Point_Schedule_Lonworks_BACnet_Niagara_2015-07-15.xlsx
XLSX spreadsheet 44 KB Posted
- Attached to
- MATOC Federal contract opportunity
- Solicitation number
- W911S7-19-R-0008
About this file
This file contains a points schedule template and sample entries for use in a federal construction contract opportunity.
The points schedule template lists columns for different building automation protocols and notes which columns apply to each. It provides a format for contractors to list function points, descriptions, hardware IDs, settings, ranges, I/O types, configuration details, trending and alarming requirements. The sample entries illustrate typical data for a VAV system, including status and control points for fans, air temperatures and pressures, scheduling, and alarms.
The related federal contract is a Multiple Award Task Order Contract for construction requirements at Fort Leonard Wood, Missouri and the Lake of the Ozarks Recreational Area. It will be set aside for total small businesses with a NAICS code of 236220 and size standard of $36.5M. The Department of the Army Materiel Command Mission and Installation Contracting Command at Fort Leonard Wood will issue the solicitation on January 3rd 2019 under number W911S7-19-R-0008, with quotes due February 4th 2019. The place of performance is the specified locations in Missouri.
Point Schedule Lonworks BACnet Niagara
View the file
Other files for this federal contract opportunity
Show all 38
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Read Me Not all columns of the Points Schedule will be used. Which are used depends on the protocol selection. Rows 4-7 of the Points Schedule in this file indicate which columns apply to which protocols. Once unused columns are deleted or hidden, rows 4-7 may also be deleted or hidden
Similarly, some notes will not apply depending on protocol selection. The column next to the notes indicate when a note is or not applicable. Remove non-applicable notes and replace the colored cells indicating applicability with blank cells.
Points Schedule-Blank
<TITLE>
| COLUMN IS USED FOR BACNET (NO NIAGARA) | Y | N | N | N | Y | Y | Y | N | N | Y | Y | Y | Y | Y |
| COLUMN IS USED FOR BACNET (WITH NIAGARA) | Y | N | N | Y | Y | Y | Y | N | N | N | Y | Y | N | Y |
| COLUMN IS USED FOR LNS LONWORKS (NO NIAGARA) | N | Y | Y | N | N | N | N | Y | Y | N | N | N | N | Y |
| COLUMN IS USED FOR LONWORKS (WITH NIAGARA) | N | Y | Y | Y | N | N | N | Y | Y | N | N | N | N | Y |
| ALARMING | PRIMARY POINT INFORMATION | NETWORK DATA EXCHANGE | OVERRIDES | TREND OBJECT LOCATION (L OR R), TYPE AND INSTANCE NUMBER | ||||||
| (PROVIDE DDC ID FOR REMOTE IN NOTES) | ALARM INFORMATION | CONFIGURATION INFORMATION | ||||||||
| FUNCTION | POINT NAME | DESCRIPTION | DDC |
HARDWARE
| ID | SETTING | ||||||||
| (WITH UNITS) | RANGE | ||||||||
| (WITH UNITS) | IO | ||||||||
| TYPE | HOA REQ'D | CONFIG. TYPE | M&C VIEW AND OVRD | LDP VIEW AND OVRD | TREND REQ'D | ALARM CONDITION | |||
| (SEE NOTES) | ALARM | ||||||||
| PRIORITY | M&C | ||||||||
| ROUTING | OBJECT TYPE AND INSTANCE NUMBER | ||||||||
| (AND PROPERTY ID) | SNVT NAME | SNVT TYPE | NIAGARA ID | DATA FROM | DATA TO | OBJECT TYPE & INSTANCE NUMBER |
OR
| COMMANDABLE | SNVT NAME | SNVT TYPE | ALARM TYPE |
| (PROVIDE DDC ID FOR REMOTE IN NOTES) | NOTIFICATION CLASS OBJECT INSTANCE NUMBER | EVENT ENROLLMENT OBJECT INSTANCE NUMBER |
| Notes: | ||
| 1) | THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING. | |
| 2) | UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW. | |
| 3) | UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM. | |
| THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA) | 4) | DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____> |
| THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA) | 5) | DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____> |
| THIS NOTE IS USED ONLY FOR LNS LONWORKS (NO NIAGARA) | 6) | DDC HW IF FOR DEVICE CONTAINING SIMPLE SCHEDULER OBJECT (OR SYSTEM SCHEDULER SEQUENCE OF OPERATIONS) FOR THIS SYSTEM: <_____> |
Points Schedule-Sample Entries
| VAV [WITH][WITHOUT] RETURN FAN | |
| EXAMPLE ONLY. This example Points Schedule is intended to demonstrate the overall format for a Points Schedule and illustrate the type and scope of entries. Points Schedules for actual systems/sequences are being updated and created under a separate effort to update HVAC Sequences of Operation. The points shown is this Points Schedule are not represetnative of a properly designed system. |
| COLUMN IS USED FOR BACNET (NO NIAGARA) | Y | N | N | N | Y | Y | Y | N | N | Y | Y | Y | Y | Y |
| COLUMN IS USED FOR BACNET (WITH NIAGARA) | Y | N | N | Y | Y | Y | Y | N | N | N | Y | Y | N | Y |
| COLUMN IS USED FOR LNS LONWORKS (NO NIAGARA) | N | Y | Y | N | N | N | N | Y | Y | N | N | N | N | Y |
| COLUMN IS USED FOR LONWORKS (WITH NIAGARA) | N | Y | Y | Y | N | N | N | Y | Y | N | N | N | N | Y |
| ALARMING | PRIMARY POINT INFORMATION | NETWORK DATA EXCHANGE | OVERRIDES | TREND OBJECT LOCATION (L OR R), TYPE AND INSTANCE NUMBER | ||||||
| (PROVIDE DDC ID FOR REMOTE IN NOTES) | ALARM INFORMATION | CONFIGURATION INFORMATION | ||||||||
| FUNCTION | POINT NAME | DESCRIPTION | DDC |
HARDWARE
| ID | SETTING | ||||||||
| (WITH UNITS) | RANGE | ||||||||
| (WITH UNITS) | IO | ||||||||
| TYPE | HOA REQ'D | CONFIG. TYPE | M&C VIEW AND OVRD | LDP VIEW AND OVRD | TREND REQ'D | ALARM CONDITION | |||
| (SEE NOTES) | ALARM | ||||||||
| PRIORITY | M&C | ||||||||
| ROUTING | OBJECT TYPE AND INSTANCE NUMBER | ||||||||
| (AND PROPERTY ID) | SNVT NAME | SNVT TYPE | NIAGARA ID | DATA FROM | DATA TO | OBJECT TYPE & INSTANCE NUMBER |
OR
| COMMANDABLE | SNVT NAME | SNVT TYPE | ALARM TYPE |
| (PROVIDE DDC ID FOR REMOTE IN NOTES) | NOTIFICATION CLASS OBJECT INSTANCE NUMBER | EVENT ENROLLMENT OBJECT INSTANCE NUMBER |
PROOFS
| SAFETIES | SF-S | SUPPLY FAN STATUS | ON/OFF | BI | V | [ V ] | [ ~ ] | SUPPLY FAN PROOF FAILED | [info] [crit] | [___] | <___> | <___> | <INTRINSIC><REMOTE ALGORITHMIC><LOCAL ALGORITHMIC><NIAGARA FRAMEWORK> | ||||||||
| RF-S | RETURN FAN STATUS | ON/OFF | BI | V | [ V ] | [ ~ ] | RETURN FAN PROOF FAILED | [info] [crit] | [___] | <___> | <___> | ||||||||||
| SA-SMK | SUPPLY AIR SMOKE | ALM/NORMAL | BI | ALM | [info] [crit] | [___] | <___> | <___> | |||||||||||||
| RA-SMK | RETURN AIR SMOKE | ALM/NORMAL | BI | ALM | [info] [crit] | [___] | <___> | <___> | |||||||||||||
| CLG-DA-T-LL | COOLING COIL DISCHARGE AIR TEMP LOW LIMIT | 39 DEG F | ALM/NORMAL | BI | H | V | [~] | ALM | [info] [crit] | [___] | <___> | <___> | |||||||||
| SA-P-HL | SUPPLY AIR PRESSURE HIGH LIMIT | [___ IWC] | ALM/NORMAL | BI | H | ALM | [info] [crit] | [___] | <___> | <___> | |||||||||||
| RST-BUT | SYSTEM RESET BUTTON (FOR SAFETIES) | [NET-IN][BI] | [<___>][~] | [<___>][~] |
SCHEDULING SYS-OCC-SCHED SYSTEM OCCUPANCY SCHEDULE SEE OCCUPANCY SCHEDULE DRAWING <NET-OUT> OC V [~] SCHEDULE OBJECT <___> <___>
| START/STOP | UNIT STATUS | UNIT STATUS (HTG AND/OR CLG REQUEST) (SEE NOTES) | NET-OUT | [V] | [ ~ ] | [ ~ ] | ~ | ~ | ~ | <___> | <___> | ||
| SYS-OCC-C | OCCUPANCY COMMAND | OCCUPIED(1)/WUCD(2)/UNOCCUPIED(3) | <NET-IN> | VO | [~] | [ ~ ] | MSV <___> | <___> | <SNVT_OCCUPANCY> |
<SNVT_TOD_EVENT>
| SYS-OCC | SYSTEM OCCUPANCY (ACTUAL) | OCCUPIED(1)/WUCD(2)/UNOCCUPIED(3) | <~><NET-OUT> | V | [V] | X | MSV <___> | <___> | SNVT_OCCUPANCY | |||||||
| SF-SS | SUPPLY FAN START/STOP | ON/OFF | BO | [~] | VO | [ V ] | [ ~ ] | <___> | <___> | |||||||
| RF-SS | RETURN FAN START/STOP | ON/OFF | BO | [~] | VO | [ V ] | [ ~ ] | <___> | <___> | |||||||
| BLDG-T | BUILDING TEMPERATURE (NIGHT STAT) | <___> | <AI><NET-IN> | V | [ ~ ] | [ ~ ] | BLDG-T LESS THAN BLDG-T-LL | [info] [crit] | [___] | <___> | <___> | |||||
| BLDG-T-LL | BUILDING TEMPERATURE LOW LIMIT | [55 DEG F] | C | VO | [ ~ ] | <___> |
| SUPPLY FAN CAPACITY CONTROL | SF-C | SUPPLY FAN COMMAND | 0-100% | AO | [~] | VO | [ ~ ] | [ ~ ] | <___> | <___> | ||||
| SA-P | SUPPLY AIR PRESSURE | <___> | AI, NET-OUT | V | [ V ] | X | SYSTEM HAS BEEN IN OCCUPIED MODE FOR MORE THAN 5 MINUTES AND SA-P IS MORE THAN 20% ABOVE OR BELOW SA-P-SP | [info] [crit] | <___> | <___> | <___> | DDC #17, |
DDC #18,
DDC #19
| SA-P-SP | SUPPLY AIR PRESSURE SETPOINT | <___> | C | VO | [ ~ ] | <___> | <___> |
| SUPPLY FAN CONTROL LOOP |
CONFIGURATION
| SETTINGS | PROPORTIONAL CONSTANT | |
| INTEGRAL CONSTANT | ||
| BIAS | ||
| MAXIMUM OUTPUT | ||
| MINIMUM OUTPUT | ||
| <____> |
| RETURN FAN CAPACITY CONTROL | SA-F | SUPPLY AIR FLOW | [0 - ___ CFM] | NET-IN | V | [ V ] | [ ~ ] | [ ~ ] | ~ | [___] | <___> | <___> | DDC#12 | ||||
| RA-F | RETURN AIR FLOW | [0 - ___ CFM] | AI | V | [ V ] | [ ~ ] | [ ~ ] | ~ | [___] | <___> | <___> | ||||||
| RF-C | RETURN FAN COMMAND | 0-100% | AO | [~] | VO | [ ~ ] | [ ~ ] | <___> | <___> | ||||||||
| F-DIFF-SP | FLOW DIFFERENCE SETPOINT | [___ CFM] | OC | VO | [ ~ ] | <___> | <___> | <___> | |||||||||
| RETURN FAN CONTROL LOOP |
CONFIGURATION
| SETTINGS | PROPORTIONAL CONSTANT | C | <___> | |||
| INTEGRAL CONSTANT | C | <___> | ||||
| BIAS | C | <___> | ||||
| MAXIMUM OUTPUT | C | <___> | ||||
| MINIMUM OUTPUT | C | <___> | ||||
| <____> | C | <___> |
| MINIMUM | ||||||||||||||||||||
| OUTSIDE AIR | MINOA-F | MINIMUM OUTSIDE AIR FLOW | [0 - ___ CFM] | AI | V | [ V ] | X | MINOA-F LESS THAN 80% OF MINOA-F-SP | [info] [crit] | [___] | <___> | <___> | ||||||||
| MINOA-D-C | MINIMUM OUTSIDE AIR DAMPER COMMAND | <0-100% OPEN> | AO | [~] | VO | [ V ] | [ ~ ] | <___> | <___> | |||||||||||
| MINOA RESET SCHEDULE FOR DCV | CO2 MAXIMUM VALUE | [___ PPM] | C | |||||||||||||||||
| CO2 MINIMUM VALUE | [___ PPM] | C | ||||||||||||||||||
| MINOA FLOW MINIMIM VALUE (AT CO2 MINIMUM VALUE) | [___ CFM] | C | ||||||||||||||||||
| MINOA FLOW MAXIMUM VALUE (AT CO2 MAXIMUM VALUE) | [___ CFM] | C | ||||||||||||||||||
| MINOA-F-SP | MINIMUM OUTSIDE AIR FLOW SETPOINT (SETTING) | [___ CFM] | C | VO | [~] | <___> | <___> | <___> | ||||||||||||
| MINIMIM OUTSIDE AIR DAMPER CONTROL LOOP |
CONFIGURATION
| SETTINGS | PROPORTIONAL CONSTANT | <___> | C | <___> | ||||
| INTEGRAL CONSTANT | <___> | C | <___> | |||||
| BIAS | <___> | C | <___> | |||||
| MAXIMUM OUTPUT | <___> | C | <___> | |||||
| MINIMUM OUTPUT | <___> | C | <___> | |||||
| <____> | <___> | C | <___> |
| MIXED AIR TEMPERATURE CONTROL WITH ECONOMIZER | OA-T | OUTSIDE AIR TEMPERATURE | <___> | AI | V | [ V ] | X | [ ~ ] | ~ | [ ~ ] | <___> | <___> | ||||
| MA-T | MIXED AIR TEMPERATURE | <___> | AI | V | [ V ] | X | [ ~ ] | ~ | [ ~ ] | <___> | <___> | |||||
| MA-D-C | MIXED AIR DAMPER COMMAND | 0-100% OPEN | AO | [~] | VO | [ V ] | [ ~ ] | <___> | <___> | |||||||
| ECO-HL-SP | ECONOMIZER HIGH LIMIT SETPOINT | [___] | C | [~] | [ V ] | <___> | <___> | <___> | ||||||||
| ECO-LL-SP | ECONOMIZER LOW LIMIT SETPOINT | [___] | C | VO | [ V ] | <___> | <___> | <___> | ||||||||
| MA-T-SP | MIXED AIR TEMPERATURE SETPOINT | [___] | C | VO | [~] | <___> | <___> | <___> | ||||||||
| MIXED AIR DAMPER CONTROL LOOP |
CONFIGURATION
| SETTINGS | <THROTTLING RANGE><PROPORTIONAL GAIN> | <___> | C | <___> | ||||
| INTEGRAL CONSTANT | <___> | C | <___> | |||||
| BIAS | <___> | C | <___> | |||||
| MAXIMUM OUTPUT | <___> | C | <___> | |||||
| MINIMUM OUTPUT | <___> | C | <___> | |||||
| <ALL OTHER CONFIG SETTINGS - ADD ROWS AS NEEDED> | <___> | C | <___> |
| SUPPLY AIR TEMPERATURE | SA-T | SUPPLY AIR TEMPERATURE | <___> | AI | V | [ V ] | X | SYSTEM HAS BEEN IN OCCUPIED MODE FOR MORE THAN 5 MINUTES AND SA-T MORE THAN 10 DEG F ABOVE OR BELOW SETPOINT | [info] [crit] | [___] | <___> | <___> | ||||
| CLG-V-C | COOLING VALVE COMMAND | <0-100% OPEN> | AO | [~] | VO | [ V ] | [ ~ ] | <___> | <___> | |||||||
| SA-T-SP | SUPPLY AIR TEMPERATURE SETPOINT | [55 DEG F] | OC | VO | [ V ] | <___> | <___> | <___> | ||||||||
| COOLING VALVE CONTROL LOOP CONFIGURATION SETTINGS | <THROTTLING RANGE><PROPORTIONAL GAIN> | <___> | C | <___> | ||||||||||||
| INTEGRAL CONSTANT | <___> | C | <___> | |||||||||||||
| BIAS | <___> | C | <___> | |||||||||||||
| MAXIMUM OUTPUT | <___> | C | <___> | |||||||||||||
| MINIMUM OUTPUT | <___> | C | <___> | |||||||||||||
| <____> | <___> | C | <___> |
| OTHER POINTS | RA-T | RETURN AIR TEMPERATURE | <___> | AI | V | [ ~ ] | [ ~ ] | [ ~ ] | ~ | [___] | <___> | <___> | ||
| MA-FLT-P-HL | MIXED AIR FILTER PRESSURE HIGH LIMIT SWITCH | <___> | ALM/NORMAL | BI | H | ~ | [ ~ ] | ALM | [info] [crit] | [___] | <___> | <___> | ||
| OA-FLT-P | OUTSIDE AIR FILTER PRESSURE | <___> | AI | V | [ ~ ] | OA-FLT-P LESS THAN OA-FLT-P-LL | [info] [crit] | [___] | <___> | <___> | ||||
| OA-FLT-P-LL | OUTSIDE AIR FILTER PRESSURE LOW LIMIT | <___> | C | ~ | [ ~ ] |
| Notes: | ||
| 1) | THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING. | |
| 2) | UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW. | |
| 3) | UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM. | |
| THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA) | 4) | DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____> |
| THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA) | 5) | DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____> |
| THIS NOTE IS USED ONLY FOR LNS LONWORKS (NO NIAGARA) | 6) | DDC HW IF FOR DEVICE CONTAINING SIMPLE SCHEDULER OBJECT (OR SYSTEM SCHEDULER SEQUENCE OF OPERATIONS) FOR THIS SYSTEM: <_____> |