This document provides details for a federal construction contract opportunity to build an F-35 three-bay specialized hangar at Truax Field in Madison, Wisconsin. The solicitation is for a single firm fixed-price contract to demolish an existing building and construct a new 31,000 square foot hangar with three bays and associated administrative and shop spaces. Key requirements include HVAC, electrical, and fire suppression systems compatible with aircraft operations. The contract also specifies lightning protection, fall protection, and an Advantor security system. The base award includes construction with optional additions for a paint/mix area and aircraft-rated pavement. Interested parties must register in SAM and can access plans through the SAM.gov website. The pre-bid conference will be held on-site with site visits. The estimated value is between $25-100 million. The completion period is 550 days from notice to proceed. The solicitation is unrestricted and requires a small business subcontracting plan from the low bidder.
View the file
Other files for this federal contract opportunity
Show all 50
F-35 THREE BAY SPECIALIZED HANGAR has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NEUTRAL
GROUND
PAD MOUNTED
TRANSFORMER 1
XO BUSHING
NEUTRAL
GROUND
TYPICAL
277/480V
PANEL
NEUTRAL
GROUND
TYPICAL
DRY TYPE
TRANSFORMER
NEUTRAL
GROUND
TYPICAL
120/208V
PANEL
TIE TO
EMGB
HOT WATER PIPING
COLD WATER PIPING
SPRINKLER PIPING
PIPE CLAMP
(TYPICAL)
BUILDING STEEL
MDP
EQUIPMENT MAIN
GROUNDING BUS
BAR (EMGB)
BUILDING
FOUNDATION
TYPICAL
BUILDING
FOUNDATION
TYPICAL
GROUND ROD
(TYPICAL)
BLDG. PERIMETER
COUNTERPOISE
TELECOMMUNICATIONS MAIN
GROUNDING BUS BAR "TMGB"
CABLE TRAY TYPICAL
NEUTRAL
GROUND
MTS
TO LIGHTNING
PROTECTION
SYSTEM.
#4/0
#3/0
#4/0 #3/0
#3/0
#3/0
#4/0
#6
#1/0
#3/0
#3/0
GAS PIPE
(TYPICAL)
NEUTRAL
GROUND
SIZE
ACCORDING TO
NEC.
#4/0
1 2
ENCLOSED
CIRCUIT
BREAKER.
PORTABLE GENERATOR SET
NEUTRAL
GROUND
CT CABINET
NEUTRAL
GROUND
PANEL HD1
NEUTRAL
GROUND
#4/0
CONTINUED TO COUNTERPOISE
SYSTEM
CONTINUED TO
CT CABINET
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
C :\U sers\aoo\D o cum ents\M y R evit\02700_Elec_A O genche.rvt
6/7/2022 11:01: 28 AM
ELECTRICAL GROUNDING
ONE-LINE DIAGRAM
EG601
WCM
GPN
GPN
SCALE: NTS
GROUNDING ONE LINE DIAGRAMA1
SHEET KEYNOTES
1. GROUNDED NEUTRAL CONDUCTOR. SIZE PER SHEET
EP601.
2. EQUIPMENT GROUNDING CONDUCTOR. SIZE PER
SHEET EP601.
3. GROUNDED ELECTRODE CONDUCTOR. SIZE PER
SHEET EP601.
4. SIZE NEUTRAL GROUND BOND PER NFPA 70.
5. UTILITY PROVIDED GROUNDED CONDUCTOR
(NEUTRAL).
1 ADDENDUM 2 06/08/2022
W
IS C O NS IN
P R
O F
E
S S I O N A L
E N G
I N E
E R
JOHN T
LITTLE
E-47833
EDMOND
OK