- Renovation of Automated Fuels Service Station
- Solicitation number
- W50S8D21B0001
- Issued by
-
Department of the Army National Guard
About this file
This document contains questions and answers regarding a solicitation for the renovation of an automated fuels service station. The solicitation seeks a dispensing system for fuel tanks that will be provided by the factory. Piping will be heat traced and the fuel management and leak detection systems will connect to an on-site computer for management. No fire suppression system is required. Offerors should refer to attached specifications and instructions for submission of bids. The solicitation was issued by the Department of the Army National Guard under number W50S8D21B0001.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Briefly reading the spec, I do have a few questions:
1. Will this be a suction or dispensing system
Dispensing system
2. Do you want all Stainless steel cabinets on the pumps
This will be part of the tank assembly provided by the factory. Please see spec sheet for all provided components
3. Will there be a Fire Suppression system
No fire suppression system is required
4. Are we tying the fuel management and or leak detection system into an on site computer management system
Yes
5. What is the Thickness of the tank/ drive slab ( I would think 8” min w/ rebar)
Please see concrete slab detail
6. Is the piping to be heat traced
Yes