This document summarizes an unrestricted invitation for bid for the construction of an F-35 three bay specialized hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The project involves demolishing an existing building and constructing a new 31,000 square foot three bay hangar with associated administrative and shop spaces to accommodate fuel cell operations, indoor wash requirements, squadron level surface coating operations, and weapons load training. The facility will also require a lightning protection system, fall protection, and an Advantor security system. The base award will be for construction of the hangar with two options for additional spaces. The bid opening will be conducted in accordance with FAR Subpart 14.4 and DFARS Subpart 214.4. Interested bidders must register in the System for Award Management and the solicitation is available on SAM.gov. The estimated value is between $25-100 million and the North American Industry Classification code is 236220.
View the file
Other files for this federal contract opportunity
Show all 50
F-35 THREE BAY SPECIALIZED HANGAR has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J
JJ
J
F-35 3-BAY HANGAR
J D
J D
3L1 - 25,27
3L1 - 23
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021N
N
PLAN TRUE
C :\U sers\aoo\D o cum ents\M y R evit\02700_Elec_A O genche.rvt
6/7/2022 11:01: 13 AM
ELECTRICAL SITE PLAN
ES101
WCM
GPN
GPN
SCALE: 1" = 20'-0"
ELECTRICAL SITE PLANA1
GENERAL NOTES
SHEET KEYNOTES
A. UTILITY COMPANY IS RESPONSIBLE FOR PRIMARY
SIDE OF TRANSFORMER CONDUIT AND
CONDUCTORS, TRANSFORMER, TRANSFORMER
PAD, SECONDARY SIDE OF TRANSFORMER
CONDUIT, CONDUCTOR AND FINAL TERMINATIONS
TO DISCONNECTING MEANS IN MAIN
SWITCHBOARD. CONTRACTOR IS RESPONSIBLE
FOR DISCONNECTING MEANS AND CT'S IN
SWITCHBOARD.
B. PROVIDE CONDUITS AND CONTROL WIRES AS
REQUIRED TO ENSURE FUNCTIONALITY OF DROP
BEAM.
C. CONTRACTOR IS RESPONSIBLE FOR VERIFYING
FIELD CONDITIONS PRIOR TO BID DATE.
1. PROPOSED LOCATION FOR BLDG XFMR.
2. PROPOSED ROUTING OF CONDUIT FROM BLDG
XFMR. UTILITY IS RESPONSIBLE FOR ROUTING
CONDUCTORS.
3. NOT USED.
4. NOT USED.
5. NOT USED.
6. 4-4" CONCRETE ENCASED DUCTS FROM EXISTING
TELECOMMUNICATIONS MANHOLE TO MAIN
COMMUNICATIONS ROOM.
7. EXISTING TELECOMMUNICATIONS MANHOLE.
SPLICE EXISTING FIBER AND EXTEND FIBER TO
MAIN COMMUNICATION ROOM.
8. DATA JUNCTION BOX FOR LOW VOLTAGE CABLE
FROM FIRE CONTROL BOX.
9. 1" RIGID STEEL CONDUIT FOR ROUTING LOW
VOLTAGE CABLE FROM SITE VALVE TO CONTROL
BOX. BOX SHALL BE SEALED OFF TO MEET CLASS1
DIV1 REQUIREMENTS.
10. APPROXIMATE LOCATION OF FIRE PANEL
CONTROLLER.TERMINATE CONDUIT INTO BOX.
COORDINATE WITH FIRE PANEL INSTALLER FOR
EXACT LOCATION.
11. POWER FOR SITE VALVE. SEE EP101 FOR DETAILS.
12. DATA JUNCTION BOX FOR LOW VOLTAGE CABLE
FROM MAIN ELECTRICAL ROOM TO GATE
CONTROLS. COORDINATE WITH GATE INSTALLER
FOR EXACT LOCATION OF JUNCTION BOX.
JUNCTION BOX TO BE NEMA 3R RATED.
13. 2" PVC CONDUIT TO ROUTE GATE ASSOCIATED
DATA CABLES TO MAIN ELECTRICAL.TRANSITION TO
RGS AND SEAL OFF CONDUIT AS REQUIRED IN
HAZARDOUS LOCATIONS.
14. 1 1/2 PVC CONDUIT TO ROUTE POWER
CONDUCTORS TO ASSOCIATED PANEL IN HANGAR.
TRANSITION TO RGS AND SEAL OFF CONDUIT AS
REQUIRED IN HAZARDOUS LOCATIONS.
15. CIRCUITS TO POWER DROP BEAM. ROUTE IN
CONDUIT DEPICTED IN KEYNOTE 14. JUNCTION
BOXES TO BE NEMA 3R RATED.
16. PAD MOUNTED CT CABINET CFCI. CT CABINET PAD
SHALL BE PROVIDED BY CONTRACTOR PER MG&E
STANDARDS.CONTRACTOR TO COORDINATE WITH
MG&E FOR PAD DETAILS.
17. PROPOSED STUB UP LOCATION FOR MTS-HD.
LOCATE STUB UP UNDER MTS-HD. REFER TO EP601
FOR CONDUIT SIZE.
18. PROPOSED STUB UP LOCATION FOR CONDUITS
SERVING SWITCHBOARD MDP. REFER TO SHEET
EP601 FOR CONDUIT QUANTITY AND SIZES.
19. UNDERGROUND FEEDS FOR MTS-HD.
0 20' 40'
1" = 20'
1 ADDENDUM 2 06/08/2022
W
IS C O NS IN
P R
O F
E
S S I O N A L
E N G
I N E
E R
JOHN T
LITTLE
E-47833
EDMOND
OK