This solicitation package seeks bids for construction services to alter an F-35 aircraft hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The project includes demolishing 19,913 square feet of hangar shop space and reconfiguring the area for F-35 aircraft maintenance operations. An additional 19,803 square feet of hangar space will be modified to accommodate F-35 aircraft, including modifications to the high expansion foam fire suppression system, aircraft make-up power and air systems, and lightning protection. The project will be awarded as a single firm fixed-price construction contract with a period of performance of 365 days from notice to proceed. The government estimates the contract value to be between $10-25 million. The pre-bid conference will be held on February 16, 2021 and bids are due by March 8, 2021. The solicitation is designated as unrestricted with a HubZone preference and requires a small business subcontracting plan for large businesses.
View the file
Other files for this federal contract opportunity
Show all 50
F-35 Alter Hangar 406 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRUAX FIELD ANGB - F-35: ALTER BLDG 406 Addendum 1
XGFG182008 24 FEB 2021
SECTION 10 22 39
FOLDING PANEL PARTITIONS
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM C423 (2009a) Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method
ASTM D751 (2006; R 2011) Coated Fabrics
ASTM E84 (2020) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E90 (2009; R2016) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
ASTM E413 (2016) Classification for Rating Sound Insulation
ASTM E557 (2012; R 2020) Standard Guide for Architectural Design and Installation Practices for Sound Isolation between Spaces Separated by Operable Partitions
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
CHEMICAL FABRICS AND FILM ASSOCIATION (CFFA)
CFFA-W-101-D (2002) Quality Standard for Vinyl Coated Fabric Wallcovering
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
SECTION 10 22 39 Page 1
20-1; TIA 20-2; TIA 20-3; TIA 20-4)
National Electrical Code
NFPA 101 (2018; ERTA 18-1; ERTA 18-2; ERTA 18-3;
ERTA 18-4; TIA 18-1; TIA 18-2; TIA 18-3;
TIA 18-4) Life Safety Code
NFPA 286 (2019) Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Coordination Drawings; G
Wiring Diagrams; G
Layouts; G
Installation Drawings; G
SD-03 Product Data
Folding Panel Partitions; G
Recycled Content for Steel Components
Recycled Content for Aluminum Components
SD-04 Samples
Partition System Samples; G
SD-06 Test Reports
Acoustical Test Reports; G
Flame and Smoke Development Tests; G
SD-07 Certificates
SECTION 10 22 39 Page 2
Installer Qualifications
Manufacturer's Qualifications
SD-08 Manufacturer's Instructions
Installation Instructions
SD-10 Operation and Maintenance Data
Folding Panel Partitions, Data Package 1 and 2; G
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certification
1.3.1.1 Finish Covering
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 QUALITY ASSURANCE
1.4.1 Coordination Drawings
Provide reflected ceiling plans, applicable details and other drawings as required to suit conditions, drawn to scale, for the following coordinated items, using input from adjacent materials/systems installers, field measurements and verification of conditions:
a. Partition track, track supports and bracing, switches, and storage layout.
b. Suspended ceiling system components and structural members used for attachment.
c. Items penetrating finished ceiling in vicinity of folding panel partition location.
1.4.2 Installer Qualifications
Installer must have a minimum of 5 years of documented successful experience in the installation of folding panel partitions. When required by manufacturer, folding panel partitions must be installed by an authorized dealer with a certified crew.
1.4.3 Manufacturer's Qualifications
Manufacturer must have a minimum of 10 years of documented successful experience in designing and manufacturing folding panel partitions conforming to the requirements specified in this Section.
SECTION 10 22 39 Page 3
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the jobsite in the manufacturer's original, unopened, and undamaged packages with labels legible and intact. Provide labels to indicate the manufacturer, brand name, size, finish, and placement location. Store partitions and accessories in unopened packages in a manner to prevent damage. Handle partition materials in accordance with manufacturer's instructions. Protect materials from the weather, humidity and temperature variations, dirt and dust, or other contaminants.
1.6 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for specified warranty periods from date of final acceptance of the work as follows:
1.6.1 Warranty Periods
a. Structural: 10 years
b. Fabric Materials: 3 years
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide manual operation, acoustical folding panel partitions, factory finished, supported from overhead track without floor gliders, as shown on the drawings including all hardware, seals, track and rollers as needed to close the specified opening.
Submit detail coordination drawings and installation drawings of each folding panel partition indicated. Include elevations, dimensions, clearances, details of construction and anchorage, and details of joints and connections.
Submit manufacturers' descriptive product data for folding panel partition indicated. Include manufacturers' literature, finishes, profiles and thicknesses of materials.
Submit manufacturers' operations and maintenance data for folding panel partition in accordance with Section 01 78 23 OPERATIONS AND MAINTENANCE
DATA.
2.1.1 Manual Operation
Manual operation must be a force no greater than 20 lbf to start movement at the rate of 3.33 ft/s (200 ft/min). Use a removable handle to extend and retract the bottom operable seals; vertical movement of seals must be 2 inches. Provide closure to the lead wall with the use of a flexible bulb;
accomplish final closing by means of a lever exerting pressure against the wall.
2.1.2 Performance Requirements
2.1.2.1 Fire Resistance Ratings
Provide covering and lining with flame spread rating of 25 or less, fuel contribution rating of 15 or less, smoke generation of 50 or less in accordance with NFPA 101 when tested in accordance with ASTM E84. Submit flame and smoke development tests reports. Provide door and partition
SECTION 10 22 39 Page 4 finishes with a Class A rating when tested in accordance with ASTM E84.
2.1.2.2 Laboratory Acoustical Requirements
Provide partitions tested in accordance with ASTM E90, by a laboratory accredited by the U.S. Bureau of Standards, that have attained a sound transmission class (STC) of not less than 48 in a fully extended position, with a Noise Reduction Coefficient (NRC) of 0.25-0.30 for napped, tufted or looped fabric . Provide documentation that the partition tested is the same construction, materials, and model number as the partition to be provided and be fully operable. Test specimen is not less than 14 feet by 9 feet. Provide a minimum panel weight of 5.5 per square foot for STC up to 40, 7.5 psf for STC up to 45, 8.5 per square foot for STC up to 50, and
10.0 per square foot for STC up to 53. Design panel thickness (3 inch nominal) and composition to provide the required STC rating in accordance with ASTM E90 and ASTM E413. Submit acoustical test reports in accordance with ASTM E90, ASTM C423 and ASTM E413.
2.1.2.3 Electrical Components, Devices and Accessories
Listed and labeled as defined in NFPA 70 by qualified testing agency, and marked for intended location and application.
2.2 MATERIALS
Provide heavy-duty type hardware standard with the manufacturer. Provide pulls and latches for all partitions. Provide partitions with keyed locks.
Provide clear anodized aluminum finish hardware. Provide horizontal and vertical trim painted grey with matching rubber.
2.3 FOLDING PANEL PARTITIONS
Provide folding panel partitions using top hung ball bearing carriers which support modular panels.
a. Provide partitions made up of a series of rigid panels, each panel being a one-piece assembly. Unless otherwise specified, use the least number of panels. The mechanical seal of the panel must actuate with a single operating action.
b. Provide paired(centerfold) type panels as indicated.
2.3.1 Panels
Provide panels of steel skin, laminated to appropriate structural acoustical backing, mounted in full perimeter protective frame. Steel for the panel frames must be manufacturer's standard . Provide . Frame must enclose and protect all edges of the surface material. Provide panels not more than 4 feet wide, except for end closure panels, and full height to track. Panels must lock in place to form a stable, rigid partition; low profile hinges may not project more than 1/4 inch maximum from panel edge.
Panel surfacing must wrap around the vertical panel edges without vertical trim.
Provide steel components that contain a minimum of 10 percent recycled content. Provide data identifying percentage of recycled content for steel components.
Provide aluminum components that contain a minimum of 30 percent recycled content. Provide data identifying percentage of recycled content for
SECTION 10 22 39 Page 5 aluminum components.
2.3.2 Partition System
Provide finish covering material minimum 54 inches wide, Type II vinyl with a minimum total weight of 13 ounces/square yard and 20 ounces/linear yard in accordance with CFFA-W-101-D, and conforming to ASTM D751 and NFPA 286. Provide acrylic backed fabric of 100 percent polyolefin .
Provide non-allergenic stain and mildew resistant fabric that does not rot or support growth of bacteria. Provide finish covering that meets emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type). Provide certification of indoor air quality for finish covering.
2.3.3 Track
Provide recess extruded aluminum track as shown. Provide aluminum that conforms to ASTM B221 . Provide track that is the manufacturer's standard product designed for the weight of the finished partition, including door.
Provide track sections in the maximum lengths practicable, and not less than 6 feet long except for narrow doors and at ends of runs where short length and "drop-out service" sections of track are required. Provide suitable joint devices such as interlocking keys at each joint to provide permanent alignment of track.
2.3.4 Suspension System
Provide a suspension system consisting of steel track connected to the structural support by threaded rods, and trolleys designed to support the weight of the partition. Provide extruded aluminum track with minimum thickness of 1/8 inch.
2.4 ACCESSORIES
2.4.1 Pass Doors
Provide ADA/ABA compliant pass door of the same materials, finish and thickness as the basic panels. Pass door panel legs require bottom thresholds. Provide pass door leaf with perimeter trim to protect face finish and to provide visual identification as required by International Building Code. Pass door leaf incorporates a self-adjusting retractable bottom seal providing sound control when door is closed. Hinges finished to match other exposed hardware.
2.4.1.1 Pass Door Hardware
a. Mechanically operated floor seal on panels containing pass doors.
b. Automatic door closer. .
c. Latchset: Passage set.
d. Lock: Key operated lock with cylinder operable from both sides of the door. Include two keys per lock.
e. Exit Sign: . Recessed, self-illuminated.
f. Prepped for door window side light.
SECTION 10 22 39 Page 6
g. Door Viewer: Installed with view in direction of swing.
h. Panic hardware for emergency exit with lock override feature.
2.4.2 Metal Soffit
Provide soffit when steel or aluminum track is recessed. Provide metal soffit of adequate thickness to protect the ceiling from damage by door operation and with the door manufacturer's standard neutral-color applied finish. Provide soffit on aluminum track that is an integral part of the track.
2.5 SEALS AND SWEEPSTRIPS
Provide perimeter seals or sound insulation, of manufacturer's standard product, to achieve the sound transmission class specified , without crack or craze when subjected to severe usage. Provide manufacturer's vertical seals between panels to ensure acoustical rating. Bottom seals consist of a vinyl sweep mechanical seal which expands in place, or provide panels which can be lowered by a removable operating device. Provide vertical seal between panels which is anodized, architectural grade, aluminum extrusion with sound seal. Sweep strips must be vinyl or other material that will not crack or craze with severe usage. Provide sweep strip STC to the specified rating.
2.6 COLOR
Provide partition system samples in sizes indicated below and colors as selected by COR from manufacturers standard colors.
2.6.1 Sample Size
a. Textile Facing Material: Full width by not less than 12 inches long.
PART 3 EXECUTION
3.1 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth. Install in accordance with the approved installation drawings and the manufacturer's written installation instructions.
3.1.1 Preparation Work
Verify dimensions and condition of openings scheduled to receive folding panel partitions. Install partitions in accordance with the approved partition layouts, manufacturer's directions, and ASTM E557. Provide structural support for the track support elements as indicated.
3.1.2 Adjustment
Adjust manually operated partitions to open and close from any position with a maximum horizontal force as specified in paragraph MANUAL OPERATION applied to pendant pull, box or handle.
SECTION 10 22 39 Page 7
3.2 FIELD TESTS
3.2.1 Operational Test
In the presence of the Contracting Officer, operate partition at least three times to demonstrate that partition is capable of being moved from the stored position to the fully extended position smoothly and quietly .
Adjust partitions which do not operate properly and retest.
3.2.2 Visual Test
Conduct visual field tests for light leakage with all room lights turned on in the space on one side of the partition. Darken space on the other side of the partition. Light leakage from the lighted space to the darkened space is not acceptable. If light leakage does occur, adjust the partition to correct the problem and retest.
3.3 CLEANING
Clean any soiled parts of the partition in accordance with manufacturer's written instructions.
-- End of Section --
SECTION 10 22 39 Page 8