06_Plumbing.pdf

PDF 4 MB Posted

Attached to
XGFG132020 Add/Alter Building 404 Truax ANGB Madison WI
Solicitation number
W912J2-18-R-1001
Issued by

About this file

06 Plumbing

View the file

Other files

File Type Posted
281300.pdf PDF
095113.pdf PDF
062023.pdf PDF
A07-404_Q&A_IV_03_Feb_2018.pdf PDF
A07-W912J2-18-R-1001-0004_Amendment_ADAL_B404_03_Feb_18.pdf PDF
283176.pdf PDF
312000.pdf PDF
061053.pdf PDF
093000.pdf PDF
237450.pdf PDF
A07-404_Q&A_III_02_Feb_2018.pdf PDF
W912J2-18-R-1001-0003.pdf PDF
237433.pdf PDF
A07-404_Q&A_II_24_Jan_2018.docx DOCX document
A07-EXHIBIT_C_Reference_Questionnaire_Package_18Jan18_NEW.docx DOCX document
A07-W912J2-18-R-1001-0002_Amendment_ADAL_B404_18_Dec_18.pdf PDF
A07-404_Q&A_I_18_Jan_2018.docx DOCX document
A07-W912J2-17-R-1001-1001_Conform_Copy_18_Jan_18.pdf PDF
EXHIBIT_A-Performance_Relevancy_Questionnaire_18_Jan_2018.doc DOC document
A07-W912J2-18-R-1001-0001_Amendment_ADAL_B404_18_Dec_18.pdf PDF
A07-Pre_Proposal_Site_Visit_Sign_In_Sheet_404.pdf PDF
A07-Pre_Proposal_Slides_404.ppt PPT presentation
00_General.pdf PDF
02_Landscaping.pdf PDF
05_Fire_Protection.pdf PDF
07_Mechanical.pdf PDF
04_Architectural.pdf PDF
03_Structural.pdf PDF
01_Civil.pdf PDF
09_Technology.pdf PDF
08_Electrical.pdf PDF
A01-XGFG132020_Specifications_Vol_1.pdf PDF
EXHIBIT_C_-_Reference_Questionnaire_Package_NEW.docx DOCX document
A07-W912J2-18-R-1001_ADAL_B404_26_Dec_17.pdf PDF
A01-XGFG132020_Specifications_Vol_2.pdf PDF
EXHIBIT_B-Subcontractor_Information_and_Consent.doc DOC document
EXHIBIT_A-Performance_Relevancy_Questionnaire.doc DOC document
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PG

PA

PITCH

AV

MV

S

FS

LS

PS

TS

PIPING SYMBOLS

PIPE TURNED TOWARD

PIPE TURNED AWAY

PIPE TURNED AWAY

FLEXIBLE CONNECTOR

UNION

FLANGES

REDUCER (CONCENTRIC)

REDUCER (ECCENTRIC)

PIPE CAP

FLUID FLOW DIRECTION

PIPE GUIDE

PIPE ANCHOR

PIPE PITCH DIRECTION

NEW CONNECTION TO EXISTING

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW TO BE INSTALLED

AUTOMATIC CONTROL VALVE (2-WAY)

AUTOMATIC CONTROL VALVE (3-WAY)

BACKFLOW PREVENTION VALVE

THROTTLING VALVE

BALANCING VALVE

FLOW MEASUREMENT STATION

RELIEF VALVE

AIR VENT (AUTO)

AIR VENT (MANUAL)

VACUUM BREAKER

PRESSURE GAUGE

TEMPERATURE GAUGE

WATER HAMMER ARRESTOR

ISOLATION/SHUT-OFF/MANUAL VALVE

GLOBE VALVE

BUTTERFLY VALVE

GATE VALVE

GLOBE ANGLE VALVE

PLUG VALVE

PRESSURE REDUCING VALVE

PRESSURE REGULATING VALVE

SOLENOID VALVE ONE-WAY (ELECTRIC)

STRAINER

PIPE TURNED TOWARD

GAUGE CONNECTION

PIPE PLUG

BALL VALVE

FLOW SENSOR

LEVEL SENSOR

PRESSURE SENSOR

TEMPERATURE SENSOR

FILTER

CHECK VALVE

SANITARY DRAIN

VENT FOR SANITARY DRAIN

DOMESTIC SOFT HOT WATER RETURN

DOMESTIC MIXED WATER

PLUMBING PIPING:

DOMESTIC HOT WATER RETURN

DOMESTIC SOFT HOT WATER

DOMESTIC HOT WATER

DOMESTIC COLD WATER

DOMESTIC SOFT COLD WATER

CW

SCW

HW

SHW

HWR

SHWR

MW

SAN

V

STORM DRAINST

CONDENSATECD

NATURAL GASG

COMPRESSOR AIRA

SCIF GENERAL NOTES:

1. THE VAULT AREA IS CONSIDERED A SENSITIVE COMPARTMENTED

INFORMATION FACILITY. ALL NEW CONSTRUCTION AND RENOVATION TO THE

AREA INCLUDING WALL CONSTRUCTION, FIRE PROTECTION/DETECTION,

MECHANICAL/HVAC, ELECTRICAL, AND TECHNOLOGY SYSTEMS MUST

COMPLY WITH THE REQUIREMENTS PROVIDED IN UNIFIED FACILITY CRITERIA

4-010-05 SENSITIVE COMPARTMENTED INFORMATION FACILITY PLANNING,

DESIGN, AND CONSTRUCTION WITH CHANGE 1, 1 OCTOBER 2013, AND

REFERENCED IC TECH SPEC FOR ICD/ICS 705 TECHNICAL SPECIFICATIONS

FOR CONSTRUCTION AND MANAGEMENT OF SENSITIVE COMPARTMENTED

INFORMATION FACILITIES, VERSION 1.2, DATED 23 APRIL 2012.

2. CONSTRUCTION, GENERAL: UFC 4-010-05 REQUIREMENTS HAVE BEEN

INCORPORATED INTO THE DESIGN DRAWINGS AND SPECIFICATIONS.

CHANGES TO THE SCOPE OF WORK PROVIDED IN THE CONTRACT

DOCUMENTS MAY INVALIDATE THE APPROVALS RECEIVED FOR THIS

CONSTRUCTION, AND COULD RESULT IN THE REMOVAL AND

RECONSTRUCTION OF FINISHED WORK. ANY PROPOSED DEVIATIONS FROM

THE CONTRACT DOCUMENTS MUST BE FULLY REVIEWED AND APPROVED BY

THE COR PRIOR TO IMPLEMENTATION.

3. ALL CONSTRUCTION MUST BE DONE IN SUCH A MANNER AS TO PROVIDE

VISUAL EVIDENCE OF UNAUTHORIZED PENETRATION. CONSTRUCTION MUST

BE COMPLETED IN A MANNER TO PROVIDE THE REQUIRED STC RATINGS FOR

SOUND CONTROL AT THE WALLS IDENTIFIED. THROUGH-WALL

PENETRATIONS OF PIPE, CONDUIT, AND DUCTWORK REQUIRE SPECIAL

CONSTRUCTION AND INSPECTION PROVISIONS WHICH HAVE BEEN

INCORPORATED INTO THE CONTRACT DOCUMENTS.

4. THE CONTRACTOR SHALL SUBMIT A LIST OF ALL MATERIALS USED IN THE

CONSTRUCTION OF THE VAULT AREA, INCLUDING DIMENSIONAL EXTENTS OF

THE USE AND LOCATION(S) WHERE USED IN THE VAULT. THIS LIST SHALL BE

KEPT UP TO DATE DURING THE COURSE OF CONSTRUCTION AND SUBMITTED

TO THE COR AS PART OF THE CLOSE-OUT REQUIREMENTS AT THE END OF

CONSTRUCTION.

5. PHOTOGRAPHY REQUIREMENTS: THE CONTRACTOR IS NOT ALLOWED TO

HAVE PHOTOGRAPHIC OR RECORDING DEVICES IN THE VAULT AREA. 115 FW

CCZ PERSONNEL WILL BE TAKING PICTURES OF ON-GOING CONSTRUCTION

IN ORDER TO DOCUMENT THAT ALL SECURITY MEASURES ARE BEING MET.

THE COR SHALL BE NOTIFIED AT LEAST ONE WORKING DAY PRIOR TO KEY

CONSTRUCTION MILESTONES. KEY CONSTRUCTION MILESTONES INCLUDE

BUT ARE NOT LIMITED TO: WALL CONSTRUCTION, INCLUDING EACH OF

MULTIPLE LAYERS OF GYPSUM BOARD, FINISHING OF PENETRATIONS,

NON-CONDUCTIVE BREAKS OF PENETRATIONS, AND SOUND BATT

INSULATION INSTALLATIONS.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:2

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

P-001

PLUMBING NOTES &

SYMBOLS

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

8. PATCH EXISTING ROOFS, WALLS, AND FLOORS DISTURBED BY DEMOLITION. RESTORE TO MATCH CONDITION

OF ORIGINAL SURROUNDING SURFACES PER SATISFACTION OF COR.

7. WHERE PIPES PASS THROUGH FLOOR SLABS, SAW-CUT SLAB AND REMOVE CONCRETE TO MINIMUM EXTENT NECESSARY TO GAIN ACCESS TO BELOW SLAB. REMOVE PIPE DOWN TO HORIZONTAL PIPING BELOW FLOOR.

6. WHERE PIPES ARE ROUTED INSIDE CMU WALLS, PIPE MAY BE ABANDONED PIPE IN PLACE. REMOVE PIPE TO 1" INSIDE WALL ON BOTH ENDS OF PIPE. DETERMINE WHERE PIPE EMERGES FROM CMU WALL AND PIPE

BACK TO NEXT BRANCH THAT IS TO REMAIN.

5. ABANDON IN PLACE UNDERGROUND PIPES SHOWN ON PLANS AS PHANTOM.

4. WHERE PIPES ARE REMOVED AND NOT RE-CONNECTED, REMOVE PIPE BACK TO NEXT BRANCH THAT IS TO REMAIN. INSTALL CAPS OR PLUGS ON OPENINGS. INSULATE AND PAINT DISTURBED PIPE SAME AS SPECIFIED

FOR NEW WORK.

3. WHERE FIXTURES AND EQUIPMENT ARE REMOVED, ALSO REMOVE ALL ASSOCIATED ROUGH-IN PIPING.

2. WHERE PIPES ARE REMOVED, ALSO REMOVE ALL VALVES, INSULATION, HANGERS, SUPPORTS, AND OTHER

ASSOCIATED COMPONENTS.

1. PIPING AND EQUIPMENT TO BE DEMOLISHED IS SHOWN DRAWN ON PLANS WITH BOLD AND DASHED LINES.

PLUMBING SYSTEM GENERAL DEMOLITION NOTES:

(1) SEE GENERAL NOTES.

REMARKS:

SANITARY DRAIN 3" AND LARGER 1/8" PER FOOT, 2 1/2" AND SMALLER 1/4" PER FOOT.

SERVICE MINIMUM PITCH

DRAIN AND VENT PITCH

WITHOUT SUSPENDED CEILING ALL EXPOSED CLOSE TO CEILING

HORIZONTAL

WITH SUSPENDED CEILING ALL

CONCEALED ABOVE SUSPENDED

CEILING

MECHANICAL ALL EXPOSED CLOSE TO WALL

VERTICAL

ALL EXCEPT MECHANICAL ALL CONCEALED INSIDE WALL SPACE

ORIENTATION ROOMS SERVICE ROUTING

LOCATION

PIPE ROUTING SCHEDULE

F FAHRENHEIT NPSH NET POSITIVE SUCTION HEAD WC WATER CLOSET

EWC ELECTRIC WATER COOLER NOM NOMINAL W WATTS OR WIDTH

ETR EXISTING TO REMAIN NO NORMALLY OPEN VTR VENT THROUGH ROOF

ET EXPANSION TANK NIC NOT IN CONTRACT VLV VALVE

ESEW EMERGENCY SHOWER AND EYE/FACE WASH NHC NO-HUB COUPLING VFD VARIABLE FREQUENCY DRIVE

EQPT EQUIPMENT NH NO-HUB V VOLTS OR VENT

ELEC ELECTRIC NG NATURAL GAS UV ULTRAVIOLET

EL ELEVATION NFPA NATIONAL FIRE PROTECTION ASSOCIATION UR URINAL

EFF EFFICIENCY NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION UNO UNLESS NOTED OTHERWISE

EEW EMERGENCY EYE/FACE WASH NC NORMALLY CLOSED UGD UNDERGROUND

EA EXHAUST AIR NA NOT APPLICABLE UFC UNIFIED FACILITIES CRITERIA

E EXISTING MTL MATERIAL TYP TYPICAL

DWV DRAIN, WASTE, AND VENT MSS MANUFACTURERS STANDARDIZATION SOCIETY TH THREADED

DWG DRAWING MOCP MINIMUM OVER CURRENT PROTECTION TFB TO FLOOR BELOW

DNS DOWN SPOUT MMBH MILLION BTU PER HOUR TFA TO FLOOR ABOVE

DN DOWN MIN MINIMUM TEMP TEMPERATURE

DISCH DISCHARGE MFR MANUFACTURER TDS TOTAL DISSOLVED SOLIDS

DIM DIMENSION MCC MOTOR CONTROL CENTER TDH TOTAL DEVELOPED HEAD

DIA DIAMETER MCA MINIMUM CIRCUIT AMPACITY TD TRENCH DRAIN

DI DUCTILE IRON MC MECHANICAL COUPLING SW SOCKET WELD

DFD DEPARTMENT OF DEFENSE MBH THOUSAND BTU PER HOUR SV SOLVENT WELD

DEMO DEMOLISH MAX MAXIMUM STL STEEL

DEG DEGREE MAWP MAXIMUM ALLOWABLE WORKING PRESSURE STD STANDARD

DCVA DOUBLE CHECK VALVE ASSEMBLY BPD MADP MAXIMUM ALLOWABLE DIFFERENTIAL PRESSURE SS STAINLESS STEEL

DBA DECIBELS, BAND A LT LAUNDRY TUB SRV SAFETY RELIEF VALVE

CU COPPER OR CUBIC LPG LIQUIFIED PETROLEUM GAS SQ SQUARE

CTW CLOSE TO WALL LIN LINEAR SPEC SPECIFICATIONS

CTCLM CLOSE TO COLUMN LCO LINE CLEANOUT SP STATIC PRESSURE

CTCLG CLOSE TO CEILING LB POUNDS SMLS SEAMLESS

CS CARBON STEEL LAV LAVATORY SHT SHEET

CRA CONCRETE REACTION ANCHOR L LENGTH OR LAVATORY SHF SOCKET HEAT FUSION

CO CLEAN OUT IPC INTERNATIONAL PLUMBING CODE SH SHOWER

COR CONTRACTING OFFICER'S REPRESENTATIVE INWC INCHES WATER COLUMN PRESSURE SDR STANDARD DIMENSION RATIO

COMP COMPRESSOR INHG INCHES MERCURY PRESSURE SD SOLDER

CL CENTERLINE IN INCH SCO STACK CLEANOUT

CISPI CAST IRON SOIL PIPE INSTITUTE IE INVERT ELEVATION SCH SCHEDULE

CI CAST IRON ID INSIDE DIAMETER SA SUPPLY AIR

BZ BRONZE IBNLT INCLUDING BUT NOT LIMITED TO RPZ REDUCED PRESSURE ZONE BPD

BW BUTTWELD IAW IN ACCORDANCE WITH RPM REVOLUTIONS PER MINUTE

BTW BOOTWASH HZ HERTZ REF REFERENCE

BTU BRITISH THERMAL UNIT HX HEAT EXCHANGER RCP REINFORCED CONCRETE PIPE

BS BLACK (MILD) STEEL HP HORSEPOWER QTY QUANTITY

BRZ BRONZE HOA HAND-OFF-AUTO PVC POLYVINYL CHLORIDE

BRS BRASS HDB HYDROSTATIC DESIGN BASIS PSIG PSI GAGE

BR BRAZE HDB HUB DRAIN PSID PSI DIFFERENTIAL

BPD BACKFLOW PREVENTION DEVICE HC HOSE CONNECTION PSIA PSI ABSOLUTE

BO BID OPTION H HEIGHT PSI POUNDS PER SQUARE INCH

BLDG BUILDING GS GALVANIZED STEEL PREDV PRESSURE REDUCING VALVE

BHF BUTT HEAT FUSION GR GROOVED PPH POUND PER HOUR

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS GPM GALLONS PER MINUTE PP POLYPROPYLENE

ASSE AMERICAN SOCIETY OF SANITARY ENGINEERING GBS GASKETED BELL AND SPIGOT PL PLACES

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS GAL GAUGE PH PHASE

ASL ABOVE SEA LEVEL GAL GALLON PE POLYETHYLENE

ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS FTWC FEET WATER COLUMN PRESSURE PDI PLUMBING DEVELOPMENT INSTITUTE

APPROX APPROXIMATELY FT FEET PD PRESSURE DROP/DIFFERENTIAL

ANG AIR NATIONAL GUARD FS FLOOR SINK P PRESSURE

ALUM ALUMINIUM FPM FEET PER MINUTE PCN PLANT CONTROL NETWORK

AHJ AUTHORITY HAVING JURISDICTION FLOW FLOW OR FLOWRATE OFOI OWNER FURNISHED, OWNER INSTALLED

AGD ABOVEGROUND FLA FULL LOAD AMPS OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

AFF ABOVE FINISHED FLOOR FFTC FORWARD FLOW TEST CONNECTION OD OUTSIDE DIAMETER

ABI ALTERNATE BID ITEM FD FLOOR DRAIN OB OUTLET BOX

A AMPS FCO FLOOR CLEANOUT NPSHR NPSH REQUIRED

ABBREVIATIONS

13. GENERAL NOTES APPLY UNLESS NOTED OTHERWISE

12. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS. CONTRCTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE PROJECT SITE PRIOR T THE START OF CONSTRUCTION. WHERE SPECIFIC DEMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMIND, CONSULT COR BEFORE PROCEEDING WITH THE WORK.

11. ALL NEW PLASTIC PIPING WITH-IN AN AIR PLENUM CEILING EXCEPT AS REQUIRED BY IMC SECTIONS 602.2.1.1 THROUGH 602.2.1.7. MATERIALS WITH-IN PLENUMS SHALL BE NON-COMBUSTIBLE OR SHELL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAT 50 WHEN TESTED IN ACCORDANCE WITH ASTM 84 OR UL 723, COMBUSTIBLE MATERIALS BE FULLY ENCLOSED WITH-IN A CONTINUOUS NON-COMBUSTIBLE ENCLOSER WITH MATERIALS LISTED AND LABELED FOR SUCH APPLICATIONS.

10. NOMINAL FINISHED FLOOR ELEVATION = 100.0 FT

9. SEQUENCE OF WORK AND/OR PLACE OF COMMENCEMENT OF WORK SHALL BE

APPROVED PRIOR TO WORK BEING STARTED.

8. VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH COR PRIOR TO INSTALLATION.

7. TEMPORARILY PATCH ALL ROOF OPENINGS WATERTIGHT UNTIL FINAL CLOSURE CAN BE MADE.

6. ALL NEW AND EXISTING ROOFING SYSTEMS SHALL BE PROTECTED FROM DAMAGE DURING CONSTRUCTION

ACTIVITIES.

5. ACCURATE AND LEGIBLE RECORD (AS-BUILT) DRAWINGS SHALL BE MAINTAINED AT THE JOB SITE, AND BE

SUBMITTED PRIOR TO FINAL PAYMENT.

4. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH RESPECT TO

EXISTING STRUCTURES, UTILITIES, AND MECHANICAL SYSTEMS, IS AS EXACT AS

COULD BE SECURED. THE INFORMATION IS NOT WARRANTED NOR GUARANTEED

ACCURATE, FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO PROCEEDING WITH WORK.

3. ELEVATION OF PIPING INDICATED ON THESE DRAWINGS ARE TO BE USED AS GUIDELINES TO ASSIST WITH INSTALLATIONS. MINOR CHANGES TO THESE ELEVATIONS MAY BE NECESSARY TO ELIMINATE UNFORESEEN

INTERFERENCES. ANY CHANGE IN ELEVATION SHALL BE APPROVED PRIOR TO CHANGE.

2. THESE DRAWINGS ARE DESIGN DRAWINGS AND ARE DIAGRAMMATIC, THEY MAY NOT

SHOW ALL PHYSICAL ARRANGEMENTS, OFFSETS, BENDS, OR ELBOWS WHICH MAY

BE REQUIRED FOR PROPER INSTALLATION OF VARIOUS MATERIALS, EQUIPMENT, AND PIPING SYSTEMS IN ALLOTTED SPACES. EXAMINE THESE AND OTHER AVAILABLE DRAWINGS TO DETERMINE SPACE LIMITATIONS AND INTERFERENCES. MAKE ANY MINOR CHANGES IN LOCATIONS OF EQUIPMENT, AND PIPING FROM THAT SHOWN ON DRAWINGS AND FOR ALL PHYSICAL DETAILS REQUIRED FOR INSTALLATION. COST FOR ADAPTING WORK TO JOB SITE CONDITIONS SHALL NOT BE CONSIDERED AS BASIS OF AN EXTRA COST TO CONTRACT.

1. ABBREVIATIONS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY TO THIS

PROJECT. ADDITIONAL ABBREVIATIONS MAY BE INDICATED IN THE CONTRACT DOCUMENTS.

GENERAL NOTES:

5 NOT ALL INFORMATION SHOWN IS APPLICABLE TO THIS BID PACKAGE

4 SEE PIPE IDENTIFICATION SCHEDULE FOR PIPE SERVICE TYPE...

3 SEE REMARKS FOR ITEMS SHOWN IN PARENTHESIS

2 SCHEDULE APPLIES UNLESS NOTED OTHERWISE

1 SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS

GENERAL SCHEDULE NOTES

tank) to controlling fixture in feet 150.0 x 1.5.

F. 225.0 ft. Developed length from water meter ( building control valve or internal pressure have a pressure loss.

water heaters and backflow preventers. Conventional water heaters usually do not

E. 15.0 psi. Pressure loss due to water softeners, water treatment devices, instantaneous pressure tank) and controlling fixture in feet 8 ft.

D. 3.47 psi. Difference in elevation between water meter ( building control valve or internal

C. 25.0 psi. Pressure needed at controlling fixture.

at internal pressure tank). ( see item 9, above).

B. 59.13 psi. Available pressure after water meter ( at the building control valve or low pressure

A. 6.96 psi. Pressure available for uniform loss (psi / 100 ft. of pipe).

WHERE:

F

A = B - ( C + D + E ) x 100

Using the following formula, find the pressure available for uniform loss ( psi / 100' of pipe).

Information Needed for Water Distribution Sizing at the building control valve). This answer is entered in Line B, below.

pressure tank). This calculation is the available pressure after the water meter ( or due to meter (step 8) from the low main pressure ( or low pressure at external

9. 59.1 psi. Subtract the loss due to friction (step 6), loss due to elevation (step 7), and loss

8. 5.00 psi. Find pressure loss due to meter. (from manufacturer or AWWA).

building control valve). (difference in elevation) 2.0 x .434 psi/ft.

7. 0.87 psi. Find pressure loss due to elevation, main to meter (or external pressure tank to

6. 0.00 psi. Find pressure loss due to friction in 4.0 inch water service.

(or at building control valve). To obtain this pressure, you must:

You Must First Find the Available Pressure After the Water...

control valve).

5. 125.0 ft. Developed length from main to meter (or external pressure tank to building

4. 2.0 in. Size of water meter (if applicable).

control valve).

3. 2.0 ft. Difference in elevation from main to meter (or external pressure tank to building

96 psi static with pressure regulator to bring pressure down to 65 psi

2. 65.0 psi. Low pressure at main in street (or at external pressure tank).

1. 68.0 gpm. Demand of building in gallons per minute.

Information Needed for Water Sizing.

WATER CALCULATION WORKSHEET

(3) MATCH FIXTURE PIPE SIZE

(2) 2" MINIMUM UNDERGROUND

(1) SEE PLUMBING SCHEDULES GENERAL NOTES ON P-001

REMARKS:

VENT PIPE SIZE SHALL NEVER DIMINISH IN DIRECTION AWAY FROM DRAIN

CONNECTION.

DRAIN PIPE SIZE SHALL NEVER DIMINISH IN DOWNSTREAM DIRECTION.

SUPPLY PIPE SIZE SHALL NEVER DIMINISH IN UPSTREAM DIRECTION.

PIPE SIZE CHANGES

CW / HW 0.75" UNLESS OTHERWISE INDICATED

VTR 4" UNLESS OTHERWISE INDICATED

VENT 1.5"

SANITARY

DRAIN

1.5" (2)

STORM DRAIN 3"

SERVICE MINIMUM PIPE SIZE (INCHES)

MINIMUM PIPE SIZES FOR CIRCUITS

WH 0.75" N/A N/A N/A

HB 0.5" N/A N/A N/A

WC 1.5" N/A 4" 2"

UR 0.75" N/A 2" 1.5"

JC 0.75" 0.75" 3" 1.5"

SK 0.5" 0.5" 1.5" (2) 1.5"

L 0.5" 0.5" 1.5" (2) 1.5"

SH 0.5" 0.5" 2" 1.5"

4" FD/HD/TD N/A N/A 4" 2"

3" FD/HD/TD N/A N/A 3" 1.5"

2" FD/HD/TD N/A N/A 2" 1.5"

EWC 0.5" N/A 1.5" (2) 1.5"

PIPE SIZE (IN) PIPE SIZE (IN) PIPE SIZE (IN)

CW HW DRAINFIXTURE VENT

SUPPLY, DRAIN, AND VENT PIPE SIZES FOR SINGLE FIXTURES (INCHES)

PIPE SIZE SCHEDULE (1)

05/04/17 TYPE B3

(4) BLACK BACKGROUND, WHITE TEXT.

(3) GREEN BACKGROUND, WITH WHITE TEXT.

(2) IN ACCORDANCE WITH ASME A31.1-2007.

(1) SEE PLUMBING SCHEDULES GENERAL NOTES.

REMARKS:

ST STORM DRAIN ST (2)

V VENT FOR SANITARY DRAIN V (4)

SAN SANITARY DRAIN SAN (4)

NPCW NON-POTABLE COLD WATER NPCW (4)

HWR HOT DOMESTIC WATER RETURN HWR (3)

HW HOT DOMESTIC WATER HW (3)

CW COLD DOMESTIC WATER CW (3)

ABBREVIATION SERVICE (2) TEXT COLORS (2)

PIPE LEBEL

PIPE IDENTIFICATION TABLE

A

B

B

C

C

D

D

E

E

G

G

H

H

J

J

K

K

L

L

M

M

N

N

P

P

Q

Q

R

R

S

S

T

T

24 24

23 23

22 22 21 21

20 20

19 19 18 18

17 17

15 15

14 14

13 13

12 12

11 11

10 10 9 9

8 8

6 6

5 5

4 4

3 3

2 2

1 1

4"

4"

4" ST(E)

5" ST(E)

(82gpm)

S

T (E

(5 g p m

S

T (E

(6 g p m

3" ST(E)

3" ST(E)

S

T (E

6" ST(E)

4"

6"6"

S T

(E

(1 g p m

6" UP TO FCO

3" ST(E) (4gpm)

4"

4" UP TO FCO

3" UP TO WCO

3" UP TO SK

2" UP TO SK

4" ST(E)

(82gpm)

S A

N (E

3" SAN(E)

UP TO FCO

S A

N (E

5" ST(E)

5"

4" ST(E)

3" SAN(E)

2" SAN(E)

UP TO SK

3"

3" SAN(E)

3" SAN(E)

(3dfu's)

S A

N (E

) 4" SAN(E)

UP TO FCO

5" ST(E)

(32gpm)

S T

(E

(2 g p m

S T

(E

S T

(E

4"

S T

(E

(5 g p m

4"

4" ST(E)

UP TO FCO(E)

4" ST(E)

4"

3"

2"

"4"

4" 4

2" 2"

2"2" 4"

4" ST(E)

3"

4"

6" ST(E)

(140gpm)

4" SAN(E)

S A

N (E

4" SAN(E)

4" SAN(E)

(68dfu's)

4" ST(E)

UP TO FCO

5" ST

5"

4" UP TO WC's

4" UP TO WC

2"

4" UP TO SH

2"

4" SAN

2" UP TO SK

2"

2" 2"

1 1/2"

2"

2"

6.001

REMOVE AND

REROUTE

3"

PD100

5"

10" ST(E)

10"10"

6"6"

4" ST(E)4"

3"

6.003

6.004

4" ST(E)

6.005

6.005

4" SAN(E)

S A

N (E

2" V(E) 2" V(E)

V (E

4" SAN(E) 4" SAN(E)

S A

N (E

5" ST(E)

V -S

T (E

2" V-ST(E)

4" SAN(E)

UP TO FD

2"

2"

2"

2" V-ST(E)

4" SAN(E)

UP TO FD

4" SAN(E)

UP TO FD

4" SAN(E)

UP TO HD

4" SAN(E)

UP TO FCO

4" ST(E)

UP TO HD

S T

(E

4" ST(E)

UP TO FCO

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:3

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

PD100

UNDERGROUND -

DRAIN AND VENT

DEMOLITION PLAN

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"1

UNDERGOUND DRAIN AND VENT DEMOLITION PLUMBING PLAN

05/04/17 TYPE B3

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"2

ENLARGED - UNDERGROUND DRAIN AND VENT

DEMOLITION PLUMBING PLAN

KEYED NOTES

6.001 REMOVE AND REROUTE PORTION OF EXISTING STORM DRAIN TO

ACCOMMODATE NEW CONSTRUCTION FLOOR ELEVATIONS.

6.003 REMOVED FLOOR CLEANOUT AND ELBOW. EXISTING PIPE TO BE EXTENDED

IN NEW WORK.

6.004 REMOVE EXISTING STORM PIPE IN WALL DOWN TO UNDERGROUND STORM

PIPE. EXISTING UNDERGROUND STORM PIPE TO BE EXTENDED IN NEW

WORK.

6.005 RECONNECT EXISTING UNDERGROUND STORM IN NEW WORK.

B

B

C

C

D

D

E

E

G

G

H

H

J

J

K

K

L

L

M

M

N

N

P

P

Q

Q

R

R

S

S

T

T

24 24

23 23

22 22 21 21

20 20

19 19 18 18

17 17

15 15

14 14

13 13

12 12

11 11

10 10 9 9

8 8

6 6

5 5

4 4

3 3

2 2

1 1

WC WC WC

UR

URUR

4"FD

4"FD

4"FD

JC

2"

4"FCO-1(E)

4" ST(E)

UP TO RD(E)

WCO

4" ST(E)

4"

WCO

WC(E)

2"

LCO

S T

(E

4" ST(E)

UP TO RD(E) LCO

S T

(E

4"FCO-1(E)

LAV

1 1/2"

4" ST(E)

UP TO RD(E)

LCO

LCO

4" ST(E)

UP TO RD(E)

SK

LT

2"FD

4"FCO(E)

WCO

OB

3"FCO

1 1/2" V(E)

V

(E )2" V(E)

UP TO VTR(E)

5"

5"

LCO 5"

4" ST(E)

4"FCO(E)

4" ST(E)

UP TO RD(E)

4"

4"FCO

LCO

3" ST(E)

UP TO RD(E)

3" ST(E)

UP TO RD(E)

3" ST(E)

3" ST(E)

3"

4"

WCO

2"2"2"

4" HD(E)

4" HD(E)

4" ST(E)

UP TO RD(E)

4" ST(E)

4" LCO(E)

4"

4"FCO

4" WCO(E)

4" ST(E)

4" ST(E)

UP TO RD(E)

6"FCO(E)

2"

OB

1 1/2"

4" WCO(E)

SK

4" ST(E)

4" ST(E)

UP TO RD(E)

4" ST(E)

UP TO RD(E)

4" ST(E)

4" LCO(E)

2" V(E)

6"FCO

2" V(E)

V (E

3"FCO(E) 2"

2" HD(E)

SH

2"

3" ST(E)

UP TO RD

3" ST(E) (4gpm)

S T

(E

3" ST(E)

SK(E)

3" WCO(E)

3" UP TO WCO

1 1/2"

4" LCO(E)

4"

S T

(E

4" ST(E)

UP TO RD(E)

4" ST

UP TO HD

4"FD(E)

4"FCO(E)

DISCONNECT PORTION OF

EXISTING STORM DRAIN AND

REROUTE PER NEW CONSTRUTION.

2"

2" UP TO VTR

3" VTR

LAV

LAV

LAV

6.002 6.002

6.002

6.002

6.002

EWC

OB

4"

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:4

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

PD101

FIRST FLOOR -

DRAIN AND VENT

DEMOLITION PLAN

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"1

FIRST FLOOR DRAIN AND VENT DEMOLITION PLUMBING PLAN

05/04/17 TYPE B3

KEYED NOTES

6.002 DISCONNECT AND REMOVE EXISTING FIXTURES IN ROOM. INCLUDING ALL

ASSOCIATED PIPING TO BELOW GRADE AND ABOVE CEILING.

B

B

C

C

D

D

E

E

G

G

H

H

J

J

K

K

L

L

M

M

N

N

P

P

Q

Q

R

R

S

S

T

T

24 24

23 23

22 22 21 21

20 20

19 19 18 18

17 17

15 15

14 14

13 13

12 12

11 11

10 10 9 9

8 8

6 6

5 5

4 4

3 3

2 2

1 1

PD131

AIR

COMPRESSOR

WATER

SOFTENER

INSTANTANEOUS

GAS

WATER

HEATER

1 1/2" 2 1/2" 3/4"

1 1/2" 1 1/2"

BPD(E)

/4

3/4"

3/4"

/2

UR UR UR

LAV

WC

WC WC WC

SH

/4

/2

/2

/4

/2

BV

BV

/2

/4

/4

SK

1" 1" 1/2"

1 1/2" 3"

1"

LT

SK

3/4" 1 1/4"

3/4"

1/2" 1 1/4"

3/4"

1/2" 1"

1/2"

3/4" CW(E)

EWH

PD131

3/4" CW(E)

/4

C

W (E

3/4" CW(E)

WH

JC

SH

LAV

LAV

LAV

REMOVE COMPRESSED AIR PIPING

OB

1"1"

WASHING

MACHINE

6.052

6.052

6.052

6.052

6.052

6.052

6.052

3/4"

WH(E)

6.053 6.053

6.052

6.052

OB

EWH

WH(E)

6.053

WH(E)

6.053

6.052

6.052

6.052

SK

OB

6.052

First Floor

100' - 0"

RST

1"

1"

1"

Mechanical Rm Floor

97' - 0"

3/4" NPCW(E)

WM(E)

PRV(E)

3/4" NPCW(E)

PRV(E)

1" CW(E)

1"

1"

6.054

6.054 6.054

6.054

6.054

CW(E)

6.054

6.054

6.054

1" 1/2"

1"

1"

HB

R

R

S

S

T

T

13 13

12 12

11 11

PD131

AIR

COMPRESSOR

WATER

SOFTENER

INSTANTANEOUS

GAS

WATER

HEATER

/4

3/4" CW(E)

/4

C

W (E

1 1/2"

1 1/2"

/2

/2

BPD

1 1/2"

2 1/2"

3/4"

1"

6.051

REMOVE ALL

COMPRESSED AIR PIPING

CP-1

6.054

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:4

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

PD131

FIRST FLOOR -

SUPPLY PLUMBING

DEMOLITION PLAN

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"1

FIRST FLOOR SUPPLY DEMOLITION PLUMBING PLAN

1/4" = 1'-0"2

ENLARGED WATER ENTRANCE DEMOLITION PLUMBING SECTION

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"3

ABOVEGROUND DRAIN AND VENT

ENLARGED DEMOLITION PLUMBING PLAN

05/04/17 TYPE B3

KEYED NOTES

6.051 DISCONNECT AND REMOVE EXISTING BACKFLOW PREVENTION DEVICE.

RE-USE BACKFLOW PREVENTION DEVICE IN NEW CONSTRUCTION FOR NEW

BOILERS FEED WATER. SEE NEW WORK.

6.052 DISCONNECT AND REMOVE EXISTING FIXTURES IN THE ROOM, INCLUDING

ALL ASSOCIATED PIPING TO BELOW GRADE AND ABOVE CEILING.

6.053 WH(E) TO REMAIN, RECONNECT UNDER NEW CONSTRUCTION.

6.054 WATER SERVICE PIPING, VALVING AND METERING TO REMAIN, ALL OTHER

CW, HW, HWR, AND AIR PIPING TO BE REMOVED IN MECHANICAL ROOM.

B

B

C

C

D

D

E

E

G

G

H

H

J

J

K

K

L

L

M

M

N

N

P

P

Q

Q

R

R

S

S

T

T

24 24

23 23

22 22 21 21

20 20

19 19 18 18

17 17

15 15

14 14

13 13

12 12

11 11

10 10 9 9

8 8

6 6

5 5

4 4

3 3

2 2

1 1

4" SAN(E)

(92dfu's)

S A

N (E

5" ST(E)

(32gpm)

S

T (E

(6 g p m

3" ST(E)

4" ST(E)

5" ST(E)

(82gpm)

S

T (E

(5 g p m

S T

(E

(1 g p m

4" ST(E)

5" ST(E)

4" ST(E)

(82gpm)

3" ST(E) (4gpm)

4" ST(E)

S T

(E

(8 g p m

2" SAN(E)

UP TO SK

3" SAN(E) 3" SAN(E) 3" SAN(E)

S A

N (E

S A

N (E

3" SAN(E)

UP TO FCO

S A

N (E

S

A N

(E

4" SAN(E)

UP TO FCO

P-100

5" ST

3" SAN

UP TO FCO

2" SAN3

S A

N

2" SAN

UP TO SK

CAP

2" SAN

UP TO SK

3" S

A N

4" SAN(E)

CAP

S A

N

2" SAN

UP TO LAV

2" SAN

UP TO LAV

4" SAN

UP TO WC'S

4" SAN

S A

N

S

A N

3" SAN

UP TO FD

2" SAN

UP TO SH

2" V

2" SAN

UP TO FD

S T

(E

S T

(E

(2 g p m

2" SAN

UP TO FCO

2" SAN

UP TO HD

1 1/2" V

6" ST

UP TO FCO

5" ST

( 144gpm )

5" ST

UP TO FCO

5" ST

( 144gpm )

5" S

T

CAP

4" ST(E)

4" ST(E)

UP TO FCO(E)

4" ST(E)

S T

(E

(5 g p m

P-100

4" ST (46gpm)

4" ST

2" SAN

UP TO SK

2" SAN

UP TO LC

2" SAN

UP TO LT

3" SAN

UP TO FD

2" SAN

2" SA

N

4" ST

2" SAN

UP TO FCO

2" SAN

UP TO EWC

2" SAN

3" SAN

UP TO FCO

3" SAN

CAP

S A

N

4" SAN(E)

5" ST

UP TO FCO

P-100

4" ST

4" ST

UP TO FCO

4" ST

UP TO FCO

S

T 5" ST

UP TO FCO

3" SAN

UP TO HD

3" SAN

UP TO FCO

3" SAN

1 1/2" V

3" SAN

UP TO HD

3" SAN

3" SAN

6.107

3" ST (24gpm)

5" ST

8" ST 8" ST

8" ST (254gpm)

4" ST (23gpm)

6" ST(E)

(133gpm)

4" SAN

(39.5dfu's)

3" SAN(E)

(3dfu's)

3" SAN

UP TO FCO

4" SAN

(22dfu's)

2" SAN (4dfu's)

4" SAN

(68dfu's)

(82gpm)

(230gpm)

(46gpm)

(2 g p m

3" ST(E)

4" ST (49gpm)

1 1/2" V

4" ST

UP TO SCO4" ST

2" V

2" SAN

3" SAN3" SAN

2" SAN

4" SAN

UP TO WCO

6.106

6.109

6.106

6.109

6.106

6.109

R

R

S

S

T

T

14 14

13 13

12 12

11 11

3" SAN

UP TO FCO

3" SAN

UP TO FCO

3" SAN

3" SAN

4" SAN(E)

4" SAN(E)

2" V-ST(E)

V (E

2" V(E)

4" ST(E)

UP TO HD

2" V2" V

2" V-ST

V

V

V -S

T

S A

N

S

A N

5" ST(E)

4" SAN(E)

UP TO FD

4" SAN(E)

UP TO FD

4" SAN(E)

UP TO FCO

4" SAN(E)

UP TO HD

S A

N (E

4" SAN(E)

4" SAN(E)

UP TO FD

S T

(E

4" ST(E)

UP TO FCO

S T

(E

S A

N (E

6.1046.1046.104

4" ST (32gpm)

K

K

L

L

M

M

N

N

P

P

19 19

18 18

17 17

3" SAN

UP TO SH

4" ST (23gpm)

S T g p m

S T

5" ST (87gpm)

S T

(E

3" SAN

UP TO SH

S A

N

6" ST(E)

3" SAN

UP TO UR'S & LAV'S

4" SAN 3" SAN

S T

(E

S T

(E

S A

N

3" SAN

UP TO FCO

2" SAN

UP TO FD

1 1/2" V

2" SAN

UP TO FD

3" SAN

UP TO SH

3" SAN

UP TO FCO

S A

N

4" SAN

UP TO WC'S

4" SA

N

1 1/2" V

6" S T(E

(133gpm

1 1/2" V

3" SAN

4" ST(E)

S A

N

4" ST(E)

(52gpm)

4" ST

UP TO RD(E)

3" SAN

UP TO HD

1 1/2" V

1 1/2" V

3" SAN

P

P

1 1/2" V

3" SAN

3" SAN4" SAN

UP TO FCO

3" SAN

S

T (E

S A

N

3" SAN

UP TO JC

3" SAN

UP TO HD

3" SAN

UP TO FD

3" SAN

6.107

8" ST

8" S T

S

T

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:2

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

P-100

UNDERGROUND

DRAIN AND VENT

PLUMBING PLAN

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"1

UNDERGOUND DRAIN AND VENT PLUMBING PLAN

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"4

ENLARGED MECHANICAL ROOM UNDERGROUND

DRAIN AND VENT PLUMBING PLAN

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"2

ENLARGED UNDERGROUND

DRAIN AND VENT PLUMBING PLAN

05/04/17 TYPE B3

PLAN

NORTH

TRUE

NORTH

1/2" = 1'-0"3

ENLARGED JANITOR CLOSET

UNDERGROUND DRAIN AND VENT PLUMBING PLAN

KEYED NOTES

6.104 EXTEND EXISTING SANITARY AND STORM VENTING TO NEWLY

CONSTRUCTED WALL.

6.106 METAL PIPE: PROVIDE A DIELECTRIC UNION INSIDE THE SCIF PERIMETER

ADJACENT TO THE PENETRATION, OR GROUND THE CONDUIT WITHIN 6" OF

THE PERIMETER PENETRATION USING A NO. 4 WIRE (0.2043-DIAMETER

COPPER WIRE) TO THE BUILDING GROUND.

6.107 END OF CIRCUIT VENT.

6.109 THERE SHALL BE NO PENETRATIONS THRU PERIMETER OF SCIF BOUNDARY

OTHER THAN SHOWN ON DRAWINGS. (ALL PIPING PENETRATIONS THRU

PERIMETER SCIF-AREA WALLS SHALL BE GROUNDED.)

B

B

C

C

D

D

E

E

G

G

H

H

J

J

K

K

L

L

M

M

N

N

P

P

Q

Q

R

R

S

S

T

T

24 24

23 23

22 22 21 21

20 20

19 19 18 18

17 17

15 15

14 14

13 13

12 12

11 11

10 10 9 9

8 8

6 6

5 5

4 4

3 3

2 2

1 1

VEST

PM/PSM

SECURE

VAULT

MECH

VEST-1

141-1

VEST

CONFERENCE

STAN

EVAL

HALLWAY

JAN

WOMEN'S

TOILET/

LOCKER

ROOM

STORAGE

AIRCREW

FLIGHT

GROUP

STORAGE

COMM

ELEC

KITCHEN/

VENDING

STOR

BRIEFING/DD

CLASSROOM

SCIF

COPY

ROOM

ARMS

NCOIC

FIRE

ALARM

STORAGE

LIBRARY

BRIEFING

ROOM

INTELLIGENCE

OPEN

OFFICE

INTEL

NCO

INTEL

SUPERVISOR

BRIEFING

ROOM

WEAPONS

HALLWAY

BREAK

ROOM

VEST

AFMT

NCOIC

DO

HALLWAY

OG CHIEF

MISSSION

PLANNING

Space

NVG

AFE

SUPERINTENDENT

AFE

INSPECTION

ROOM

AIRCREW

FLIGHT

GROUP

VEST-2

141-2

LARGE

BRIEFING

BREAK

ROOM

STORAGE

Space

Space

FS CC

OG CC

CCA

OSS CC

FLIGHT

COMMANDER

WORK

ROOM

SECURED

VEST

ISSO &

SSR

HALLWAY

MAINT

DEBRIEF

AFE

NCOIC

SIMULATOR

SUPPORT

OFFICE

OPEN

OFFICE

TRAIN

OSF

SCHEDULING

SOF AREA

MEN'S

TOILET/

LOCKER

ROOM

HALLWAY

COMM/

COMPUTER

STORAGE

BREIFING

ROOM

BRIEFING

ROOM

ACMI/CLASSIFIED

WORK

ROOM

AFMT

OPEN

OFFICE

LOBBY

4" ST(E)

UP TO RD(E)

4" ST

WITH WCO @ 3'AFF

3"FCO-1

SK-2

1 1/2" V

4" ST(E)

4" WCO(E)

6"FCO(E)

3" ST(E)

3" ST(E)

UP TO RD(E)

3" LCO(E)

SK-1

1 1/2" V

3"FCO-1

3"FCO-1

2" V2" V

2" V-ST

4" ST(E)

UP TO RD(E)

LCO

4" ST

4" ST (49gpm)

WC-2 WC-1

2" V

1 1/2" V

JC-1

3"FD-1

3"FD-1

2" V

2"SH-1

2"FD-1

4"FCO-1

3" ST(E)

3" ST(E)

UP TO RD(E)

3" ST(E)

UP TO RD(E)

L-1 L-1

3"FCO(E)

6"FCO-1

4"FCO(E)

4" ST(E)

UP TO RD(E)

4" ST(E)

1 1/2" V(E)

SK-1

1 1/2" V(E)

3" V(E)

V (E

2" V(E) 2" V(E)

2"FCO-1(E)

1 1/2" V

2" HD

4" ST

5" ST

( 144gpm )

4" ST

DN BELOW LOW ROOF

5" ST

UP TO RD(E)

4" WCO(E)

4" ST(E)

UP TO RD(E)

4" LCO(E)

S T

(E

4" ST(E)

4" ST(E)

UP TO RD(E)

4" ST(E)

3" ST(E)

UP TO RD

3" ST(E) (4gpm)

S T

(E

3"

3" ST(E)

1 1/2" V

1 1/2" V

4" ST(E)

UP TO RD(E)

S T

(E

S T

(E

4" LCO(E) 4"FCO-1(E)

4" ST(E)

UP TO RD(E)

4"FCO(E)

4" HD(E)

4" HD(E)

5" ST (87gpm)

4" ST

4" ST

5" LCO

4"FCO-1(E)

4" ST(E)

UP TO RD(E)

4" ST(E)

4" WCO(E)

4" ST(E) WCO4" ST

S T

4" LCO(E)

SK-2

4" ST

UP TO RD(E)

S T

(E

4" LCO

4" ST

4" ST

4" ST (46gpm) P-101

4" ST(E)

UP TO RD(E)

4" ST(E)

SK-1

2" V

UP TO 3"VTR

4" LCO

S T

S T

4" ST

4" ST 4" ST

4" ST 4" LCO

4" LCO

4" LCO

4" LCO

4" ST

UP TO RD-1

4" ST

UP TO RD-1

4" ST

UP TO RD-1

4" ST

UP TO RD-1

4" DSN-1

S T

6.108

1 1/2" V UP

5" ST(E)

(87gpm)

4"FD

4"FCO

1 1/2" V

6.106

LC-1

1 1/2" V

3"FD-1

LT-1

4" WCO

6.101

6.101 6.101

6.103

1 1/2" V

EWC-12"FCO-1

3"FCO-1

/2

V

5"FCO-1

4"FCO-1

4"FCO-1

5"FCO-1

1 1/2" V

3" HD

3" HD

1 1/2" V

3"FCO-1

3" HD

2" V

2" V

UP TO 3"VTR

V

4"FD(E)

6.106

6.106

2" V

UP TO 3"VTR

2" V

4" DSN-1

6.108

3"FCO-1

4" ST

UP TO RD-1

4" ST

UP TO RD-1

(29gpm)

(28gpm)

(28gpm)

(35gpm)

(35gpm)

(6 g p m

(32gpm)

(32gpm)

(50gpm)

4" ST(E)

(82gpm)

(4gpm)

(4gpm)

(24gpm)

(50gpm)

6"FCO-1

(49gpm)

(49gpm)

(43gpm)

(23gpm)

4" ST(E)

UP TO RD(E)4"FD(E)

(32gpm)

(32gpm)

(23gpm)

(44gpm)

3" ST(E)

(24gpm)

4" ST(E)

UP TO RD(E)

(23gpm)

4" ST(E)

GD-1

6.109

6.106

6.109

6.106

6.109

K

K

L

L

M

M

N

N

P

P

19 19

18 18

L-1 L-1

3"FD-1 2"SH-2

2"FD-1

1 1/2" V

3"FCO-1

2" V

V

UR-2UR-1UR-1

WC-1

4" WCO

4" SAN4" SAN

2" V

UP TO 4"VTR

V

WC-1 WC-2

4" ST

UP TO RD(E)

4" ST

4" ST

UP TO RD(E)

2"FCO-1

2"SH-1

2"FD-1

4" WCO

1 1/2" V

MEN'S

TOILET/

LOCKER

ROOM

MEN'S

TOILET/

LOCKER

ROOM

(23gpm)

1 1/2" V1 1/2" V

1 1/2" V

1 1/2" V

3" HD

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:3

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

P-101

FIRST FLOOR -

DRAIN AND VENT

PLUMBING PLAN

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

KEYED NOTES

6.101 INSULATE ALL NEW STORM PIPE.

6.103 ROUTE DISHWASHER DRAIN TO SINK TAILPIECE TRAP

WITH AIR GAP FITTING.

6.106 METAL PIPE: PROVIDE A DIELECTRIC UNION INSIDE

THE SCIF PERIMETER ADJACENT TO THE

PENETRATION, OR GROUND THE CONDUIT WITHIN 6"

OF THE PERIMETER PENETRATION USING A NO. 4

WIRE (0.2043-DIAMETER COPPER WIRE) TO THE

BUILDING GROUND.

6.108 DOWN SPOUT (DSN-1) EXITS BUILDING ABOVE CEILING

SPACE.

6.109 THERE SHALL BE NO PENETRATIONS THRU

PERIMETER OF SCIF BOUNDARY OTHER THAN SHOWN

ON DRAWINGS. (ALL PIPING PENETRATIONS THRU

PERIMETER SCIF-AREA WALLS SHALL BE GROUNDED.)

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"1

FIRST FLOOR DRAIN AND VENT PLAN

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"2

ENLARGED FIRST FLOOR DRAIN AND VENT PLAN

05/04/17 TYPE B3

B

B

C

C

D

D

E

E

G

G

H

H

J

J

K

K

L

L

M

M

N

N

P

P

Q

Q

R

R

S

S

T

T

24 24

23 23

22 22 21 21

20 20

19 19 18 18

17 17

15 15

14 14

13 13

12 12

11 11

10 10 9 9

8 8

6 6

5 5

4 4

3 3

2 2

1 1

OSS CC

P-131

1" CW

2" SCW

3/4" SHW

3/4" HWR

3/4" SCW

3/4" SHW

3/4" HWR

1/2" HWR

3/4" SHW

3/4" SCW

3/4" CW

SK-2

/4

C

W

3/4" CW

3/4" CW3/4" CW

3/4" CW(E)

3/4" CW(E)

/4

C

W

SK-1

SK-2

3/4" CW(E)

/4

C

W (E

WH-13/4" CW

3/4" CW

6.152

VEST

PM/PSM

SECURE

VAULT

MECH

VEST-1

141-1

VEST

CONFERENCE

148 STAN

EVAL

HALLWAY

JAN

WOMEN'S

TOILET/

LOCKER

ROOM

STORAGE

AIRCREW

FLIGHT

GROUP

STORAGE

COMM

ELEC

KITCHEN/

VENDING

STOR

BRIEFING/DD

CLASSROOM

SCIF

COPY

ROOM

ARMS

NCOIC

FIRE

ALARM

STORAGE

LIBRARY

BRIEFING

ROOM

INTELLIGENCE

OPEN

OFFICE

INTEL

NCO

INTEL

SUPERVISOR

BRIEFING

ROOM

WEAPONS

HALLWAY

BREAK

ROOM

VEST

AFMT

NCOIC

DO

HALLWAY

OG CHIEF

MISSSION

PLANNING

NVG

AFE

SUPERINTENDENT

AFE

INSPECTION

ROOM

AIRCREW

FLIGHT

GROUP

VEST-2

141-2

LARGE

BRIEFING

BREAK

ROOM

STORAGE

Space

FS CC

OG CC

CCA

FLIGHT

COMMANDER

WORK

ROOM

SECURED

VEST

ISSO &

SSR

HALLWAY

MAINT

DEBRIEF

AFE

NCOIC

SIMULATOR

SUPPORT

OFFICE

OPEN

OFFICE

TRAIN

OSF

SCHEDULING

SOF AREA

MEN'S

TOILET/

LOCKER

ROOM

HALLWAY

COMM/

COMPUTER

STORAGE

BREIFING

ROOM

BRIEFING

ROOM

ACMI/CLASSIFIED

WORK

ROOM

AFMT

OPEN

OFFICE

LOBBY

SK-1

/2

N

P C

W

/4

N P

C W

1/2" NPCW

LC-1

LT-1

BV-1

(0.25gpm)

BV-1

(0.25gpm)

3/4" HWR

3/4" SCW

3/4" SHW

SK-1

6.156

/4

C

W

IC-1 (MOUNT WALL

BOX IC-1 @ 48"AFF)

1/2" SCW

1/2" SHW

TO DISHWASHER

1/2" NPCW

6.154

1/2" NPCW

1/2" NPCW

6.154

3/4" NPCW

IC-1 (MOUNT WALL

BOX IC-1 @ 48"AFF)

WH(E)

P-131

P-131

6.154

1/2" HWR

3/4" SHW

3/4" SCW

/4

N

P C

W

3/4" NPCW

1/2" SHW

DN TO DISHWASHER

6.153

6.152

6.153

EWC-1

1/2" CW

1" CW

2" SCW

3/4" SHW

3/4" HWR

3/4" CW

3/4" SCW

3/4" SHW

3/4" HWR

/4

C

W

6.152

6.153

6.152

6.153

WH-1

WH(E)

WH(E)

WH-1

3/4" HWR

1 1/4" SHW

2" SCW

1 1/4" CW

3/4" NPCW

1" NPCW

1 1/4" CW

2" SCW

1" SHW

3/4" HWR

38.0 SFU'S

5.5 SFU'S

43.5 SFU'S

61.5 SFU'S

9.0 SFU'S

6.0 SFU'S

76.5 SFU'S

R

R

S

S

T

T

13 13

12 12

11 112 P-131

3/4" CW(E)

3/4" CW

3/4" NPCW

PRV(E)

MECH

3/4" CW(E)

3/4" HWR

1 1/2" SHW

2" SCW

1 1/4" CW

GWH-1

CP-1

ET-1

WS-1WS-1

3/4" NPCW

3/4" NPCW

3/4" HWR

1 1/4" SHW

2" SCW

1 1/4" CW

3/4" NPCW

3/4" HWR

3/4" SHW

3/4" SCW

3/4" CW

1/2" NPCW

6.157

76.5 SFU'S

GWH-1

WS-1

WS-1

MMV-1

CP-1

ET-1

2" SCW

1 1/2" SHW

3/4" HWR

PRV(E)

PRV(E) WM(E)

3/4" NPCW(E)

3/4" NPCW

C W

CONCENTRIC VENT THRU ROOF

(EXTEND PIPE THRU EXISTING ROOF)

3/4" HWR

1 1/4" SHW

2" SCW

1 1/2" SHW

1 1/2" SCW

C W

(E

S C

W

1 1/2" SHW

2" CW

2" CW

C W

(E

2" SCW

2" CW

/4

N

P C

W

3/4" NPCW

3/4" NPCW

2" SCW (TYP)

2" CW (TYP)

1 1/4" CW

1 1/4" CW

3/4" CW

WM

4" CW(E)

6.158

6.158

6.158

6.158

6.158

RPZ-1

RPZ-2

1" NPCW

TO BOILERS

C W

K

K

L

L

M

M

N

N

19 19

18 18

WC-1 WC-1 WC-2

BV-1

(.25gpm)

SH-2

SH-1

UR-2UR-1UR-1

L-1 L-1

3/4" CW

3/4" CW

2" SCW

1" SHW

3/4" HWR

1 1/2" SCW

3/4" SCW

3/4" SHW

3/4" HWR

BV-1

(.25gpm)

MEN'S

TOILET/

LOCKER

ROOM

MEN'S

TOILET/

LOCKER

ROOM

S C

W

2" SCW2" SCW

3/4" CW

1" SCW

1" SHW

1 1/4" SCW

1/2" SHW

3/4" HWR

3/4" SCW

TP

K

K

L

L

M

M

N

N

P

P

13 13

12 12

11 11

WOMEN'S

TOILET/

LOCKER

ROOM

WOMEN'S

TOILET/

LOCKER

ROOM

JAN

JC-1

3/4" NPCW

1 1/4" CW

2" SCW

1" SHW

3/4" HWR

3/4" NPCW

2" SCW

1" SHW

3/4" HWR

WC-2 WC-1

SH-2

L-1L-1

/4

C

W

BV-1

(.25gpm)

BV-1

(.25gpm)

1 1/2" SCW

2" SCW

1 1/4" CW

3/4" HWR

3/4" SHW

3/4" SCW

3/4" SCW

3/4" SHW

3/4" SCW

3/4" SHW

TP

BV-1

(.25gpm)

3/4" SCW

3/4" SHW

3/4" HWR 3/4" HWR

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:3

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

P-131

FIRST FLOOR -

SUPPLY PLUMBING

PLAN

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

KEYED NOTES

6.152 METAL PIPE: PROVIDE A DIELECTRIC UNION INSIDE THE SCIF PERIMETER

ADJACENT TO THE PENETRATION, OR GROUND THE CONDUIT WITHIN 6" OF

THE PERIMETER PENETRATION USING A NO. 4 WIRE (0.2043-DIAMETER

COPPER WIRE) TO THE BUILDING GROUND.

6.153 THERE SHALL BE NO PENETRATIONS THRU PERIMETER OF SCIF BOUNDARY

OTHER THAN SHOWN ON DRAWINGS. (ALL PIPING PENETRATIONS THRU

PERIMETER SCIF-AREA WALLS SHALL BE GROUNDED.)

6.154 1/2" NPW TO HUMIDIFIER. COORDINATE WITH HVAC CONTRACTOR FOR

CONNECTION LOCATION AND TYPE.

6.156 ROUTE SCW AND SHW UNDER COUNTER TO WALL BEFORE ROUTING IN

CEILING SPACE.

6.157 ROUTE NPCW TO MECHANICAL CRAC UNIT. COORDINATE LOCATION WITH

MECHANICAL CONTRACTOR.

6.158 REFERENCE SHEET P-501 FOR ADDITIONAL VALVING AND CONNECTIONS.

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"1

FIRST FLOOR SUPPLY PLUMBING

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"3

ENLARGED MECHANICAL ROOM PLUMBING PLAN

NO SCALE2

WATER ENTRANCE, WATER SOFTNER,

AND WATER HEATER ISO ARRANGEMENT

05/04/17 TYPE B3

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"4

ENLARGED MENS SHOWER/TOILET ROOM

PLAN

NORTH

TRUE

NORTH

1/4" = 1'-0"5

ENLARGED WOMEN'S SHOWER/TOILET ROOM

WITHOUT CONCRETE TOPPINGWITH CONCRETE TOPPING

FINISHED FLOORCONCRETE TOPPING

CONCRETE

FLOOR

WATERPROOFING

MEMBRANE. EXTEND

MIN. 12" FROM DRAIN

IN ALL DIRECTIONS

EXTEND WATERPROOFING

MEMBRANE INTO SEEPAGE

PAN & SECURE WITH

CLAMPING COLLAR.

ABOVEGROUND:

PROVIDE UNDER DECK

CLAMP ON THIN SLAB

INSTALLATIONS OF 5"

OR LESS

TO TRAP

CONCRETE FLOOR

FINISHED

FLOOR

SCORIATED SECURED

POLISHED NICKEL BRONZE TOP

IN PUBLIC AREAS

CONCRETE FLOOR

GAS AND WATERTIGHT

TAPERED THREADED PLUG PIPE

CONCRETE FLOOR

IN CARPET AREAS

PROVIDE TOP WITH

CARPET MARKER

PROVIDE EXTRA HEAVY DUTY

SECURED ADJUSTABLE TOP IN

MECHANICAL RM'S, APPARATUS

BAYS, UTILITY AREAS, ETC.

/4

2" MIN

HUB DRAIN

JOINT FILLER

FLOOR SURFACE

FLOOR SLAB

TRAP PRIMER

CONNECTION

P-TRAP

0' - 0 31/128"

1" MIN.

/2

28"-60"

FINISHED WALL SURFACE

VENT STACK-PIPE

MATERIAL AS SPECIFIED

MECHANICAL CONNECTOR

IF REQUIRED

CLEANOUT TEE SAME MATERIAL

AS CONNECTED PIPE

STAINLESS STEEL COVER PLATE

WITH SECURING SCREW

FINISHED FLOOR

UNDERGROUND DRAIN OR VENT

LINE PIPE MATERIAL AS SPECIFIED

WALL LINE

VENT STACK

PIPE MATERIAL AS SPECIFIED

MECHANICAL CONNECTOR

IF REQUIRED (TYP)

CLEANOUT TEE

SAME MATERIAL AS

CONNECTED PIPE

FINISHED FLOOR

UNDERGROUND DRAIN OR VENT

LINE PIPE MATERIAL AS SPECIFIED

/1

12"

MIN.

VENT TERMINAL

ROOFING

ROOF

CONSTRUCTION

SLEEVE ROOF

CONSTRUCTION

AS REQUIRED

INCREASER WHEN

REQUIRED

VENT STACK

FLASHING BY

ROOFING CONTRACTOR

BALL VALVE

PROVIDE PIPE FLANGE

ON HOSE BIBB WHEN

PIPE IS CONCEALED IN

WALL

HOSE BIBB

(HB-1)

HOSE CONNECTION

VACUUM BREAKER

(NON-REMOVABLE)

3/4" NPT

PIPE CLAMPS W/RUBBER

PIPE CUSHION BETWEEN

PIPE & CLAMP

UNISTRUT -WHERE

PIPE IS EXPOSED

PROVIDE PVC COVERING

AROUND ALL INSTALLATION

IN WET AREAS

INTERIOR WALL

WALL SLEEVE, OF

SPECIFIED MATERIAL

ESCUTCHEON

WHERE SPECIFIED

PIPE INSULATION

AND JACKETING

WHERE CALLED FOR

TIGHTLY CAULK WITH

SILICONE SEALANT

FOR MIN. 2" EACH END

PIPE - MUST BE

FREE OF STRAIN

TIGHTLY PACKED

WITH FOAM - IN

PLACE INSULATION

1/2" TO 1"

CLEARANCE

ALL SIDES

/3

"D" 1

FOUNDATION WALL

BOTTOM OF FOOTING

FOOTING BEARING REGION

CASING END

SEAL (TYP)

EXTEND CASING

BEYOND FOOTING

BEARING REGION

PIPE

NOTES:

1. CASING PIPE NOT REQUIRED

WHERE "D" IS MORE THAN 2

TIMES DIAMETER OF PIPE

AND GREATER THAN 18".

PIPE

/8

2" MIN

TOP OF FOOTING

PENETRATION IAW

SPECIFICATIONS

FOUNDATION WALL

PIPE DIAMETER LONGITUDINAL SHIELD LENGTH

UP TO 3"

4"

6"

8" & LARGER

12"

15"

21"

* INCOMPRESSIBLE INSULATING

BLOCK AT HANGER WITH

24" SHIELD

THREADED ROD

CLAMP

UNISTRUT HANGER

SHEET METAL INSULATION

SHIELD (18 GAUGE)

OR MANUFACTURED HANGER

SHIELD PER SPECIFICATIONS

INSULATION

CLEVIS TYPE HANGER

DOUBLE LOCK

NUT

THREADED ROD

CW

CW

NC NC

H W

4" CONCRETE PAD

GAS WATER

HEATER

STORE

WATER AT

140°F.

HOT WATER

RETURN

STRAINER WITH BLOW-OFF

CIRCULATING PUMP

T & P RELIEF VALVE

EXTEND TO 6" AFF

COMBUSTION AIR PIPES,

SIZE, MATERIAL, AND

ROUTING TO EXTERIOR

IAW WATER HEATER

MANUFACTURER'S

LITERATURE.

DRAIN VALVE

FINISHED

FLOOR

PVC INDIRECT

CONDENSATE DRAIN.

SIZE IAW WATER

HEATER

MANUFACTURER'S

LITERATURE. ROUTE

TO DRAIN.

THERMOSTATIC

MIXING VALVE

(ADJUSTABLE)

EXPANSION TANK. SUPPORT

INDEPENDENTLY OF PIPING.

120°F MIXED

WATER,

(ADJUSTABLE)

THERMOMETER

HEAT TRAP

BYPASS (NORMALLY CLOSED)

DRAIN

OVERFLOW

INDIRECT

DRAIN

BRINE

SOFT WATER

HARD WATER

FLOW

SENSOR

2" 2" 1 1/2"

2" 2" 1 1/2"

BRINE

TANK

RESIN

TANK

RESIN

TANK

RESIN

TANK

4" CONCRETE PAD

CONTROL

VALVE

CONTROL

VALVE

CONTROL

VALVE

/2

/2

/2

/2

/2

2"

1/8"1"

METAL ROOF DECK

ANCHOR SCREW WITH OVERSIZED WASHER,

MINIMIZE COMPRESSION, MAX. 12" SPACING

PVC PIPE INSULATION SHIELD

MASTIC AT ALL JOINTS

AND EXPOSED INSULATION

PVC PIPE INSULATION SHIELD

DRAIN PIPE INSULATION. SEE SPECS.

ROOF DRAIN PIPING

PVC PIPE INSULATION SHIELD

NO HUB DRAIN PIPE COUPLING

DRAIN PIPE EXTENSION AS REQUIRED

PVC PIPE INSULATION SHIELD. GLASS FIBER BATT

INSULATION AS REQUIRED TO MAINTAIN MINIMUM 1"

THICK INSULATION. TRIM BACK BOLT AS NEEDED TO

ENCAPSULATE WITHIN INSULATION SHIELD

1" THICK GLASS FIBER INSULATION BOARD. 3.0 PCF, ASJ.

EXTEND 1" PAST FIRST UNOBSTRUCTED FLUTE. APPLY

MASTIC AT EXPOSED INSULATION

MINERAL FIBER INSULATION (MIN. 20%

COMPRESSION) FILL FLUTES AT PERIMETER

OF 1" GLASS FIBER INSULATION BOARD.

APPLY MASTIC AT EXPOSED INSULATION

UNDERDECK CLAMP

ROOF DRAIN

CONDITIONS AT TOP SIDE OF METAL DECK

MAY VARY (SEE ARCHITECTURAL ROOF

PENETRATION DETAILS)

TIMER

AQUASTAT

SHUTOFF VALVE

(TYP)

STRAINER WITH

BLOW-OFF

UNION(TYP)

POWER

CHECK

VALVE

PUMP

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:3

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

P-501

PLUMBING DETAILS

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

NO SCALE1

FLOOR DRAIN - CAST IN PLACE

NO SCALE2

FLOOR CLEANOUT (FCO)

NO SCALE3

HUB DRAIN (HD)

NO SCALE4

WALL CLEANOUT (WCO)

NO SCALE5

STACK CLEANOUT (SCO)

NO SCALE6

VENT THRU ROOF (VTR)

NO SCALE7

HOSE BIBB (HB-1)

NO SCALE8

INTERIOR WALL PIPE SLEEVE

NO SCALE9

PIPE UNDER FOOTING

NO SCALE10

PIPE

THROUGH FOUNDATION WALL

NO SCALE11

INSULATED PIPE SUPPORTS

NO SCALE12

GAS WATER

HEATER WITH MASTER THERMO-MIXING VALVE

NO SCALE13

WATER SOFTENER 4 RESIN TANK

NO SCALE15

INSULATION ROOF DRAIN UNDERSIDE

05/04/17 TYPE B3

NO SCALE14

HOT WATER CIRCULATING PUMP DETAIL

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

/3

/2

:1

:3

A

M C

R e v it L o c a l\

-1

.0

-P

-C e n tr a l-jo n .t ie d e m e a d h u n t.

c o m

.r v t

W

IS

C O

N S

IN

A

IR

N

A T

IO

N

A L G

U A

R D

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

A D

A L B

P-601

PLUMBING

SCHEDULES

XGFG132020ANG NO.:

3141300-141489.01

JET

RMM

May 4, 2017

MFP

(4) OWNER FURNISHED, CONTRACTOR INSTALLED

(3) EXTERNAL DISCONNECT REQUIRED.

(2) DISCONNECT INCLUDED

(1) SEE GENERAL NOTES P-001 (5) EXPOSED PIPING TO BE CHROME PLATED

REMARKS:

RPZ-2

REDUCED PRESSURE BACKFLOW

PREVENTER

WATTS 3/4"-909QTS

REDUCED PRESSURE ZONE ASSEMBLY, ASSE 1013, 3/4", BRONZE.WITH 1/4 TURN BALL VALVES, STRAINER AND AIR GAP FITTING, DISCHARGE TO NEAREST DRAIN. (FOR SUPPLY TO HUMIDIFIERS)

N/A N/A N/A

RPZ-1 REDUCED PRESSURE BACKFLOW... EXISTING REUSE EXISTING RPZ, RELOCATE AS SHOWN ON PLANS FOR BOILER FILL N/A N/A N/A

FCO-2

FLOOR CLEANOUT (MECHANICAL, UTILITY

RMS. ETC)

JR SMITH, 4263 CAST IRON WITH ANCHOR FLANGE, HEAVY DUTY CAST IRON COVER N/A N/A N/A

FCO-1 FLOOR CLEANOUT (PUBLIC AREAS) JR SMITH, 4020 CAST IRON, MEDIUM DUTY NICKEL-BRONZE COVER N/A N/A N/A

BV BALANCING VALVE (CIRCUIT SETTER) B&G - WITH MEMORY STOP SEE DRAWINGS FOR LOCATIONS AND FLOWS N/A N/A

FD-2 FLOOR DRAIN (MECH. AND MAINT. AREA'S) ZURN Z-556-Y-VP

CAST IRON BODY, 9" DIAMETER TOP DRAIN, COMBINATION MEMBRANE FLASHING CLAMP AND FRAME

FOR HEAVY DUTY CAST IRON DEEP FLANGE, SLOTTED GRATE AND SEDIMENT BUCKET.

N/A N/A

FD-1 FLOOR DRAIN (PUBLIC AND STAFF AREA'S) ZURN Z-415-B-VP

CAST IRON BODY, COMBINATION INVERTIBLE MEMBRANE CLAMP, ADJUSTABLE COLLAR WITH HEEL PROOF POLISHED NICKEL BRONZE STRAINER VANDAL PROOF TOP. PROVIDE SQUARE STRAINERS IN

TILED FLOORS.

N/A N/A

DSN-1 DOWN SPOUT NOZZLE ZURN, Z199 NICKEL BRONZE DOWNSPOUT NOZZLE WITH THREADED INLET. N/A N/A

RD-1 ROOF DRAIN / OVERFLOW DRAIN ASSEMBLY ZURN Z164

12" DIA. ROOF DRAIN AND OVERFLOW DRAIN, CAST IRON BODIES WITH COMBINATION MEMBRANE FLASHING CLAMP/GRAVEL GUARDS, DOUBLE TOP SET CHECK PLATES, AND LOW SILHOUETTE CAST IRON DOMES, AND EXTENSION COLLARS. COORDINATE EXACT LOCATION WITH ARCHITECTURAL PLANS.

N/A N/A

HB-1 HOSE BIBB WOODFORD MODEL 24 STANDARD CHROME FINISH, WITH ASSE 1019 VACUUM BREAKER N/A N/A

WH-1 WALL HYDRANT WOODFORD, MODEL 65 AUTOMATIC DRAINING WITH ANTI-SIPHON ASSE 1019 VACUUM BREAKER. 3/4" INLET N/A N/A

TP TRAP PRIMING SYSTEM

PPP PRIME-TIME ELECTRONIC TRAP PRIMING

SYSTEM

INSTALL ON FLOOR DRAINS IN REST ROOMS, JANITORS CLOSETS, MECHANICAL ROOMS, TRASH ROOM, LAUNDRY ROOMS, KITCHEN, SERVICE ROOMS ETC.

120 / 1

GD-1 SINK DISPOSER INSINKERATOR EVOLUTION

FOOD WASTE DISPOSER WITH 1-1/2" DRAIN CONNECTION, SOUND REDUCING TECHNOLOGY, STAINLESS

STEEL GRIND CHAMBER, AND MANUAL RESET MOTOR OVERLOAD PROTECTION.

120 / 1 8.1 (3)

IC-1 WALL BOX (REF. ICE MAKER) GUY GREY, BIM875QTS ICE MACHINE CONNECTION WALL BOX WITH INTEGRAL WATER HAMMER ARRESTER. N/A N/A

LC-1 WALL BOX (LAUNDRY) GUY GREY, SERIES WB200HATM WASH MACHINE CONNECTION WALL BOX WITH INTEGRAL WATER HAMMER ARRESTER. N/A N/A

FAUCET CHICAGO FAUCET MODEL 526-317ABCP

DECK MOUNTED, CHROME PLATED, RIGID/SWING DOUBLE BEND SPOUT FAUCET WITH 4" WRISTBLADE

HANDLES, 4" CENTERS HOT AND COLD WATER SINK FAUCET.

N/A N/A (5)

LT-1

LAUNDRY TUB MUSTEE MODEL 19F

TUB TO BE ONE PIECE MOLDED CONSTRUCTION USING STURCTURAL THERMOPLASTIC. TUB TO

INCLUDE INTEGRAL MOLDED DRAIN ASSENBLY FOR 1.5" P TRAP, STOPPER AND HEAVY GAUGE STEEL

LEGS WITH BUILT-IN LEVELERS, 18 GALLON CAPACITY AND 13" DEEP.

N/A N/A

EWC-1 ELECTRIC WATER COOLER ELKAY LVRCGRNTL8WSK

WALL MOUNTED DUEL LEVEL WATER COOLER WITH EWF3000 WATER FILTER SYSTEM AND BOTTLE

FILLER, 8 GPH OF 50°F WATER AT 90 F AMBIENT AND 80 F INLET WATER,PROVIDE FLOOR MOUNTED

CARRIER, PROVIDE ALL COMPONENTS REQUIRED FOR COMPLETE INSTALLATION.

115 / 1, 260

WATTS

3.8 AMPS. (3)

SERVICE RECEPTOR FAUCET

CHICAGO FAUCETS - 911-IS WITH ELEVATED

VACUUM BREAKER.

SERVICE SINK FAUCET WITH WALL BRACE, VACUUM BREAKER. AND PAIL HOOK ON SPOUT. N/A N/A

JC-1

SERVICE SINK KOHER WHITBY K-6710

FLOOR MOUNTED CAST IRON MOP SINK. 28"X 28" WITH 3" DRAIN HOLE, STAINLESS STEEL STRAINER, 36"

HIGH X 28" WIDE STAINLESS STEEL BACK PLATES TO PROTECT WALLS AND RIM GUARDS.

N/A N/A

HAND HELD SHOWER DIVERTER VALVE POWERS - 141-600F WATER DIVERTER VALVE FOR FIXED HEAD SHOWER AND HAND HELD SHOWER, N/A N/A (5)

HAND HELD SHOWER CHICAGO 151-CP

ADJUSTABLE HOOK WITH 24" WALL SLIDE BAR, 60" HOSE WITH 1/2" NPSM FEMALE CONNECTION, HAND SPRAY, ALL CHROME PLATED. WITH ZURN Z7000-VB IN-LINE VACUUM BEREAKER (ASSE 1014).

N/A N/A (5)

SHOWER HEAD SPEAKMAN S-2253E15 SHOWER HEAD, WITH BALL JOINT SPRAY HEAD AT 1.5 GPM. S-2520 SHOWER ARM. N/A N/A (5)

SHOWER MIXING VALVE CHICAGO, 2500 VOCCP

THERMOSTATIC/PRESSURE BALANCING SHOWER VALVE WITH INTEGRAL CHECK/SERVICE STOPS, AND

ALL COMPONENTS FOR COMPLETE OPERATION.

N/A N/A (5)

SH-2

(ADA)

SHOWER RECEPTOR FIELD BUILT REFER TO ARCHITECTURAL DRAWINGS. (PROVIDE 2" FD-1 FLOOR DRAIN.) N/A N/A

SHOWER HEAD SPEAKMAN S-2253E15 SHOWER HEAD, WITH BALL JOINT SPRAY HEAD AT 1.5 GPM. S-2520 SHOWER ARM. N/A N/A (5)

SHOWER MIXING VALVE CHICAGO, 2500 VOCCP

THERMOSTATIC/PRESSURE BALANCING SHOWER VALVE WITH INTEGRAL CHECK/SERVICE STOPS, AND

ALL COMPONENTS FOR COMPLETE OPERATION.

N/A N/A (5)SH-1

SHOWER RECEPTOR FIELD BUILT REFER TO ARCHITECTURAL DRAWINGS. (PROVIDE 2" FD-1 FLOOR DRAIN.) N/A N/A

SINK FAUCET MOEN: MODEL 8225SMF1.5

DECK MOUNTED, ADA COMPLIANT, CHROME PLATED, HEAVY DUTY RIGID/SWING GOOSENECK SPOUT

KITCHEN FAUCET WITH WRIST BLADE INDEXED HANDLES AND 1.5 GPM AERATOR.

N/A N/A (5)

SK-2

SINK, SINGLE COMPARTMENT ELKAY LR-2522-7.5

SINGLE COMPARTMENT, 18 GAUGE TYPE 302 S/S, COUNTER MOUNT. PROVIDE AND INSTALL CHROME

PLATED CAST BRASS "P" TRAP, LOOSE KEY ANGLE STOPS WITH SHIELD CAPS, SUPPLIES AND

ESCUTCHEON PLATES ON SUPPLIES AND DRAIN PIPES.

N/A N/A (5)

SINK FAUCET MOEN: MODEL 8225SMF1.5

DECK MOUNTED, ADA COMPLIANT, CHROME PLATED, HEAVY DUTY RIGID/SWING GOOSENECK SPOUT

KITCHEN FAUCET WITH WRIST BLADE INDEXED HANDLES AND 1.5 GPM AERATOR.

N/A N/A

SK-1

(ADA)

SINK, DOUBLE COMPARTMENT (KITCHEN) ELKAY LRAD-3322-65

DOUBLE BASIN, 18 GAUGE TYPE 302 S/S, COUNTER MOUNT, 6.5 INCH DEEP. PROVIDE AND INSTALL CHROME PLATED CAST BRASS "P" TRAP, LOOSE KEY ANGLE STOPS WITH SHIELD CAPS, SUPPLIES AND ESCUTCHEON PLATES ON SUPPLIES AND DRAIN PIPES. PROVIDE OFFSET TAILPEICE AS REQUIRED TO

MEET ADA REQUIREMENTS. PROVIDE GD-1 ON ONE COMPARTMENT.

N/A N/A (5)

LAVATORY FAUCET MOAN (COMMERCIAL) MODEL 8416F0.5

ADA SINGLE LEVER SOLID BRASS CONSTRUCTION, CHROME LAVATORY FAUCET, 0.5 GPM FLOW

AERATOR, TEMPERATURE LIMIT STOP, CERAMIC DISC CARTRIDGE, OFFSET GRID STRAINER DRAIN, LESS POP UP. ASSE 1070 THERMOSTATIC MIXING VALVE, AND SUPPLYS, PROVIDE ALL COMPONENTS

FOR COMPLETE AND PROPER OPERATION OF FIXTURE.

N/A N/A (5)

L-1

(ADA)

LAVATORY BOWL INTEGRAL WITH COUNTER

SEE ARCH PLANS. PROVIDE AND INSTALL CHROME PLATED CAST BRASS "P" TRAP WITH OFFSET TAILPIECE AND GRID STRAINER, LOOSE KEY ANGLE STOPS, SUPPLIES AND ESCUTCHEON PLATES AROUND ALL PIPE PENETRATIONS. PROVIDE TRAP WRAP ON ALL EXPOSED SUPPLY & DRAIN PIPING

BELOW SINK.

N/A N/A (5)

URINAL FLUSHOMETER SLOAN ROYAL - 186-0.125

0.125 GPF, EXPOSED, MANUAL OPERATED FLUSHOMETER FOR 3/4" TOP SPUD, SCREWDRIVER

BAK-CHEK ANGLE STOP, CHROME PLATED, AND ADJUSTABLE TAILPIECE. REQUIREMENTS.

N/A N/A

UR-2

(ADA)

URINAL (WALL MOUNTED) KOHLER BARDON K-4904-ET

0.125 GPF, WALL MOUNTED, WHITE, VITREOUS CHINA URINAL WITH 3/4" TOP SPUD, AND 2" WASTE OUTLET. PROVIDE COMMERCIAL ADJUSTABLE FLOOR STANDING CARRIER AND ALL ACCESSORIES FOR COMPLETE INSTALLATION. MOUNTING HEIGHT TO COMPLY WITH ADA REQUIREMENTS, (LIP TO BE A

MAX. OF 17" AFF)

N/A N/A

URINAL FLUSHOMETER SLOAN ROYAL - 186-0.125

0.125 GPF, EXPOSED, MANUAL OPERATED FLUSHOMETER FOR 3/4" TOP SPUD, SCREWDRIVER

BAK-CHEK ANGLE STOP, CHROME PLATED, AND ADJUSTABLE TAILPIECE. REQUIREMENTS.

N/A N/A

UR-1

URINAL (WALL MOUNTED) KOHLER BARDON K-4904-ET

0.125 GPF, WALL MOUNTED, WHITE, VITREOUS CHINA URINAL WITH 3/4" TOP SPUD, AND 2" WASTE OUTLET. PROVIDE COMMERCIAL ADJUSTABLE FLOOR STANDING CARRIER AND ALL ACCESSORIES FOR

COMPLETE INSTALLATION.

N/A N/A

WATER CLOSET FLUSHOMETER SLOAN ROYAL 111-1.28

1.28 GPF, EXPOSED MANUAL OPERATED FLUSHOMETER, 1.5" SPUD, FLUSH HANDLE TO BE ON WIDE

SIDE OF FIXTURE.

N/A N/A

SEAT BEMIS 1655-SS/C ELONGATED OPEN FRONT SEAT WITH ANTI-MICROBIAL AGENT AND WITHOUT COVER. N/A N/A

WC-2

(ADA)

WATER CLOSET (WALL MOUNTED) KOHLER KINGSTON K-4325

1.28 GPF, WALL MOUNTED, BACK OUTLET, WHITE, ELONGATED, VITREOUS CHINA, SIPHON JET, 1-1/2" TOP SPUD, 2-1/4" PASSAGE WAY. ALL TRIM TO BE VANDAL RESISTANT. PROVIDE ALL COMPONENTS AS REQUIRED FOR COMPLETE OPERATION INCLUDING BUT NOT LIMITED TO COMMERCIAL ADJUSTABLE

CARRIERS. (MOUNT RIM AT 16" AFF, SEAT HEIGHT TO BE BETWEEN 17 AND 19" AFF.)

N/A N/A

WATER CLOSET FLUSHOMETER SLOAN ROYAL 111-128

1.28 GPF. EXPOSED, MANUAL FLUSHOMETER WITH 1.5" SPUD COUPLING. INSTALL TO COMPLY WITH ADA

REQUIREMENTS.

N/A N/A

SEAT BEMIS 1655-SS/C ELONGATED OPEN FRONT SEAT WITH…