RFI 32-35.pdf
PDF 81 KB Posted
- Attached to
- Repair and Add to Maintenance Complex - Hangar B Project Federal contract opportunity
- Solicitation number
- W50S8E22B0001
About this file
This document contains a request for information and associated federal contract opportunity for repair and addition work at an aircraft hangar complex. The request for information seeks specifications for flooring finishes and clarification on partition wall types and flooring transitions. The federal contract opportunity solicitation will repair and add to an existing hangar, with an option for communications wiring work. It is a 100% small business set-aside with a magnitude over $10 million. The pre-bid conference is scheduled for November 10th and bids are due November 23rd. The contract duration is 365 days from notice to proceed. The work must be performed at the 106th Rescue Wing in Westhampton Beach, New York and the North American Industry Classification code is 236220.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract of Offers Page 3.pdf | ||
| Abstract of Offers Page 2.pdf | ||
| Attendance Sheet.pdf | ||
| Abstract of Offers Page 1.pdf | ||
| 10 22 19.pdf | ||
| Attachment A Modified - Specifications Addendum.pdf | ||
| W50S8E22B0001 0003.pdf | ||
| RFI 50.pdf | ||
| RFI 48-49.pdf | ||
| WS0S8E22B0001 - Blank Vetting Form.xlsx | XLSX spreadsheet | |
| RFI 45-47.pdf | ||
| RFI 36-44.pdf | ||
| W50S8E22B0001 0002.pdf | ||
| 10 51 13 - Metal Lockers.pdf | ||
| RFI 17-31.pdf | ||
| W50S8E22B0001 0001.pdf | ||
| RFI 1-16.pdf | ||
| Attendance Sheet Page 1.pdf | ||
| PreBid Site Visit Photos_20220518.pdf | ||
| Attendance Sheet Page 2.pdf | ||
| PREBID Conference Slides.pdf | ||
| Attachment A - Specifications Addendum.pdf | ||
| Specifications - Vol 1.pdf | ||
| Drawings.pdf | ||
| Specifications - Vol 2.pdf | ||
| Solicitation W50S8E22B0001.pdf |
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10 June 2022
Solicitation # W50S8E22B0001 Repair and Add to Maintenance Hangar B Complex
Request for Information (RFI) 32- 35
Q32- Please provide specs for the flooring finishes. The plans and spec sections provided to not contain manufacturer, color or material information on any of the flooring.
A32 – Refer spec section 2.3 Interior finishes of spec 09 06 00.
Q33- Which callout takes precedence? The general notes for all new partition walls or the details on A-501-E? General notes call out impact resistant GWB UNO--A501 partition types only callout "X" GWB at full height Partition Type S2
A33 – Provide Impact Resistant GWB at all partitions with the following exceptions: STC rated walls and Fire Rated walls. For walls that carry Fire rating utilize type X. For walls that carry STC rating utilize Type x or type of GWB utilized in tested assembly.
Q34- A-701 base callout RES-1 is listed at epoxy flooring areas. There is no definition in the LEGEND for RES-1--- For base install Are we to assume RB-1 or does the epoxy finish run up the walls?
A34 – Epoxy Finish EF-1 is to run up the walls. Follow per spec 090600 paragraph 2.3.2.4
Q35- No fire extinguisher callout in south section of PEMB(KEYPLAN Section E). Should there be a fire extinguisher callout in Paint Booth/ Composite Shop vicinity? If so cabinet or wall bracket?
A35 – Yes provide additional fire extinguisher on exterior wall of composite shop. The fire extinguisher shall be a cabinet.