLITION PLAN -
FIRE ALARM
XGFG132020ANG NO.:
3141300-141489.01
MRF
ARG
May 4, 2017
JRH/MRF
KEYED NOTES
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1 FIRST FLOOR DEMOLITION PLAN - FIRE ALARM
05/04/17 TYPE B3
S SS
S S
S S S
S S S
S
S
S
S
S
S
S S
S S
S S
S S
S
S
S S
S
S
S S
S
S S
S
S
S
S
S
S S
S
S
SS
S
S
S
S
S
S
S
S
S S S S
SSS
S
S
S
S
SS
S
S
S
S
S
S
S
S
S
S
S
S
S
S S
S
S S
S
S S S
S
S
SS
S S
VV
V V
V
S S
S S
V
S
S
S
S S
S
S
S
S
S
S
TSTSFS
S
FS
M M
C M
LOC
LO
C
LOC
LOC
LO
C
LOC
LO
C
FMCP
FM
C
P
FIRE ALARM GENERAL NOTES:
1.
2.
REFER TO TO SHEET F-001 FOR FIRE ALARM AND MASS NOTIFICATION
RISER DIAGRAM.
NEW DEVICES BEING INSTALLED ON EXISTING GYPBOARD WALL SHALL BE
CUT INTO EXISTING WALL AND BE FLUSH MOUNTED.
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
L
L
M
M
N
N
P
P
Q
Q
R
R
S
S
T
T
24 24
23 23
22 22
21 21
20 20
19 19
18 18
17 17
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9 9
8 8
6 6
5 5
4 4
3 3
2 2
1 1
INTEL VAULT
CLASSROOM111
INTEL
INTEL OIC
INTEL NCOIC
BRIEFING
ROOM 3
BRIEFING
ROOM 1
HALLWAY
BRIEFING
ROOM 2
BRIEFING
ROOM 4
LIBRARY
STORAGE
BREAK ROOM
MISSION
PLANNING
WEAPONS
ACMI
ISSO & SSR
COMM/
COMPUTER
STORAGE
LOBBY
VEST
MX DEBRIEF
SECURED
VEST
FLIGHT
COMMANDERS
OPEN OFFICE
PM/PSM
SECURE
VAULT
CORR
SIMULATOR
ELEC
FIRE ALARM
SIMULATOR
SUPPORT
OFFICE
ARMS NCOIC
VEST
ARMS
COPY ROOM
SOF 141
VEST
AFMT NCOIC
STORAGE
TRAINING
OFFICER
SCHEDULING
HALLWAY
AIRFIELD
MANAGEMENT
DIRECTOR OF
OPERATIONS
FIGHTER
SQUADRON
COMMANDER
OPERATIONS
GROUP
COMMANDER
VEST149
HALLWAY
HALLWAY
CONFERENCE
ROOM
STAN EVAL
OPERATIONS
CHIEF 151
CCA
OSS
COMMANDER
MEN'S
TOILET/
LOCKER
ROOM
AFE NCOIC
AIRCREW
FLIGHT
EQUIPMENT
AFE
SUPERINTENDENT,
FEO
NVG
AFE
INSPECTION
ROOM
STORAGE163
JANITOR
WOMEN'S
TOILET/
LOCKER
ROOM
HALLWAY
VEST
KITCHEN/
VENDING
BREAK ROOM
MAIN
BRIEFING
ROOM
MECH
AFE
STORAGE
ELEC
COMM
F-201
F-201
15 15
15 15
15 15 15
151515
WP
WP
WP
WP
WP
WP
WP
9.401
9.401
9.401
9.401
9.401
9.401
9.401
9.402
9.404
9.403
9.402
9.4039.403
9.4039.403
9.403
DS DS
DS
DS
DS
WP
9.407
DS
DS
DS
DS DS
166C
STORAGE
166B
STORAGE
166A
STORAGE
WOMENS
ENTRY
TO RTS/I LOCATED
IN FIRE ALARM 126
TO RTS/I LOCATED
IN FIRE ALARM 126
R
TS
/I
(3)
TO RTS/I LOCATED
IN JAN 163
TO RTS/I LOCATED
IN FIRE ALARM 126
CONTROL MODULE SHALL BE
INTERFACED INTO BUILDING
PAGING SYSTEM SO THAT
PAGING SYSTEM IS SILENCED
UPON FIRE ALARM INITIATION.
T
T
16 16
ELEC
MONACO
INTERFACE
PANEL
19 19 18 18
FIRE ALARM
RTS/I(7)
1/2" MINIMUM
SEPARATION BETWEEN
STEEL CONDUIT
CLASS 1 TYPE A
DIELECTRIC LINK
THREADED COUPLING
(SCH. 80 PVC)
SECURE AREA INTERIOR WALL
SEAL WITH ACOUSTICAL FIRE PROOF
SEALANT ALL THE WAY AROUND
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
5/ 3/
:3
7:
P M
C :\R ev it
Lo ca l\3
-1
9.
-E
-C en tra l-2
7_ m rf.
rv t
W
IS
C O
N
SI
N A
IR
N
AT
IO
N
AL
G U
AR
D
TR
U
AX
F
IE
LD
A N
G B
M
AD
IS
O
N , W
I
AD
AL
B
F-201
FIRST FLOOR PLAN -
FIRE ALARM
XGFG132020ANG NO.:
3141300-141489.01
MRF
ARG
May 4, 2017
JRH/MRF
KEYED NOTES
9.401 CONDUIT ASSOCIATED WITH EXTERIOR MOUNTED FIRE ALARM
NOTIFICATION DEVICE SHALL BE ROUTED INTERIOR TO THE BUILDING IN
FURRED CAVITY. CORE DRILL EXTERIOR WALL FOR CONDUIT INSTALLATION.
PROVIDE SURFACE MOUNTED EXTERIOR WEATHERPROOF BACKBOX.
9.402 SECURE AREA PERIMETER. COORDINATE WITH GENERAL CONTRACTOR.
MINIMIZE, CO-LOCATE, AND SEAL ALL SECURE AREA PENETRATIONS. SEE
DETAIL 1/E-501. CAULK AND SEAL ALL CONDUIT PENETRATIONS IN A
MANNER THAT MAINTAINS ROOM'S SOUND TRANSMISSION CALSS (STC)
RATING OF 55. ALL DEVICES/CONDUIT LOCATED ON THIS PERIMETER WALL
SHALL BE SURFACE MOUNTED.
9.403 DOTTED LINE INDICATES BOUNDARY OF SOUND ASSEMBLY GROUP 4 -
MINIMUM STC 55. CAULK AND SEAL ALL CONDUITS IN A MANNER THAT
MAINTAINS ROOM'S SOUND TRANSMISSION CLASS (STC) RATING OF 50.
9.404 FIRE ALARM WIRELESS ANTENNA SHALL BE SURFACE MOUNTED TO
EXTERIOR FACADE ABOVE ROOF.
9.407 SECURE AREA PERIMETER. COORDINATE WITH GENERAL CONTRACTOR.
MINIMIZE, CO-LOCATE, AND SEAL ALL SECURE AREA PENETRATIONS. SEE
DETAIL 4/F-201.
PLAN
NORTH
TRUE
NORTH
1/8" = 1'-0"1 FIRST FLOOR PLAN - FIRE ALARM
PLAN
NORTH
TRUE
NORTH
1/4" = 1'-0"2 ENLARGED FIRE ALARM PLAN - ELEC 170
PLAN
NORTH
TRUE
NORTH
1/4" = 1'-0"3 ENLARGED FIRE ALARM PLAN - FIRE ALARM 126
NO SCALE4 SECURE AREA PENETRATION DETAIL
05/04/17 TYPE B3
| Sheets |
| F-001 - FIRE PROTECTION & FIRE ALARM NOTES, SYMBOLS, ABBREV., SCHEDULES & DETAILS |
| F-101 - FIRE PROTECTION - FIRST FLOOR PLAN |