This document includes a federal contract opportunity notice and an associated site inspection report for a traffic monitoring station. The contract opportunity is for roadwork projects in the Great Smoky Mountains National Park, consisting of asphalt paving, concrete repairs, drainage work, guardrail replacement and other tasks across three schedules. The total project value is estimated between $25-35 million. Proposals from small businesses are due in February 2023 as specified in the solicitation.
The related site inspection report provides details on the condition and maintenance needs of an automatic traffic recorder station. Items addressed include loop and sensor functionality, cabinet cleaning and repairs, solar panel voltage checks, and telecommunications checks. The report recommends remedial repairs such as conduit installation, loop splicing and painting the cabinet. It verifies the station is fully operational following repairs.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATR NO.
Temp: 62 Sunny x P.Cloudy Cloudy Rain Fog Snow
Road Type: x Asphalt PCC Other: Yes x No
Sensor x loop only loop-loop Other: Median: Yes x No Type:
Layout:
Site Profile: Open x Wooded Hilly Urban Residential Other:
(check all that apply)
Pull-off for Vehicle? x Yes No If No, Explain:
Clear View of Road from Cabinet? x Yes No Cabinet Location vs Road: x Level Above Below
Power: x AC Solar - Panel Type/Model:
Communications: x Landline Cell - Antenna Type/Model:
(check all that apply)
Poor:
Weed Wack Grass: Yes Clean Solar Panel: Yes Tighten Antenna Mount: Yes
Trim Vegetation: Yes Tighten Panel Mount: Yes Tighten Cabinet Mount: Yes
Seal Loops: Yes x Volume Vehicle Class Other:
COMMENT
LOOP #
Unloaded solar panel voltage:
AC/Solar properly grounded? x Yes No Battery connections corrosion free? x Yes No
COMMENT
DURATION
STUDIES BEING PERFORMED
Other Actions:
Loop sealant satisfactory: Excellent:
Vacuumed and cleaned cabinet interior.
Good:
Comments:
CHECK ACTIONS TAKEN
Comments: All loops are paved over.
PARKLOCATION
35.68689GPS COORDINATES:
Fair:
WEATHER CONDITIONS:
Telephone number 865-436-3830. Modem answered when dialed. Telephone voltage = 48.3 V
Vehicle parked on grass near park headquarters.
GENERAL SITE REVIEW / MAINTENANCE
Comments:
Passing allowed:
Comments:
PERMANENT TRAFFIC MONITORING INSPECTION CHECKLIST - PAGE 1
TECH
Aditya Ramachandran
-83.535912
GRSM 10/9/2012 13:00
DATE TIME
Sugarlands
MACHINE COUNT
Count Verification
MANUAL COUNT
Newfound Gap Road (To Gatlinburg)
Newfound Gap Road (To Cherokee, NC)
ROAD NAME
5450 vehicle passage
ADR backup battery = 6.69 volts DC, ADR onboard battery = 3.6 volts DC voltsA/C voltage: 124.3 volts
POWER
ATR NO.
Dial tone free of noise? x Yes No Lines properly grounded? x Yes No
Make/Model of Modem: Serial Number:
Proper connections? x Yes No Status lights working? x Yes No
Free of dust? x Yes No
COMMENT:
Mounting: x Pole mount - Type: Wood x Metal Concrete Pedestal Mount Pad Mount
Other: If Other, please explain:
Ladder required to reach? Yes x No
Does it close properly? x Yes No Lubricate Door Lock: Yes Replace Filter: x Yes
Does it seal properly? x Yes No Lubricate Padlock: Yes Seal Leaks: x Yes
Does door lock work? x Yes No Lubricate Hinges: Yes Set Insect Traps: Yes
Is there a padlock? Yes x No Condition Door Seal: Yes Set Rodent Traps: Yes
Does separate lock work? Yes No Replace Door Seal: Yes Vacuum Interior: x Yes
Free of dirt, insects, rodents? Yes x No
Does it have a vent? x Yes No
Is there a filter? x Yes No
Is there working fan? Yes x No
Any leaking holes? Yes x No
Do any leads/connectors show signs of corrosion? Yes x No Are comm lines properly marked? x Yes No
Are all loop/sensor leads properly marked? x Yes No Are power lines properly marked? x Yes No
Are ground lines properly marked? x Yes No
Make/Model of ATR: Serial #: Tag #:
Proper connections: x Yes No Correct Date & Time? x Yes No
Status lights working? x Yes No
LOOP #
CHECK ACTIONS TAKEN
LOOP/SENSOR SETTINGS
PERMANENT TRAFFIC MONITORING INSPECTION CHECKLIST - PAGE 2
TRAFFIC CABINET TYPE / MODEL:
COMMUNICATIONS
LPM 14-E 118/889
NEMA 3R
Other Actions:
Vacuumed, cleaned and wiped down cabinet.
Replaced filter.
Caulked conduit entry holes in bottom of cabinet.
Cabinet does not have a separate lock.
10230-0009
83.5 1.3
Newfound Gap Road N 86.6
Newfound Gap Road
0.8
N/A
Wiped off modem. Telephone number 865-436-3830.
ROAD NAME DIRECTION Inductance (mh ) Resistance (ohms )
S
ATR (AUTOMATIC TRAFFIC RECORDER)
PEEK ADR 1000-24 (8 lane model)
Free of Defects: Yes No Free of Defects: Yes No Free of Defects: Yes No
Defects: Defects: Defects:
Lid Installed: Yes No Lid Installed: Yes No Lid Installed: Yes No
Lid Fit Properly: Yes No Lid Fit Properly: Yes No Lid Fit Properly: Yes No
Draining Properly: Yes No Draining Properly: Yes No Draining Properly: Yes No
Leads Marked Properly: Yes No Leads Marked Properly: Yes No Leads Marked Properly: Yes No
Waterproof Splices: Yes No Waterproof Splices: Yes No Waterproof Splices: Yes No
Splices on Hook: Yes No Splices on Hook: Yes No Splices on Hook: Yes No
Proper Service Loops: Yes No Proper Service Loops: Yes No Proper Service Loops: Yes No
Box Type: Box Type: Box Type:
Free of Defects: Yes No Free of Defects: Yes No Free of Defects: Yes No
Defects: Defects: Defects:
Lid Installed: Yes No Lid Installed: Yes No Lid Installed: Yes No
Lid Fit Properly: Yes No Lid Fit Properly: Yes No Lid Fit Properly: Yes No
Draining Properly: Yes No Draining Properly: Yes No Draining Properly: Yes No
Leads Marked Properly: Yes No Leads Marked Properly: Yes No Leads Marked Properly: Yes No
Waterproof Splices: Yes No Waterproof Splices: Yes No Waterproof Splices: Yes No
Splices on Hook: Yes No Splices on Hook: Yes No Splices on Hook: Yes No
Proper Service Loops: Yes No Proper Service Loops: Yes No Proper Service Loops: Yes No
Box Type: Box Type: Box Type:
Free of Defects: Yes No Free of Defects: Yes No Free of Defects: Yes No
Defects: Defects: Defects:
Lid Installed: Yes No Lid Installed: Yes No Lid Installed: Yes No
Lid Fit Properly: Yes No Lid Fit Properly: Yes No Lid Fit Properly: Yes No
Draining Properly: Yes No Draining Properly: Yes No Draining Properly: Yes No
Leads Marked Properly: Yes No Leads Marked Properly: Yes No Leads Marked Properly: Yes No
Waterproof Splices: Yes No Waterproof Splices: Yes No Waterproof Splices: Yes No
Splices on Hook: Yes No Splices on Hook: Yes No Splices on Hook: Yes No
Proper Service Loops: Yes No Proper Service Loops: Yes No Proper Service Loops: Yes No
Box Type: Box Type: Box Type:
COMMENTS
Junction Box #7
Junction Box #3
Loops wires traced. No junction boxes found.
PERMANENT TRAFFIC MONITORING INSPECTION CHECKLIST - PAGE 3
Junction Box #8 Junction Box #9
Junction Box #1
Junction Box #4 Junction Box #5 Junction Box #6
ATR No.
Junction Box #2
* Draw and label lanes, direction, shoulders,sensors, loops, cabinet, pull boxes, lane dividers, median type, etc.
* Mark any anomalies and label (i.e. loose or missing sealant/epoxy, cracks or potholes, bad pulloff, etc.
NOT TO SCALE
PERMANENT TRAFFIC MONITORING INSPECTION CHECKLIST - PAGE 4
ATR No. Location Park
401 Sugarlands GRSM
Sketch of Site (As-built)
Legend
FEATURE PROPOSED EXISTING FEATURE PROPOSED EXISTING
CABLE AND CONDUIT SERVICE POLE
PULLBOX SOLAR PANEL
SPLICE BOX TRAFFIC SIGN N/A
JUNCTION BOX TRAFFIC DIRECTION N/A
CABINET STOP BAR N/A SB
LOOP DETECTOR 3 TURNS GATE N/A
N ew fo u n d
G ap
R d
(U S s s
Notes -
1. All loops are paved over.
2. Distance and size measurements for loops are approximate.
45 '
20 '
Sugarlands Visitor Center
Little River Road
GREAT SMOKY
MOUNTAINS
NATIONAL PARK
STA 401
Sugarlands
To park facilities
To G at lin b u rg
65 '
La n e
La n e
Park Headquarters Rd.
To Cades Cove
Location Park
Sugarlands GRSM
1. Install 12" x 12" steel splice box at loop location.
2. Install 1" RGS conduit from roadway to splice box (20 feet).
3. Install 2" RGS conduit from splice box to cabinet (30 feet).
4. Splice and terminate loops.
5. Prepare and paint cabinet NPS brown.
6. Conduct electronic and system operability tests.
TOTAL: 13,000.00$
Estimate includes traffic control, mobilization, and all parts and materials required to perform the work described above.
PERMANENT TRAFFIC MONITORING INSPECTION CHECKLIST - PAGE 5
Repair Recommendations
ATR No.
1. Loops are paved over.
Summary of observations:
2. Cabinet is not painted NPS brown color (it is green).
Remedial repairs that were completed at the site to address the numbers items above include:
3. Grounded loop harness.
After completion of all remedial site repairs, the operational status of the system was tested using comparison between manual and machine counts of vehicles using mechanical tally counters. Based on on this test, the site was found to be fully operational, with all loops counting. Tally counter photos are provided with this report.
4. Cabinet filter is dirty.
4. Replaced cabinet filter.
The work required to standardize the system to the SCR amendments to FLH FP-03, ASTM E2532-06 and ASTM
E2561-07A are described below.
3. Loop harness for ADR is not grounded.
5. Non-standard conduit used for loop lead-in from ground to cabinet. Use of conduit to roadway cannot be determined without destructive investigation.
Robert.Owolabi Rectangle
Robert.Owolabi Rectangle