NJ ANG F-16 MTC Flight Sim - AQRC 189015 Addm No 5 - Spec Sect 01_45_00 - Attmts.pdf
PDF 355 KB Posted
- Attached to
- Construction of F16 Mission Training Center
- Solicitation number
- W50S8F-26-R-A011
- Issued by
-
Department of the Army National Guard
About this file
This document is Addendum No. 5 (dated July 10, 2026) to a federal construction contract for the NJANG F-16 MTC (Flight Simulator Facility) at Atlantic City Air National Guard Base, New Jersey. It specifies Quality Control (QC) specialist qualifications, areas of responsibility, and surveillance frequency requirements for eight distinct construction disciplines, and provides a detailed Schedule of Fire Protection System Inspections by the Fire Protection QC (FPQC) Specialist.
The QC Specialist Experience Matrix establishes minimum qualifications for Civil, Structural, Architectural, Mechanical, Electrical, Fire Protection, Communications/ESS, and Roofing specialists. Requirements vary by discipline—for example, Civil requires a graduate Civil Engineer with PE and 2 years experience or a technician with 5 years experience; Structural requires a graduate Structural Engineer with 2 years experience or 5 years inspection experience; and Fire Protection requires NICET Level III/IV certification or Registered Fire Protection Engineer status. All specialists must perform weekly surveillance during their respective installation phases. The Fire Protection QC schedule divides surveillance into three phases: (1) Surveillance During Construction, including visual inspections and observations of fire suppression systems, special fire suppression systems, passive fire protection, and fire alarm systems; (2) Pre-Final Acceptance Inspection, requiring the FPQC to inspect all fire protection and life safety systems, witness functional testing, identify deficiencies, and certify conformance; and (3) Final Acceptance Inspection, requiring verification of proper installation and operation, end-to-end fire alarm testing, and certification that all deficiencies have been corrected. Documentation in FPQC Reports per UFGS 01 45 00 is mandatory for all inspections and observations, with deficiencies recorded in a rework list.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFB JV | Atkins / Black & Veatch / FSB
QC Specialist Experience Matrix Addendum No. 5 July 10, 2026
Project: NJANG F-16 MTC (Flight Simulator Facility – Atlantic City ANGB, NJ
QC Area Minimum Qualifications Area of Responsibility QC Surveillance Frequency
Assigned QC Specialist
Civil Graduate Civil Engineer or Construction Man-ager with PE (preferred) and 2 years experi-ence, or Technician with 5 years experience
Earthwork, utilities, paving, grad-ing, erosion control
Weekly during site work; periodic thereafter
(TBD)
Structural Graduate Structural Engineer or PE with 2 years experience, or 5 years structural in-spection experience
Foundations, reinforcing steel, anchor bolts, structural steel, welding, concrete placement
Weekly during structural work
(TBD)
Architectural 5 years experience inspecting architectural finishes
Masonry, drywall, ceilings, doors, hardware, finishes, roofing, water-proofing
Weekly during ar-chitectural work
(TBD)
Mechanical Graduate Mechanical Engineer or Licensed Mechanical Contractor with 2 years experi-ence, or 5 years field supervision
HVAC, plumbing, TAB, controls, insulation, piping, equipment startup
Weekly during in-stallation and startup
(TBD)
Electrical Graduate Electrical Engineer or Licensed Master Electrician with 2 years experience, or 5 years field supervision
Power distribution, lighting, grounding, generators, UPS, fire alarm interfaces
Weekly during electrical installa-tion
(TBD)
Fire Protec-tion
NICET Level III/IV or Registered Fire Protec-tion Engineer
Sprinkler systems, fire alarm, ac-ceptance testing
Weekly installation and all testing
(TBD)
Communica-tions/ESS
BICSI RCDD or manufacturer-certified techni-cian with 5 years experience
Structured cabling, IDS, ACS, CCTV, fiber optic systems
Weekly during in-stallation and com-missioning
(TBD)
Roofing Manufacturer-certified roofing inspector Roofing installation, flashing, test-ing, warranty inspections
Weekly during roof-ing work
(TBD)
SCHEDULE OF FIRE PROTECTION SYSTEM
INSPECTIONS BY FPQC SPECIALIST
1. INSTRUCTIONS for FPQC Specialist:
Perform surveillance of fire protection system installation during construction and during pre-final and final acceptance inspections. Surveillance includes either visual inspections or observations performed by the FPQC as indicated in the following Schedule of Fire Protection System Inspections.
Check boxes in the schedule indicate the inspections or observations that are applicable to this project, which must be performed and documented by the FPQC.
Surveillance of fire protection system inspections is divided into three phases:
Surveillance During Construction – Includes periodic on-site visits by the FPQC during construction
Pre-Final Acceptance Inspection – FPQC must be onsite during pre-final acceptance inspection
Final Acceptance inspection – FPQC must be onsite during final acceptance inspection
2. INSPECTION TYPE
VISUAL INSPECTION:
Perform on-site visual inspections as indicated in the Schedule of Fire Protection System Inspections as construction progresses to confirm work conforms with the contract requirements including but not limited to verifying proper installation of equipment and materials in accordance with applicable codes. Where work will be covered up by finished walls and ceilings, inspections must be scheduled and performed when work is still visible.
OBSERVATION:
Observe component and system testing in person on-site as indicated in the Schedule of Fire Protection System Inspections. Confirm testing is completed in accordance with applicable codes and that testing was successful.
DOCUMENTATION:
Document all inspections and observations in the FPQC Report in accordance with UFGS 01 45 00.
Document any deficiencies and all work observed that has been successfully performed in accordance with the contract documents. Record deficiencies in the rework list.
Addedum No. 5, dated July 10, 2026
PERFORM SURVEILLANCE DURING CONSTRUCTION
~ FIRE SUPPRESSION SYSTEM ~
PERFORM
TASK IF
CHECKED
TASK
INSPECTION
TYPE DESCRIPTION
☒ 1. Verify proper installation of underground service main and service; laterals, thrust blocks, tie-rods and connection to above ground piping.
VISUAL
INSPECTION
✓ Visually inspect materials
✓ Visually inspect installation
☒ 2. Verify proper orientation of fire hydrants and fire department access
VISUAL
INSPECTION
✓ Visually inspect installation and orientation
☐ 3. Verify proper installation of interior and exterior attachments, coatings, and vortex plate prior to filling fire protection water tank
VISUAL
INSPECTION
✓ Visually inspect fire protection water tank installation
☒ 4. Hydrostatic/leak test for underground piping
OBSERVE ✓ Verify proper test method
✓ Confirm test was successful
☒ 5. Hydrostatic/leak test for above ground piping prior to ceiling installation
OBSERVE ✓ Verify proper test method
✓ Confirm test was successful
☒ 6. Underground system flush prior to connection to the riser
OBSERVE ✓ Verify system was properly flushed
☒ 7. Forward flow and cross connection control test for Backflow preventer
OBSERVE ✓ Verify proper test method
✓ Confirm test was successful
☒ 8. Suction pipe flush prior to fire pump startup
OBSERVE ✓ Verify system was properly flushed
☒ 9. Hydrostatic test fire pump suction and discharge piping
OBSERVE ✓ Verify proper test method
✓ Confirm test was successful
☒ 10. Fire pump startup OBSERVE ✓ Confirm successful startup
☒ 11. Verify proper installation of sprinkler piping prior to wall or ceiling installation
VISUAL
INSPECTION
✓ Inspect pipe hangars, bracing, sprinkler heads
✓ Inspect for sprinkler obstructions;
damaged, painted or covered heads
✓ Verify proper location of control valves, drains, vents, backflow, test header
✓ Verify proper component mounting heights
☒ 12. Document inspections and observations in FPQC Report
DOCUMENT ✓ Submit report for each day inspections or observations occur
✓ Annotate deficiencies and satisfactory work observed
✓ Record rework items in FPQC report
~ SPECIAL FIRE SUPPRESSION SYSTEM ~
PERFORM
TASK IF
CHECKED
TASK
INSPECTION
TYPE DESCRIPTION
☐ 1. Verify proper installation of gaseous fire suppression system
VISUAL
INSPECTION
✓ Inspect gas cylinders, initiating controls, shutdowns, aborts, and visual warning
☐ 2. Verify proper installation of IR hangar detector
VISUAL
INSPECTION
✓ Inspect detector and nozzle layout
✓ Inspect for obstructions, abort stations
✓ Inspect riser piping
☐ 3. Verify proper installation of elevator fire protection
VISUAL
INSPECTION
✓ Inspect elevator recall functions
✓ Inspect two-way communication
☒ 4. Verify proper installation of fire suppression in secure spaces
VISUAL
INSPECTION
✓ Inspect location of sprinkler piping and sprinklers
☒ 5. Document inspections and observations in FPQC Report
DOCUMENT ✓ Submit report for each day inspections or observations occur
✓ Document deficiencies and satisfactory work observed in FPQC Report
✓ Record deficiencies in rework list
~ PASSIVE FIRE PROTECTION SYSTEMS ~
PERFORM
TASK IF
CHECKED
TASK
INSPECTION
TYPE DESCRIPTION
☒ 1. Verify proper construction of fire rated assemblies
VISUAL
INSPECTION
✓ Inspect partitions for proper fire rated construction per design
✓ Inspect doors and door hardware for proper fire rating
✓ Inspect glass for proper fire rating
☐ 2. Verify proper installation of fireproofing
VISUAL
INSPECTION
✓ Inspect for use of proper fireproofing materials
✓ Inspect for cracking, spalling or delaminating
✓ Inspect for proper application thickness
☒ 3. Verify proper installation of firestopping
VISUAL
INSPECTION
✓ Inspect to confirm firestopping system is UL tested or an engineering judgement has been obtained and submitted
✓ Inspect for use of proper firestopping materials
✓ Inspect penetrations through fire rated walls, partitions and ceilings
✓ Inspect construction joints and gaps
☒ 4. Document inspections and observations in FPQC Report
DOCUMENT ✓ Submit report for each day inspections or observations occur
✓ Document deficiencies and satisfactory work observed in FPQC Report
✓ Record deficiencies in rework list
~ FIRE ALARM SYSTEMS ~
PERFORM
TASK IF
CHECKED
TASK
INSPECTION
TYPE DESCRIPTION
☒ 1. Verify proper installation of fire alarm system after conduit is installed and wiring pulled, but before devices are installed
VISUAL
INSPECTION
✓ Inspect conduit, wiring, conduit fill, wire type
✓ Inspect installation heights of back boxes
☒ 2. Document inspections and observations in FPQC Report
DOCUMENT ✓ Submit report for each day inspections or observations occur
✓ Document deficiencies and satisfactory work observed in FPQC Report
✓ Record deficiencies in rework list
~ END OF SURVEILLANCE DURING CONSTRUCTION SECTION
PERFORM DURING PRE-FINAL ACCEPTANCE INSPECTION
PERFORM
TASK IF
CHECKED
TASK
INSPECTION
TYPE DESCRIPTION
☒ 1. Inspect all fire protection systems and all life safety features
VISUAL
INSPECTION
✓ Verify proper installation of fire protection and life safety systems
☒ 2. Witness functional testing of all fire protection and life safety systems
OBSERVE ✓ Verify proper testing is performed on fire protection and life safety systems
☒ 3. Identify deficiencies that require correction
VISUAL
INSPECTION
✓ Document deficiencies in FPQC Report and record in rework list
☒ 4. Verify rework items have been corrected
VISUAL
INSPECTION
✓ Record re-inspection results on FPQC Report
☒ 5. Document results of pre-final inspection and photograph unsatisfactory conditions
DOCUMENT ✓ Document results of pre-final inspection in FPQC Report
☒ 6. Certify installation and operation of all fire protection and life safety systems conform to the contract documents
DOCUMENT ✓ Provide separate letter certifying conformance with contract requirements
~ END OF PRE-FINAL INSPECTION SECTION
PERFORM DURING FINAL ACCEPTANCE INSPECTION
PERFORM
TASK IF
CHECKED
TASK
INSPECTION
TYPE DESCRIPTION
☒ 1. Verify proper installation and operation of all fire protection systems and all life safety features
VISUAL
INSPECTION
✓ Witness final acceptance testing
✓ End-to-end testing of fire alarm system
☒ 2. Note any deficiencies identified by Government FPE on deficiency list
DOCUMENT ✓ Document deficiencies identified by Government FPE on deficiency list
☒ 3. Verify all deficiencies have been corrected
VISUAL
INSPECTION
✓ Inspect rework to confirm all deficiencies have been corrected
☒ 4. Certify that all deficiencies have been corrected
DOCUMENT ✓ Document inspection results on FPQC Report
~ END OF FINAL ACCEPTANCE INSPECTION SECTION