This document summarizes a federal solicitation for construction services. The solicitation seeks the construction of an Advanced Individual Training Complex at Fort Gordon, including a battalion headquarters, barracks to house 600 soldiers, a running track, physical training facilities, building information systems, fire protection and alarm systems, video surveillance and intrusion detection. Supporting facilities such as utilities, site development, parking and landscaping are also required. The scope requires compliance with Department of Defense antiterrorism standards and accessibility requirements. Sustainability, energy efficiency, and cyber security measures must be incorporated. The project has an estimated value between $25-100 million and a period of performance of 720 calendar days. Bids will be evaluated using sealed bidding procedures in accordance with the FAR.
View the file
Other files
Show 40 more
Latest 50 of 58 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING LEGENDPLUMBING GENERAL NOTES
1. FURNISH ALL LABOR, INSTALL ALL MATERIALS AND EQUIPMENT, AND INCLUDE ALL SERVICES AND INCIDENTALS PROPER TO THE INSTALLATION OF WORK INVOLVED FOR A COMPLETE AND OPERATING FACILITY.
2. CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES, SPECS AND DRAWINGS.
3. PROVIDE CLEARANCES AROUND EQUIPMENT AS RECOMMENDED BY MANUFACTURER. COORDINATE EQUIPMENT
ELECTRICAL REQUIREMENTS WITH ELECTRICAL DRAWINGS.
4. THE PLUMBING DRAWINGS ARE GENERALLY DIAGRAMMATIC AND SHOW THE RELATIONSHIP BETWEEN EQUIPMENT AND CONNECTIONS. DO NOT SCALE THE DRAWINGS FOR EXACT SIZE OR LOCATIONS. DETAILS AND ASSEMBLY
DRAWINGS ARE SPECIFIC AND SHALL BE ADHERED TO.
5. THE PLUMBING SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS, SPECIFICATIONS, NFPA 54 AND THE INTERNATIONAL PLUMBING CODE.
6. ALL BUILDINGS SHALL BE DESIGNED FOR SEISMIC DESIGN CATEGORY "B".
7. CONCRETE HOUSEKEEPING PAD SIZES SHALL BE COORDINATED WITH INSTALLED EQUIPMENT.
8. COORDINATE VENT THRU ROOF AND WATER HEATER INTAKE/FLUE PIPING PENETRATIONS THRU ROOF WITH
ROOFING CONTRACTOR. FLASHING SHALL BE BY ROOFING CONTRACTOR.
9. REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPE AND PIPE SIZES NOT SHOWN.
10. PROVIDE EXPANSION JOINTS IN PIPING WHEN CROSSING THE BUILDING SEISMIC JOINT BETWEEN AREAS B AND D.
EXPANSION JOINTS SHALL PROVIDE AT LEAST 3 INCHES OF MOVEMENT. EXPANSION JOINTS SHALL BE OF EITHER THE BRAIDED HOSE DOGLEG ASSEMBLY OR BRAIDED HOSE V LOOP TYPE. REFER TO SPECIFICATION SECTION 23 05 48.19.
SANITARY SEWER
SANITARY VENT
CONDENSATE DRAIN (SEE MP-PLATES)
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRCULATED
GATE VALVE
BALL VALVE
A.S.M.E. RATED T&P RELIEF VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
PIPE DROP
PIPE RISE
FLANGE
UNION
HOSE BIBB/WALL HYDRANT
PIPE TEE
PIPE ELBOW
DRAWING NOTE
PLUBMING EQUIPMENT TAG
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BOTTOM OF PIPE
CONDENSATE DRAIN
CLEANOUT
EXTERIOR CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
HOSE BIBB
HUB DRAIN
INVERT
REDUCED PRESSURE PRINCIPAL BACKFLOW PREVENTER
SANITARY SEWER
VENT
VENT THRU ROOF
WALL HYDRANT
WATER HAMMER ARRESTOR
- APPLIES TO ALL P-SERIES SHEETS- APPLIES TO ALL P-SERIES SHEETS
X" SS
X" V
X" CD
X" CW
X" HW
X" HWR
P - #
AFF
AFG
BFF
BFG
BOP
CD
CO
ECO
FCO
FD
HB
HD
INV
RPBP
SS
V
VTR
WH
WHA
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\k6endles\Desktop\Tele-Work Revit Projects\Gor0402 (PN55516)\FY20PN55516_BKS_PLUMB_R18_TW Current.rvt3/16/2021 2:14:15 PM
N O
VE
M
BE
R
W
2H N
-2 1-
B-
L.
S
AL
AS
L.
S
AL
AS
S.
B
AR
BI
N A
1-
-0
P-001
PL
U
M
BI
N G
L
EG
EN
D
SA
VA
N N
AH
D
IS
TR
IC
T
W . O
G
LE
TH
O
R
PE
A
VE
SA
VA
N
N
AH
, G A
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AI
T
BA
R
R
AC
KS
C
O M
PL
EX
, P H
FY
, P
N
VO
LU
M E
-B
AR
R
AC
KS
(P
LU
M
BI
N G
, M
EC
H
AN
IC
AL
, E
LE
C
TR
IC
AL
, A N
D
TE
LE
C
O M
M U
N
IC
AT
IO
N
K.
D
IX
O
N
READY TO ADVERTISE (RTA)
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
3/
/2
ELECTRICAL LEGEND
LED LUMINAIRES. SEE LIGHT FIXTURE SCHEDULE, DETAILS, AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
LOWER CASE DENOTES THE DEVICE THAT CONTROLS FIXTURE
LUMINAIRE TYPE DESIGNATION
SYMBOL DENOTES GENERAL TYPE OF LUMINAIRE
UNSWITCHED NIGHT LIGHT (ON 24
HOURS)
a A2
NT
T
LCP
OS
DS
LVX
ELI
PC
LIGHTING AND LIGHTING CONTROLS SYSTEM LEGEND
v fan
LED LUMINAIRES WITH EMERGENCY DRIVERS OR CONNECTED TO AN
EMERGENCY LIGHTING INVERTER
WALL MOUNTED LED LUMINAIRE.
WALL MOUNTED LED LUMINAIRE WITH EMERGENCY DRIVER.
WALL MOUNTED LED LUMINAIRES.
SUSPENDED LED LUMINAIRE.
SUSPENDED LED LUMINAIRE WITH INTEGRAL EMERGENCY
DRIVER.
EXIT LIGHT, CEILING MOUNTED, SHADING INDICATES FACES.
PROVIDE DIRECTIONAL ARROWS WHEN INDICATED.
EXIT LIGHT, WALL MOUNTED, SHADING INDICATES FACES. PROVIDE
DIRECTIONAL ARROWS WHEN INDICATED. MOUNT BOTTOM OF
FIXTURE 6" ABOVE TOP OF DOOR UNLESS OTHERWISE INDICATED.
WALL SWITCH, SINGLE POLE, 20A SWITCH. WHERE SUBSCRIPT IS
PRESENT, IT DENOTES THE FOLLOWING:
3 - THREE WAY SWITCH.
4 - FOUR WAY SWITCH.
a - SINGLE LOWER CASE LETTER (EXCEPT LETTER "m")
DENOTES THE SWITCH THAT CONTROLS THE FIXTURES.
WP - WEATHERPROOF (GASKETED).
MOTOR RATED SWITCH FOR CEILING FAN.
WALL SWITCH SENSOR, LINE VOLTAGE. SUBSCRIPT "v" DENOTES SIGNLE RELAY, SUBSCRIPT "dv" DENOTES DUAL RELAY, DUAL SWITCH.
DIGITAL TIME SWITCH, LOW VOLTAGE.
LOW VOLTAGE, MULTI-BUTTON WALLSTATION CONNECTED TO ROOM
CONTROLLER. SUBSCRIPTS ARE DENOTED VIA DETAILS.
OCCUPANCY SENSOR. WALL MOUNTED, DUAL TECHNOLOGY
ULTRASONIC / PIR) SENSOR UNLESS OTHERWISE INDICATED.
SUBSCRIPT "P" INDICATES PIR ONLY.
OCCUPANCY SENSOR. CEILING MOUNTED OR SUSPENDED AT HEIGHT
OF LIGHTING FIXUTE. ULTRASONIC SENSOR UOI.
DAYLIGHT SENSOR. CEILING MOUNTED OR SUSPENDED AT HEIGHT
OF LIGHTING FIXTURE.
EXTERIOR PHOTOCELL.
LIGHTING CONTROL PANEL (LCP).
EMERGENCY LIGHTING INVERTER.
# INDICATES LIGHTING CONTROL STRATEGY. SEE SHEET EL602.#
LED LUMINAIRE WITH ASYMMETRIC LIGHT DISTRIBTION. ARROW
DENOTES DIRECTION OF LIGHT DISTRIBUTION..
dv
M
C
J
NEMA 5-20R CEILING MOUNTED DUPLEX RECEPTACLE OUTLET.
JUNCTION BOX, WALL MOUNTED. MH = 1'-6" UNLESS OTHERWISE
NOTED OR INDICATED.
MOTOR RATED SWITCH
MOTOR DISCONNECT/SAFETY SWITCH. SWITCH SHALL BE RATED
30/3/NF/1 UNLESS OTHERWISE INDICATED WHERE:
'30' DENOTES SWITCH AMPERE RATING;
'3' DENOTES NUMBER OF POLES;
'NF' DENOTES NON-FUSED;
('F##' DENOTES FUSED AND FUSE RATING);
'1' DENOTES SWITCH ENCLOSURE'S NEAMA RATING.
FUSE RATING (WHEN INDICATED) SHALL BE IN ACCORDANCE WITH
EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.
T #
SPD
PANELBOARD - MH IN ACCORDANCE WITH NEC
DRY-TYPE TRANSFORMER
SURGE PROTECTIVE DEVICE
NEMA 5-20R DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLE, MOUNTED
IN 2-GANG FLOOR BOX.
NEMA 5-20R DUPLEX RECEPTACLE, MH=18" UOI. SUBSCRIPT 'X' (WHERE
PRESENT) DENOTES THE FOLLOWING:
G - DENOTES GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
RECEPTACLE
WP - DENOTES GFCI RECEPTACLE WITH WEATHER PROOF
WHILE-IN-USE HOUSING.
GC - DENOTES GFCI RECEPTACLE WITH BOTTOM OF
RECEPTACLE MOUNTED 2" ABOVE COUNTERTOP
BACKSPLASH.
E - DENOTES RECEPTACLE FOR ELECTRIC WATER COOLER.
COORDINATE MOUNTING WITH EQUIPMENT PROVIDED.
GROUND FAULT PROTECTION INDICATED BY NOTE.
TV - DENOTES RECPTACLE FOR TELEVISION. MOUNT ADJACENT
TO CATV OUTLET.
OS - DENOTES RECEPTACLE CONTROLLED BY ROOM
OCCUPANCY SENSORS VIA RECEPTACLE-RATED
SWITCHPACK. OUTLET SHALL BE MARKED IN ACCORDANCE
WITH NEC, ARTICLE 406.3(E).
R - DENOTES RECEPTACLE MOUNTED ABOVE
COMMUNICATIONS RACK. SEE DETAIL 1 ON EP501.
V - DENOTES RECEPTACLE FOR VENDING MACHINE; MOUNTING
HEIGHT 48" AFF; GFCI RECEPTACLE;
POWER & ELECTRICAL SYSTEMS LEGEND
FIRE PUMP MOTOR CONNECTION
MOTOR CONNECTION JUNCTION BOX. M
NEMA TYPE 14-30R FOR LAUNDRY DRYER EQUIPMENT. PROVIDE 3#10, 1
#12G IN 1/2" C.
NEMA TYPE 6-20R RECEPTACLE MOUNTED ABOVE COMMUNICATIONS
RACK PER DETAIL 1 ON EP501.
NEMA 5-20R DOUBLE DUPLEX RECEPTACLE, MH=18" UOI. SUBSCRIPTS
"X" IDENTIFIED FOR DUPLEX RECEPTACLES ARE APPLICABLE TO
DOUBLE DUPLEX (QUADRAPLEX) RECEPTACLES.
RECESSED 4-GANG POWER AND COMMUNICATIONS FLOOR BOX.
PROVIDE (2) NEMA 5-20R DUPLEX RECEPTACLES IN THE POWER
COMPARTMENT OF EACH FLOOR BOX.
RECESSED 8-GANG POWER AND COMMUNICATIONS FLOOR BOX.
PROVIDE (4) NEMA 5-20R DUPLEX RECEPTACLES IN THE POWER
COMPARTMENT OF EACH FLOOR BOX.
D R
TTB
CTB
FIRE-RETARDANT PLYWOOD BACKBOARD WITH NO ADDED UREA
FORMALDEHYDE. SEE SPECIFICATIONS 01 33 29 FOR FSC
CERTIFICATION REQUIREMENTS.
ps 3-POSITION SWITCH FOR PROJECTOR SCREEN. MH = 46" AFF UOI.
NEMA 5-20R SIMPLEX RECEPTACLE, MH=18" UOI. SUBSCRIPTS "X"
IDENTIFIED FOR DUPLEX RECEPTACLES ARE APPLICABLE TO SIMPLEX
RECEPTACLES.
GENERAL NOTES
1. SEE PLATE E-002 FOR ABBREVIATIONS AND TYPICAL MOUNTING HEIGHT
DIAGRAM.
2. MOUNTING HEIGHT, UNLESS OTHERWISE NOTED, IS TO CENTER LINE OF
EQUIPMENT.
3. PRESENSE OF SYMBOLS IN LEGEND DOES NOT INDICATE THAT A DEVICE OR
SYSTEM IS REQUIRED IN FACILITY CONSTRUCTION.
4. MOUNT OUTLET BOXES SO THAT NONE OCCUR BACK TO BACK IN WALLS.
5. MECHANICAL EQUIPMENT IS SHOWN IN APPROXIMATE LOCATIONS. FOR
EXACT LOCATIONS OF MECHANICAL EQUIPMENT AND PIPING, SEE
MECHANICAL DRAWINGS. PROVIDE DISCONNECT SWITCHES AS REQUIRED BY
THE NATIONAL ELECTRICAL CODE EVEN IF NOT INDICATED ON THE
ELECTRICAL DRAWINGS.
6. COORDINATE THE LOCATIONS AND MOUNTING HEIGHTS OF LIGHTING
FIXTURES IN MECHANICAL AND ELECTRICAL ROOMS WITH THE FINAL
LOCATIONS OF PIPES, DUCTS AND OTHER EQUIPMENT FOR BEST
ARRANGEMENT. FIXTURES SHALL BE EASILY ACCESSIBLE FOR RELAMPING.
7. CONDUCTOR AND CONDUIT SIZES ARE BASED ON COPPER CONDUCTORS
WITH THWN INSULATION IN EMT CONDUIT. CIRCUIT BREAKERS, TERMINALS,
ETC. SHALL BE RATED AND MARKED FOR 75 DEGREES MINIMUM. THE
CONTRACTOR SHALL ADJUST CONDUIT SIZES BASED ON ACTUAL TYPE OF
CONDUCTORS AND CONDUIT INSTALLED.
8. CIRCUIT NUMBERS ARE SHOWN ADJACENT TO ELECTRICAL DEVICES.
WIRING SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS
RECOMMENDATIONS AND/OR REQUIREMENTS.
9. ALL WIRING SHALL BE CONCEALED UNLESS INDICATED OTHERWISE.
CONDUITS SHALL NOT BE RUN IN ANY UL RATED SLAB.
10. REVISE PANELBOARD SCHEDULES ON AS-BUILT-DRAWING AND PANEL
DIRECTORIES TO REFLECT FINAL INSTALLATION CONDITIONS.
11. SEAL PENETRATIONS THROUGH ROOFS, CEILINGS, FLOORS, WALLS AND
FIRE WALLS TO MAINTAIN THE INTEGRITY OF THE AIR BARRIER, FIRE AND
ACOUSTIC RATINGS OF THE ROOF, CEILINGS, WALLS AND FLOORS.
12. COMPONENTS WHICH CONSTITUTE AN ELECTRICAL SYSTEM SHALL BE
FULLY COMPATIBLE WITH ONE ANOTHER AND SHALL BE APPROVED BY THE
VARIOUS MANUFACTURERS FOR USE WITH ALL OTHER COMPONENTS WITHIN
THE SYSTEM. (ONE EXAMPLE OF AN ELECTRICAL SYSTEM IS THE BUILDING
LIGHTING SYSTEM COMPRISED OF FIXTURES, LAMPS, SWITCHES, BALLASTS,
OCCUPANCY SENSORS AND DIMMING EQUIPMENT).
13. LOCATE ALL RACEWAYS TO AVOID INTERFERENCE WITH DUCTS, PIPES,
MECHANICAL EQUIPMENT, WITH REMOVAL OF CEILING TILES, OR WITH
ACCESS TO EQUIPMENT WHICH REQUIRES PERIODIC ADJUSTMENT OR
MAINTENANCE.
14. PROVIDE NAMEPLATES ON THE EXTERIOR OF ALL ELECTRICAL PANELS
AND ENCLOSURES AS FOLLOWS: DEVICE ID, DEVICE RATING, POWER SOURCE,
ARC FAULT DATA. ARC-FAULT DATA SHALL MEET 2015 NFPA 70E
REQUIREMENTS.
15. FOR DISCONNECT SWITCHES AND MOTOR STARTERS THE TOP LINE SHALL
BE THE NAME/DESIGNATION OF THE EQUIPMENT BEING FED BY THE
SWITCH/STARTER.
16. PROVIDE SEPARATE NEUTRALS FOR EACH CIRCUIT UTILIZING A NEUTRAL
CONDUCTOR. MULTI-WIRE CIRCUITS ARE NOT ALLOWED.
17. PROVIDE EQUIVALENT CONDUIT PATHWAYS WHERE CABLE TRAY IS
INTERRUPTED BY NONACCESSIBLE CEILINGS.
18. THE INTERRUPTING RATING OF THE PANELBOARDS AND ELECTRICAL
EQUIPMENT SHALL BE INCREASED TO THE NEXT AVAILABLE RATING WHERE
THERE IS NOT A RATING THAT IS EQUAL TO THE EQUIPMENT'S LISTED SHORT
CIRCUIT RATING.
19. PROVIDE GROUNDING CONDUCTORS IN ALL CONDUITS.
20. RACEWAYS CROSSING STRUCTURAL EXPANSION JOINTS OR SEISMIC
JOINTS SHALL BE PROVIDED WITH EXPANSION FITTINGS TO COMPENSATE
FOR THE BUILDING EXPANSION AND CONTRACTION AND TO PROVIDE FOR
CONTINUITY OF GROUNDING. EXPANSION FITTINGS SHALL HAVE AN INTEGRAL
BONDING JUMPER. ONLY FITTING LISTED AS EXPANSION TYPES WILL BE
CONSIDERED SUITABLE.
21. RECEPTACLES THAT HAVE GFI PROTECTION ARE TO BE WIRED SUCH
THAT THE LOSS OF POWER ON ONE RECEPTACLE DOES NOT AFFECT
DOWNSTREAM RECEPTACLES.
22. NOTE REMOVED
23. ALL EMPTY RACEWAYS AND JUNCTION BOXES SHALL HAVE PULL STRINGS
INSTALLED FOR USE TO INSTALL CABLES BY OTHERS.
TW
SYSTEM GROUND, SIZE IN ACCORDANCE WITH NEC ARTICLE 250
GROUND ROD, "TW" INDICATES TEST WELL
LIGHTNING PROTECTION ROOF CONDUCTORS. SEE DRAWINGS FOR
SIZE.
AIR TERMINAL; NUMBER DENOTES LENGTH OF AIR TERMINAL.
LIGHTNING PROTECTION COUNTERPOISE CONDUCTORS. SEE
DRAWINGS FOR SIZE.
LIGHTNING PROTECTION & GROUNDING SYSTEMS LEGEND
LIGHTNING PROTECTION DOWN CONDUCTORS. SEE DRAWINGS
FOR SIZE.
DOWN-CONDUCTOR IN CONDUIT CONCEALED IN EXTERIOR WALL.
12"
A AMPERES
ACS ACCESS CONTROL SYSTEM
AFF ABOVE FINISHED FLOOR
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CF/CI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CKT CIRCUIT
COR CONTRACTING OFFICER'S REPRESENTATIVE
CU COPPER
DMS DOOR MONITORING SYSTEM
DVI DIGITAL VIDEO INPUT
EF EXHAUST FAN
ELU EMERGENCY LIGHT UNIT
ESS ELECTRONIC SECURITY SYSTEM
EWC ELECTRIC WATER COOLER
FACP FIRE ALARM CONTROL PANEL
G, GND GROUND
GF/CI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GF/GI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HACR HEATING AND AIR CONDITIONING REFRIGERATION
HP HORSEPOWER
HZ HERTZ
IDS INTRUSION DETECTION SYSTEM
IMC INTERMEDIATE METAL CONDUIT
KWH KILOWATT HOUR
LED LIGHT EMITTING DIODE
LT LIGHT
LVS LOW VOLTAGE SWITCH
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT BREAKER
MFR MANUFACTURER
MH MOUNTING HEIGHT
MLO MAIN LUGS ONLY
MNS MASS NOTIFICATION SYSTEM
MTD MOUNTED
N.E.C. NATIONAL ELECTRICAL CODE
NEC NETWORK ENTERPRISE CENTER
NF NON-FUSED
NO., # NUMBER
NTS NOT TO SCALE
OS OCCUPANCY SENSOR
PH PHASE
PIR PASSIVE INFRARED
R/W RACEWAY
SER SERVICE ENTRANCE RATED
SPD SURGE PROTECTIVE DEVICE
SSMR STANDING-SEAM METAL ROOF
TR TELECOMMUNICATIONS ROOM
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
UL UNDERWRITERS LABORATORY
UOI UNLESS OTHERWISE INDICATED
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT-AMPERE
WP WEATHERPROOF
WWB WELDED-WIRE BASKET CABLE TRAY
XFMR TRANSFORMER
ABBREVIATIONS
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
FY20PN55516_BKS_LIGHT,POWER_R18_detached.rvt
3/18/2021 1:49:13 PM
D
EC
EM
BE
R
W
2H N
-2 1-
B-
S.
A
AR
O
N
S.
A
AR
O
N
S.
B
AR
BI
N A
1-
-0
E-001
EL
EC
TR
IC
AL
L
EG
EN
D
G
EN
ER
AL
N O
TE
S
SA
VA
N N
AH
D
IS
TR
IC
T
W . O
G
LE
TH
O
R
PE
A
VE
SA
VA
N
N
AH
, G A
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AI
T
BA
R
R
AC
KS
C
O M
PL
EX
, P H
FY
, P
N
VO
LU
M E
-B
AR
R
AC
KS
(P
LU
M
BI
N G
, M
EC
H
AN
IC
AL
, E
LE
C
TR
IC
AL
A N
D
TE
LE
C
O M
M U
N
IC
AT
IO
N
R . D
AV
IS
READY TO ADVERTISE (RTA)
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
M
AR
2 1
NOTES, TELECOMMUNICATIONS:
1. ALL TELECOMMUNICATIONS WORK SHALL MEET THE REQUIREMENTS OF UFC 3-580-01 FOR "INTERIOR", I3A CRITERIA FOR
"EXTERIOR", AND ANSI/TIA STANDARDS.
2. ALL 8P8C (RJ45 TYPE) CONNECTORS SHALL HAVE A DEDICATED UTP, 4-PAIR, #24 AWG COPPER CABLE, RATED CATEGORY 6 PER
ANSI/TIA 568-D.2 STANDARD.
3. ALL CATEGORY 6 CABLING INSTALLED UNDERGROUND, IN OR UNDER THE FIRST FLOOR SLAB, OR IN WET LOCATIONS SHALL BE
RATED FOR WET LOCATIONS.
4. FOR CATEGORY 6 CABLING, A MINIMUM OF 10 FEET OF CABLE SLACK SHALL BE PROVIDED AT THE TELECOMMUNICATIONS ROOM AND A MINIMUM OF 3 FEET OF CABLE SLACK SHALL BE PROVIDED ABOVE THE SUSPENDED CEILING FOR THE TELECOMMUNICATIONS OUTLET. THE REQUIRED CABLE SLACK LENGTHS ARE IN ADDITION TO THE TOTAL CABLE LENGTHS
REQUIRED TO REACH THE TELECOMMUNICATIONS OUTLETS.
5. BACK-TO-BACK OUTLET BOXES SHALL BE SPACED NOT LESS THAN 16" ON CENTER.
6. ALL CONDUIT TO TELECOMMUNICATIONS OUTLET BOXES (INCLUDING FLOOR BOXES) SHALL BE A MINIMUM OF 1" EMT UNLESS OTHERWISE INDICATED. CONDUITS SHALL BE CONCEALED IN CEILINGS AND WALLS, EXCEPT AS OTHERWISE INDICATED.
7. PULL BOXES SHALL BE PLACED IN CONDUIT RUNS WHERE A CONTINUOUS CONDUIT LENGTH EXCEEDS 100 FEET, OR WHERE THERE ARE MORE THAN TWO 90 DEGREE BENDS. PULL BOXES SHALL BE PLACED IN STRAIGHT, ALIGNED RUNS OF CONDUIT AND
NOT BE USED IN LIEU OF A BEND. PULLBOXES SHALL BE DIRECTLY ACCESSIBLE.
8. ALL TELECOMMUNICATIONS CABLE TRAY, CONDUITS, AND WIRING SHALL BE INSTALLED AND ROUTED IAW UFC 3-580-01, NEMA VE 2, NFPA 70, AND TIA STANDARDS. THESE CABLE TRAYS SHALL NOT BE USED TO RUN CABLING FOR CATV, FIRE ALARM/MASS NOTIFICATION, ETC. CABLE TRAYS SHALL ALSO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
9. RACEWAYS/CABLE TRAYS CROSSING STRUCTURAL EXPANSION JOINTS OR SEISMIC JOINTS SHALL BE PROVIDED WITH PROPER EXPANSION FITTINGS TO COMPENSATE FOR THE BUILDING EXPANSION AND CONTRACTION AND TO PROVIDE FOR CONTINUITY OF
GROUNDING.
10. PROVIDE PIPE SLEEVES FOR POWER AND COMMUNICATIONS ENTRANCE AND EXIT CONDUITS THROUGH SLABS AT THE TIME OF THE CONSTRUCTION OF THE SLAB. NO DRILLING OR PUNCHING THROUGH SLABS WILL BE ALLOWED.
11. SEAL PENETRATIONS THROUGH FLOORS AND FIRE WALLS TO MAINTAIN THE INTEGRITY OF THE FIRE AND ACOUSTIC RATINGS
OF THE WALLS AND FLOORS.
12. A MINIMUM OF 36 INCHES OF SPACE SHALL BE PROVIDED BOTH IN FRONT OF AND BEHIND THE RACK AND BEHIND ANY INSTALLED EQUIPMENT. PROVIDE 100 PERCENT SPARE RACK CAPACITY BASED ON THE AMOUNT OF RACK CAPACITY UTILIZED BY
THE PATCH PANELS PROVIDED.
13. INSTALL PLYWOOD BACKBOARDS WITH THE "A" SIDE FACING OUT. PLYWOOD BACKBOARDS SHALL NOT BE PAINTED.
BACKBOARDS SHALL BE SIGNED BY NEC QA/QC PRIOR TO INSTALLATION.
14. CAT6 OUTLETS SHALL UTILIZE TIA-568A PIN CONFIGURATION.
CABLE
GAUGE
CABLE SIZE
CABLE NUMBER
CABLE COUNT
100 PR 24 AWG
CA01 301-400
DOUBLE GANG
JACKS SHALL BE ARRANGED AND LABELED ACCORDING TO THEIR LOCATIONS IN A ROOM. THEY
SHALL BE ARRANGED CLOCKWISE IN ASCENDING ORDER AROUND THE ROOM WHILE STANDING
IN THE DOORWAY LOOKING INTO THE ROOM. FLOOR JACK NUMBER ARRANGEMENT SHOULD
WORK IN CLOCKWISE ORDER LOOKING OUT THE TR DOORWAY. THIS LABELING SCHEME
ADHERES TO THE REQUIRMENTS OUTLINED IN THE ANSI/TIA 606-C TELECOMMUNICATION
STANDARD.
TELECOMMUNICATIONS LABELING SCHEME
TELEPHONE OUTLET WITH MOUNTING PINS AND (1) CAT 6, 8P8C CONNECTOR.
MH = 60" UOI. SUBSCRIPT DENOTES THE FOLLOWING:
"IDS" - PROVIDE CONNECTION FOR IDS CONTROL PANEL.
"WP" - INDICATES A WEATHERPROOF WHILE-IN-USE COVER.
NIPR OUTLET WITH (4) NIPR CAT 6, 8P8C CONNECTORS. MH = 18" UOI.
NIPR OUTLET WITH (2) NIPR CAT 6, 8P8C CONNECTORS AND (2) BLANK POSITIONS.
MH = 18" UOI.
PROVIDE (1) CATEGORY 6, 8P8C (RJ45 TYPE) CONNECTOR. MH = 18" UOI. SUBSCRIPT
DENOTES THE FOLLOWING:
"2" - PROVIDE (2) CAT 6, 8P8C (RJ45 TYPE) CONNECTORS AND (2) BLANK POSITIONS
PROVIDE 4-PAIR CAT 6 CABLE IN 1-INCH CONDUIT FROM TELECOMMUNICATIONS ROOM TO
UMCS PANEL. ADDITIONALLY, PROVIDE 4-PAIR CAT 6 CABLE IN 1" CONDUIT FROM EACH
METER (ELEC, GAS, WATER) TO THE UMCS PANEL.
RECESSED 8-GANG POWER AND COMMUNICATIONS FLOOR BOX. PROVIDE (4) NIPR, (4)
ACN, AND (4) ULLS-A CAT 6, 8P8C CONNECTORS (AND 1 EMPTY GANG) IN THE
COMMUNICATIONS COMPARTMENT OF EACH FLOOR BOX. SEE E-001 FOR POWER
REQUIREMENTS.
RECESSED 4-GANG POWER AND NIPR COMMUNICATIONS FLOOR BOX. PROVIDE (4) DATA
CAT 6, 8P8C CONNECTORS (AND 1 EMPTY GANG) IN THE COMMUNICATIONS
COMPARTMENT OF EACH FLOOR BOX. SEE E-001 FOR POWER REQUIREMENTS.
CATV OUTLET CONSISTING OF ONE "F" CONNECTOR OUTLET. MH = 60" UOI.
3/4" A-C, VOID-FREE, FIRE-RETARDANT PLYWOOD BACKBOARD WITH NO ADDED UREA
FORMALDEHYDE. SEE SPECIFICATION 01 33 29 FOR FOREST STEWARDSHIP COUNCIL
(FSC) CERTIFICATION REQUIREMENTS. PLYWOOD SHALL BE SIGNED BY NEC QA/QC TO
ENSURE COMPLIANCE PRIOR TO INSTALLATION.
7-FT, 19-INCH ALUMINUM RACK WITH VERTICAL WIRE MANAGEMENT ASSEMBLY.
CABLE TRAY. TR'S SHALL HAVE CABLE RUNWAY. BASKET TYPE SHALL BE PROVIDED
ELSEWHERE UOI.
SIPRNET PROTECTIVE DISTRIBUTION (PDS) SYSTEM. MH = 8'-6" UOI.
4-INCH THROUGH WALL CONDUIT.
THROUGH FLOOR STUB UP OR CONDUIT SLEEVE.
PRIMARY BONDING BUSBAR, MH 18" AFF.
SECONDARY BONDING BUSBAR, MH 18" AFF.
JUNCTION BOX, WALL MOUNTED, MH 18" AFF UOI.
JUNCTION BOX, CEILING MOUNTED.
TELECOMMUNICATIONS LEGEND GENERAL NOTES
J
SBB
TR1-R1-PP1
TR1-R1-PP1
TERMINATION
LOCATIONS
TR1 - TR2
TV
J
PORT #
PATCH PANEL #
RACK #
TR ROOM #
PP1
OUTLET ROOM #
PORT #
RM 101
SPECIAL CIRCUITS (I.E.- IDS, ETC.) SHALL BE TERMINATED
ON THE 110 BLOCKS IN THE MAIN NIPR TR.
IDS
PATCH PANEL #
PATCH PANELS LABELING SCHEME
TR1-RR1-PP1
PATCH PANEL #
RACK #
TR ROOM #CABLE
GAUGE
CABLE SIZE
CABLE NUMBER
CABLE COUNT
12 FIBER SM
FC01 1-12
TERMINATION
LOCATIONS
TR1 - TR2
MMAC-1-X
PORT
CARD #
DEVICE
TR1-PP1-X
JACK #
PATCH PANEL #
TR ROOM #
CABLES SHALL BE LABELED WITHIN 12 INCHES OF THE END OF THE CABLE AND CABLE
IDENTIFIERS SHALL APPEAR TWO (2) TIMES ON THE LABEL FOR INCREASED VISIBILITY.
NOTES, TELECOMMUNICATIONS LABELING SCHEME:
1. LABEL MEDIA SHALL BE PRESSURE SENSITIVE AND CONSIST OF TWO PARTS: A LABEL FACE AND CLEAR ADHESIVE MATERIAL. EACH LABEL MUST CONTAIN A WHITE PRINTABLE AREA AND A CLEAR SELF-LAMINATING AREA THAT WILL WRAP AROUND THE CABLE AND LAMINATE THE WHITE
PRINTABLE AREA. EACH LABEL MUST BE MACHINE PRINTED AND HAVE BLACK PRINT OF THE
WHITE LABEL MATERIAL.
BACKBONE CABLES
LABELING SCHEME
PATCH CABLES LABELING
SCHEME
HORIZONTAL CABLES LABELING
SCHEME
OUTLETS LABELING SCHEME
JACKS SHALL BE COLOR CODED TO
MATCH THE CLASSIFICATION OF THE
NETWORK:
UMCS
AFF ABOVE FINISHED FLOOR
BBC BACKBONE BONDING CONDUCTOR
C CONDUIT
CAT CATEGORY
CATV CABLE TELEVISION
CKT CIRCUIT
CFCI CONTRACTOR-FURNISHED, CONTRACTOR-INSTALLED
COR CONTRACTING OFFICER'S REPRESENTATIVE
CU COPPER
FOC FIBER OPTIC CABLE
GFCI GOVERNMENT-FURNISHED, GOVERNMENT-INSTALLED
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFGI GOVERNMENT-FURNISHED, GOVERNMENT-INSTALLED
G GROUND
IAW IN ACCORDANCE WITH
MH MOUNTING HEIGHT
MTD MOUNTED
NEC NFPA 70, NATIONAL ELECTRICAL CODE, 2017
NIPR NON-SECURE INTERNET PROTOCOL ROUTER
NTS NOT TO SCALE
PBB PRIMARY BONDING BUSBAR
PP PATCH PANEL
SBB SECONDARY BONDING BUSBAR
SBC SECONDARY BONDING CONDUCTOR
SIPR SECURE INTERNET PROTOCOL ROUTER
SPD SURGE PROTECTIVE DEVICE
TBB TELECOMMUNICATIONS BONDING BACKBONE
TMGB TELECOMMUNICATIONS MAIN GROUND BAR
TGB TELECOMMUNICATIONS GROUND BAR
TR TELECOMMUNICATIONS ROOM
TYP TYPICAL
ULLS-A UNIT LEVEL LOGISTICS SYSTEM - AVIATION
UOI UNLESS OTHERWISE INDICATED
UON UNLESS OTHERWISE NOTED
VOIP VOICE OVER INTERNET PROTOCOL
W, WP WEATHERPROOF
ABBREVIATIONS
PBB
AUDIO VISUAL (AV) SYSTEM LEGEND
CEILING-MOUNTED HDMI OUTLET AND VGA OUTLET. PROVIDE EACH IN DEDICATED
1-1/4" CONDUIT WITH PULL STRINGS TO CORRESPONDING AV WALL OUTLETS.
WALL-MOUNTED HDMI OUTLET AND VGA OUTLET. PROVIDE EACH IN DEDICATED
CONDUIT WITH PULL STRINGS TO CORRESPONDING AV CEILIING. MH = 48" AFF UOI.
WALL MOUNTED 24"(H) X 24"(W) X 24"(D) AUDIO VISUAL (AV) ENCLOSURE. MH = 48"
SPECIAL SYSYEMS (SECURITY) SYSTEM LEGEND
DPS
DA
KP
MS
BMS
GFGI WALL MOUNTED SECURITY CAMERAS, FIXED MOUNTED.
GFGI CEILING MOUNTED SECURITY CAMERAS, FIXED MOUNTED.
UL 634 LEVEL 2 HIGH SECURITY SENSOR. PROVIDED WITH DOOR HARDWARE. PROVIDE
INFRASTRUCTURE AS INDICATED ON T-504 AND T-603.
GFGI CARD READER. PROVIDE INFRASTRUCTURE AS INDICATED ON T-603.
GFGI ACCESS CONTROL CABINET. POWER AND DATA CIRCUITS FOR CABINETS SHALL BE
CFCI.
GFGI BALANCED MAGNETIC SWITCH
GFGI KEY PAD.
GFGI PASSIVE INFRARED MOTION SENSOR
GFGI DURESS ALARM.
GFGI IDS CONTROL PANEL. PROVIDE CONDUIT TO JUNCTION BOX AT EACH IDS PANEL
DEVICE LOCATION. POWER AND DATA CIRCUIT FOR PANEL SHALL BE CFCI.
CR
ACS
IDS
AV
AV
AV
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
P:\Revit Projects\Gor0402 (PN55516)\Barracks\_Telework Working\07_Amendment 0002 Revit Files\FY20PN55516_BKS_TELCOMM_R18_TW Current.rvt3/18/2021 2:00:10 PM
D
EC
EM
BE
R
W
2H N
-2 1-
B-
J.
T
EL
LE
Z
J.
T
EL
LE
Z
S.
B
AR
BI
N A
1-
-0
T-001
TE
LE
C O
M M
U N
IC
AT
IO
N
S
LE
G
EN
D A
N D
G
EN
ER
AL
N O
TE
S
SA
VA
N N
AH
D
IS
TR
IC
T
W . O
G
LE
TH
O
R
PE
A
VE
SA
VA
N
N
AH
, G A
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AI
T
BA
R
R
AC
KS
C
O M
PL
EX
, P H
FY
, P
N
VO
LU
M E
-B
AR
R
AC
KS
(P
LU
M
BI
N G
, M
EC
H
AN
IC
AL
, E
LE
C
TR
IC
AL
A N
D
TE
LE
C
O M
M U
N
IC
AT
IO
N
R . D
AV
IS
READY TO ADVERTISE (RTA)
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
M
AR
2 1
BUILDING ACCESS CONTROL SYSTEM RISER DIAGRAM NOTES:
1. THE CONTRACTOR SHALL PROVIDE THE INFRASTRUCTURE FOR A GFGI BUILDING ACCESS CONTROL SYSTEM. CONTRACTOR SHALL ALSO FURNISH AND INSTALL UL 634 LEVEL 2 HIGH SECURITY SENSORS, ELECTRIC POWER TRANSFER (EPT), AND OTHER DEVICES INDICATED ON T-504. COORDINATE BUILDING ACCESS CONTROL SYSTEM WITH ARCHITECTURAL DRAWINGS AND DOOR HARDWARE
SPEC 08 71 00.
2. SLEEPING ROOM ACCESS CONTROL SHALL BE A CFCI SYSTEM AND SHALL BE A STANDALONE SYSTEM FOR EACH SLEEPING ROOM
DOOR AS INDICATED IN DOOR HARDWARE SPEC 08 71 00.
DOOR CONTROLLER
BUILDING ACCESS CONTROL SYSTEM
ENCLOSURE
ROOM 1108A
RS-485
DATA NETWORK
DOOR 1
DOOR 2
DOOR 3
DOOR 4
DOOR 5
DOOR 6
DOOR 7
DOOR 8
POWER SUPPLY
BATTERY
DOOR CONTROLLER
RS-485
DOOR 1
DOOR 2
DOOR 3
DOOR 4
DOOR 5
DOOR 6
DOOR 7
DOOR 8
RS-485
POWER SUPPLY
BATTERY
(1) DPS
DOOR 1000B
(1) DPS
DOOR 1000C
(1) DPS
DOOR 1000O
(1) DPS
DOOR 1000P
CARD READER
ELECTRIC LATCH
(2) DPS
DOOR 1000I
CARD READER
ELECTRIC LATCH
(2) DPS
DOOR 1000A
(2) DPS
DOOR 1000H
DOOR 1000G
(2) DPS
DOOR 1000F
DOOR 201
DOOR 1000M
TO ACS WORKSTATION VIA
DATA OUTLET
DOOR CONTROLLER
BUILDING ACCESS CONTROL SYSTEM
ENCLOSURE
ROOM 1108A
RS-485
DATA NETWORK
DOOR 1
DOOR 2
DOOR 3
DOOR 4
DOOR 5
DOOR 6
DOOR 7
DOOR 8
RS-485
POWER SUPPLY
BATTERY
DOOR CONTROLLER
RS-485
DOOR 1
DOOR 2
DOOR 3
DOOR 4
DOOR 5
DOOR 6
DOOR 7
DOOR 8
RS-485
POWER SUPPLY
BATTERY
TO ACS WORKSTATION VIA
DATA OUTLET
(1) DPS
DOOR 1000J
(2) DPS
(1) DPS
CARD READER
ELECTRIC LATCH
(2) DPS
DOOR 101
DOOR 102
DOOR 103
DOOR 104
(1) DPS
CARD READER
ELECTRIC LATCH
(1) DPS
CARD READER
ELECTRIC LATCH
(1) DPS
(1) DPS
DOOR 202
(1) DPS
DOOR 203
(1) DPS
DOOR 204
(1) DPS
DOOR 301
(1) DPS
DOOR 302
(1) DPS
DOOR 303
(1) DPS
DOOR 304
(1) DPS
DOOR 401
(1) DPS
DOOR 402
(1) DPS
DOOR 403
(1) DPS
DOOR 404
(1) DPS
DOOR 501
(1) DPS
DOOR 502
(1) DPS
DOOR 503
(1) DPS
DOOR 504
(1) DPS
DOOR 1000D
DOOR CONTROLLER
BUILDING ACCESS CONTROL SYSTEM
ENCLOSURE
ROOM 1108A
RS-485
DATA NETWORK
DOOR 1
DOOR 2
DOOR 3
DOOR 4
DOOR 5
DOOR 6
DOOR 7
DOOR 8
RS-485
POWER SUPPLY
BATTERY
DOOR CONTROLLER
RS-485
DOOR 1
DOOR 2
DOOR 3
DOOR 4
DOOR 5
DOOR 6
DOOR 7
DOOR 8
POWER SUPPLY
BATTERY
TO ACS WORKSTATION VIA
DATA OUTLET
(2) DPS
DOOR 1000N
(2) DPS
DOOR 1092
(1) DPS
DOOR 1105
(1) DPS
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
P:\Revit Projects\Gor0402 (PN55516)\Barracks\_Telework Working\07_Amendment 0002 Revit Files\FY20PN55516_BKS_TELCOMM_R18_TW Current.rvt3/18/2021 1:58:55 PM
D
EC
EM
BE
R
W
2H N
-2 1-
B-
J.
T
EL
LE
Z
J.
T
EL
LE
Z
S.
B
AR
BI
N A
1-
-0
T-603
C O
M M
R
IS
ER
D
IA
G
R
AM
S -B
U
IL
D
IN
G A
C C
ES
S
C O
N
TR
O L
SY
ST
EM
SA
VA
N N
AH
D
IS
TR
IC
T
W . O
G
LE
TH
O
R
PE
A
VE
SA
VA
N
N
AH
, G A
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AI
T
BA
R
R
AC
KS
C
O M
PL
EX
, P H
FY
, P
N
VO
LU
M E
-B
AR
R
AC
KS
(P
LU
M
BI
N G
, M
EC
H
AN
IC
AL
, E
LE
C
TR
IC
AL
A N
D
TE
LE
C
O M
M U
N
IC
AT
IO
N
R . D
AV
IS
READY TO ADVERTISE (RTA)
BUILDING ACCESS CONTROL SYSTEM RISER DIAGRAM1
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
M
AR
2 1
EXISTING
PH-GLP-2
EXISTING
PH-GLP-1
EXISTING
PH-GLP-6
EXISTING
PH-GLP-5
EXISTING
PH-GLP-4
EXISTING
PH-GLP-3
EXISTING
PH-ET-4
EXISTING
PH-ET-6
EXISTING
PH-ET-1
EXISTING
PH-ET-2
EXISTING
PH-ET-3
EXISTING
PH-ET-5
EXISTING
PH-BT-1
EXISTING
PH-AS-2
EXISTING
PH-AS-1
EXISTING
PH-AS-6
EXISTING
PH-AS-5
EXISTING
PH-AS-4
EXISTING
PH-AS-3
EXIST. 6" GSS
EXIST. 6" GSR
EXIST. 6" GSS
EXIST. 6" GSR
EXISTING
6" GSS&R TO
WELL FIELD 1
EXISTING
6" GSS&R TO
WELL FIELD 2
EXISTING
6" GSS&R TO
WELL FIELD 6
EXISTING 6"
GSS&R TO
WELL FIELD 5
EXISTING
8" GSS&R TO
WELL FIELD 4
EXISTING
6" GSS&R TO
WELL FIELD 3
EXISTING
8" GSS&R TO
PH. 2 B/COF.
SHUT OFF
VALVES
(TYP)
EXISTING DDC PANELS
EXISTING
CHEMICAL
FEED TANK
2 1/2" GSS&R
TO PHASE 3
BN HQ. SEE
MS101 FOR
CONT.
8" GSS&R TO PHASE 3
B/COF. SEE MS101
FOR CONTINUATION
CTP-1
NEW 6" GSS
NEW 6" GSR
EXIST. 6" GSS
EXIST. 6" GSR
EXIST. 6" GSS
EXIST. 6" GSR
EXIST. 8" GSS
EXIST. 8" GSR
EXIST. 6" GSS
EXIST. 6" GSR
NEW 6" GSS&R TO
NEW COOLING
TOWER. SEE MS101
FOR CONTINUATION
CONNECT NEW 6"
GSS&R PIPING TO
EXISTING VALVES
NEW DDC PANEL
NEW CHEMICAL TREATMENT
FEED SYSTEM (CTFS-1)
TO CT-1
CHEMICAL TREATMENT
LINES TO CLOSED
CIRCUIT COOLER
WATER BASIN, SEE
MP401X FOR CONT.
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
US Army Corps of Engineers ®
D
C
B
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
E
F
G
2 3 4 5 6 7 8 9 10
C:\Users\K6ENXSWW\Desktop\Tele-Work Revit Projects\Gor0402 (PN55516) BKS\FY20_PN55516_BKS PUMPHOUSE_MECH_R18_TW Current.rvt3/11/2021 9:08:30 AM
D
EC
EM
BE
R
W
2H N
-2 1-
B-
S.
W
YL
LI
E
S.
W
YL
LI
E
S.
B
AR
BI
N A
1-
-0
MP101X
PU
M
P H
O U
SE
H
YD
R
O N
IC
P
IP
IN
G P
LA
N
SA
VA
N N
AH
D
IS
TR
IC
T
W . O
G
LE
TH
O
R
PE
A
VE
SA
VA
N
N
AH
, G A
FO
R
T G
O R
D O
N , G
EO
R
G
IA
AI
T
BA
R
R
AC
KS
C
O M
PL
EX
, P H
FY
, P
N
VO
LU
M E
-B
AR
R
AC
KS
(P
LU
M
BI
N G
, M
EC
H
AN
IC
AL
EL
EC
TR
IC
AL
A N
D T
EL
EC
O M
M U
N
IC
AT
IO
N
K.
D
IX
O
N
READY TO ADVERTISE (RTA)
PUMP HOUSE PIPING PLAN1
PLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
M
AR
| P-001 PLUMBING LEGEND |
| E-001 ELECTRICAL LEGEND & GENERAL NOTES |
| T-001 TELECOMMUNICATIONS LEGEND AND GENERAL NOTES |
| T-603 COMM RISER DIAGRAMS - BUILDING ACCESS CONTROL SYSTEM |
| MP101X PUMP HOUSE HYDRONIC PIPING PLAN |
File details come from the government source that posted it. Updated .