This document outlines the sequences of operation for HVAC control systems and components to be installed under a firm fixed price contract for Repair Building 785 at the United States Military Academy in West Point, NY. The contract is solicited by the U.S. Army Corps of Engineers New York District to provide a Defense Health Agency/Medical Command-certified Dental Clinic for the U.S. Army Dental Activity Command. The document specifies sequences of operation for air handling units, terminal units including VAV boxes and radiation, and hydronic systems. It defines occupancy schedules, control loops, setpoints, and safeties for various HVAC equipment.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPAIR BUILDING 785, DENTAC 31800173.001
WEST POINT, NY
SECTION 23 09 93
SEQUENCES OF OPERATION FOR HVAC CONTROL
11/15
PART 1 GENERAL
1.1 DEFINITIONS
For definitions related to this Section, see Section 23 09 00
INSTRUMENTATION AND CONTROL FOR HVAC.
1.2 SUBMITTALS
Submittals related to this Section are specified in Section 23 09 00
INSTRUMENTATION AND CONTROL FOR HVAC.
PART 2 PRODUCTS
Products related to this Section are specified in Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC and related Sections 23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC and 23 09 23.01 LONWORKS
DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL SYSTEMS.
PART 3 EXECUTION
Sequences of Operation are defined on the Drawings as well as in this Section.
3.1 SEQUENCES OF OPERATION FOR OCCUPANCY SCHEDULING
3.1.1 System Scheduler Requirements
The System Scheduler functionality must reside in either a piece of DDC Hardware dedicated to this functionality or in the DDC Hardware controlling the system AHU. A single piece of DDC Hardware dedicated to scheduling (performing no other control functionality) may contain multiple System Schedulers. Provide a unique System Scheduler for: each AHU including it's associated Terminal Units, and each stand-alone Terminal Unit (those not dependent upon AHU service). Each System Scheduler must provide the following functionality:
3.1.1.1 Scheduled Occupancy Input
Accept network variable of type SNVT_occupancy. Support the following possible values: OC_STANDBY, OC_OCCUPIED and OC_UNOCCUPIED.
3.1.1.2 Occupancy Override Input
Accept network variable of type SNVT_occupancy. Support the following possible values: OC_STANDBY, OC_OCCUPIED, OC_UNOCCUPIED, and OC_NUL.
3.1.1.3 Space Occupancy Inputs
For systems with multiple occupancy sensors, accept multiple inputs of network variable type SNVT_Occupancy. Support the following possible values: OC_OCCUPIED, OC_UNOCCUPIED, and OC_NUL. For systems with a
SECTION 23 09 93 Page 1 single occupancy sensor, accept a network variable input of type SNVT_Occupancy or a hardware binary input (BI) indicating the space occupancy status as Occupied or Unoccupied.
3.1.1.4 Air Handler Occupancy Output
For a System Scheduler for a system containing an air handler, output one or more SNVTs indicating the desired occupancy status as one of the following possible values: Warm-Up-Cool-Down (when required by the AHU Sequence of Operation), Occupied and Unoccupied.
3.1.1.5 Terminal Unit Occupancy Output
For a System Scheduler for a stand-alone terminal unit or a group of terminal units served by a single air handler, output one or more SNVTs indicating the desired occupancy status as one of the following possible values: Occupied and Unoccupied.
3.1.1.6 Default Schedule
Incorporate a 24-hour 7-day default schedule as shown on the drawings which may be activated and deactivated by the System Scheduler Logic.
3.1.1.7 Communication Determination
Determine the time elapsed between receipts of the scheduled occupancy input SNVT, and use this elapsed time to activate and deactivate the Default Schedule as specified. (This provides the capability for the system scheduler to use its Default Schedule if it loses communication with the UMCS).
3.1.2 System Scheduler Output Determination
For controlling an Air Handler, interpret a SNVT input of OC_STANDBY as Warm-Up-Cool-Down if the sequence of operation supports that mode, otherwise interpret OC_STANDBY as Occupied. For Terminal Units, interpret OC_STANDBY as Occupied.
3.1.2.1 Air Handler Occupancy Output
If more than 95 minutes have passed since the last receipt of the Scheduled Occupancy input, determine the Air Handler Occupancy Output by the default schedule and the Space Occupancy Inputs. Otherwise, determine the output as follows:
a. If the Override Occupancy Input is not OC_NUL, determine the Air Handler Occupancy Output from the Override Occupancy Input.
b. Otherwise, if at least the required number (as shown on the Occupancy Schedule Drawing) of Space Occupancy Inputs are OC_OCCUPIED or the hardware BI is Occupied the Air Handler Occupancy Output must be
OC_OCCUPIED.
c. Otherwise, determine the Air Handler Occupancy Output from the Scheduled Occupancy Input SNVT.
3.1.2.2 Terminal Unit Occupancy Output
If more than 95 minutes have passed since the last receipt of the
SECTION 23 09 93 Page 2
Scheduled Occupancy input, determine the Terminal Unit Occupancy Output by the default schedule. Otherwise, determine the output as follows:
a. If the Override Occupancy Input is not OC_NUL, determine the Terminal Unit Occupancy Output from the Override Occupancy Input SNVT:
b. Otherwise, determine the Terminal Unit Occupancy Output from the Scheduled Occupancy SNVT.
3.1.3 Air Handler System Scheduling
a. Bind the AHU Occupancy Output SNVT from the System Scheduler to the DDC Hardware that executes the Occupancy Mode Determination part of the Air Handler Sequence of Operation
b. For Air Handlers using occupancy sensors, bind the output SNVT (of type SNVT_Occupancy) of each occupancy sensor to a Space Occupancy Input of the System Scheduler.
c. Bind the Terminal Unit Occupancy Output SNVT from the System Scheduler to each AHU-Dependent Terminal Unit.
d. AHU-Dependent Terminal Units with occupancy sensors must have the Effective Occupancy SNVT (of type SNVT_Occupancy) of each Terminal Unit bound to a Space Occupancy Input of the System Scheduler.
3.1.4 Stand-Alone Terminal Unit Scheduling
Bind the Terminal Unit Occupancy Output from the System Scheduler to the DDC Hardware that executes the Occupancy Mode Determination part of the Terminal Unit Sequence of Operation.
3.2 SEQUENCES OF OPERATION FOR AIR HANDLING UNITS
3.2.1 Variable Air Volume System with Return Fan
Install DDC hardware to perform this Sequence of Operation and to provide SNVT inputs and outputs as specified and shown on the Points Schedule.
Unless otherwise specified, all modulating control shall be proportional-integral (PI) control.
3.2.1.1 HAND-OFF-AUTO Switches
Supply fan variable frequency drive (VFD) unit shall accept a Fire Alarm Panel (FAP) signal that takes precedence over all other VFD inputs and switches and shall cause the VFD to run at 100 percent speed. The VFD shall accept an occupant accessible emergency shutoff switch as shown.
The supply fan variable frequency drive (VFD) unit shall have an integral H-O-A switch:
3.2.1.1.1 HAND
With the H-O-A switch in HAND position, the supply fan shall start and run continuously, subject to Safeties. Fan speed shall be under manual-operator control.
3.2.1.1.2 OFF
With the H-O-A switch in OFF position, the supply fan shall stop.
SECTION 23 09 93 Page 3
3.2.1.1.3 AUTO
With the H-O-A switch in AUTO position, the supply fan shall run subject to the Supply Fan Start/Stop Signal (SF-SS) and Safeties. Fan speed shall be under control of the DDC Hardware.
3.2.1.2 Return Fan Variable Frequency Drive
Return fan variable frequency drive (VFD) unit shall accept a Fire Alarm Panel (FAP) signal that takes precedence over all other VFD inputs and switches and shall cause the VFD to run at 100 percent speed. The return fan variable frequency drive (VFD) unit shall have an integral H-O-A switch:
3.2.1.2.1 HAND
With the H-O-A switch in HAND position, the return fan shall run subject to Safeties. Fan speed shall be under manual-operator control.
3.2.1.2.2 OFF
With the H-O-A switch in OFF position, the return fan shall be off.
3.2.1.2.3 AUTO
With the H-O-A switch in AUTO position, the return fan shall run subject to the supply fan running. Fan speed shall be under control of the DDC Hardware.
3.2.1.3 Occupancy Modes
The system shall obtain its Occupancy Mode input from the System Scheduler as specified and shown. The system shall operate in one of the following modes: Occupied, Unoccupied, or Warm Up/Cool Down.
3.2.1.4 Proofs and Safeties
The supply fan, return fan, and all DDC Hardware control loops shall be subject to Proofs and Safeties. Safeties shall be direct-hardwire interlocked to the VFD as shown. DDC Hardware shall monitor all proofs and safeties and failure of any proof or activation of any safety shall result in all control loops being disabled and the AHU fan being commanded off until reset.
3.2.1.4.1 Proofs
a. Supply fan status (SF-S)
b. Return fan status (RF-S)
3.2.1.4.2 Safeties
a. Preheat coil discharge air temperature low limit (freezestat) (PH-DA-T-LL) for systems with a preheat coil. Cooling coil discharge air temperature low limit (freezestat) (CLG-DA-T-LL) for all other systems
b. Supply air duct pressure high limit (SA-P-HL)
SECTION 23 09 93 Page 4
c. Supply air smoke (SA-SMK)
d. Return air smoke (RA-SMK)
3.2.1.4.3 DDC Hardware Reset
DDC Hardware reset of all proofs and safeties shall be via a local binary push-button (RST-BUT) input to the DDC Hardware, via a remote command to the DDC Hardware via SNVT or both (where the Contractor provides both reset functions and the operator can use either one to perform the reset), as shown on the Points Schedule drawing.
3.2.1.5 System Enable and Loop Enable
3.2.1.5.1 Occupied Mode
The supply fan shall be enabled (SYS-ENA) and commanded to run (SF-SS).
All control loops shall be enabled.
3.2.1.5.2 Unoccupied Mode
While the building temperature (BLDG-T) is above the low limit setpoint (BLDG-T-LL) all control loops shall be disabled and the supply fan shall not run. When BLDG-T drops below BLDG-T-LL (with a 5 degrees F deadband) the supply fan shall be enabled (SYS-ENA) and commanded to run (SF-SS), the Supply Duct Static Pressure Control, Return Fan Volume Control, Preheat Control loops shall be enabled. The Minimum Outside Air Flow Control, Mixed Air Temperature Control, and Cooling Coil Control loops shall be disabled.
3.2.1.5.3 Warm Up/Cool Down
The supply fan shall be enabled (SYS-ENA) and commanded to run (SF-SS).
The Minimum Outside Air Flow Control loop shall be disabled and all other control loops shall be enabled.
3.2.1.6 Fan Capacity Control
3.2.1.6.1 Supply Duct Static Pressure Control
When this loop is enabled the DDC Hardware shall modulate the supply fan variable frequency drive unit to maintain the duct static pressure (SA-P) at setpoint (SA-P-SP) as shown, as measured by the duct static pressure tap and sensor as shown. When this loop is disabled, the DDC Hardware capacity modulation output to the VFD shall be zero percent.
3.2.1.6.2 Return Fan Volume Control
When this loop is enabled the DDC Hardware shall modulate the return fan variable frequency drive unit to maintain a constant volumetric airflow difference at setpoint (F-DIFF-SP) as shown, as measured by the airflow measurement arrays located in the supply and return ducts as shown. When this loop is disabled, the output to the VFD shall be zero percent.
3.2.1.7 Minimum Outside Air Flow Control
When this loop is enabled the DDC Hardware shall modulate the minimum outside air damper to maintain the minimum OA volumetric flow (MINOA-F) at
SECTION 23 09 93 Page 5 setpoint (MINOA-F-SP) as shown. When this loop is disabled, the minimum outside air damper shall be closed.
3.2.1.8 Mixed Air Temperature Control With Economizer
3.2.1.8.1 Enabled Loop
When this loop is enabled, and the Economizer is ON as determined by the Economizer Enable Logic, the DDC Hardware shall modulate the economizer outside air, relief, and return air dampers to maintain the mixed air temperature (MA-T) at setpoint (MA-T-SP) as shown.
3.2.1.8.2 Disabled Loop
When this loop is disabled, or the Economizer is OFF as determined by the Economizer Enable Logic, the economizer outside air and relief air dampers shall be closed, and the return air damper shall be open.
3.2.1.8.3 Economizer Enable Logic
The economizer shall be ON when the outside air dry bulb temperature is between the high limit (ECO-HL-SP) and low limit (ECO-LL-SP) setpoints as shown. The Economizer shall otherwise be OFF. ECO-HL-SP and ECO-LL-SP shall each have a 2 degrees F deadband.
3.2.1.9 Cooling Coil Control
When this loop is enabled the DDC Hardware shall modulate the cooling coil valve to maintain the supply air temperature (SA-T) setpoint (SA-T-SP) as shown. When this loop is disabled, the cooling coil valve shall be closed.
3.2.1.10 Preheat Coil Control
When this loop is enabled the DDC Hardware shall modulate the preheat coil valve to maintain the preheat coil discharge air temperature (PH-DA-T) at setpoint (PH-DA-T-SP) as shown. When this loop is disabled, the preheat coil valve shall be closed.
3.3 SEQUENCES OF OPERATION FOR TERMINAL UNITS
3.3.1 Zone Temperature Control - Cooling-Only VAV Box
Install DDC hardware to perform this Sequence of Operation and to provide SNVT inputs and outputs as specified and shown on the Points Schedule.
Unless otherwise specified, all modulating control shall be proportional-integral (PI) control.
3.3.1.1 Occupancy Modes
3.3.1.1.1 Occupied
The VAV box DDC Hardware shall be in the Occupied Mode when the local space occupancy input(s) (ZN-OCC) indicate that the space is occupied or when the input from the System Scheduler (SYS-OCC) is occupied.
3.3.1.1.2 Unoccupied
The VAV box DDC Hardware must be in the Unoccupied Mode when the local space occupancy input(s) (ZN-OCC) indicate that the space is unoccupied
SECTION 23 09 93 Page 6 and the input from the System Scheduler (SYS-OCC) is unoccupied.
Safeties
This system has no safeties.
3.3.1.2 Zone Temperature Control
3.3.1.2.1 Occupied Mode
In the Occupied Mode the zone temperature setpoint (ZN-T-SP) must be at the configured setpoint or at the occupant-adjustable setpoint via the wall-mounted thermostat, as shown. The DDC Hardware must modulate the VAV box damper to maintain VAV box supply air flow (VAV-SA-F) at setpoint as measured by a multi-point flow sensing element at the inlet to the VAV box. Sequence as indicated: Upon a rise in zone temperature (ZN-T) above zone setpoint (ZN-T-SP), subject to the zone temperature setpoint deadband as indicated, adjust the airflow setpoint between minimum and maximum flow based on the difference between zone temperature and zone temperature setpoint as indicated.
3.3.1.2.2 Unoccupied Mode
In the Unoccupied Mode the VAV box damper shall be at its minimum position.
3.3.2 Zone Temperature Control - VAV Box with Reheat
Install DDC hardware to perform this Sequence of Operation and to provide SNVT inputs and outputs as specified and shown on the Points Schedule.
Unless otherwise specified, all modulating control shall be proportional-integral (PI) control.
3.3.2.1 Occupancy Modes
3.3.2.1.1 Occupied
The VAV box DDC Hardware shall be in the Occupied Mode when the local space occupancy input(s) (ZN-OCC) indicate that the space is occupied or when the input from the System Scheduler (SYS-OCC) is occupied.
3.3.2.1.2 Unoccupied
The VAV box DDC Hardware shall be in the Unoccupied Mode when the local space occupancy input(s) (ZN-OCC) indicate that the space is unoccupied and the input from the System Scheduler (SYS-OCC) is unoccupied.
3.3.2.2 Safeties
VAV boxes with electric resistance heating elements shall require proof of air flow before activating the heating elements.
3.3.2.3 Zone Temperature Control
a. In the Occupied Mode the zone temperature setpoint (ZN-T-SP) shall be at the configured setpoint or at the occupant-adjustable setpoint via the wall-mounted thermostat, as shown.
b. In the Unoccupied Mode the zone temperature setpoint (ZN-T-SP) shall be at the configured setpoint as shown.
SECTION 23 09 93 Page 7
c. The DDC Hardware shall modulate the VAV box damper to maintain VAV box supply air flow (VAV-SA-F) at setpoint as measured by a multi-point flow sensing element at the inlet to the VAV box. Sequencing shall be as shown: Upon a rise in zone temperature above zone temperature setpoint (ZN-T-SP), subject to the zone temperature setpoint deadband as shown, the airflow setpoint shall be adjusted between minimum and maximum flow based on the difference between zone temperature and zone temperature setpoint as shown. Upon a fall in zone temperature below zone temperature setpoint, subject to the deadband as shown, the airflow shall be maintained at a fixed air flow setpoint (with a setting independent of the cooling minimum air flow), and the heating valve shall modulate towards open or the staged electric resistance heating coil(s) shall cycle on in sequence.
3.3.3 Perimeter Radiation Control Sequence
Install DDC hardware to perform this Sequence of Operation and to provide SNVT inputs and outputs as specified and shown on the Points Schedule.
Unless otherwise specified, all modulating control shall be proportional-integral (PI) control.
3.3.3.1 Occupancy Modes
3.3.3.1.1 Occupied
The radiator DDC Hardware shall be in the Occupied Mode when the local space occupancy input(s) indicate that the space is occupied or when the input from the System Scheduler is occupied.
3.3.3.1.2 Unoccupied
The radiator DDC Hardware shall be in the Unoccupied Mode when the local space occupancy input(s) indicate that the space is unoccupied and when the input from the System Scheduler is unoccupied.
3.3.3.2 Safeties
This system has no safeties.
3.3.3.3 Space Temperature Control
3.3.3.3.1 Occupied Mode
In the Occupied Mode the DDC Hardware shall modulate the heating control valve to maintain space temperature at the configured setpoint or at the occupant-adjustable setpoint via the wall-mounted thermostat, as shown.
3.3.3.3.2 Unoccupied Mode
In the Unoccupied Mode the DDC Hardware shall modulate the heating control valve to maintain space temperature at the configured setpoint as shown.
3.3.4 Unit Heater and Cabinet Unit Heater
Install DDC hardware to perform this Sequence of Operation and to provide SNVT inputs and outputs as specified and shown on the Points Schedule.
Unless otherwise specified, all modulating control shall be proportional-integral (PI) control.
SECTION 23 09 93 Page 8
3.3.4.1 Off-Auto Switch
3.3.4.1.1 OFF
With the thermostat OFF-AUTO switch in the OFF position, the DDC Hardware shall stop the fan and close the heating control valve.
3.3.4.1.2 AUTO
With the thermostat OFF-AUTO switch in the AUTO position, the DDC Hardware shall control the unit in accordance with its Occupancy Mode.
3.3.4.2 Occupancy Modes
3.3.4.2.1 Occupied
The unit heater DDC Hardware shall be in the Occupied Mode when the local space occupancy input(s) indicate that the space is occupied or when the input from the System Scheduler is occupied.
3.3.4.2.2 Unoccupied
The unit heater DDC Hardware shall be in the Unoccupied Mode when the local space occupancy input(s) indicate that the space is unoccupied and when the input from the System Scheduler is unoccupied.
3.3.4.3 Safeties
The unit shall run subject to the unit manufacturer's safeties.
3.3.4.4 Space Temperature Control
3.3.4.4.1 Occupied Mode
In the Occupied Mode the DDC Hardware shall modulate the heating control valve and cycle the multi-speed fan to maintain space temperature at the configured setpoint or at the occupant-adjustable setpoint via the wall-mounted thermostat, as shown.
3.3.4.4.2 Unoccupied Mode
In the Unoccupied Mode the DDC Hardware shall modulate the heating control valve and cycle the multi-speed fan to maintain space temperature at the configured setpoint as shown.
3.4 SEQUENCES OF OPERATION FOR HYDRONIC SYSTEMS
3.4.1 Hydronic Secondary with Variable Speed Pump
Install DDC hardware to perform this Sequence of Operation and to provide SNVT inputs and outputs as specified and shown on the Points Schedule.
Unless otherwise specified, all modulating control shall be proportional-integral (PI) control.
3.4.1.1 System Enable and Loop Enable :
a. This system shall monitor the enabled status of all systems served by this system. If one or more systems served by this system are enabled, SECTION 23 09 93 Page 9 this system shall be enabled (SYS-ENA). If all systems served by this system are not enabled, this system shall not be enabled.
b. When this system is enabled (SYS-ENA) the Pressure Control loop shall be enabled.
3.4.1.2 HAND-OFF-AUTO Switch
The hot water pump variable frequency drive (VFD) unit shall have an integral H-O-A switch:
3.4.1.2.1 HAND
With the H-O-A switch in HAND position, the pump starts and runs continuously. Pump speed shall be under manual-operator control.
3.4.1.2.2 OFF
With the H-O-A switch in OFF position, the pump stops.
3.4.1.2.3 AUTO
With the H-O-A switch in AUTO position, the pump shall run subject to the Hot Water Pump Start/Stop (HW-PMP-SS) command and pump speed shall be under control of the DDC system.
3.4.1.3 Proofs and Safeties
DDC Hardware shall monitor all proofs and safeties.
3.4.1.3.1 Proofs
None
3.4.1.3.2 Safeties
None
3.4.1.3.3 DDC Hardware Reset
DDC Hardware reset of all proofs and safeties shall be via a local binary push-button (RST-BUT) input to the DDC Hardware, via a remote command to the DDC Hardware via SNVT or both (where the Contractor provides both reset functions and the operator can use either one to perform the reset), as shown on the Points Schedule drawing.
3.4.1.4 Pressure Control
When this loop is enabled the DDC Hardware shall modulate the pump variable frequency drive unit to maintain the pipe system pressure at setpoint as shown, as measured by the differential pressure tap and sensor as shown. When this loop is disabled, the DDC Hardware capacity modulation output to the VFD shall be zero percent.
-- End of Section --