This document package includes engineering drawings and specifications for the renovation of an automated fuels service station. Key details include specifications for a 6,000 gallon double-wall unleaded fuel storage tank with secondary containment, piping, dispensers, pumps, controls and monitoring equipment. Additional requirements include installation of a remote fill box, emergency shutoff valves, grounding, signage, and safety equipment. The solicitation is issued by the Department of the Army National Guard to upgrade an existing facility in accordance with NFPA 30 fire code standards and EPA vapor recovery regulations. Bids are due by the specified date for the project, which is to be completed on an expedited schedule.

View the file

Other files

File Type Posted
Abstract of Offers - Construction.pdf PDF
Bid Opening Attendance Sheet.pdf PDF
RFI 10.pdf PDF
RFI 9.pdf PDF
Solicitation Amendment W50S8D21B0001_0004.pdf PDF
RFI 8.pdf PDF
FM-010_FMU_Installation_Manual(052413).pdf PDF
RFI 5.pdf PDF
RFI 6.pdf PDF
208-pe2.PNG PNG image
112664R1.pdf PDF
Bollard Detail.PNG PNG image
10 Asph- Conc-PVMT Detail.pdf PDF
208-p3.PNG PNG image
112663R1.pdf PDF
208-pe1.PNG PNG image
RFI 7.pdf PDF
208-p4.PNG PNG image
PVMT Detail.pdf PDF
Solicitation Amendment W50S8D21B0001_0003.pdf PDF
Solicitation Amendment W50S8D21B0001_0002.pdf PDF
RFI 4.pdf PDF
RFI 3.pdf PDF
208-p4.jpg JPG image
Pre-Bid Conference Attendance List.pdf PDF
Pre-Bid Conference Slides.pdf PDF
Pre-Bid Conference Minutes.pdf PDF
Solicitation Amendment W50S8D21B0001_0001.pdf PDF
RFI 2.pdf PDF
Concrete Slab Detail.PNG PNG image
Previous Contract Soils Results.pdf PDF
Q 61392_DIESEL - Updated 2 Dec 2019.pdf PDF
RFI 1.pdf PDF
Plan 2 of 2.pdf PDF
Plan 1 of 2.pdf PDF
W50S8D21B0001.pdf PDF
Performance Work Statement.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A A

B B

C C

D D

SHEET 1 OF 5

DRAWN BY

MEMCO REP

QUOTE #

Customer Approval Signature

AP

DF

12/2/2019

DWG NO

Q#61392

C-6K DIS FG UNL AIR NATIONAL

SIZE

C

SCALE

REV

AIR NATIONAL GUARD

Q#61392

*LEAD TIMES BEGIN UPON RECEIPT OF SIGNED APPROVED

DRAWING, WHICH MUST BE RETURNED BEFORE

PRODUCTION CAN BEGIN*

This document and all information and design thereon are the property of Envirosafe Fuel Systems. This document is confidential and must not be made public or copied without written authorization from Envirosafe and is subject to return upon demand. No use of this document or any design thereon is permitted except as is specifically authorized in writing by Envirosafe. Acceptance of possession of this document constitutes full agreement with the above conditions. All Rights Reserved. Memco, Inc

STI

SwRI

UL

NOTES:

1. UNLEADED FUEL USE

2.TNEMEC 3 PART PAINT FOR HIGH PERFORMANCE FINISH

3. UL 2085 LABELED AND LISTED

4. 2 HOUR RATING TESTED TO SWRI 97-04 NFPA 30 A FIRE RESISTANT TANK

5. ENGINEERED HURRICANE TIE-DOWN

6. LEAD TIME IS DEPENDENT ON IMMEDIATE APPROVAL

CUSTOMER REQUESTED

COMPLETION DATE :

WELD AND BLAST INTERIOR FOR

CHEMLINE 4000 EPOXY LINING

ZINC PRIMER

DETAIL A

SCALE 1/8

A

B

B

A A

B B

C C

D D

SHEET 2 OF 5

DRAWN BY

MEMCO REP

QUOTE #

Customer Approval Signature

AP

C-6K DIS FG UNL AIR NATIONAL

SIZE

C

SCALE

REV

SHELL THICKNESS: 1/4"

HEAD THICKNESS: 5/16"

STI

SwRI

UL

Q#61392

AIR NATIONAL GUARD

*LEAD TIMES BEGIN UPON RECEIPT OF SIGNED APPROVED

DRAWING, WHICH MUST BE RETURNED BEFORE

PRODUCTION CAN BEGIN*

This document and all information and design thereon are the property of Envirosafe Fuel Systems. This document is confidential and must not be made public or copied without written authorization from Envirosafe and is subject to return upon demand. No use of this document or any design thereon is permitted except as is specifically authorized in writing by Envirosafe. Acceptance of possession of this document constitutes full agreement with the above conditions. All Rights Reserved. Memco, Inc

25.13

25.13

218.003''

PRIMARY TANK

SECONDARY TANK

CONCRETE INSULATION

FOR FIRE RATING

8''x8''x1/4''

STRIKER PLATE

20 17 27 18 16 22 9 14 15 14 9 13 2829

6 7 5 5 3 7

3 5 5 4 5 6

18.00

1% TANK GRADE

86.59

6.00

4.25

S E

E

S

H E

E T

**TANK ONLY**

6.00 ABOVE

FROM BOTTOM

OF TANK

SECTION B-B

SCALE 1/18

PARTS LIST

ITEM QTY DESCRIPTION

1 1 6,000 GALLON FIREGUARD TANK MOUNTEED ON SADDLES

WITH 1% TANK GRADE (SLOPE TANK FROM ISSUE END TO

RECEIPT END)

2 1 MANWAY 36'' W/12'' NECK W/ GASKET & BOLTS SNIGLE PUNCH

HINGED W/HANDLES 36'' ID

3 2 8 IN NPT THREADED FLANGE

4 1 6 IN NPT THREADED FLANGE

5 5 4 IN NPT THREADED FLANGE

6 3 3" NPT THREADED FLANGE (CONCRETE PORT)

7 2 3 IN NPT THREADED FLANGE

8 2 2 IN NPT THREADED FLANGE

9 2 LIFTING LUG

10 1 REMOTE FILL BOX, TOP CONNECTION, SS W/ 3'' SS FEMALE QD

COUPLER, SS BALL VALVE, SS HAND PUMP

11 1 DISPENSER W/10:1 PULSER W/ ELECTRO-MECHANICAL

TOTALIZERS

12 1 3/4'' NOZZLE GAS WITH 3/4''x18' HOSE PUMPFLEX II, 3/4''x12''

HOSE WHIP, 3/4'' BREAKAWAY AND 3/4'' SWIVEL

13 1 3'' OVERFILL PREVENTION VALVE WITH TEST MECHANISM AND

DIFFUSER

14 2 VENT EMERGENCY 8IN 8OZ./SQ.IN- MALE THREAD- w/O-RING

15 1 VENT PRESSURE VACUUM 3'' 8 OZ/SQ.IN ALUMINUM INTERNAL

16 1 FE PETRO 3/4 HP w/RISER, 88IN - 149IN (240V 1 PH)

17 1 2" ANTI-SYPHON VALVE

18 1 VALVE BALL 2IN

19 1 INTERNAL LADDER

20 1 6' WEATHER COVER

21 1 VALVE EMERGENCY SHUT-OFF 2''X1.5'' CONTAINMENT BODY

STYLE

22 1 918 CLOCK GAUGE WITH ALARM BOX & STANDARD FLOAT

23 1 REEL GROUNDING 50' W/CABLE AND CLAMP S

24 1 MOISTURE HAND PUMP

25 2 VALVE BALL FULL FLOW 1"

26 1 VALVE ANTI-SIPHON 1"

27 1 PLATFORM W/42'' TALL REMOVABLE HANDRAILS

28 1 L-SHAPE LADDER TO ACCESS PLATFORM (SHIPPED

SEPARATELY AND INSTALLED BY OTHERS)

29 1 MONITORING CAP 2"

30 1 VAPOR RECOVERY KIT 3''

31 1 FUEL SAMPLING KIT WITH GTP 1/4'' BALL VALVE, GTP PROBE

1/4'' W 2-1/4'' TUBE LENGTH AND DUST CAP

32 1 INTERSTITIAL LEAK GAUGE

33 1 ENCLOSURE ADALET HAZ LOC TYPE 4/7/9 8''X10''X6'' W/ PAN &

HINGES W/ 3- 1/2'' NPT CONDUIT

34 1 PUMP SWITCH, COVER & BACKPLATE, 1/2" EXPLOSION PROOF

BOX

35 1 3" VERTICAL CHECK VALVE

36 1 35W IP66 LED HIGH BAY 5,075 LUMEN, 4000K, 120 DEGREE

BEAM ANGLE

37 1 TANK DECAL KIT (NOT SHOWN)

38 1 TOUCH UP PAINT (NOT SHOWN AND SHIPPED SEPARATELY)

A A

B B

C C

D D

SHEET 3 OF 5

DRAWN BY

MEMCO REP

QUOTE #

Customer Approval Signature

AP

C-6K DIS FG UNL AIR NATIONAL

SIZE

C

SCALE

REV

STI

SwRI

UL

Q#61392

AIR NATIONAL GUARD

*LEAD TIMES BEGIN UPON RECEIPT OF SIGNED APPROVED

DRAWING, WHICH MUST BE RETURNED BEFORE

PRODUCTION CAN BEGIN*

This document and all information and design thereon are the property of Envirosafe Fuel Systems. This document is confidential and must not be made public or copied without written authorization from Envirosafe and is subject to return upon demand. No use of this document or any design thereon is permitted except as is specifically authorized in writing by Envirosafe. Acceptance of possession of this document constitutes full agreement with the above conditions. All Rights Reserved. Memco, Inc

A A

B B

C C

D D

SHEET 4 OF 5

DRAWN BY

MEMCO REP

QUOTE #

Customer Approval Signature

AP

C-6K DIS FG UNL AIR NATIONAL

SIZE

C

SCALE

REV

This document and all information and design thereon are the property of Envirosafe Fuel Systems. This document is confidential and must not be made public or copied without written authorization from Envirosafe and is subject to return upon demand. No use of this document or any design thereon is permitted except as is specifically authorized in writing by Envirosafe. Acceptance of possession of this document constitutes full agreement with the above conditions. All Rights Reserved. Memco, Inc

*LEAD TIMES BEGIN UPON RECEIPT OF SIGNED APPROVED

DRAWING, WHICH MUST BE RETURNED BEFORE

PRODUCTION CAN BEGIN*

STI

SwRI

UL

ALARM BOX

94.50

108.86

FOR MANUFACTURING

USE ONLY

26 25

AIR NATIONAL GUARD

220 V 1 PH

CONNECTION

TO PUMP

110 V 1 PH

CONNECTION TO

DISPENSER

GROUNDING LUG

11.00

120 V

CONNECTION

TO LIGHT