RFI-11 - M-501 - MECHANICAL DETAILS.pdf
PDF 51 KB Posted
- Solicitation number
- W912DS26BA032
About this file
This is a mechanical details drawing for a natural gas pressure regulator and meter assembly for a power generation project with microgrid at Joint Base McGuire-Dix-Lakehurst, New Jersey. The drawing, designated M-501 and prepared by Burns and McDonnell for the US Army Corps of Engineers New York District, specifies the installation and configuration of natural gas infrastructure to support generators.
The technical requirements include a 2-inch natural gas pressure regulator with a 14,000 cubic feet per hour capacity and 1 PSI outlet pressure, a gas cock, gas meter, gas strainer, drip leg, gas relief valve piped to atmosphere, and a gas supply pressure reducing valve calibrated to 10 to 20 inches of water column or per generator manufacturer specifications. The contractor must provide two meters: one New Jersey Natural Gas Company meter and one AF pulse meter kit with 2-wire Form A pulse output via exterior-rated RS485 cable, including upstream gasket strainers and white-on-black phenolic labels with cable protection by conduit. The regulator assembly must be installed near the generators per civil drawing CS112, with the contractor responsible for confirming the regulator assembly layout and pad size with the utility provider and ensuring final gas train assembly compliance with the generator manufacturer's specifications. The drawing was originally submitted in July 2026 and revised for bidder inquiries in September 2026.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GAS COCK
GAS COCK
GAS
METER
PRESSURE REGULATOR,
1 PSI OUTLET PRESSURE
2" NG
14,000 CFH
CAPACITY
GRADE
NOTES:
1. INSTALL THE GAS REGULATOR ASSEMBLY NEAR THE GENERATORS. REFER
TO CIVIL CS112 SHEET FOR MORE INFORMATION.
2. CONTRACTOR TO CONFIRM NATURAL GAS REGULATOR ASSEMBLY LAYOUT
WITH THE UTILITY PROVIDER.
3. CONTRACTOR TO CONFIRM REGULATOR ASSEMBLY PAD SIZE WITH THE
UTILITY PROVIDER.
4. CONTRACTOR SHALL PROVIDE TWO METERS, ONE METER IS THE NJNG CO
METER AND THE SECOND IS THE AF PULSE METER KIT.
A. AF GAS METER WITH PULSE OUTPUT. PULSE KIT MUST PRODUCE 2
WIRE (FORM A) PULSE OUTPUT VIA EXTERIOR RATED RS485 CABLE.
MUST INCLUDE A VISUAL RESISTER ON DIAL. METER SHALL INCLUDE
UPSTREAM GASKET STRAINERS. LABELS SHALL BE WHITE ON BLACK
PHENOLIC. CABLE SHALL BE PROTECTED BY CONDUIT.
TO AMRS ELETRIC METER
SEE NOTE 4
1" AFF MINIMUM
GAS RELIEF VALVE
PIPED TO ATMOSPHERE
GAS SUPPLY PRESSURE REDUCING
VALVE. PROVIDE PRESSURES
BETWEEN 10" TO 20" W.C. OR PER
GENERATOR MANUFACTURER'S
REQUIREMENTS.
GAS STRAINER
DRIP LEG
GAS SERVICE
CONNECTION
S
TO GENERATOR
NOTES:
1. DETAIL IS PROVIDED FOR REFERENCE OF
MINIMUM REQUIREMENTS. PROVIDE GAS
TRAIN ASSEMBLY TO MEET FINAL GENERATOR
MANuFACTURER'S REQUIREMENTS.
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K
A N
S A
S C
IT
Y
M
O
A L T
E R
N A
T E
I N
F O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J O
IN
T
-B A
S E
M C
G U
IR
E
-D
IX
-L A
K E
H U
R S
T N
J P
O W
E R
G E
N E
R A
T
IO
N W
IT
H
M
IC
R O
G R
ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S N
E W
Y O
R K
D
IS
T R
IC
T
F
E D
E R
A L P
L A
Z A
R
M
-3
N E
W Y
O R
K N
Y
-0
R E
V
IS
E D
F O
R B
ID
D
E R
I N
Q U
IR
IE
S
M-501
M E
C H
A N
IC
A
L D
E T
A
IL
S
C U
T T
M C
R A
IN
T L A
G O
N
IK
O S
C U
T T
J U
L Y
SCALE: NTS
J14
NATURAL GAS PRESSURE REGULATOR WITH METER
SCALE: NTS
J1
NATURAL GAS GENERATOR CONNECTION
R
T A
S U
B M
IT
T
A L
J U
L Y
R
E V
IS
E
D F
O R
B
ID
D E
R I N
Q U
IR
IE
S S
E P
T
File details come from the government source that posted it. Updated .