Attachment 5 Sheet G_203 .pdf

PDF 710 KB Posted

Attached to
GSU Transformer Supply, Oahe Dam, SD & Ft Peck Dam, MT
Solicitation number
W9128F25RA053
Issued by

About this file

This document is a Requirements Summary Sheet for the U.S. Army Corps of Engineers' Oahe Dam 230 kV Single-Phase Generator Step-Up (GSU) Transformers project located in Omaha, Nebraska. The specification details the technical requirements for four single-phase transformers with a 68,667 kVA rating, 230,000 Grdy/132,790 (H) - 13,800 Delta (X) voltage configuration, and 60 Hz frequency. Key technical specifications include a 65°C temperature rise, 10.6% impedance, 900 kV BIL (Basic Impulse Level) for high-voltage windings, and cooling class of OFAF or ODAF with a maximum sound level of 70 dB.

The transformers will be fully assembled with specific requirements for core construction, oil preservation using nitrogen gas blanketing, and extensive factory acceptance testing. Detailed accessories include multiple spare parts, specific nameplate requirements, control and power cabinets with various monitoring systems, and provisions for fall arrest systems. The transformers are designed to operate in ambient temperatures up to 45 degrees Celsius, with specific requirements for core design, bushings, insulating oil, and external/internal painting. The solicitation number is W9128F25R0002, issued by the U.S. Army Corps of Engineers Hydroelectric Design Center in Portland, Oregon, with a document date of January 2025.

View the file

Other files

File Type Posted
Attachment 3 Transformer Oil Tests Table Am-0006.pdf PDF
Attachment 2 Sheet G-103 Am-0006.pdf PDF
Solicitation Amendment W9128F25RA0530006 SF 30.pdf PDF
Attachment 1 Specifications Am-0006.pdf PDF
Solicitation Amendment W9128F25BA0080002 SF 30.pdf PDF
Solicitation Amendment W9128F25RA0530005 SF 30.pdf PDF
Attachment 6 Sheet G_204.pdf PDF
Attachment 4 Specifications AM 0005.pdf PDF
Attachment 2 Addendum to 52.212-2 Am-0005.pdf PDF
Solicitation Amendment - W9128F25RA0530005.pdf PDF
Attachment 1 Price Schedule Am-0005.pdf PDF
Attachment 3 Section 01 22 00 Am-0005.pdf PDF
Solicitation Amendment W9128F25RA0530004 SF 30.pdf PDF
Attachment-1 Price Schedule - Updated.pdf PDF
Solicitation Amendment W9128F25RA0530003 SF 30.pdf PDF
Site Visit Attendees Fort Peck_MT.pdf PDF
Site Visit Attendees Attendees Oahe Dam_SD.pdf PDF
Solicitation Amendment - W9128F25RA0530002 SF 30.pdf PDF
Solicitation Amendment W9128F25RA0530001 SF 30.pdf PDF
Attachment-4 OA_FP GSU Transformer Contract Drawings 2 of 3 (1).pdf PDF
Attachment-4 OA_FP GSU Transformer Contract Drawings 2 of 3.pdf PDF
Attachment-5 OA_FP GSU Transformer Supply specs.pdf PDF
Attachment-3 Oahe GSU Transformer Reference Drawings.pdf PDF
Attachment-1 Price Schedule.pdf PDF
Solicitation - W9128F25RA053.pdf PDF
Attachment-4 OA_FP GSU Transformer Contract Drawings 1 of 3.pdf PDF
Addendum to 52.212-2.pdf PDF
Attachment-4 OA_FP GSU Transformer Contract Drawings 3 of 3.pdf PDF
Attachment-4 OA_FP GSU Transformer Contract Drawings 2 of 3.pdf PDF
Attachment-2 Fort Peck GSU Transformer Reference Drawings.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J O

R D

A N

S F

IN

K

P

.E

R E

Q U

IR

E

M E

N T

S S

U M

M A

R Y

S H

E E

T

O A

H E

K

V

-P H

A S

E T

R A

N S

F O

R M

E R

S

G-203

D

F

IL

E R

M

W A

T K

IN

S

/2

/2

C L

A S

S O

D A

F

A L

L O

W A

N C

E F

O R

O

IL

-D

IR

E C

T E

D

A

IR

-F O

R C

E D

C

O O

L

IN

G

F O

P .0

G

-2 .d g n

D

F

IL

E

A N

S I

D

F

IN

A L

F O

R T

P E

C K

A N

D O

A H

E D

A M

S T

R A

N S

F O

R M

E R

S U

P P

L Y

P O

W E

R H

O U

S E

M

IS

S O

U R

I R

IV

E

R

O A

H E

D A

M

W F

R

O M

A H

A N

E B

R A

S K

A

O M

A H

A D

IS

T

R

IC

T

P O

R T

L A

N D

O

R E

G O

N

H Y

D R

O E

L E

C T

R

IC

D E

S

IG

N C

E N

T E

R

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

S

F

IL

E N

A M

E

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

IS

S

U E

D A

T E

S I Z

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

SHEET ID

®of Engineers

US Army Corps

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

J A

N U

A R

Y

NAMEPLATE DATA:

TANK AND CONSTRUCTION:

ACCESSORIES:

BUSHINGS: INSULATING OIL:

SEPARATE CONTROL AND POWER CABINETS:

SPARE PARTS:

FACTORY ASSEMBLY AND PAINT:

FACTORY ACCEPTANCE TESTS (F.A.T.):

REQUIREMENTS SUMMARY SHEET

OAHE DAM 230 KV SINGLE-PHASE GSU TRANSFORMERS

(REFERENCE SPECIFICATION SECTION 48 19 23.05 26)

NAPTHENIC BASE - ASTM D 3487 TYPE II; 0.3% BY MASS OF OXIDATION INHIBITOR∙ TYPE:

(4) COMPLETELY ASSEMBLED AND WITNESSING OF FACTORY ACCEPTANCE TESTS

(3) COMPLETED CORE/COIL ASSEMBLY, BUT PRIOR TO TANKING

(2) AFTER COMPLETION OF WINDINGS BUT PRIOR TO LANDING ON CORE

(1) DESIGN REVIEW MEETING

GOVERNMENT INSPECTIONS PERFORMED DURING∙ INSPECTIONS:

FOR ONE WEEK PRIOR TO OIL FILLING.

PRIMER COAT, OIL-RESISTANT FINISH COAT - WHITE. ALLOW TO CURE∙ INTERIOR PAINT:

CABINETS, SHALL REMAIN UNPAINTED. COVER TO RECEIVE A NON-SLIP COATING.

5BG 7/0.4 HIGH-GLOSS. CORROSION RESISTANT SURFACES, AND STAINLESS STEEL

PRIMER COAT, EPOXY BASE COAT, POLYURETHANE TOP COAT - MUNSELL∙ EXTERIOR PAINT:

MATCH-MARKED FOR EASE OF REASSEMBLY.

TRANSFORMER TO BE FULLY ASSEMBLED, WITH REMOVABLE COMPONENTS∙ ASSEMBLY:

4,700 GAL∙ MAXIMUM OIL VOLULME:

160,000 LB∙ MAXIMUM TRANSFORMER WEIGHT:

70 DB∙ MAXIMUM SOUND LEVEL (ONAF):

NITROGEN GAS BLANKETED∙ OIL PRESERVATION SYSTEM:

65 ºC∙ TEMPERATURE RISE:

5 TAPS; 2 @ +2.5%, 2 @ -2.5% OF NOMINAL 230 KV TAP∙ SECONDARY WINDING (H) DETC:

60 HZ∙ FREQUENCY:

10.6% @ 68,667 KVA (H-X)∙ IMPEDANCE:

SINGLE-PHASE∙ PHASING:

900 (H1) / 110 (X) / 150 (H2)∙ BIL LEVELS, KV:

230,000 GRDY / 132,790 (H) - 13,800 DELTA (X)∙ VOLTAGE RATINGS:

68,667∙ KVA RATING:

OFAF OR ODAF∙ COOLING CLASS:

CLASS II GSU POWER TRANSFORMER∙ TYPE:

ANALOG TEMPERATURE GAUGE FUNCTIONAL VERIFICATION∙

BUSHING CURRENT TRANSFORMER ROUTINE TESTS∙

AND POWER FACTOR TESTS DURING TRANSFORMER F.A.T.

EACH HIGH-VOLTAGE AND HIGH-VOLTAGE NEUTRAL BUSHING ARE TO UNDERGO CAPACITANCE∙

ALL ELECTRICAL AND ELECTO-MECHANICAL DEVICES ARE TO BE FUNCTIONALLY TESTED∙

DE-ENERGIZED TAP CHANGER MECHANICAL OPERATIONAL TEST (5 COMPLETE CYCLES)∙

SHIPPING CONFIGURATION

- ONE SFRA TEST TO BE PERFORMED WITH THE TRANSFORMER IN THE

OIL FILLED

- ONE SFRA TEST TO BE PERFORMED WITH THE TRANSFORMER FULLY ASSEMBLED AND

- CABLE INTEGRITY TEST REQUIRED

SWEEP FREQUENCY RESPONSE ANALYSIS (WITH ELECTRONIC DATA FILES)∙

LEAKAGE REACTANCE (WITH ELECTRONIC DATA FILES)∙

ONE HOUR LEVEL: 300 PC

INDUCED VOLTAGE TESTS - ACCEPTANCE CRITERIA: 7,200 CYCLE ENHANCEMENT LEVEL: 500 PC;∙

AUDIBLE SOUND LEVEL TESTS∙

LIGHTNING IMPULSE TESTS∙

- OFAF WITH ALL COOLING GROUPS IN OPERATION AT 100% RATED LOAD

- OFAF WITH ONE COOLING GROUP IN OPERATION AT 70% RATED LOAD

TEMPERATURE RISE TESTS ARE TO BE PERFORMED AT THE FOLLOWING COOLING STAGES:∙

ALL 'ROUTINE' TESTS (IEEE C57.12.00, TABLE 17)∙

HEAVY-DUTY WITH LARGE THRUST-FACE SLEEVE BEARINGS, THERMO-SYPHON DESIGN.∙ PUMPS:

HOT-DIP GALVANIZED ENCLOSURES AND FAN GUARDS.∙ FORCED-AIR (OFAF) COOLERS:

STEEL. MAXIMUM DESIGN FLUX DENSITY OF 1.75 TESLA. STEP-LAP CONSTRUCTION.

LAMINATIONS MAXIMUM THICKNESS OF 0.270MM, COLD-ROLLED, GRAIN-ORIENTED∙ CORE:

SEISMIC CALCULATIONS REQUIRED FOR MAIN TANK AND ALL MAJOR COMPONENTS.∙ SEISMIC:

DESIGN LOADS FOR EACH EYE SHALL BE TWO TIMES THE ACTUAL LOAD.∙ LIFTING EYES:

DESIGNED FOR PAD MOUNTING WITH SEISMIC WELDING TO STEEL PLATES.∙ BASE:

8517412)

DESIGNED FOR USE WITH THE FALL ARREST ANCHOR POST. (EXAMPLE MODEL DBI-SALA

UNI-ANCHOR PLATE AND LUG,∙ PORTABLE FALL ARREST ANCHOR POST MOUNTING PLATE:

GROUND PAD AT BASE OF TANK.

#4/0 INSULATED COPPER CONDUCTOR FROM NEUTRAL BUSHING TO TANK∙ GROUNDING:

STAINLESS STEEL BALL-TYPE (RADIATORS MAY USE BUTTERFLY-TYPE)∙ VALVES:

CROSS-SECTION.

O-RING GASKETS ARE NOT TO BE USED FOR GASKET GROOVES OF RECTANGULAR

THAT THE LOW-VOLTAGE BUSHING GASKETS ARE TO BE FLUOROELASTOMETIC RUBBER.

NITRILE NBR (BUNA-N), DURO 50-70, 25% COMPRESSION, WITH THE EXCEPTION∙ GASKETS:

24-INCH DIAMETER (QTY: 2)∙ MANHOLE:

(QTY 1): PRESSURE REGULATOR FOR INERT-GAS EQUIPMENT∙

(QTY 1): VALVE OF EACH SIZE AND TYPE∙

(QTY 1): FUSE OF EACH TYPE AND RATING∙

PLATE TO THE FIBER-OPTIC WINDING TEMPERATURE MONITOR

(QTY 10): FIBER OPTIC EXTENSION CABLE THAT CONNECTS THE FEED-THROUGH WALL∙

(QTY 3): COOLING FAN COMPLETE WITH MOTOR∙

(QTY 1): OIL FLOW INDICATOR WITH FLOW SWITCH ALARM CONTACTS∙

(QTY 1): OIL PUMP WITH MOTOR∙

(QTY 1): OIL TEMPERATURE INDICATOR∙

(QTY 1): WINDING TEMPERATURE INDICATOR∙

(QTY 1): LIQUID LEVEL INDICATOR∙

ON THE TRANSFORMERS

(QTY 1): TRANSFORMER MONITOR CONFIGURED THE SAME AS THAT PROVIDED∙

(QTY 1): RAPID PRESSURE RISE SEAL-IN RELAY∙

(QTY 1): RAPID PRESSURE RISE RELAY∙

(QTY 1): PRESSURE RELIEF DEVICE∙

(QTY 1): RELAY AND CONTACTOR OF EACH TYPE AND RATING∙

(QTY 1): BUSHING CURRENT TRANSFORMER OF EACH TYPE AND RATING∙

(QTY 9): SET OF GASKETS FOR TRANSFORMER ON-SITE REASSEMBLY AFTER DELIVERY∙

(QTY 2): COMPLETE GASKET SET∙

(QTY 2): 25 KV LOW-VOLTAGE WINDING BUSHING∙

(QTY 2): 25 KV HIGH-VOLTAGE NEUTRAL BUSHING∙

(QTY 2): 230 KV HIGH-VOLTAGE WINDING BUSHING∙

ANODIZED ALUMINUM OR STAINLESS STEEL WITH ENGRAVED BLACK LETTERING.

- DEVICE NAMEPLATES WITHIN THE CONTROL AND POWER CABINETS MADE OF

BUSHINGS MADE OF STAINLESS STEEL WITH BLACK LETTERING.

- EQUIPMENT NAMEPLATES FOR THE HIGH-VOLTAGE BUSHINGS AND LOW-VOLTAGE

LIFT POSITIONS

- AN ADDITIONAL LIFTING DIAGRAM NAMEPLATE INDICATING SLING LOCATIONS AND

CALCULATED X/R RATIO∙

PRESSURE AND VACUUM THE TANK WILL WITHSTAND∙

GOVERNMENT CONTRACT NUMBER∙

PLANT LOCATION∙

MANUFACTURING DATE∙

TABLE 7, INCLUDING THE FOLLOWING:

- CAST BRONZE OR STAINLESS STEEL WITH INFORMATION LISTED IN IEEE C57.12.00,

∙ NAMEPLATES:

- FOLD-DOWN MAINTENANCE TRAY ON INSIDE OF CONTROL CABINET DOOR.

GRADE HUMIDISTAT / THERMOSTAT CONTROL.

- PTC RESISTOR DESIGN ENCLOSURE HEATERS WITH INTEGRAL FANS, AND INDUSTRIAL

CABINET.

- 120 V AC, 20 A HOSPITAL GRADE GFCI RECEPTACLE MOUNTED INSIDE THE CONTROL

- 120 V AC, 1,000 LUMEN LED TYPE A19 LAMPS WITH DOOR-ACTUATED SWITCH.

IN POWER CABINET.

- ALL CIRCUITS, WIRING AND EQUIPMENT RATED GREATER THAN 120 V AC TO BE MOUNTED

IN CABINET DOOR FOR VIEWING.

ON SWING PANEL WITHIN CONTROL CABINET, WITH WEATHERPROOF WINDOW PROVIDED

- FIBER-OPTIC WINDING TEMPERATURE MONITOR (EXAMPLE: NEOPTIX MODEL 408) MOUNTED

DOOR FOR VIEWING.

PANEL WITHIN CONTROL CABINET, WITH WEATHERPROOF WINDOW PROVIDED IN CABINET

- TRANSFORMER MONITOR WITH COOLING CONTROL (SEL MODEL 2414) MOUNTED ON SWING

FOR VIEWING.

WITHIN CONTROL CABINET, WITH WEATHERPROOF WINDOW PROVIDED IN CABINET DOOR

- ONE 10 PT. ANNUNCIATOR (EXAMPLE: SEL MODEL 2533) MOUNTED ON SWING PANEL

SERIES 24)

- LOCKOUT RELAY WITH TRIP COIL MONITORING AND INDICATORS (EXAMPLE: ELECTROSWITCH

∙ SPECIAL FEATURES:

- 125 AND 250 V DC CIRCUITS - RATED 125/250 OR 250 V DC, AND 10,000 A INTERRUPTING

- 120 V AC CIRCUITS - RATED 250 V DC AND 120/240 OR 240 V AC, AND 10,000 A INTERRUPTING

- 480 V AC CIRCUITS - RATED 600 V AC AND 35,000 A INTERRUPTING AT 480 VAC

∙ MOLDED-CASE CIRCUIT BREAKERS:

120 V AC CIRCUITS - 10 A

- SINGLE-BREAK INDUCTIVE LOAD INTERRUPTING RATING: 125 V DC CIRCUITS - 1.5 A;

- RATED FOR 600 V AC OR 250 V DC

∙ SWITCHES:

120 V AC CIRCUITS - 6.0 A

- SINGLE-CONTACT INDUCTIVE LOAD INTERRUPTING CAPACITY: 125 V DC CIRCUITS - 1.0 A;

- RATED FOR 125 V DC OR 120 V AC; MEETS REQUIREMENTS OF NEMA ICS5; 10 A CONTACTS

∙ AUXILIARY RELAYS:

600 V, 30 A MINIMUM, 90 ºC RATED TERMINATIONS.∙ TERMINAL BLOCKS:

RESISTANT MALLEABLE CAST IRON WITH CAST COVERS AND LIQUID-TIGHT HUBS.

JOINT COMPOUND APPLIED. OUTLET AND JUNCTION BOXES ARE TO BE CORROSION

CHANNELS NOT ALLOWED. ALL CONDUIT THREADED JOINTS ARE TO HAVE A CONDUCTIVE

ALL WIRING TO BE RUN IN CONDUIT. WIRE RUNS THROUGH TANK REINFORCING∙ CONDUIT:

GROUND - GREEN/YELLOW

PHASE B - ORANGE; PHASE C - YELLOW; GROUNDED NEUTRAL - WHITE; INSULATED

XLPE; 3-PHASE POWER CONDUCTORS COLOR CODED: PHASE A - BROWN;∙ WIRING:

POWER - 125 V DC; COOLING FANS - 480 V AC, 3-WIRE, 3-PHASE, 60 HZ

CONTROL POWER - 125 V DC; ANNUNCIATION∙ GOVERNMENT-FURNISHED POWER:

IN CONTROL CABINET. SOLAR SHIELDING ON TOP, FRONT AND SIDE PANELS OF ENCLOSURES.

PROVISIONS. WINDOWS FOR VIEWING THE TEMPERATURE MONITOR AND ANNUNCIATOR

WEATHER-PROOF TYPE 304 STAINLESS STEEL WITH LOCKING∙ CABINET MATERIAL:

ABB RND2)

DUAL TANK NITROGEN REGULATOR CABINET WITH ELECTRICAL PACKAGE (EXAMPLE∙

(EXAMPLE: DBI-SALA, MODEL 8516691)

PORTABLE FALL ARREST SYSTEM ANCHOR POST WITH DAVIT ARM∙

RAPID PRESSURE RISE RELAY (EXAMPLE: QUALITROL, MODEL 900-FLA)∙

SCHAFFER MODEL CALISTO R9)

ON-LINE DISSOLVED GAS AND MOISTURE CONTENT MONITOR (EXAMPLE: MORGAN∙

(EXAMPLE: QUALITROL, MODEL XPRD)

DIRECTED-FLOW PRESSURE RELIEF DEVICE WITH METAL DISCHARGE PIPING∙

OIL FLOW INDICATORS∙

OIL LEVEL INDICATOR (EXAMPLE: QUALITROL, MODEL 042)∙

WTI AND OTI GAUGES WITH RTDS (EXAMPLE: AKM)∙

2.5 KV CLASS, 45 KV BIL, 100 AMP∙ SFRA TEST SHIPPING BUSHING:

2.5 KV CLASS, 45 KV BIL, 100 AMP∙ CORE GROUNDS:

(NO BUSHING CURRENT TRANSFORMER REQUIRED)

EXTERIOR WITH RESIN-IMPREGNATED SYNTHETIC (RIS) CONDENSER CORE DESIGN

25 KV CLASS, 150 KV BIL, 400 AMP, DRAW-LEAD DESIGN, COMPOSITE∙ NEUTRAL (H0):

INDICATING EQUIPMENT OR TRANSFORMER TEMPERATURE MONITOR SYSTEM)

(BUSHING CURRENT TRANSFORMERS AS REQUIRED FOR THE WINDING TEMPERATURE

BULK-TYPE, LOW-CORONA, LIGHT CONTAMINATION, 125 ºC TEMPERATURE RISE RATING

25 KV CLASS, 150 KV BIL, 6,000 AMP, PORCELAIN CONSTRUCTION,∙ PRIMARY WINDING (X):

C400 RELAYING ACCURACY)

CORE DESIGN (TWO 1,200:5 MRCT PER BUSHING, 0.3B-1.8 METERING ACCURACY,

COMPOSITE EXTERIOR WITH RESIN-IMPREGNATED SYNTHETIC (RIS) CONDENSER

230 KV CLASS, 900 KV BIL, 800 AMP, DRAW-LEAD DESIGN, ∙ SECONDARY WINDING (H):

UNUSUAL SERVICE CONDITIONS:

CELSIUS (SEE SHEET G-202)

36.4 DEGREESMAXIMUM AVERAGE AMBIENT AIR TEMPERATURE (24-HOUR PERIOD):∙

47.2 DEGREES CELSIUS (SEE SHEET G-202)MAXIMUM AMBIENT AIR TEMPERATURE:∙

TEMPERATURE OF 45 DEGREES CELSIUS.

∙ TRANSFORMERS ARE TO BE CAPABLE OF FULL LOAD OPERATION AT AN AMBIENT

File details come from the government source that posted it. Updated .