17_ITEM 01.3-7_ADD 03_02700SF102.pdf

PDF 436 KB Posted

Attached to
F-35 THREE BAY SPECIALIZED HANGAR Federal contract opportunity
Solicitation number
W50S9F-22-B-0001
Issued by
Department of the Army National Guard

About this file

This is an invitation for bid for construction services to build an F-35 three bay specialized hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The project scope includes demolishing an existing 19,875 square foot building and constructing a new 31,000 square foot three bay hangar with associated administrative and shop spaces to support fuel cell operations, indoor wash requirements, squadron level surface coating operations and weapons load training. The facility will also require a lightning protection system, fall protection, and an Advantor security system.

The solicitation includes a base CLIN for construction of the new hangar and two option CLINs, one for a paint/mix addition and another for aircraft rated pavement. The pre-bid conference will be held on-site at Truax Field and bids must be submitted through the System for Award Management website. The contract duration is 550 days from notice to proceed. The estimated value is between $25-100 million and the North American Industry Classification Code is 236220. The Department of the Army National Guard is the issuing agency.

View the file

Other files for this federal contract opportunity

Other files attached to F-35 THREE BAY SPECIALIZED HANGAR, newest first.
File Type Posted
02_ITEM 01.2-2_ADD 04_Section 04 20 00.pdf PDF
04_ITEM 01.2-4_ADD 04_Section 07 24 00.pdf PDF
10_ITEM 01.2-10_ADD 04_Section 32 13 14.13.pdf PDF
15_ITEM 01.3-5_ADD 04_02700SF105.pdf PDF
17_ITEM 01.3-7_ADD 04_02700SF503.pdf PDF
23_ITEM 01.3-13_ADD 04_02700A-503.pdf PDF
25_ITEM 01.3-15_ADD 04_02700ES101.pdf PDF
26_ITEM 01.3-16_ADD 04_02700EP102.pdf PDF
27_ITEM 01.3-17_ADD 04_02700EP701.pdf PDF
03_ITEM 01.2-3_ADD 03_Section 05 50 13.pdf PDF
09_ITEM 01.2-9_ADD 03_Section 26 05 26.00 40.pdf PDF
11_ITEM 01.3-1_ADD 03_02700G-002.pdf PDF
13_ITEM 01.3-3_ADD 03_02700C-401.pdf PDF
15_ITEM 01.3-5_ADD 03_02700C-404.pdf PDF
16_ITEM 01.3-6_ADD 03_02700C-601.pdf PDF
18_ITEM 01.3-8_ADD 03_02700SF103.pdf PDF
33_ITEM 01.3-23_ADD 03_02700IG-500.pdf PDF
34_ITEM 01.3-24_ADD 03_02700FX102.pdf PDF
36_ITEM 01.3-26_ADD 03_02700FA102.pdf PDF
MAT MGMT PPLAN_Approval for 3-Bay Hangar.pdf PDF
W50S9F22B0001 Solicitation - Ammend 0001.pdf PDF
Questions and Answers 1.pdf PDF
01_FSB2020-270-00_WI-ANG_3-Bay_ADD NO. 02_2022.06.08_Narrative.pdf PDF
05_ITEM 01.2-4_ADD 02_Section 03 30 00.pdf PDF
06_ITEM 01.2-5_ADD 02_Section 04 20 00.pdf PDF
09_ITEM 01.2-10_ADD 02_Section 09 06 00.pdf PDF
10_ITEM 01.2-11_ADD 02_Section 11 94 10.pdf PDF
14_ITEM 01.2-15_ADD 02_Section 32 13 14.13.pdf PDF
15_ITEM 01.3-1_ADD 02_02700G-102.pdf PDF
16_ITEM 01.3-2_ADD 02_02700C-101.pdf PDF
19_ITEM 01.3-5_ADD 02_02700C-402.pdf PDF
20_ITEM 01.3-6_ADD 02_02700S-001.pdf PDF
28_ITEM 01.3-14_ADD 02_02700SF210.pdf PDF
29_ITEM 01.3-15_ADD 02_02700SF502.pdf PDF
30_ITEM 01.3-16_ADD 02_02700AD-101.pdf PDF
35_ITEM 01.3-21_ADD 02_02700A-402.pdf PDF
36_ITEM 01.3-22_ADD 02_02700A-500.pdf PDF
37_ITEM 01.3-23_ADD 02_02700A-501.pdf PDF
38_ITEM 01.3-24_ADD 02_02700A-702.pdf PDF
42_ITEM 01.3-28_ADD 02_02700ES101.pdf PDF
43_ITEM 01.3-29_ADD 02_02700EG101.pdf PDF
Bid Opening Directions.pdf PDF
02_ITEM 01.2-1_ADD 02_PROJECT TOC.pdf PDF
08_ITEM 01.2-9_ADD 02_Section 08 87 35.pdf PDF
17_ITEM 01.3-3_ADD 02_02700C-301.pdf PDF
F-35 3-Bay Hangar Site Visit Attendance.pdf PDF
Supplemental Site Visit Instructions.pdf PDF
ATTACHMENT 2 - Volume 4 - WI ANG F-35 3-Bay CD Specs ADD 01 (1 of 2).pdf PDF
ATTACHMENT 6 - 20220208 Single Source Determination - Marshall Best - Redacted.pdf PDF
ATTACHMENT 7 - 20220208 Single Source Determination - Monaco - Redacted.pdf PDF
Show all 50

F-35 THREE BAY SPECIALIZED HANGAR has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

GFEC

C

B

B

MK LD

H

8C1

SF209

D1

SF210

W

X3

W18X35 W18X40

W18X35

W

X4

W18X35 W21X44

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X2

W

X4

W

X4

W

X4

W12X14

W 10X22

W10X12

14'-2 3/8" 5'-10 3/4" 2'-8 1/4"

10'-10 5/8" 25'-8 1/8" 35'-2 3/4" 2'-11"

20'-6" 20'-8" 20'-6"

3' -1

0"

9' -9

'-7

'-6

'-0

'-1

0"

'-4

/4

9' -0

'-0

/8

C1

SF202

C1

SF207

C1

SF206

C1

SF208

C4

SF402

W16X26

W

X2

W

X2

W

X2

W

X2

W

X2

W16X26

W

X2

W

X2

4'-0" 5'-0" 5'-0" 5'-0" 5'-0" 4'-0" 5'-0" 5'-0" 4'-9 1/4"

4'-0 1/8"

5'-0" 3'-9" 3'-9 1/4"

1'-7 1/4"

2'-11"

W

X2

W

X4

W

X4

W

X4

W

X4

W

X4

W

X4

W

X4

W

X4

W

X4

W

X4

W

X5

W

X1

W

X1

W

X1

W18X35

3'-8" 5'-0" 5'-0" 5'-3 1/2" 4'-3 1/2"

5'-2" 5'-3" 4'-0" 5'-0"

1'-3 1/8" 3'-8 7/8"

5'-0" 5'-0" 4'-0"

4'-3 1/8" 8 7/8" 5'-0" 4'-9 5/8"

3'-11 3/4"

3'-4 3/8" 4'-7 3/8" 4'-2 1/2"

4'-9 1/2"

2'-10 1/4"

3' -6

/8

7' -8

/2

7'

-9

/2

4 1/4"

C.2 G.6F.7B.7

4.3

3/4"

1 1/2"

2' -3

/2

3'

-6

3' -6

1/ 2"

4'-1 3/8"

4 1/2"

4'-6" 4'-6"

1'-6 1/8"

HVU-1

1500 LBS

RTU

2670 LBS

EF

72 LBS

2'-11"

W

X2

1'-4 5/8"

1'-1 3/8"

W16X26

W16X26 W16X26

W16X26

W

X3

BRACING

BR

AC

IN

G

BR

AC

IN

G

MATCHLINE

SEE A1 /

SF103

MATCHLINE

SEE A1 /

SF103

A1

SF206

A1

SF208

A1

SF207

A1

SF209

W

X2

CMU

WALL

STEEL

FRAMING

W

X2 21' -0

SF504

A3

SF502

C1

TYP

SF502

C2

TYP

SF507

A1

SF507

B5

TYP

PIPE RACK

(REFER ELEV)

GIRTS TYP

(REFER ELEV)

20'-1 1/8" 23'-10" 22'-0" 22'-6" 9'-0"

4'-9 1/4"

4'-0 1/8"

5'-0"

AT GRID 6

SF507

D5

SIM

W

X3

SF507

B3

SIM

SF507

B43 1/2"

DECK BRG

116'-8 1/8"

DECK BRG

116'-8 1/8"

EF

72 LBS

EF

72 LBS

1. PROVIDE BOTTOM FLANGE BRACES ON ALL PERIMETER ROOF

BEAMS AS SHOWN ON DETAILS.

2. ALL SUSPENDED MECHANICAL, ELECTRICAL AND FIRE

PROTECTION PIPES OR EQUIPMENT SHALL BE SUPPORTED BY

BEAMS. PROVIDE KICKERS AS NEEDED. ATTACHMENT TO

METAL DECK FROM BELOW IS NOT ALLOWED.

3. LOCATION AND WEIGHTS OF MECHANICAL EQUIPMENT SHOWN

ON PLAN ARE BASIS OF DESIGN. VERIFY WITH MECHANICAL

FOR ADDITIONAL INFORMATION. GC TO COORDINATE FINAL

LOCATION AND WEIGHT WITH SUPPORT REQUIREMENTS.

LOW ROOF FRAMING PLAN NOTES

2 MECHANICAL ROOF TOP UNIT OR MAKE UP AIR UNIT. REFER

TO MECHANICAL FOR UNIT SCHEDULING. GC TO COORD

FINAL LOCATION OF THE W8X18 SUPPLEMENTARY STEEL TO

SUPPORT UNIT CURBS ONCE FINAL UNITS HAVE BEEN

SELECTED. GC TO COORDINATE OPENINGS THRU ROOF OR

WALL AND PROVIDE ANGLE FRAMING FOR ROOF OPENING

AND COLD FORMED FRAMING AT WALL OPENINGS.

MECHANICAL EXHAUST FAN. REFER TO MECHANICAL

DRAWINGS FOR FAN SCHEDULING. PROVIDE ANGLE FRAME

AT EXHAUST FAN TO SUPPORT DUCT PENETRATION IN THE

DECK AND THE EXHAUST FAN CURB PER DETAIL .

GC TO COORD LOCATION OF ANGLE FRAME ONCE FINAL

UNIT SIZE AND LOCATION HAVE BEEN SELECTED.

A3 / S-002

1 ROOF DECKING

1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED

WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL

SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP

FASTENERS 20" OC.

4 PCA UNITS. PROVIDE STEEL FRAMING AS SHOWN ON

DETAIL . REFER TO MECHANICAL DRAWINGS

FOR UNIT SCHEDULING.

5 SKYLIGHTS AND SKYLIGHT OPENING FRAMING

6 CMU WALL BELOW. REFER TO FOUNDATION PLAN.

A1 / SF508

7 ROOF DECKING

1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED

WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL

SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP

FASTENERS 6" OC.

8 EXPANSION JOINT ALONG WALL

9 MECHANICAL GAS PIPE ANCHOR. REFER TO DETAIL

A4/SF101.

COORDINATE FINAL LOCATION AND HEIGHT WITH THE

MECHANICAL CONTRACTOR.

10 ROOF ACCESS HATCH. PROVIDE ROOF FRAMING

OPENING PER DETAIL A3/S-002.

5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436

405.840.2931 | fsb-ae.com

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

FSB2020-270-00

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

NWC / JBC

F-

3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin

Ai r N at io na l G ua rd

C

B

A

D

C

B

A

54321

DECEMBER 23, 2021N

N

PROJECT

KEYPLAN

A

PLAN TRUE

C :\U sers\ich\D o cum ents\M y R evit\02700_Stru_ih ortonXV Z5D

.rvt

6/13/2022 11:07 :38 AM

LOW ROOF FRAMING PLAN -

SECTOR ONE

SF102

TJD

GMR

GMR

SCALE: 1/8" = 1'-0"

LOW ROOF FRAMING PLAN - SECTOR ONEA1

0 4' 8' 16'

1/8" = 1'-0"

1 ADDENDUM 2 06/08/2022

2 ADDENDUM 3 06/14/2022

W

IS C O NS IN

P R

O F

E

S S I O N A L

E N G

I N E

E R

GENE O.

BROWN

E-47748

OKLAHOMA CITY

OK

File details come from the government source that posted it. Updated .