08.2 Revised SPECS - Replace Storefront - 2271 2272 2273 PDPG25013.pdf

PDF 383 KB Posted

Attached to
REPLACE EXTERIOR DOORS
Solicitation number
W50S74-26-Q-A021
Issued by

About this file

This document contains technical specifications for storefront replacement work at three MARB buildings (2271, 2272, 2273), organized into five specification sections addressing aluminum framing, curtain wall systems, blast-resistant windows, door hardware, and glazing requirements.

Section 08 41 13 (Aluminum-Framed Entrances and Storefronts) specifies narrow-stile aluminum entrance doors with impact-resistant capabilities designed for high-traffic applications. Requirements include 6063-T5 aluminum extrusions, EPDM or thermoplastic elastomer glazing gaskets, structural silicone sealants, and rigid thermal barriers. The system must withstand wind loads of 40 psf (positive) and 10 psf (negative) on exterior walls, with maximum deflection of L/175 or 3/4 inches. Certified test reports are required for wind load resistance, deflection, condensation resistance (CRF minimum 66), thermal transmittance (U-value maximum 0.53), water infiltration, and structural performance. Door corner construction must use mechanical clip fastening with SIGMA deep penetration plug welds and 1 1/8 inch fillet welds. Hardware includes mortise locksets, panic devices, surface closers, and exit devices. Manufacturers include Ives, Schlage, Von Duprin, and LCN. The contractor must conduct pre-installation meetings within 30 days of contract award and submit shop drawings, product data, finish samples, and certified test reports. Warranties include 2-year manufacturer coverage for materials and 10-year coverage for insulating glass units against seal failure.

Section 08 44 00 (Curtain Wall and Glazed Assemblies) specifies a stick-system curtain wall with aluminum framing, insulated panels, windows, and glazing for vertical mullion configuration. Aluminum alloys must meet AA ASD1 standards with minimum recycled content of 20 percent; structural steel must conform to ASTM specifications. The system must withstand 30 psf design wind loads per ASCE 7, with maximum deflection of L/175 or 3/4 inches. Seismic performance requirements per AAMA 501.4 & 501.6 include Phase I testing at 0.005 times story height and Phase II at 0.010 times story height with no damage or failure. Thermal conductance testing per ASTM C1363 requires maximum U-value of 0.36 for complete wall assembly. Factory testing must demonstrate water penetration resistance per ASTM E331 at 20 percent of design wind pressure (minimum 4 psf), air infiltration not exceeding 0.06 cfm per square foot per ASTM E283, and window structural adequacy per ASTM E330/E330M with no glass breakage. Panels must have maximum U-value of 0.036. Finishes include Type II anodized aluminum and fluoropolymer paints meeting AAMA 2604/2605. The contractor must submit structural and thermal calculations, conduct mockup testing, and provide as-built schedules with keying, wiring diagrams, and manufacturer maintenance information.

Section 08 56 53 (Blast Resistant Tempered Glass Windows) specifies tempered glass windows compliant with ASTM C1048 Grade B and ANSI Z97.1, designed to withstand uniform static loads per acceptance criteria using statistical analysis. At least two sample window assemblies per window type must be tested under increasing uniform static loads until failure occurs in glass or frame. The static load capacity formula is rs = 0.876 ru (50 psi for 18x18 inch glass). Acceptance criteria require the arithmetic mean failure load r̄ to satisfy r̄ ≥ rs + sA, where s is sample standard deviation and A is the acceptance coefficient from a provided statistical table. Windows must conform to AAMA/WDMA/CSA 101/I.S.2/A440 with weatherstripping and hardware allowing operation after withstanding design blast pressure. Environmental conditions require minimum 40°F for glazing work with manufacturer-approved warming procedures. Glass manufacturer's instructions for setting and sealing materials must be submitted and followed.

Section 08 71 00 (Door Hardware) establishes comprehensive hardware requirements including hinges (Ives preferred), locks (Schlage mortise locksets), exit devices (Von Duprin panic hardware), and closers (LCN surface-mounted). Key specifications mandate hinges with sufficient throw to permit maximum door swing; mortise locksets with 0.75-inch throw stainless steel latchbolts, field-changeable handing, and independent breakaway spindles; panic devices with 1,000,000-cycle rating and 2000-pound static load resistance for exterior doors; and door closers with 10,000,000-cycle rating, rack-and-pinion type, non-sized, non-handed, and adjustable for 5-pound opening pressure (exterior and interior). Hardware finish is BHMA 622 Matte Black throughout. The key system is Schlage FSIC full-size interchangeable core with temporary construction keying and permanent cores installed by the government. Installation locations are specified per SDI-100 and building codes, with latching hardware positioned 34-44 inches above finished floor and panic hardware at 36-44 inches. Acceptable manufacturers include Stanley (hinges), Trimco (accessories), Zero (thresholds), and Glynn-Johnson (overhead stops). The contractor must conduct pre-installation meetings with manufacturers, verify existing conditions before ordering, and provide an as-built schedule including keying plan. Hardware warranties include 10 years for locksets and exit devices (3 years electrical), 30 years for closers, and 1-2 years for other items.

Section 08 81 00 (Glazing) specifies clear, annealed, laminated, tempered, heat-strengthened, spandrel, and fire-rated glass per ASTM and GANA standards. Insulating glass units must have inner panes of annealed Type I flat glass and outer panes of tempered glass, with Low-E coatings achieving U-value maximum of 0.28 Btu/hr-ft²-F and SHGC maximum of 0.30. All glazing material in doors and sidelights must meet 16 CFR 1201 safety standards. Setting and sealing materials include elastomeric sealants (ASTM C920 Type S, Grade NS, white color), neoprene setting blocks (Shore A 70-90 durometer), edge blocks (Shore A 50 durometer), and preformed gaskets conforming to ASTM C509 or C864. The contractor must follow GANA Glazing Manual, IGMA TM-3000, and IGMA TB-3001 recommendations for preparation, installation, and protection. Glass edges exposed in finish work must be ground smooth in the shop, and labels must remain in place until installation approval. The contractor must provide 10-year warranty for insulating glass units against seal failure causing obstruction to vision, excluding glass breakage.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPLACE STOREFRONT - BUILDINGS 2271 2272 2273 MARB

SECTION 08 41 13

ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)

AAMA 1503 (2009) Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections

AAMA 2605 (2013) Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

AAMA 501 (2015) Methods of Test for Exterior Walls

AAMA 800 (2010) Voluntary Specifications and Test Methods for Sealants

AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)

ASCE 7 (2010; Errata 2011; Supp 1 2013) Minimum Design Loads for Buildings and Other Structures

ASTM INTERNATIONAL (ASTM)

ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM E1105 (2015) Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference

ASTM E1424 (1991; R 2016) Standard Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure and Temperature Differences Across the Specimen

ASTM E1886 (2013a) Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Missile(s) and Exposed

SECTION 08 41 13 Page 1 to Cyclic Pressure Differentials

ASTM E1996 (2014a) Standard Specification for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Windborne Debris in Hurricanes

ASTM E283 (2004; R 2012) Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen

ASTM E330/E330M (2014) Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference

ASTM E331 (2000; R 2016) Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference

ASTM E783 (2002; R 2010) Standard Test Method for Field Measurement of Air Leakage Through Installed Exterior Windows and Doors

ASTM F1642 (2012) Standard Test Method for Glazing and Glazing Systems Subject to Airblast Loadings

BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)

ANSI/BHMA A156.10 (2011) Power Operated Pedestrian Doors

ANSI/BHMA A156.4 (2013) Door Controls - Closers

INTERNATIONAL CODE COUNCIL (ICC)

ICC IBC (2015) International Building Code

U.S. GENERAL SERVICES ADMINISTRATION (GSA)

FS TT-P-645 (Rev C) Primer, Paint, Zinc-Molybdate, Alkyd Type

UNDERWRITERS LABORATORIES (UL)

UL 325 (2013; Reprint Dec 2016) UL Standard for Safety Door, Drapery, Gate, Louver, and Window Operators and Systems

1.2 ADMINISTRATIVE REQUIREMENTS

1.2.1 Pre-Installation Meetings

Conduct a meeting before installation begins to verify the project requirements, substrate conditions, manufacturer's installation instructions, and manufacturer's warranty requirements.

SECTION 08 41 13 Page 2

Within 30 days of the Contract Award, submit the following for review and approval by the Contracting Officer:

a. List of product installations

b. Sample warranty

c. Finish and color samples

d. Manufacturer's catalog data

Concurrently submit certified test reports showing compliance with specified performance characteristics and UL 325 for the following:

a. Wind Load (Resistance) in accordance with AAMA 501

b. Deflection in accordance with ASTM F1642

c. Condensation Resistance and Thermal Transmittance Performance Requirements in accordance with AAMA 1503

d. Water Infiltration in accordance with ASTM E331

e. Structural Requirements in accordance with ASTM F1642

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 81 13 LEED V2009 REQUIREMENTS.

Submit the following in accordance with Section 01 33 00 SUBMITTAL

PROCEDURES:

SD-01 Preconstruction Submittals

Sample Warranty; G

List of Product Installations; G

SD-02 Shop Drawings

Installation Drawings; G

Fabrication Drawings; G

SD-03 Product Data

Manufacturer's Catalog Data; G

Finish; G

SD-04 Samples

Finish and Color Samples; G

SD-06 Test Reports

SECTION 08 41 13 Page 3

Certified Test Reports; G

Deflection

Air Infiltration

Condensation Resistance and Thermal Transmittance

Water Infiltration

SD-08 Manufacturer's Instructions

Manufacturer's Instructions

SD-11 Closeout Submittals

Manufacturer's Product Warranty

1.4 QUALITY CONTROL

1.4.1 Qualifications

1.4.1.1 Installer Qualifications

Provide documentation of the installer's experience in performing the work specified in this section.

Ensure that the installers have specialized in work similar to that required for this project, and that they are acceptable to product manufacturer.

1.4.1.2 Manufacturer Qualifications

Ensure that manufacturers meet the requirements specified in this section and project drawings.

Ensure that the manufacturer is capable of providing field service representation during construction, approving acceptable installers and approving application methods.

1.4.2 Single-Source Responsibility

When aluminum entrances are part of a building enclosure system, that includes storefront framing, windows, a curtain wall system, and related products, provide building enclosure system products from a single-source manufacturer.

Use a single source manufacturer with sole responsibility for providing design, structural engineering, and custom fabrication for door portal systems and for supplying components, materials, and products. Do not use products provided from numerous sources for assembly at the site. Ensure that the following work items and components are fabricated or supplied by a single source are:

a. Glazed walls to be constructed around door portals as specified in this Section.

b. Door operating hardware to be installed on or within door portals as specified in Section 08 71 00 DOOR HARDWARE.

SECTION 08 41 13 Page 4

c. Glass as specified in Section 08 81 00 GLAZING.

1.5 DELIVERY, STORAGE, AND HANDLING

1.5.1 Ordering

To avoid construction delays, comply with the manufacturer's lead-time requirements and instructions for ordering.

1.5.2 Packing, Shipping, Handling and Unloading

Deliver materials in the manufacturer's original, unopened, undamaged containers with identification labels intact.

1.5.3 Storage and Protection

Store materials in a way that protects them from exposure to harmful weather conditions. Avoid damaging the storefront material and components during handling. Protect storefront material against damage from elements, construction activities, and other hazards before, during, and after storefront installation.

Do not use adhesive papers or sprayed coatings that become firmly bonded when exposed to sunlight. Do not leave coating residue on surfaces.

1.6 PROJECT / SITE CONDITIONS

1.6.1 Field Measurements

Verify actual measurements or openings by taking field measurements before fabrication; record these measurements on shop drawings. To avoid construction delays, coordinate field measurements, and fabrication schedule with construction progress.

1.7 WARRANTY

Provide a written manufacturer's warranty, executed by a company official, warranting against defects in materials and products for 2 years from the date of shipment. Warrant that the door corner construction is for the life of the project. Provide a written installer's warranty, warranting work to be watertight and free from defective materials, defective workmanship, and glass breakage as a result of defective design, and agreeing to replace components that fail within 2 years.

The warranty states the following:

a. Watertight and airtight system installation is completed within specified tolerances.

b. The completed installation remains free of rattles, wind whistles and noise caused by thermal movement and wind pressure.

c. System is structurally sound and free from distortion.

d. Glass and glazing gaskets will not break or "pop" from frames as a result of design, wind load pressure, movement caused by expansion or contraction, or structural loading.

SECTION 08 41 13 Page 5

Provide a written thermal integrity warranty for 2 years from ship date against thermal barrier system failure resulting from the following:

a. Longitudinal and transverse thermal barrier shrinkage.

b. Thermal barrier cracking.

c. Structural failure of the thermal barrier material.

d. Loss of adhesion or loss of prescribed edge pressure on glazing material, resulting in excessive air and water infiltration.

PART 2 PRODUCTS

2.1 SYSTEM DESCRIPTION

Provide aluminum entrances, with glass and glazing, door hardware, and components.

Aluminum entrances include impact resistance entrances; narrow stile, 2 1/4 inch vertical face dimension, 1 3/4 inch depth, for interior structural silicone glaze, for high-traffic/impact-resistant applications.

a. Provide offset glazing, inside mount frames, bottom weep.

2.1.1 Design Requirements for Aluminum (Entrances and Components)

Provide a door portal system designed to withstand the following loads without breakage, loss, failure of seals, product deterioration, or other defects.

a. Dead and Live Loads: Determined by ASCE 7 and calculated in accordance with applicable codes.

b. Seismic Loads: Design and install the system to comply with the seismic requirements for the project location in accordance with Section 1613 of the International Building Code, ICC IBC .

c. Wind Loads: Design and install the system so that the effects of wind load acting inward and outward normal to the plane of the wall are in accordance with ASTM E330/E330M .

d. Thermal Loads And Movement:

(1) Ambient Temperature Range: 120 degrees F

(2) Material Surfaces Range: 180 degrees F

e. Water and Air Resistance: Provide weatherstripping, exterior gaskets, sealants, and other accessories to resist water and air penetration.

f. Impact-Protective Systems Provide an impact-protective system in accordance with ASTM E1886 and ASTM E1996.

2.1.1.1 Material Standard

ASTM B221; 6063-T5 alloy and tempered.

Provide door stile and rail face dimensions of the entrance doors as

SECTION 08 41 13 Page 6 follows:

Vertical Stile Top Rail Bottom Rail

3-1/2 inches 3-1/2 inches 6-1/2 inches

Provide major portions of the door members at 0.125 inches nominal in thickness and glazing molding at 0.050 inches thick.

2.1.1.2 Sealants

Provide either ethylene propylene diene monomer (EPDM) elastomeric extrusions or thermoplastic elastomer glazing gaskets. Structural silicone sealant is required.

Internal Sealants: Provide sealants that according to the manufacturer will remain permanently elastic, tacky, non-drying, non-migrating, and weather tight.

2.1.1.3 Thermal Barrier

Use a rigid, structural thermal barrier to separate all exterior aluminum from interior aluminum. For purposes of this specification, a structural thermal barrier is defined as a system that transfers shear during bending and, therefore, promotes composite action between the exterior and interior extrusions. Do not use a nonstructural thermal barrier. Ensure that the thermal barrier provides a structural connection between the two sides of the door.

2.2 FABRICATION

Provide the following information when submitting fabrication drawings for custom fabrications:

a. Indicate elevations, detailed design, dimensions, member profiles, joint locations, arrangement of units, and member connections.

b. Show the following items:

(1) Details of special shapes.

(2) Reinforcing.

(3) Anchorage system.

(4) Interfacing with building construction.

(5) Provisions for expansion and contraction.

(6) Thermal breaks.

c. Indicate typical glazing details, locations of various types and thickness of glass and internal sealant requirements as recommended by the sealant manufacturer.

d. Clearly indicate locations of exposed fasteners and joints.

e. Clearly show where and how the manufacturer's system deviates from Contract drawings and these specifications.

SECTION 08 41 13 Page 7

2.2.1 Entrance System Fabrication

Provide door corner construction consisting of mechanical clip fastening, SIGMA deep penetration plug welds and 1 1/8 inch long fillet welds inside and outside all four corners. Provide a hook-in type exterior glazing stop with EPDM glazing gaskets reinforced with non-stretchable cord. Provide an interior glazing stop that is mechanically fastened to the door member and that incorporates a silicone-compatible spacer used with silicone sealant.

Accurately fit and secure joints and corners. Make joints hairline in appearance. Remove burrs and smooth edges. Prepare components with internal reinforcement for door hardware. Arrange fasteners and attachments so that they are concealed from view.

Separate dissimilar metals with protective coating or pre-formed separators in order to prevent contact and corrosion.

2.2.2 Shop Assembly

Fabricate and assemble units with joints only at the intersection of aluminum members with hairline joints; rigidly secure these units, and seal them in accordance with the manufacturer's recommendations.

2.2.2.1 Welding

Conceal welds on aluminum members in accordance with AWS recommendations or methods recommended by the manufacturer. Members showing welding bloom or discoloration on finish or material distortion will be rejected by the Contacting Officer.

2.2.3 Finish

Type II Anodized in accordance with ASTM B580

a. Color: Black

2.2.4 Fabrication Tolerance

Fabricate and assemble units with joints only at intersection of aluminum members with hairline joints; rigidly secure these units, and seal them in accordance with the manufacturer's recommendations.

Fabricate aluminum entrances in accordance with the entrance manufacturer's prescribed tolerances.

SECTION 08 41 13 Page 8

2.2.4.1 Material Cuts

Square to 1/32 inch off square, over largest dimension; proportionate amount of 1/32 inch on the two dimensions.

2.2.4.2 Maximum Offset at Consecutive Members

1/64 inch in alignment between two consecutive members in line, end to end.

2.2.4.3 Maximum Offset at Glazing Pocket Corners

1/64 inch between framing members at glazing pocket corners.

2.2.4.4 Joints

Between adjacent members in same assembly: Joints are hairline and square to the adjacent member.

2.2.4.5 Variation

In squaring diagonals for doors and fabricated assemblies: 1/16 inch.

2.2.4.6 Flatness

For doors and fabricated assemblies: plus/minus 1/16 inch of neutral plane.

2.3 MATERIALS

2.3.1 Sealants

Refer to Section 07 92 00 JOINT SEALANTS. Ensure that all sealants conform to AAMA 800.

2.3.2 Glass

Refer to Section 08 81 00 GLAZING.

2.4 ACCESSORIES

2.4.1 Fasteners

Provide stainless steel fasteners in areas where the fasteners are exposed.

Use non-corrosive and compatible fasteners with components being fastened.

Do not use exposed fasteners, except where unavoidable for application of hardware.

In areas where fasteners are not exposed, use aluminum, non-magnetic stainless steel, or other materials warranted by the manufacturer.

For exposed locations, provide countersunk Phillips head screws when items with a matching finish are fastened. For concealed locations, provide the manufacturer's standard fasteners.

Provide nuts or washers that have been designed with a means to prevent disengagement; do not deform fastener threads.

SECTION 08 41 13 Page 9

2.4.2 Perimeter Anchors

When steel anchors are used, provide insulation between steel material and aluminum material in order to prevent galvanic action.

2.4.2.1 Inserts and Anchorage Devices

Provide manufacturer's standard formed or fabricated assemblies, steel or aluminum, of shapes, plates, bars, or tubes. Shop-coat steel assemblies after fabrication with an alkyd zinc chromate primer complying with

FS TT-P-645 .

2.4.3 Standard Entrance Hardware

2.4.3.1 Weatherstripping

Equip meeting stiles on pairs of doors with an adjustable astragal using wool pile with a polymeric fin.

Provide door weatherstripping on a single-acting offset pivot or butt-hung door and frame (single or pairs) consisting of a thermoplastic elastomer weatherstripping on a tubular shape with a semi-rigid polymeric backing.

Provide sill-sweep strips: Provide an EPDM blade gasket sweep strip in an aluminum extrusion applied to the interior exposed surface of the bottom rail with concealed fasteners. (Provide as necessary to meet specified performance tests.)

2.4.3.2 Threshold

Provide an extruded aluminum threshold, one piece per door opening, with ribbed surface.

2.4.3.3 Offset Pivots

Provide the manufacturer's standard top and bottom pivots with one intermediate offset pivot.

2.4.3.4 Panic Device

Provide the manufacturer's recommended standard panic hardware.

2.4.3.5 Closer

Provide a surface closer in accordance with ANSI/BHMA A156.4 .

2.4.3.6 Security Lock or Dead Lock

Provide A/R MS 1850A lock with two A/R 1871 cylinder operated flush bolts.

2.4.3.7 Cylinder(s)/Thumb-turn

Provide the manufacturer's recommended standard.

2.4.3.8 Cylinder Guard

Provide the manufacturer's recommended standard.

SECTION 08 41 13 Page 10

PART 3 EXECUTION

3.1 EXAMINATION

3.1.1 Site Verification of Conditions

Verify that the condition of substrate previously installed under other sections is acceptable for product installation in accordance with the manufacturer's instructions.

Verify that openings are sized to receive the storefront system and that the sill plate is level in accordance with the manufacturer's acceptable tolerances.

3.2 PREPARATION

Field-verify dimensions before fabricating components for the door portal assembly.

Coordinate requirements for locations of blockouts for anchorage of door portal columns and other embedded components with Section 03 30 00

CAST-IN-PLACE CONCRETE.

Coordinate the erection of door portal with installation of surrounding glass wall and door assemblies. Ensure that the door portals can provide support and anchorage for assembly components.

3.2.1 Adjacent Surfaces Protection

Protect adjacent work areas and finish surfaces from damage during product installation.

3.2.2 Aluminum Surface Protection

Protect aluminum surfaces from contact with lime, mortar, cement, acids, and other harmful contaminants.

3.3 INSTALLATION

Submit installation drawings for review and approval.

Install the entrance system in accordance with the manufacturer's instructions and the AAMA storefront and entrance guide specifications manual. Attach the entrance system to the structure, allowing it to be adjusted to accommodate construction tolerances and other irregularities.

Provide alignment attachments and shims to permanently fasten the system to the building structure. Align the assembly so that it is plumb and level, and free of warp and twist. Maintain assembly dimensional tolerances aligning with adjacent work.

Set thresholds in a bed of mastic and secure the thresholds. Protect aluminum members in contact with masonry, steel, concrete, or dissimilar materials using nylon pads or a bituminous coating. Shim and brace the aluminum system before anchoring the system to the structure. Verify that weep holes are open, and the metal joints are sealed in accordance with the manufacturer's installation instructions. Seal metal-to-metal joints using a sealant recommended by the system manufacturer.

SECTION 08 41 13 Page 11

3.3.1 Tolerances

Ensure that tolerances for wall thickness and other cross-sectional dimensions of entrance members are nominal and in compliance with Aluminum Standards and Data, published by the Aluminum Association.

3.3.2 Adjusting

Adjust operating hardware for smooth operation, and as recommended by the manufacturer.

3.3.3 Related Products Installation Requirements

3.3.3.1 Sealants (Perimeter)

Refer to Section 07 92 00 JOINT SEALANTS.

3.3.3.2 Glass

Refer to Section 08 81 00 GLAZING.

3.4 FIELD QUALITY CONTROL

3.4.1 Air Infiltration

Test air infiltration in accordance with ASTM E783

Submit certified test reports showing compliance with specified performance characteristics as follows:

a. For single-acting offset pivot, butt hung, or continuous geared hinge entrances in the closed and locked position, test the specimen in accordance with ANSI/BHMA A156.10 , and ASTM E283 at a pressure differential of 1.57 psf for pairs of doors; ensure that maximum infiltration for a pair of 7 foot by 8 foot entrance doors and frame is

1.2 cfm/square foot.

b. Ensure the maximum allowable infiltration for a completed storefront system does not exceed 0.06 cfm/square foot when tested in accordance with ASTM E1424 at a differential static pressure of 6.24 psf.

3.4.2 Wind Loads

Provide a completed storefront system capable of withstanding wind pressure loads, normal to the wall plane indicated, as follows:

a. Exterior Walls

(1) Positive Pressure: 40 psf

(2) Negative Pressure: 10 psf

b. Interior Walls: (pressure acting in either direction) 10 psf

3.4.3 Deflection

Submit certified test reports showing that the maximum allowable deflection in a member when tested in accordance with ASTM E330/E330M with allowable stress is L/175 or 3/4 inches maximum.

SECTION 08 41 13 Page 12

3.4.4 Condensation Resistance and Thermal Transmittance

Submit certified test reports showing compliance with specified performance characteristics as follows:

a. U-Value Requirements:

(1) Perform test in accordance with the AAMA 1503 procedure and on the configuration specified therein.

(2) Thermal Transmittance ("U" Value) maximum 0.53 BTU/hr/sf/deg F at 15 mph exterior wind.

b. CRF Class Requirements:

(1) Perform a test in accordance with AAMA 1503.

(2) Condensation Resistance Factor Requirements (CRF) minimum 66.

3.4.5 Water Infiltration

Submit certified test reports showing that the system is designed to provide no uncontrolled water when tested in accordance with ASTM E1105 at a static pressure of 8 psf.

3.5 ADJUSTING AND CLEANING

3.5.1 Protection

Protect the installed product's finish surfaces from damage during construction. Protect the aluminum storefront system from damage from grinding and polishing compounds, plaster, lime, acid, cement, or other harmful contaminants.

3.5.2 Cleaning

Repair or replace damaged installed products. Clean installed products in accordance with manufacturer's instructions before acceptance remove excess mastic, mastic smears, and other foreign materials. Remove construction debris from the project site and legally dispose of this debris.

3.6 WARRANTY

Submit three signed copies of the manufacturer's product warranty for the entrance system as follows:

a. Warranty Period: Five years from Date of Substantial Completion of the project, provided that the Limited Warranty begins no later than six months from the date of shipment by the manufacturer. In addition, support welded door corner construction with a limited lifetime warranty for the life of the door under normal use.

Ensure that the Warranty's language is identical to the "As Approved" version of the sample warranty submitted to and returned from the Contracting Officer.

-- End of Section --

SECTION 08 41 13 Page 13

REPLACE STOREFRONT - BUILDINGS 2272 2272 2273 MARB

SECTION 08 44 00

CURTAIN WALL AND GLAZED ASSEMBLIES

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ALUMINUM ASSOCIATION (AA)

AA ADM (2015) Aluminum Design Manual

AA ASD1 (2013) Aluminum Standards and Data

AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)

AAMA 501.1 (2005) Standard Test Method for Water Penetration of Windows, Curtain Walls and Doors Using Dynamic Pressure

AAMA 501.4 & 501.6 (2009) Recommended Static Test Method for Evaluating Curtain Wall and Storefront Systems Subjected to Seismic and Wind Induced Interstory Drifts & Recommended Dynamic Test Method for Determining the Seismic Drift Causing Glass Fallout from a Wall System

AAMA 609 & 610 (2015) Cleaning and Maintenance Guide for Architecturally Finished Aluminum

AAMA 611 (2014) Voluntary Specification for Anodized Architectural Aluminum

AAMA 800 (2010) Voluntary Specifications and Test Methods for Sealants

AAMA CW-10 (2015) Care and Handling of Architectural Aluminum from Shop to Site

AAMA MCWM-1 (1989) Metal Curtain Wall Manual

AAMA/WDMA/CSA 101/I.S.2/A440 (2011; Update 1 2014) North American Fenestration Standard/Specification for Windows, Doors, and Skylights

AAMA 2604 (2013) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels

AAMA 2605 (2013) Voluntary Specification, SECTION 08 44 00 Page 1

Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

AMERICAN IRON AND STEEL INSTITUTE (AISI)

AISC/AISI 121 (2004) Standard Definitions for Use in the Design of Steel Structures

AISI SG03-3 (2002; Suppl 2001-2004; R 2008) Cold-Formed Steel Design Manual Set

AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)

ASCE 7 (2010; Errata 2011; Supp 1 2013) Minimum Design Loads for Buildings and Other Structures

AMERICAN WELDING SOCIETY (AWS)

AWS A5.1/A5.1M (2012) Specification for Carbon Steel Electrodes for Shielded Metal Arc Welding

AWS A5.10/A5.10M (2012) Welding Consumables - Wire Electrodes, Wires and Rods for Welding of Aluminum and Aluminum-Alloys - Classification

AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel

ASTM INTERNATIONAL (ASTM)

ASTM A1008/A1008M (2016) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardened

ASTM A1011/A1011M (2015) Standard Specification for Steel, Sheet, and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability and Ultra-High Strength

ASTM A123/A123M (2013) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware

ASTM A27/A27M (2013; R 2016) Standard Specification for Steel Castings, Carbon, for General Application

ASTM A283/A283M (2013) Standard Specification for Low and Intermediate Tensile Strength Carbon Steel

SECTION 08 44 00 Page 2

Plates

ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel

ASTM A424/A424M (2009a; R 2016) Standard Specification for Steel Sheet for Porcelain Enameling

ASTM A47/A47M (1999; R 2014) Standard Specification for Ferritic Malleable Iron Castings

ASTM A501/A501M (2014) Standard Specification for Hot-Formed Welded and Seamless Carbon Steel Structural Tubing

ASTM A572/A572M (2015) Standard Specification for High-Strength Low-Alloy Columbium-Vanadium Structural Steel

ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM B108/B108M (2015) Standard Specification for Aluminum-Alloy Permanent Mold Castings

ASTM B136 (1984; R 2013) Standard Method for Measurement of Stain Resistance of Anodic Coatings on Aluminum

ASTM B137 (1995; R 2014) Standard Test Method for Measurement of Coating Mass Per Unit Area on Anodically Coated Aluminum

ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate

ASTM B211 (2012) Standard Specification for Aluminum and Aluminum-Alloy Bar, Rod, and Wire

ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM B244 (2009; R 2014) Standard Method for Measurement of Thickness of Anodic Coatings on Aluminum and of Other Nonconductive Coatings on Nonmagnetic Basis Metals with Eddy-Current Instruments

ASTM B26/B26M (2014; E 2015) Standard Specification for Aluminum-Alloy Sand Castings

ASTM B316/B316M (2010) Standard Specification for Aluminum and Aluminum-Alloy Rivet and Cold-Heading Wire and Rods

ASTM B85/B85M (2014) Standard Specification for

SECTION 08 44 00 Page 3

Aluminum-Alloy Die Castings

ASTM C1036 (2016) Standard Specification for Flat Glass

ASTM C1048 (2012; E 2012) Standard Specification for Heat-Treated Flat Glass - Kind HS, Kind FT Coated and Uncoated Glass

ASTM C1363 (2011) Standard Test Method for Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus

ASTM C542 (2005; R 2011) Lock-Strip Gaskets

ASTM C864 (2005; R 2015) Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers

ASTM C920 (2014a) Standard Specification for Elastomeric Joint Sealants

ASTM D1037 (2012) Evaluating Properties of Wood-Base Fiber and Particle Panel Materials

ASTM D1730 (2009; R 2014) Standard Practices for Preparation of Aluminum and Aluminum-Alloy Surfaces for Painting

ASTM E283 (2004; R 2012) Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen

ASTM E330/E330M (2014) Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference

ASTM E331 (2000; R 2016) Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference

ASTM E34 (2011) Chemical Analysis of Aluminum and Aluminum-Base Alloys

ASTM E546 (2014) Frost Point of Sealed Insulating Glass Units

ASTM E576 (2014) Frost Point of Sealed Insulating Glass Units in the Vertical Position

ASTM E774 (1997) Classification of the Durability of Sealed Insulating Glass Units

ASTM E84 (2016) Standard Test Method for Surface Burning Characteristics of Building

SECTION 08 44 00 Page 4

Materials

NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)

NAAMM AMP 500 (2006) Metal Finishes Manual

SOCIETY FOR PROTECTIVE COATINGS (SSPC)

SSPC 7/NACE No.4 (2007; E 2004) Brush-Off Blast Cleaning

SSPC SP 1 (2015) Solvent Cleaning

SSPC SP 3 (1982; E 2004) Power Tool Cleaning

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

16 CFR 1201 Safety Standard for Architectural Glazing Materials

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 81 13 LEED V2009 REQUIREMENTS.

Submit the following in accordance with Section 01 33 00 SUBMITTAL

PROCEDURES:

SD-02 Shop Drawings

Glazed Curtain Wall System

Submit for curtain wall system, accessories, and mock-up.

Tentative approval of drawings must be received before fabrication of mock-up. Final approval of drawings will be deferred pending approval of mock-up and accessories. Drawings must indicate in detail all system parts including elevations, full-size sections, framing, jointing, panels, types and thickness of metal, flashing and coping details, field connections, weep and drainage system, finishes, sealing methods, glazing, glass sizes and details, firestopping insulation materials, and erection details.

Installation Drawings

SD-03 Product Data

Glazed Curtain Wall System

Include descriptive literature, detailed specifications, and available performance test data.

Preventive Maintenance and Inspection

Metals For Fabrication

SECTION 08 44 00 Page 5

Nonskinning Sealing Compound

Metal Accessories

Curtain-Wall Framing Members

Aluminum Doors and Frames

Curtain Wall Frame

Panels

Thermal Insulation Materials

Sealants and Caulkings

Curtain-Wall Installation Materials

Masonry Anchorage Devices

Sample Warranties

SD-05 Design Data

Calculations

Finish

Exposed-to-View Aluminum Finish

Porcelain-Enamel

Seismic Calculations

SD-08 Manufacturer's Instructions

Glazed Curtain Wall System

Insulating Glass

SD-11 Closeout Submittals

Recycled Content of Aluminum Doors and Frames; S

Recycled Content of Aluminum Curtain-Wall Framing Members; S

Recycled Content of Aluminum Windows; S

WARRANTY

1.3 REQUIREMENT FOR DESIGN DATA

Submit structural and thermal calculations for complete wall assembly.

1.4 QUALITY ASSURANCE

1.4.1 Testing Requirements

The components listed below must be tested in accordance with the

SECTION 08 44 00 Page 6 requirements below, and meet performance requirements specified.

a. Joint and Glazing Sealants: Perform tests as required by applicable publications referenced.

b. Preformed Compression Gaskets and Seals: ASTM C864.

c. Preformed Lock-strip Gaskets: ASTM C542, modified as follows: Heat age specimens seven days at 158 degrees F, in zipped or locked position under full design compression. Unzip, cool for one hour, re-zip, and test lip seal pressure, which must be minimum 2.5 pounds per linear inch on any extruded or corner specimen.

d. Spandrel Glass: Fallout resistance test, ASTM C1048.

e. Anodized Finishes: Stain resistance, coating weight, and coating thickness tests, ASTM B136, ASTM B137, and ASTM B244, respectively.

f. Insulating Glass: ASTM E546 or ASTM E576 at minus 20 degrees F, no frost or dew point.

1.4.2 Mockup

1.4.2.1 Construction

Construct at job site full size typical wall unit which incorporates horizontal and vertical joints, framing, window units, panels, glazing, and other accessories as detailed and specified. Mock-up wall unit size and design must be as indicated.

1.4.2.2 Performance Test

Conduct after approval of visual aspects has been obtained. Finished work must match approved mock-up.

1.4.2.3 Approved Mock-Up

After completion and approval of test results. Approved mock-up must remain property of the Contractor.

1.4.3 Factory Tests

Perform the following tests except that where a curtain wall system or component of similar type, size, and design as specified for this project has been previously tested, under the conditions specified herein, the resulting test reports may be submitted in lieu of testing the components.

1.4.3.1 Deflection and Structural Tests

No curtain wall framing member shall deflect, in a direction normal to the plane of the wall, more than 1/175 of its clear span or 3/4 inch, whichever is less, when tested in accordance with ASTM E330/E330M , except that when a plastered surface will be affected the deflection must not exceed 1/360 of the span. No framing member shall have a permanent deformation in excess of 0.2 percent of its clear span when tested in accordance with ASTM E330/E330M for a minimum test period of 10 seconds at 1.5 times the design wind pressures specified.

SECTION 08 44 00 Page 7

1.4.3.2 Water Penetration Test

No water penetration shall occur when the wall is tested in accordance with ASTM E331 at a differential static test pressure of 20 percent of the inward acting design wind pressure as specified, but not less than 4 psf.

Make provision in the wall construction for adequate drainage to the outside of water leakage or condensation that occurs within the outer face of the wall. Leave drainage and weep openings in members and wall open during test.

1.4.3.3 Air Infiltration Test

Air infiltration through the wall, when tested in accordance with ASTM E283, must not exceed 0.06 cfm per square foot of fixed wall area, plus the permissible allowance specified for operable windows within the test area.

1.4.3.4 Delamination Test

Adhesively bonded metal-faced panels must show no evidence of delamination, warpage or other deterioration or damage when subjected to the six "Accelerated Aging Cycles" specified in ASTM D1037.

1.4.3.5 Thermal Conductance Tests

The thermal transmittance of opaque panels must not exceed specified U-value, when tested in accordance with ASTM C1363. The average calculated thermal transmittance of the complete wall assembly including panels, windows, and all other components must not exceed a U-value of 0.36.

Determine U-values of components in accordance with ASTM C1363.

1.4.3.6 Window Tests

Windows must meet the requirements specified in 08 81 00 GLAZING except where the requirements of this section differ, this section governs.

Provide windows that meet the same requirements for deflection and structural adequacy as specified for framing members when tested in accordance with ASTM E330/E330M , except permanent deformation must not exceed 0.4 percent; there must be no glass breakage, and no permanent damage to fasteners, anchors, hardware, or operating devices. Provide windows that have no water penetration when tested in accordance with

ASTM E331.

1.4.3.7 Fire Resistance Tests

Insulation provided in the curtain wall system field applied in conjunction with the curtain wall system must have a flame spread rating not exceeding 75 and a smoke developed rating not exceeding 150 when tested in accordance with ASTM E84, except as specified otherwise herein.

a. Insulation: Insulation contained entirely within panel assemblies which meets the flame spread and smoke developed ratings of 75 and 150 respectively isolated from the building interior by masonry walls, masonry cavity walls, or encased in masonry core is not required to comply with the flame spread and smoke developed ratings specified.

1.5 GLAZED CURTAIN WALL SYSTEM REQUIREMENTS

Provide system complete with framing, mullions, trim, panels, windows, glass, glazing, sealants, insulation, fasteners, anchors, accessories, SECTION 08 44 00 Page 8 concealed auxiliary members, and attachment devices for securing the wall to the structure as specified or indicated.

1.5.1 Source

Furnish curtain wall system components by one manufacturer or fabricator;

however, all components need not be products of the same manufacturer.

1.5.2 Design

Stick system with mullions, horizontal rails, panels, window units, spandrel panels. Fully coordinate system accessories directly incorporated, and adjacent to contiguous related work and insure materials compatibility, deflection limitations, thermal movements, and clearances and tolerances as indicated or specified.

1.5.3 Thermal Movement

Fabricate, assemble, and erect system with adequate allowances for expansion and contraction of components and fastenings to prevent buckling damage, joint seal failure, glass breakage, undue stress on fastenings or other detrimental effects. For design purposes, base provisions for thermal movement on assumed ambient temperature range of from 40 degrees F to 120 degrees F.

1.5.4 Tolerances

Design and erect wall system to accommodate tolerances in building frame and other contiguous work as indicated or specified. Provide with the following tolerances:

a. Maximum variation from plane or location shown on approved shop drawings: 1/8 inch per 12 feet of length up to not more than 1/2 inch in any total length.

b. Maximum offset from true alignment between two identical members abutting end to end in line: 1/16 inch.

1.5.5 Structural Requirements

Members may not deflect in a direction parallel to the plane of the wall, when carrying its full design load, more than an amount which will reduce the edge cover or glass bite below 75 percent of the design dimension.

After deflection under full design load, members may not have a clearance between itself and the top of the panel, glass, sash, or other part immediately below it less than 1/8 inch. The clearance between the member and an operable window or door must be minimum 1/16 inch. Design entire system to withstand the indicated wind and concentrated loads, and the following wind loads acting normal to the plane of the wall:

a. On the first stories above grade 40 psf acting inward, and the same load acting outward.

c. On corner areas, extending 15 feet from the building corners on all facades, the outward-acting (negative) design load must be increased to 50 pounds per square foot.

SECTION 08 44 00 Page 9

1.5.6 Seismic Calculations

When tested to AAMA 501.4 & 501.6 , system must meet design displacement of

0.010 times the story height and ultimate displacement of 1.5 times the design displacement. Provide with the following tolerances:

a. Phase I: 3 stroke cycles using .005 times the story height - no damage or failure.

b. Phase II: 3 stroke cycles using .010 times the story height - no damage or failure.

1.6 QUALIFICATION OF WELDERS

Welding must be performed by certified welders qualified in accordance with AWS D1.1/D1.1M using procedures, materials, and equipment of the type required for the work.

1.7 DELIVERY AND STORAGE

Inspect materials delivered to the site for damage; unload and store with a minimum of handling in accordance with recommendations contained in AAMA CW-10. Storage spaces must be dry locations with adequate ventilation, free from heavy dust, not subject to combustion products or sources of water, and must allow for easy access for inspection and handling. Deliver caulking and sealing compounds to the job site in sealed containers labeled to show the designated name, formula or specifications number; lot number; color; date of manufacturer; shelf life; and curing time when applicable.

1.7.1 Protective Covering

Prior to shipment from the factory, place knocked-down lineal members in cardboard containers and cover finished surfaces of aluminum with protective covering of adhesive paper, waterproof tape, or strippable plastic. Covering must not chip, peel, or flake due to temperature or weather, must protect against discoloration and surface damage from transportation, and storage, and must be resistant to alkaline mortar and plaster. Do not cover aluminum surfaces that will be in contact with sealants after installation.

1.7.2 Identification

Prior to delivery, mark wall components to correspond with shop and erection drawings placement location and erection.

1.8 WARRANTY

Guarantee insulating glass units not to develop material obstruction of vision as a result of dust or film formation on the inner glass surface caused by failure of the seal, other than through glass breakage, within a period of 5 years from date of acceptance of work by the Government.

Replace units failing to comply with the terms of this guarantee with new units without additional cost to the Government. The Contractor must require the manufacturer to execute their warranties in writing directly to the Government.

SECTION 08 44 00 Page 10

1.8.1 Sample Warranties

Provide curtain wall and glazing assembly material and workmanship warranties meeting specified requirements. Provide revision or amendment to standard membrane manufacturer warranty to comply with the specified requirements.

a. Project Warranty: Refer to Section 01 33 00 SUBMITTAL PROCEDURES for project warranty provisions.

b. Manufacturer's Warranty: Submit, for Owner's acceptance, Manufacturer's standard warranty document executed by authorized company official manufacturer's warranty is in addition to, and not a limitation of, other rights Owner may have under the Contract Documents.

c. Assembly Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of steel fire-rated glazed curtain-wall systems that do not comply with requirements or that deteriorate as defined in this Section within specified warranty period .

d. Finish Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components on which finishes fail within specified warranty period. Warranty does not include normal weathering. Determine warranty on finish by type of finish selected.

e. Beneficiary: Issue warranty in the legal name of the project Owner .

f. Warranty Period: 2 years commencing on Date of Substantial Completion, covering complete curtain wall system for failure to meet specified requirements.

g. Warranty Acceptance: Owner is sole authority who will determine acceptability of manufacturer's warranty documents.

1.9 INTERPRETATION OF AWS CODE

Section 05 05 23.16 STRUCTURAL WELDING applies to work specified in this section.

AWS code, when referred to herein, shall mean AWS D1.1/D1.1M , "Structural Welding Code - Steel" with the following modification:

Revise AWS code Section 1, "General Provisions," Paragraph 1.1 as follows:

References to the need for approval shall mean "Approval by the Contracting Officer" and references to the "Building Commissioner" shall mean the "Contracting Officer."

1.10 QUALIFICATIONS FOR THE CURTAIN-WALL INSTALLER

Submit a written description of the proposed curtain-wall system installer giving the name of the curtain-wall manufacturer, qualifications of personnel, years of concurrent contracting experience, lists of projects similar in scope to the specified work, and other information as may be required by the Contracting Officer.

SECTION 08 44 00 Page 11

1.11 PERFORMANCE REQUIREMENTS

1.11.1 Allowable Design Stresses

Aluminum-alloy framing member allowable design stresses must be in accordance with the requirements of AA ADM pertaining to building type structures made of the specified aluminum alloy.

Hot-rolled structural-steel member allowable design stresses and design rules must be in accordance with the requirements of AISC/AISI 121 pertaining to the specified structural steel.

Cold-formed light-gage steel structural member allowable design stresses and design rules must be in accordance with the requirements of AISI SG03-3 SG570 pertaining to structural members formed from the specified structural-steel sheet or strip.

1.11.2 Design Wind Load

Design windload must be 30 pounds per square foot. Design windload must be in accordance with ASCE 7.

1.11.3 Structural Capacity

Design curtain-wall system, including framing members, windows, doors and frames, metal accessories, panels, and glazing to withstand the specified design windload acting normal to the plane of the curtain wall and acting either inward or outward.

Deflection of any metal framing member in a direction normal to the plane of the curtain wall, when subjected to the test of structural performance, using the specified windload in accordance with AAMA/WDMA/CSA 101/I.S.2/A440 , must not exceed 1/175 of the clear span of the member or 3/4 inch, whichever value is less.

Deflection of any metal member in a direction parallel to the plane of the curtain wall, when the metal member is carrying its full design load, must not exceed 75 percent of the design clearance dimension between that member and the glass, sash, panels, or other part immediately below it.

1.11.4 Provisions for Thermal Movement

Design curtain-wall systems, including framing members, windows, doors and frames, metal accessories, and other components incorporated into the curtain wall, to allow for expansion and contraction of the component parts at an ambient temperature of 100 degrees F without causing buckling, opening of joints, overstressing of fasteners, or other harmful effects.

1.12 DRAWINGS

Installation Drawings must include the following information for curtain wall assemblies.

Curtain-wall locations in building, layout and elevations, dimensions, shapes and sizes of members, thickness of metals, types and locations of shop and field connections, details of anchorage to building construction, glazing provisions, and other pertinent construction and erection details.

Location and details of anchorage devices that are to be cast-in-place in

SECTION 08 44 00 Page 12 concrete and masonry construction.

Panel dimensions, thicknesses and kinds of materials, edge details, details of installation in curtain-wall framing, and other pertinent construction and erection details.

1.13 MANUFACTURER'S INFORMATION

Preventive Maintenance and Inspection must consist of the aluminum manufacturer's recommended cleaning materials and application methods, including detrimental effects to the aluminum finish when improperly applied.

PART 2 PRODUCTS

2.1 PRODUCT SUSTAINABILITY CRITERIA

For products in this section, where applicable and to extent allowed by performance criteria, provide and document the following:

2.1.1 Recycled content of Aluminum Doors and Frames

Provide aluminum doors and frames meeting the recycled content requirements as stated within this section and provide documentation in accordance with Section 01 81 13 LEED V2009 REQUIREMENTS.

2.1.2 Recycled content of Aluminum Curtain-wall Framing Members

Provide aluminum curtain-wall framing members meeting the recycled content requirements as stated within this section and provide documentation in accordance with Section 01 81 13 LEED V2009 REQUIREMENTS.

2.1.3 Recycled Content of Aluminum Windows

Provide aluminum windows meeting the recycled content requirements as stated within this section and provide documentation in accordance with Section 01 81 13 LEED V2009 REQUIREMENTS.

2.2 MATERIALS

2.2.1 Aluminum

Must be free from defects impairing strength or durability of surface finish. Provide standard alloys conforming to standards and designations of AA ASD1. Special alloys, not covered by the following ASTM specifications, must conform to standards and designations recommended by the manufacturer for the purpose intended.

Provide Aluminum Doors, Frames, Curtain-wall Framing Members, Window Frames with a minimum recycled content of 20 percent.

2.2.1.1 Wrought Aluminum Alloys

Must be those which include aluminum alloying elements not exceeding the following maximum limits when tested and additional in accordance with ASTM E34. These limits apply to both bare products and the core of clad products. The cladding of clad products must be within the same limits

SECTION 08 44 00 Page 13 except that the maximum zinc limit may be 2.5 percent in order to assure that the cladding is anodic to the core. Special wrought alloys with a silicon content not more than 7.0 percent will be acceptable for limited structural uses where special appearance is required:

ALLOY PERCENT

Silicon 1.5

Magnesium, Manganese, and Chromium combined

6.0

Iron 1.0

Copper 0.4

Zinc 1.0

Within the chemical composition limits set forth above, wrought aluminum alloys must conform to the following:

a. Extruded bars, rods, shapes and tubes: ASTM B221.

b. Sheet and Plate: ASTM B209.

2.2.1.2 Cast Aluminum Alloys

Provide those in which the alloying elements are silicon, magnesium, manganese, or a combination of these.

This is the start of the file's text. The full file is on GovTribe.